Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.3 CrAccepted-AOC | ₹3.3 Cr | L1 | Accepted-AOC Being lowest Bidder |
| 2 | L2₹3.9 Cr+₹63.7 L (19.2%)Rejected-Finance SHIV BARI ROAD NEAR KASUMAL HOTEL BIKANER 334003 RAJASTHAN | BIKANER | BIKANER | RAJASTHAN | 334003 | ₹3.9 Cr+₹63.7 L (19.2%) | L2 | Rejected-Finance Not Lowest Bidder |
| 3 | L3₹4.1 Cr+₹82.0 L (24.7%)Rejected-Finance 70 VARDHMAN NAGAR A P O SHYAM NAGAR AJMER ROAD JAIPUR PIN 342019 | JAIPUR | 342019 | ₹4.1 Cr+₹82.0 L (24.7%) | L3 | Rejected-Finance Not Lowest Bidder |
| 4 | L4₹4.2 Cr+₹86.6 L (26.1%)Rejected-Finance 84 A VIJAY NAGAR COLONY LALGHATI PO NAYAPURA BHOPAL 462032 | 462032 | ₹4.2 Cr+₹86.6 L (26.1%) | L4 | Rejected-Finance Not Lowest Bidder |
| 5 | L5₹4.7 Cr+₹1.4 Cr (42.0%)Rejected-Finance 13 29 3RD FLOOR EAST PATEL NAGAR NEW DELHI 110 008 | WEST | DELHI | 110008 | ₹4.7 Cr+₹1.4 Cr (42.0%) | L5 | Rejected-Finance Not Lowest Bidder |
Tender Value
₹3.8 Cr
EMD Value
₹4.5 L
Closing Date
10 Jan 2022, 6:00 pmClosed
Chief Engineer Bathinda
HQ Chief Engineer Bathinda Mil AStn
Provn of 33/ 11 KV Sub Stn at Bikaner Mil Stn
2021_MES_489118_1
CE BTZ BKN TOKEN of 19 OF 2021-22
Open Tender
Electrical and Maintenance Works
Lump-sum
365 days
Bikaner
As per NIT
8 documents required · 8 mandatory
₹2,000
GE (P) Bkaner
₹4.5 L
Yes
5 Feb 2022
26 Nov 2021
12 Jan 2022
26 Nov 2021
10 Jan 2022
16 Dec 2021
Amount
BLANK
SCHEDULE 'A' SECTION-I (BUILDING/STRUCTURE WORKS)
Lump sum price worked out by the tenderer for “Building Work / Structure Work” as listed in Schedule ‘A’ Section - I.
SCHEDULE 'A' SECTION-II (PART-I) (INTERNAL ELECTRIFICATION WORKS)
Lump sum price worked out by the tenderer for “INTERNAL ELECTRIFICATION WORK” as listed in Schedule ‘A’ Section - II (Part-I)
SCHEDULE 'A' SECTION-II (PART-II) (INTERNAL ELECTRIFICATION WORKS)
Supply and hanging/ fixing ceiling fan 1200mm sweep AC supply (input voltage range : 120 to 280 volts), BLDC type, five star rated, BEE & ISI marked, super enamelled copper winding of 'B' class insulation, single phase 26 W (+ 10%), PF 0.90 (Min), air delivery of 220 cum/ minute (CMM), 350 RPM (+ 10%), temperature rise 40 degree maximum, without remote, with electronic regulator, 3 Blades, down rod including accessories, white colour, total harmonic less than 10%, 5 speed, hanging in position including making connection with and including flexible cord twin core twisted copper conductor of size 23/0.0076 from ceiling rose to fan complete all as specified and directed. Note : (i) Serial Number as issued by Engineer-in-charge of ceiling fan and GE office name shall also be written on fan with red colour permanent marker, cost for the same shall deemed to be included in the quoted unit rate, nothing extra shall be paid on this account.
S&F Exhaust fan, 230 mm sweep steel body, 240 volts complete with lovers shutters and mounted in suitable opening arrangement in wall and connecting up including three core PVC insulated PVC sheathed copper conductor flexible cable 24/0.2mm drawn in flexible PVC conduit and fixed by using 4 Nos, 200 mm long 12 mm dia fasteners bolts nuts and washers and grouted in wall in CM(1:3), complete all as specified. (Necessary civil work required for fixing of exhaust fan is deemed to be included in overall quoted rate)
S&F Exhaust fan, 450 mm steel body sweep, 240 volts complete with lovers shutters and mounted in suitable opening arrangement in wall and connecting up including three core PVC insulated PVC sheathed copper conductor flexible cable 24/0.2mm drawn in flexible PVC conduit and fixed by using 4 Nos, 200 mm long 12 mm dia fasteners bolts nuts and washers and grouted in wall in CM(1:3), complete all as specified. (Necessary civil work required for fixing of exhaust fan is deemed to be included in overall quoted rate)
S & F of MCB suitable for 240 volts AC supply, SP with over load and short circuit protection and rupturing capacity not less than 10KA as specified and 6amps to 32 Amps.
S & F of MCB suitable for 240 volts AC supply, SPN with over load and short circuit protection and rupturing capacity not less than 10KA as specified and 6 to 32 Amps.
Earthing to distribution board complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m below normal ground level) with top edge of the plate at a depth not less than 1.5 m below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to galvanized earth lead 4.00mm dia upto 7.50 metre, including nuts, bolts, check nuts & washers of galvanized iron or steel and riveted to earth plate at one end and connecting to running earth wire/over head line conductor along pole at the other end, GI wire encased in and including 15mm bore GI light grade pipe with all fittings fixed with and including 25 x 4 mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe light grade and incl funnel, wire mesh, copper lugs etc from bottom of earth pit to top of electrode complete with earth pit in PCC 1:3:6 type C-1 using 20mm graded crushed stone aggregate(including PCC pit cover) and RCC 1:2:4 type B-1 cover complete all specified and shown in electrical plate No 3 of SSR Pt-I connecting earth electrode to test point with and including earthing lead including necessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance n.exc 50m and taking out old material all as specified and directed by Engineer-in-Charge. Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner (ii) The unit rate includes earthing lead & protection pipe upto 7.5 metre from top of earth plate.
Supply and fixing of LED complete fitting including batten and T-8 Retro LED polycarbonate 1 x 20 Watt, appx 4 feet long, environment friendly, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting complete fitting with all accessories and following specification all as directed by Engr - in Charge:- (a) Lumen system efficacy of luminaire should be minimum 100 Lumen per watt .(b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Max 10% (f) IP rating : IP -20 (g) CRCA pre coated housing with two coloured plastic end cap (h) LED Driver of the make as of the luminaire (J) LED driver should be complete with all protection viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection minimum 2.5 KV (l) CCT : 6500K (m) CRI : More than 80 (n) Rated life time 50000 burning hrs (Average 10 to 12 hrs daily)
Supply and fixing of LED complete fitting including batten and T-8 Retro LED polycarbonate 2 x 20 Watt, appx 4 feet long, environment friendly, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting complete fitting with all accessories and following specification all as directed by Engr - in Charge:- (a) Lumen system efficacy of luminaire should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to plus 45° (d) Power factor : Minimum 0.95 (e) THD : Max 10% (f) IP rating : IP -20 (g) CRCA pre coated housing with two coloured plastic end cap. (h) LED Driver of the make as of the luminaire. (J) LED driver should be complete with all protection viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer (k) Surge protection mininum 2.5 KV (l) CCT : 6500K (m) CRI : More than 80 (n) Rated life time 50000 burning hrs (Average 10 to 12 hrs daily)
Supply and fixing of LED mirror light fitting 1 x 5 Watt, extruded polycarbonate environment friendly, including electric with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting complete fitting with all accessories and following specification all as directed by Engr - in Charge:- (a) Lumen system efficacy of luminaire should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to plus 45° (d) Power factor : Minimum 0.95 (e) THD : Max 10% (f) IP rating : IP -20 (g) CRCA pre coated housing with two coloured plastic end cap. (h) LED Driver of the make as of the luminaire. (j) LED driver should be complete with all protection viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection mininum 2.5 KV (l) CCT : 6500K (m) CRI : More than 80 (n) Rated life time 50000 burning hrs (Average 10 to 12 hrs daily)
Supply and fixing of LED lamp minimum 3 star rated 5 W LED B-22 base including lamp holder complete all as specified and directed by Engr - in Charge with following specification:- (a) Lumen system efficacy of luminaire should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to plus 45° (d) Power factor : Minimum 0.90 (e) CRI : More than 80
Supply and fixing energy efficient LED street light fitting of 1 X 25 watt pressure die cast alumunium housing/body, heat resistant clear toughened glass, better optics for uniform distribution street/Roadway luminare, with driver, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting complete fitting with all accessories and following specification all as directed by Engr - in Charge:- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max 10% (f) IP rating : IP -66 (g) IK rating : IK07 (h) CRCA pre coated housing with two coloured plastic end cap. (j) LED Driver of the make as of the luminaire. (k) LED driver should be complete with all protection viz open/short circuit protection, over voltage protection, all as per standard design of manufacture. (l) Surge protection minimum 10 KV (inbuilt + extended) (m) CCT : 5700K (m) CRI : Minimum 70 (n) Lens: High efficiency wide angle lens (o) BIS approved fixtures and driver (p) Rated life time 50000 burning hrs (Average 10 to 12 hrs daily)
Note for item No 13 to 17 (a) Contractor shall submit LM – 79 and LM – 80 reports obtain from manufactures . (b) Contractor shall to furnish a replacement warranty of 05 years for LED light fittings complete including lamps from the date of completion of CA. The product will be replaced including taking down and re-fixing new luminary free of cost in the following case ;- (i) Manufacturing defects. (ii) Failure due to mechanical and electrical impact. (iii) Drop in luminary (or Lux at 1 mtr) below 90% of claimed values of lumens (or Lux at 1 mtr) of the LED luminaries. I All LED light/luminary must meet the provision laid down in IS – 16101 , 16102 Part –I/II ,16103 Part –I , 16104 ,16105 ,16106 , 16108/2012 and 15885 Part –II / Section 13. (d) Minor items required for completion of job are included in overall cost quoted by Contractor. Nothing extra shall be payable on this account contractor. Nothing extra shall be payble on this account.
S&F Wiring with twin core PVC insulated sheathed cable with copper conductor having single strand of 0.6 mm dia taped for telephone wiring from terminal box to telephone socket complete all as specified.(Conduit and conduit accessories shall be measured and paid separately.
Mild steel box flush mounted 100mm x100mmx100mm having holes for 20 mm conduit entry including 3 pin telephone socket outlet flush type duly marked with symbol of telephone and 3 mm thick plastic laminated sheet cover complete for telephone connection all as specified.
SUBTOTAL
SCHEDULE 'A' SECTION-III (INTERNAL WATER SUPPLY WORKS)
Lump sum price worked out by the tenderer for “INTERNAL WATER SUPPLY WORK” as listed in Schedule ‘A’ Section - III
SCHEDULE 'A' SECTION- IV (Part-I) (SEWAGE DISPOSAL WORKS)
Lump sum price worked out by the tenderer for “SEWAGE DISPOSAL WORKS” as listed in Schedule ‘A’ Section -IV (Part-I)
SCHEDULE 'A' SECTION- IV (Part-II) (SEWAGE DISPOSAL WORKS)
DWCPE (SN8) confirming to IS-16098, 150 mm nominal bore complete laid in trenches and jointed including testing with and including necessary jointing material tees/ union/ socket etc complete as per manufacturers instructions. NOTES:- (i) Earth work shall be measured & paid for separately under respective items of Schedule 'A'/BoQ. (ii) The rate of necessary tees/ union/ socket/ other accessories of same material and size of pipe is included in this item and nothing shall be paid extra on this account.
BLANK
Subtotal
SCHEDULE 'A' SECTION-V (BITUMINOUS ROAD WORKS)
Lump sum price worked out by the tenderer for “BITUMINOUS ROAD WORKS” as listed in Schedule ‘A’ Section -V (Part-I)
SCHEDULE 'A' SECTION - VI (INTERLOCKING PAVER BLOCK WORKS)
Lump sum price worked out by the tenderer for “INTERLOCKING PAVER BLOCK WORKS” as listed in Schedule ‘A’ Section -VI (PART-I)
SCHEDULE 'A' SECTION - VII (CHAIN LINK FENCING WORKS)
Lump sum price worked out by the tenderer for “CHAIN LINK FENCING WORKS” as listed in Schedule ‘A’ Section -VII
SCHEDULE 'A' SECTION - VIII (AREA DRAINAGE WORKS)
Lump sum price worked out by the tenderer for “(AREA DRAINAGE WORKS” as listed in Schedule ‘A’ Section -VIII
SCHEDULE 'A' SECTION - IX, (PART-I ) (EXTERNAL WATER SUPPLY WORKS)
Lump sum price worked out by the tenderer for “EXTERNAL WATER SUPPLY WORKS” as listed in Schedule ‘A’ Section -IX (Part-I)
SCHEDULE 'A' SECTION - IX, (PART-II ) (EXTERNAL WATER SUPPLY WORKS)
Material and labour for tapping from existing line of any size for branch connection 25mm dia GI tubing including all fixtures and fittings as per site requirement including drilling/cutting/threading etc complete all as specified and as directed.
Boring of horizontal holes 160 mm dia, manually without disturbing the tap surface for laying of cables/GI pipe under road, pavement hard standing complete all as specified and as directed by Engr-in-Charge.
Subtotal
SCHEDULE 'A' SECTION - X (PART-I) (EXTERNAL ELECTRIFICATION WORKS)
Lump sum price worked out by the tenderer for “EXTERNAL ELECTRIFICATION WORKS” as listed in Schedule ‘A’ Section -X (Part-I)
SCHEDULE 'A' SECTION - X (PART-II) (EXTERNAL ELECTRIFICATION WORKS)
Supply, transporting, erection, testing & commissioning of 36kV,1800MVA, 1250A,50Hz, voltage class outdoor type Vacuum Circuit Breaker, for use on system voltage 33kV along with indoor CRP panel as per description below. The Circuit Breaker and accessories shall confirm to IEC 62271-100 or IS 13118 and other relevant IEC/IS standard. The Circuit breaker shall be complete with terminal connection, operating mechanism, control cabinets, cable accessories, with gland, terminal block, lugs, necessary steel support structure for CB and control cabinet. The Circuit Breaker shall be required to perform as per technical parameters given below: (Contd Ser No 48 to 51)
a) Installation - Outdoor, 3-Pole,vacuum Live Tank, porcelain Clad, Switchyard Breaker. B) Rated Voltage -36kV c) Rated Current -1250A D) power frequency withstand voltage (kV rms) - 95 kV e) 12/50 µsec. Lightning impulse withstand voltage (kV peak) -195kVp. f) Rated Short Circuit Current Breaking capacity (3 sec.) at rated voltage specified : 31.5kA . g) Control Voltage including Trip /closing coil - 110VDC h) Spring charge voltage - 230VAC i) Symmetrical Interrupting Capacity (kA rms) as per IEC : 31.5kA j) Rated Short Circuit Making Current (kAp) - 80 kAp k) Out of Phase Breaking Capacity - As per IEC. l) Rated Operating Duty : As per IEC. m) Temperature Rise over the design ambient temperature - As per IEC 62271-100. n) Operating Mechanism - Spring type. o) Creepage Distance - 900mm. p) No.of Trip/close coils - 2 nos. each. q) Spring charging handle - Integral part of Operating mechanism. (Separate Spring charge handle not acceptable).
Note : i) Cost of supply and fix of Outdoor type Terminal Kiosk having terminals /disconnecting links for termination of CT/PT wiring including PT secondary fuses complete all as required at site are deemed to be included in the quoted rate. Ii) Cost of construction of foundation including construction material, MS work and necessary earth work as per manufacturer design for breaker & TK complete all as required at site are deemed to be included in the quoted rate. (iii) Factory Inspection Shall be carried out by Rep of GE/CWE. All costs on this account are included in over all cost quoted by the contractor. (iv) Pre commission shall be carried ot by SEI from HQ CE SWC or rep nominated by accepting officer. All cost on this account shall be borne by contractor. (v) Drawings for VCB shall be approved by GE before placement of order by contractor
SINGLE FEEDER CONTROL & RELAY PANEL : Panel Simplex type fabricated from 2 mm MS sheet for Side / Top / Rear and with 3mm for Front / Gland plate, Paint Shade-exterior shade- No.631 of IS-5, Interior shade - No.631 of IS-5 Panel size : 750mm (Width) x 610mm (Depth) x 2315mm (Including 100 mm base channel) (Height). Also having Digital Power Ananlyser Make Elmeasure Model EN 8400 eNavigator or equivalent model RS 485 Enabled with suitable wiring complete
Supply and installation of outdoor type 33 KV, single phase, oil cooled CT of ratio 400/5-5, burden core 1 : 15 VA/5P10 Amp; Core 2 : 15 VA/0.5 class.
Supply and installation of outdoor type 33 KV single phase out door oil cooled PT of ratio 33 KV/rt3/110 V/rt3/110V/rt3,Star, Star feeder connected 100 VA/CL 0.5.
Supply, Installation, testing , Commissioning of 11kV Air Insulated Indoor type Switchgear Panels with maximum system voltage rating of 12kV consisting of 1 Incomers of 1250A VCB + 3 Outgoing Feeders with 800A VCB ,Busbar Rating of 1250A,Short Circuit Capacity of 26.3kA .Bus-bars shall have full Voltage Sleeving on it and shall be self-supported type ,i.e. without any support insulators . The Incomer Panels shall contain Line PT arragement . The Panel, Vacuum Circuit Breaker , Vacuum Bottle, Numerical relays shall be of same make as the Panel Manufacturer . Bus bar should be of electrolyte Copper.The panel shall be tested for IAC AFLR for 26.3kA/1s. (Contd Ser No 55 to 56)
The IED (Numerical relay) shall be Complied to 61850 protocol without any external protocol converter. GOOSE signals shall be freely configurable.WEB HMI feature should be present. Inter-operability test shall preferably shall be done. Proof w.r.t Interoperability shall be submitted by the Manufacturer. The relay shall have integral arc-protection based on simultaneous detection of current and light to ensure reduced cubicle damage and increase personal safety. (<15 ms) The relay must support IEC 61850 Edition 1 and Edition 2(with test reports) and shall supports HSR and PRP redundancy protocols. It shall comply with international standard of NERC CIP or BREW for cyber security . The Circuit Breaker shall be of floor rolling design with encapsulated Vacuum bottles, and shall have all fool-proof interlocks as :Interlocks shall be provided to prevent a ‘Closed’ breaker to rack out from ‘Service’ to ‘Test’ /'Isolated’, position or insert a ‘closed’ breaker from ‘Test’ to ‘Service’ position. In either case the breaker contacts must remain in open position. Before racking out the breaker must be fully discharged from any static charge. Switchgear should be SCADA Compatible. All Panels shall have integral earth Switch with making capacity . VCB Panels shall be from one same Manufacturer to ensure ease of maintenance after expiry of warranty period. Panels shall be tested for Seismic Zone -IV as Bikaner Station falls under the same Earthquake Zone .Type Test reports shall be submitted for the same.
The Switchboard shall be configured as follows : 1 Incomers of 1250 A VCB and 3 Outgoing Feeders with 800A VCB . Incomer CTs :200-100/1-1, 5VA, Cl-5P10, Cl-1.0Outgoing Panel CTs : 100-50/1-1,5VA,Cl-5P10,Cl-1.0Incomer VTs : 11000/V3/110/V3/110/3,50VA,Cl-1.0,3P Incomer IEDs : Feeder Protection and Control Relay, Protections 50,51,50N,51N,46,49,67,67N,27,59,59N,95, Measurement for 3I,I0,3U,U0,Kw,KVA,PF,Hz,Kwh, 16 DI + 10 DO, One front RS 485 Port, Two Rear FO(LC) Port for IEC-61850 Protocol, Drawout Type with CT Shorting feature.Outgoing IEDs : Feeder Protection and Control Relay, Protections 50,51,50N,51N,46,49,95, Measurement for 3I, I0, 4 DI + 6 DO, One front RJ45 Port, Two Rear FO(LC) Port for IEC-61850 Protocol, Drawout Type with CT Shorting feature.Other necessary items like AC/DC MCBs , Power pack with each panel, TNC Switches, Indication Lamps (R,Y,B,ON,OFF, Spring Charge, Test, Service) shall be considered in the scope of Panel and shall be factory fitted only . Digital Power Ananlyser Make Elmeasure Model EN 8400 eNavigator or equivalent Make and Model, RS 485 Enabled with suitable wiring complete for every panel. No system house panel are required.Make : ABB, Siemens and Schneider, CG. Note :-(i) Factory Inspection Shall be carried out by Rep of accepting GE/ CWE. All costs on this account are included in over all cost quoted by the contractor.(ii) Pre commission test shall be carried ot by SEI from HQ CE SWC or rep nominated by accepting officer. All cost on this account shall be borne by contractor. (iii) Drawings for VCB shall be approved by GE before placement of order by contractor. (iv) CT ratio will be decided by the GE at the time of execution
Supply and Fixing Switch air break, gang operated outdoor, horizontally operated type, HT 33000 volts triple pole 400 Amps 3 insulator per phase tilting/rocking type (horizontal type), with fixed contacts of phosphorous bronze and moving contacts of copper pipe, manually operated from ground level with operating mechanism including mild steel galvanized light grade 25 mm bore operating rod, pad locking arrangements, MS arcing horns, flexible braiding earthing blades, rod and contacts without drop out fuse assembly and jumpers with panthar conductor line, taps, clamps, colour coated HT sleeves and fittings suitable for horizontal mounting, supplied and fixed, complete all as specified and as directed by Engineer-in-Charge.
All as per SI No 57 here-in above but for HT 33000 Volts triple pole 200 Amps all as specified and as directed by Engineer-in-Charge.
Supply and Fixing Switch air break, gang operated outdoor, horizontally operated type, HT 11000 volts triple pole 400 Amps 3 insulator per phase tilting/rocking type (horizontal type), with fixed contacts of phosphorous bronze and moving contacts of copper pipe, manually operated from ground level with operating mechanism including mild steel galvanized light grade 25 mm bore operating rod, pad locking arrangements, MS arcing horns, flexible braiding earthing blades, rod and contacts without drop out fuse assembly and jumpers with mink conductor line, taps, clamps, colour coated HT sleeves and fittings suitable for horizontal mounting, supplied and fixed, complete all as specified and as directed by Engineer-in-Charge.
All as per SI Item No 59 here-in above but for HT 11000 Volts triple pole 200 Amps all as specified and as directed by Engineer-in-Charge.
Supply and Fixing Lightening arrestors expulsion type complete with all fittings, transmission class, discharge capacity 65 KA station class suitable for 33000 Volts including connecting to earth wire 4mm dia GI wire, supplied and fixed complete all as specified and as directed by Engineer-in-Charge.
All as per SI Item No 61 here-in above but for HT 11000 Volts all as specified and as directed by Engineer-in-Charge.
Supply, installation, commissioning and testing of Transformer HT 33 KV 3 Phase, LT 433 volts 3 Phase 4 wire, 100 KVA capacity, copper wound, step down, outdoor, oil cooled, all as per latest IS (IS 1180) including initial oil filling to appropriate level with desired strength, with & including all standard fittings/ accessories such as Off load tap changer, silica gel breather with oil seal, conservator tank with drain valve, explosion vent, thermometer dial type, oil level gauge, filter valve, lifting lug, channel feet, oil filling holes with cover, earthing terminal, LV box, air release valves, bi-directional roller-04 Nos, rating and diagram plate, etc complete including necessary foundation as per manufacturer specifications all as specified and as directed. Note : - (i) Factory Inspection Shall be carried out by Rep of accepting GE / CWE. All costs on this account are included in overall cost quoted by the contractor. (ii) Pre commission test shall be carried ot by SEI from HQ CE SWC or rep nominated by accepting officer. All cost on this account shall be borne by contractor.
Earthing to poles/lightening arrestor /GOD switch complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m below normal ground level) with top edge of the plate at a depth not less than 1.5 m below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to galvanized earth lead 4.00mm dia upto 7.50 metre, including nuts, bolts, check nuts & washers of galvanized iron or steel and riveted to earth plate at one end and connecting to running earth wire/over head line conductor along pole at the other end, GI wire encased in and including 15mm bore GI light grade pipe with all fittings fixed with and including 25 x 3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe light grade and incl funnel, wire mesh, copper lugs etc from bottom of earth pit to top of electrode complete with earth pit in PCC 1:3:6 type C-1 using 20mm graded crushed stone aggregate(including PCC pit cover) and RCC 1:2:4 type B-1 cover complete all specified and shown in electrical plate No 3 of SSR Pt-I connecting earth electrode to test point with and including earthing lead including necessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance n.exc 50m and taking out old material all as specified and directed by Engineer-in-Charge. (Note : 12 No Earthing of SCADA Works have been clubbed under this item )
All as per SI Item No 64 here-in above but using galvanised iron strip 32 x 6 mm as earthing lead and protection pipe 40 mm dia GI pipe complete all as specified and as directed by Engineer-in-Charge. Note for item No 64 & 65:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for metering shall be provided in slanting manner. (ii) The unit rate includes earthing lead & protection pipe upto 7.5 metre from top of earth plate.
Material and Labour Cross arm, bracings, stiffeners, supports, clamps, and back plates fabricated from structural steel section grade of Fe-290 (Grade E-165) such as channel angle iron, flat iron etc including nuts bolts, washers welding, bending cold or not drilling holes for bolts in any clamp or size including two coat of aluminium paint (under and finished coat) over a coat of primer (red oxide) after preparation of steel surfaces complete all as specified. Note: Unexposed surface shall be given one coat of primer only while computing the weight, the weight of paint shall not considered.
Supply and stringing Aluminium conductor, steel reinforced (ACSR) of any size/make including stringing for overhead line on HT poles including aluminium binding wire 14 SWG, jumpers, line tapes, conducting jelly etc, supplied and fixed complete all as specified and as directed by Engineer-in-Charge. (Notes: (i) The ACSR conductors shall be conforming to IS-398 and as specified in SSR Part-I. (ii) The unit rate quoted shall also be deemed to include for supply & fixing of aluminium binding wire, aluminium tapes etc which shall not be included in the weight of conductors. (iii) Weight of conductors shall be determined by measuring true horizontal distance between centers of two adjacent poles and compounding the weight of conductors of that size and length and 3% extra added for sag, jointing, jumpers etc. (iv) Weight of the conductors shall be calculated from the nominal weights given in tables in the relevant IS.)
Supply and Fixing Galvanised steel wire, 4mm dia including galvanised mild steel binding wire 1.63 mm dia or Cradles, guards fabricated with galvanised steel wire 3.15mm dia including binding with 1.63 mm dia galvanised steel wire complete all as specified and as directed by Engineer in Charge.
Boring of horizontal holes 160 mm dia, manually without disturbing the top surface for laying of cables/GI pipes under road , pavement, hard standing complete all as specified and as directed by the Engineer-in-Charge.
Supply and Fixing Disc type Insulator, porcelain, vitreous, 145 mm height , 255 mm dia ball and socket type, white, brown or green, double disc assembly for tension with tension clamps for conductors, working pressure 11000 volts complete all as specified and directed.
Supply and Fixing Pin type Insulator , porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanized iron washers and one galvanized iron nut, 150 mm height , 150 mm dia for 11000 volts grade complete all as specified and directed.
Supply and Fixing Pin type, porcelain, vitreous, white, brown or green insulator (SC-PN-3301) including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 220 mm height and 280 mm dia. for working pressure 33000 volts grade, supplied and fixed complete all as specified and as directed by Engineer-in-Charge.
Supply and Fixing galvanised mild steel Disc insulator ( Tongue and clevis type) strain hardware fitting with three bolted tension clamp and one cross arm clamp suitable for ACSR weasel conductor of 11 KV Over head line supplied and fixed complete all as specified and as directed by Engineer-in-Charge.
Supply and Fixing galvanised mild steel Disc insulator ( Tongue and clevis type) strain hardware fitting with three bolted tension clamp and one cross arm clamp suitable for ACSR rabbit conductor of 11 KV Over head line supplied and fixed complete all as specified and as directed by Engineer-in-Charge.
Supply and Fixing galvanised mild steel Disc insulator ( Tongue and clevis type) strain hardware fitting with three bolted tension clamp and one cross arm clamp suitable for ACSR Dog conductor of 33 KV Over head line supplied and fixed complete all as specified and as directed by Engineer-in-Charge.
Supply and Fixing galvanised mild steel Disc insulator ( Tongue and clevis type) strain hardware fitting with three bolted tension clamp and one cross arm clamp suitable for ACSR panthar conductor of 33 KV Over head line supplied and fixed complete all as specified and as directed by Engineer-in-Charge.
Dismantling and Shifting of existing 11 KV, VCB complete, to Prop 33/11 KV S/Stn at KM Area from the existing location of the VCB at KLP power house. Reassembling and installation the same at new location given and connecting to HT cable and SCADA panel connections. Testing and commissioning on load as specified and all as directed by Eng-in-charge. Any part broken during shifting will be replaced by the contractor free of cost. Cost of Nuts, bolts, washer, anchor bolts, etc required for installation is deemed to be included in rate quoted. Cost of technical experts for reassembling of VCB is deemed to be included in rate quoted. Note : Cost of tools and all kind T&P required for dismantling, shifting and reassembling is deemed to be included in rate quoted.
Disconnecting connection of 33/ 11 KVA transformer 5 / 3.15 MVA and Shifting from one 33/11 Sub Stn to other substation inside Military area approx 5 KM away including connecting, charging, testing complete all as directed by Eng-in-Charge Note : Cost of tools and all kind T&P required for dismantling, shifting and reassembling is deemed to be included in rate quoted.
Supply and laying Cross linked poly-ethylene (XLPE) insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables ( heavy duty) with aluminium conductor, 33000 volts grade (earthed type) of cross-sectional area 240 Sqmm 3 core conforming to IS-7098 (Part-I) laid in trenches/through pipe in road crossings/ paths /drains /ducts /floors /along poles/walls/ceilings/ equipments etc. complete supply and fixed/ laid all as specified and as directed by Engineer-in-Charge.( Note:-(i) Necessary excavation and earth work, brick protection, sand cushioning and cover and GI pipe shall be measured and paid for separately. )
Supply and Fixing Cable jointing kit for HT 33 KV (Earthed) cable for out door end termination ,cold shrinkable type joint kit complete with jointing material and accessories suitable for 3 Core XLPE armoured aluminium Conductor cable of size 240 sqmm including testing after jointing, fixing complete all as specified as directed by Engineer-in-Charge.
Supply and erecting Steel tubular swaged poles complete with MS base plate, finial taper plug, as specified type 410 SP-64(12.00 mtr long) including painting of complete pole 12m long with 2 coats of aluminium anti corrosive paints of first quality over a coat of red oxide primer including painting to pole upto 1.5m height from top of PCC coping with synthetic enamel paint 2 coat in black and white alternate strip including numbering in 8 cm height of number with white paint both paint aluminium/synthetic duly approved by the GE complete all as specified and directed by Engineer-in-charge. ( Note:- Necessary Earth work and PCC will be measured and paid separately)
Supply and erecting Steel tubular swaged poles complete with MS base plate, finial taper plug, as specified type 410 SP-55(11.00 mtr long) including painting of complete pole 11m long with 2 coats of aluminium anti corrosive paints of first quality over a coat of red oxide primer including painting to pole upto 1.5m height from top of PCC coping with synthetic enamel paint 2 coat in black and white alternate strip including numbering in 8 cm height of number with white paint both paint aluminium/synthetic duly approved by the GE complete all as specified and directed by Engineer-in-charge. ( Note:- Necessary Earth work and PCC will be measured and paid separately)
Supply and Fixing Stay assembly complete with 20 mm dia, 2000 mm long GI stay rod, with threaded ends and GI nuts, two number thimbles, MS galvanised clamps made out of 40mmx 6mm flat iron including MS nuts, bolts and washers, 300mm x 300mm x 6mm MS galvanised stay plate, stay bow, loop insulator, galvanized stay strand 7/4 mm including shackle and stay clamp and also including painting of exposed MS work with two coats of aluminium paint over a coat of red oxide zinc chromate primer, material and labour complete all as shown in electrical plate No 1 of MES Schedule Part-I complete all as specified and as directed by Engineer-in-Charge. ( Note:- Necessary Earth work and PCC will be measured and paid separately)
Supply and fixing LT Feeder Pillar Box cubical type of size 120x100x50 cm , 415 volt, factory made dust proof vermin proof (Kiosik type) for out door use made out of CRCA sheet 3.15 mm thick powder coated, machine pressed, both side opening in two halves with provision of rubber beading and locking system, including aluminium bus bar of 160 Amp capacity,4 strip mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers each MCCB/ cubical switch shall have be independent opening, panel should be mounted on angle iron frame and legs (vertical height of legs not less than 30 cm except in PCC) made from angle of size 50x50x5 mm, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer legs grouted in PCC(1:3:6) type B-2(using 40 mm graded stone aggregate) complete including all connection/ control wiring with suitable size of copper conductor cable ,including danger notice sticker ,comprising the following accessory including testing complete all as specified. (Contd Ser No 85)
Supply and fixing energy efficient LED wide angle flood light fitting of 150 watt capacity with driver, including electric connection with using twin core flexible copper conductor cable of size 2.5 sqmm including 20mm dia steel stove enemalled conduit fixed along PCC/ steel tubular pole with clamps made out of MS flat iron of size 25 x 3mm at not more than 100 cm c/c matching with section of poles, including suitable size of nuts, bolts and washers with two coats of aluminium paint over a coat of red oxide primer complete. Fitting with all accessories and following specification all as directed by Engr – in Charge:- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max 10% (f) IP rating : IP66 (g) IK rating : IK07 (h) Epoxy powder coated pressure die cast aluminium alloy housing and front cover clear toughened glass. (j) Built in potted LED Driver of the make as of the luminaire. (k) LED driver should be complete with all protection viz open/short circuit protection, over voltage protection, all as per standard design of manufacture. (l) Surge protection minimum 10 KV (inbuilt + extended) (m) CRI : More than 80 and CCT : 5700 K. (n) Lens: High efficiency wide angle lens (o) BIS approved fixtures and driver (p) Rated life time 50000 burning hrs (Average 10 to 12 hrs daily)
Note for item No – 86: (a) Contractor shall submit LM – 79 and LM – 80 reports obtain from manufactures. (b) Contractor shall to furnish a replacement warranty of 05 years for LED light fittings complete including lamps from the date of completion of CA. The product will be replaced including taking down and re-fixing new luminary free of cost in the following case ;- (i) Manufacturing defects. (ii) Failure due to mechanical and electrical impact. (iii) Drop in luminary (or Lux at 1 mtr) below 90% of claimed values of lumens (or Lux at 1 mtr) of the LED luminaries. (c) All LED light/luminary must meet the provision laid down in IS – 16101 , 16102 Part –I/II ,16103 Part –I , 16104 ,16105 ,16106 , 16108/2012 and 15885 Part –II / Section 13. (d) Minor items required for completion of job are included in overall cost quoted by Contractor. Nothing extra shall be payable on this account.
Supply and erecting steel tubular swaged poles complete with MS base plate, finial taper plug as specified type 410 SP-31 (9.00 mtr long) including painting of complete pole 9m long with 2 coats of aluminium anti-corrosive paints of first quality over a coat of red oxide primer including paintings to pole upto 1.5 m height form top of PCC coping with synthetic enamel paint 02 coats in black and white alternates strip including numbering in 8 cm height of number with white paint both paint aluminum/sythetic duly approved by the GE complete all as specified. ( Note:- Necessary Earth work and PCC will be measured and paid separately)
Supply and fixing thermoplastic cable junction box with IP 66/67 weather proof protection for outdoor installation with knockouts for cable entry of size 205x255x122 mm suitable for LT UG cable 10 Sqmm to 25 Sqmm
Supply & fixing FRLS PVC insulated Copper conductor, two single core of size 1.5sqmm complete for terminal box to street/ flood light fitting.
Supply and laying 40 mm graded stone aggregate under 2/4 pole structure around the 2/4 pole structure complete all as specified and as directed by Engineer-in-Charge.
M & L Anti-climbing devices, spikes-type fabricated out of MS flat 40mm x 6 mm in two parts with 14 Nos, 250mm long 12 mm dia spikes made to shape including nuts, bolts & washers and welding in two halves to suit the cross section of the pole including painting with two coats of aluminium paint over a coat of red oxide zinc chromate primer, supply and fixed, complete all as specified and as directed by Engineer-in-Charge.
Re-stringing of existing HT 33 KV over head line ACSR conductor of any size/type including repair of existing loose conductor, contraction etc, on existing HT lattice pole including replacement of aluminium binding wire of suitable size carefully without damaging of insulator etc complete all as specified and directed by Engineer-in-Charge. (Note :- Unit for measurement of this item “Each Span” which shall comprise of 3 Nos conductors and GI wire between respective pole)
Trimming/pruning of tree branches coming across electric power head lines HT 33 /11 KV feeder, clearing the span and making the feeder free from touching the tree branches and removing cut tree branches from road and disposing at distance of more than 500 mtr complete all as specified and as directed by Engineer-in-Charge.
Preparation of old painted surfaces and painting of MS Lattice tower pole 12.5 mtr long upto the top surface of pole with 2 coats of aluminium anti corrosive paint of best quality (aluminium/synthetic as approved by the GE) complete all as specified and as directed by Engineer-in-Charge.
Supply, fabrication and installation for 33 KV tower structure for Sub Station structure including necessary welding and painting with 2 coats of aluminium anti-corrosive paint of first quality over a coat of red oxide primer from outside and inside surface all as per drawing complete with foundation bolts all as specified and directed.
Supply,fabrication and installation for 33 KV beam structure for Sub Station 33 KV yard structure including necessary welding and painting with 2 coats of aluminium anti-corrosive paint of first quality over a coat of red oxide primer from outside and inside surface all as per drawing complete all as specified and directed.
Supply, fabrication and installation for 11 KV beam structure for Sub Station 11 KV yard structure including necessary welding and painting with 2 coats of aluminium anti-corrosive paint of first quality over a coat of red oxide primer from outside and inside surface all as per drawing complete all as specified and directed.
Material and Labour Danger notice plate of HT, 25x20cm size 1.60 mm thick of mild steel sheet, vitreous, enameled white, with letters, figures and conventional skull & bones in signal red colour and fixed with MS clamps made out of 25 mm x 3mm MS flat iron including bolts and nuts of approved size complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing Backlit Glow sign board box type of size 20x4 feet, made out of MS pipe frame 25x25x1.5 mm painted with one coat red oxide primer and 2 coat synthetic enamel paint, Top, Bottom and Side cover made of 25 SWG GI sheet with power coating and back side of board covered with 26 SWG plain GI Sheet with rivet and screws, Flex made out of Backlit of LG Hi-Flex, writing work with approved colour and font should be digitally printed, minimum one LED tube light 18 Watt is provided per Six Sqr Feet of board area for Lighting/Illumination inside board with copper wiring, including necessary brackets, clamps, anchor bolts etc required for fixing on Roof / Parapets of building.
Dismantling of ACSR of any size.
Dismantling poles/struts any size
Dismantling cross arms of MS channel angle sections etc. complete
Dismantling stay wire with bow and stay rod.
Dismantling insulators any type, any size
Dismantling of MS Lattice tower 12 mtr height
Re fixing of taken down Aluminium conductor steel reinforced (ACSR) of any size (Squirrel/weasel/ferret etc) vide item No. including jointing for over head line on poles including binding wire 14 SWG, Jumpers, line tapes etc complete all as specified any size. ( Old retrieved ACSR obtained from Item No 100 here-in-before shall be reused.)
Supply and Fixing Disc type Insulator, porcelain, vitreous, 145 mm height , 255 mm dia ball and socket type, white, brown or green, four disc assembly for tension with tension clamps for conductors, working pressure 33000 volts complete all as specified and directed.
Subtotal
SCHEDULE 'A' SECTION - XI (EARTH WORKS )
Lump sum price worked out by the tenderer for “EARTH WORKS” as listed in Schedule ‘A’ Section -XI
M/s Rohit Construction Co.
Pioneer Enterprises
POONAM ELECTRIC INDUSTRY
Leo Air and Power Solution pvt Ltd.
SAGGI ELECTRIC COMPANY
Jagdish Prashad and Company
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .