Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.9 LAccepted-AOC HOUSE NO 415 ALIKAN ROAD MANDI DABWALI SIRSA HARYANA 125104 | MANDI DABWALI | SIRSA | HARYANA | 125104 | L1 | Accepted-AOC Being the lowest bidder | |
| 2 | L2₹23.2 L+₹29,197 (1.28%)Rejected-Finance C O SHRI AMRENDER KUMAR YADAV IACHHIPUR SANTOSH NAGAR GORAKHNATH GORAKHPUR UTTAR PRADESH PIN 273015 | GORAKHPUR | UTTAR PRADESH | 273015 | L2 | Rejected-Finance Not the Lowest Bidder | |
| 3 | L3₹24.5 L+₹1.6 L (6.90%)Rejected-Finance NURSERY SCHOOL 1 SECTOR 33 SUNCITY KURUKSHETRA ROAD KAITHAL 136027 HARYANA | KAITHAL | KAITHAL | HARYANA | 136027 | L3 | Rejected-Finance Not the Lowest Bidder | |
| 4 | L4₹26.6 L+₹3.8 L (16.4%)Rejected-Finance | L4 | Rejected-Finance Not the Lowest Bidder | |
| 5 | L5₹28.9 L+₹6.0 L (26.2%)Rejected-Finance RCP GURUDWARA ROAD WARD NO 29 SURATGARH SRI GANGANAGAR 335804 | SURATGARH | SRI GANGANAGAR | RAJASTHAN | 335804 | L5 | Rejected-Finance Not the Lowest Bidder |
| Sl No | Description | Qty | Unit | SRI SAI CONSTRUCTION COMPANY L5 | MAJOR REFREGERATION AND ELECTRICALS L6 | S.K BUILDERS AND ENGINEERS L4 | godara construction company L3 | Truly Technos LLP L7 | SIGMA ENGINEERS AND CONTRACTORS L1 | SHIVA BUILDERS L2 |
|---|---|---|---|---|---|---|---|---|---|---|
| .10Notes:- (i) 100 percent nonperishable items of the work shall be deposited by the L1 bidder within 30 days after placing of work order. (ii) The critical path network shall be submitted by L1 bidder immediately after the acceptance of tender and approved by GE. (iii) The bidders must ensure to visit the site, check relevant documents and makes of materials required to be incorporated under the subject from concern Engineer-in-Charge. (iv) Material obtained from demolition/dismantled and the serviceable material (other than reused in the work) shall be the property of the Govt and shall be removed and deposited in the MES Store Yard without any extra cost to Govt. (v) In case of non-availability of any make mentioned under list of Makes, the L1 Bidder shall obtain non-availability / non-manufacturing certificate from the concern OEM / authorised dealers and submitted to Accepting Officer, the L1 bidder may be incorporated Group-I category makes as approved by HQ CE SWC Jaipur / HQ CE BTZ in the works after prior approval of Accepting Officer. (vi) L1 Bidder shall produce E-way bill alongwith test certificate from OEM / manufacturer for costly items / major items of amount above Rs 50,000/- along with RAR’s and Final Bill. (vii) L1 Bidder shall be maintained an album containing Photos of all the material brought at site and each stage wise work progress and kept at site. Same shall be deposited in Engineer-in-Charge office after completion of work. (viii) The cost of all the above provisions shall be deemed to be included in the quoted rate of bidder, nothing extra shall be paid to the bidder. | ||||||||||
| 1.00 | Taking down carefully or drawing out from conduit, existing copper / aluminium point wiring for light, fan, bell, socket, power point etc complete including fixture and fittings such as switches, sockets, ceiling rose, pendent holder, light fittings, top sheet covers, fan regulators and making good the disturbed surfaces of wall/ceiling complete all as specified and as directed by Engineer-in-charge. | 1,545 | Per Point | 10 ₹15,450 Lowest | 65 ₹1,00,425 | 20 ₹30,900 | 30 ₹46,350 | 10 ₹15,450 Lowest | 20 ₹30,900 | 10 ₹15,450 Lowest |
| 2.00 | M&L for Modular point wiring including provn of inverter connection complete with 1.5 Sqmm (nominal cross section area) FRLSH PVC insulated multistranded unsheathed copper conductor cable drawn in and including concealed PVC rigid conduit medium grade 20 mm dia, pipe hooks, elbows, junction covers and junction boxes including cutting chases in walls and making good the disturbed surfaces of wall with all jointing accessories including provision of pressed steel modular sunken terminal boxes made of 1.2mm thick pressed steel sheet, 60mm deep of suitable length and painted with red oxide primer and modular decorative sheet cover including 2.5 Sqmm PVC insulated multistranded unsheathed copper conductor wire as earth continuity to common earth and connecting to earth dolly for one light point, fan point, bell point controlled by one switch complete all as specified and directed by Engineer-in-Charge. | 1,005 | Per Point | 390 ₹3,91,950 | 400 ₹4,02,000 | 500 ₹5,02,500 | 350 ₹3,51,750 Lowest | 727 ₹7,30,635 | 360 ₹3,61,800 | 410 ₹4,12,050 |
| 2.01 | All as per serial item No. 02 here-in-before but for One light point controlled by Two 2- way switches. | 10 | Per Point | 425 ₹4,250 | 450 ₹4,500 | 500 ₹5,000 | 350 ₹3,500 Lowest | 1,350 ₹13,500 | 380 ₹3,800 | 450 ₹4,500 |
| 2.02 | All as per serial item No. 02 here-in-before but for One bell or buzzer point controlled by by one push button on same board with other or independent switches | 20 | Per Point | 430 ₹8,600 | 425 ₹8,500 | 500 ₹10,000 | 350 ₹7,000 | 940 ₹18,800 | 360 ₹7,200 | 200 ₹4,000 Lowest |
| 3.00 | M&L for Modular point wiring including provn of inverter connection complete with 2.5 Sqmm (nominal cross section area) FRLSH PVC insulated multistranded unsheathed copper conductor cable drawn in and including concealed PVC rigid conduit medium grade 25 mm dia, pipe hooks, elbows, junction covers and junction boxes including cutting chases in walls and making good the disturbed surfaces of wall with all jointing accessories including provision of pressed steel modular sunken terminal boxes made of 1.2mm thick pressed steel sheet, 60mm deep of suitable length and painted with red oxide primer and modular decorative sheet cover including 2.5 Sqmm PVC insulated multistranded unsheathed copper conductor wire as earth continuity to common earth and connecting to earth dolly for One 3 pin 5 Amp socket outlet on the same board with other switches complete all as specified and directed by Engineer-in-Charge. | 150 | Per Point | 300 ₹45,000 Lowest | 500 ₹75,000 | 600 ₹90,000 | 550 ₹82,500 | 880 ₹1,32,000 | 500 ₹75,000 | 550 ₹82,500 |
| 3.01 | All as per serial item No. 03 here-in-before but for One 3 pin 5 Amp socket outlet on independent board. | 180 | Per Point | 450 ₹81,000 Lowest | 500 ₹90,000 | 600 ₹1,08,000 | 550 ₹99,000 | 1,030 ₹1,85,400 | 500 ₹90,000 | 550 ₹99,000 |
| 3.02 | All as per serial item No. 03 here-in-before but for one socket outlet 3 pin, 15/16 Amps on independent board | 180 | Per Point | 600 ₹1,08,000 | 500 ₹90,000 Lowest | 600 ₹1,08,000 | 550 ₹99,000 | 1,130 ₹2,03,400 | 500 ₹90,000 Lowest | 580 ₹1,04,400 |
| 4.00 | S&F Modular switch piano flush type 6 Amps single pole, one way, complete all as specified and directed by Engineer-in-charge. | 1,335 | Each | 60 ₹80,100 | 60 ₹80,100 | 50 ₹66,750 | 19 ₹25,365 Lowest | 28 ₹37,380 | 28 ₹37,380 | 25 ₹33,375 |
| 5.00 | S&F Modular switch piano flush type 5/6 Amps single pole, two way, complete all as specified and directed by Engineer-in-charge. | 20 | Each | 70 ₹1,400 | 90 ₹1,800 | 40 ₹800 Lowest | 100 ₹2,000 | 58 ₹1,160 | 45 ₹900 | 40 ₹800 Lowest |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
13 Aug 2025, 6:00 pmClosed
GE (A) Suratgarh
GE (Army) Suratgarh
REPAIR TO INTERNAL WIRING AND REPLACEMENT OF ELECTRICAL FITTING IN CERTAIN OTM ACCN LESS COMPREHENSIVE MAINT BLDGS UNDER AGE E/M AT SURATGARH MIL STN.
2025_MES_721174_1
GE (A) SOG Token No 25/25-26
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
Suratgarh
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (A) Suratgarh
₹80,000
Yes
8 Oct 2025
18 Jul 2025
15 Aug 2025
18 Jul 2025
13 Aug 2025
1 Aug 2025
Amount
Notes:- (i) 100 percent nonperishable items of the work shall be deposited by the L1 bidder within 30 days after placing of work order. (ii) The critical path network shall be submitted by L1 bidder immediately after the acceptance of tender and approved by GE. (iii) The bidders must ensure to visit the site, check relevant documents and makes of materials required to be incorporated under the subject from concern Engineer-in-Charge. (iv) Material obtained from demolition/dismantled and the serviceable material (other than reused in the work) shall be the property of the Govt and shall be removed and deposited in the MES Store Yard without any extra cost to Govt. (v) In case of non-availability of any make mentioned under list of Makes, the L1 Bidder shall obtain non-availability / non-manufacturing certificate from the concern OEM / authorised dealers and submitted to Accepting Officer, the L1 bidder may be incorporated Group-I category makes as approved by HQ CE SWC Jaipur / HQ CE BTZ in the works after prior approval of Accepting Officer. (vi) L1 Bidder shall produce E-way bill alongwith test certificate from OEM / manufacturer for costly items / major items of amount above Rs 50,000/- along with RAR’s and Final Bill. (vii) L1 Bidder shall be maintained an album containing Photos of all the material brought at site and each stage wise work progress and kept at site. Same shall be deposited in Engineer-in-Charge office after completion of work. (viii) The cost of all the above provisions shall be deemed to be included in the quoted rate of bidder, nothing extra shall be paid to the bidder.
Taking down carefully or drawing out from conduit, existing copper / aluminium point wiring for light, fan, bell, socket, power point etc complete including fixture and fittings such as switches, sockets, ceiling rose, pendent holder, light fittings, top sheet covers, fan regulators and making good the disturbed surfaces of wall/ceiling complete all as specified and as directed by Engineer-in-charge.
M&L for Modular point wiring including provn of inverter connection complete with 1.5 Sqmm (nominal cross section area) FRLSH PVC insulated multistranded unsheathed copper conductor cable drawn in and including concealed PVC rigid conduit medium grade 20 mm dia, pipe hooks, elbows, junction covers and junction boxes including cutting chases in walls and making good the disturbed surfaces of wall with all jointing accessories including provision of pressed steel modular sunken terminal boxes made of 1.2mm thick pressed steel sheet, 60mm deep of suitable length and painted with red oxide primer and modular decorative sheet cover including 2.5 Sqmm PVC insulated multistranded unsheathed copper conductor wire as earth continuity to common earth and connecting to earth dolly for one light point, fan point, bell point controlled by one switch complete all as specified and directed by Engineer-in-Charge.
All as per serial item No. 02 here-in-before but for One light point controlled by Two 2- way switches.
All as per serial item No. 02 here-in-before but for One bell or buzzer point controlled by by one push button on same board with other or independent switches
M&L for Modular point wiring including provn of inverter connection complete with 2.5 Sqmm (nominal cross section area) FRLSH PVC insulated multistranded unsheathed copper conductor cable drawn in and including concealed PVC rigid conduit medium grade 25 mm dia, pipe hooks, elbows, junction covers and junction boxes including cutting chases in walls and making good the disturbed surfaces of wall with all jointing accessories including provision of pressed steel modular sunken terminal boxes made of 1.2mm thick pressed steel sheet, 60mm deep of suitable length and painted with red oxide primer and modular decorative sheet cover including 2.5 Sqmm PVC insulated multistranded unsheathed copper conductor wire as earth continuity to common earth and connecting to earth dolly for One 3 pin 5 Amp socket outlet on the same board with other switches complete all as specified and directed by Engineer-in-Charge.
All as per serial item No. 03 here-in-before but for One 3 pin 5 Amp socket outlet on independent board.
All as per serial item No. 03 here-in-before but for one socket outlet 3 pin, 15/16 Amps on independent board
S&F Modular switch piano flush type 6 Amps single pole, one way, complete all as specified and directed by Engineer-in-charge.
S&F Modular switch piano flush type 5/6 Amps single pole, two way, complete all as specified and directed by Engineer-in-charge.
S&F Modular switch piano flush type 15/16 Amps single pole, one way, complete all as specified and directed by Engineer-in-charge.
S&F Modular socket flush type 2 / 3 pin, 6 Amps, 230 volts, complete all as specified and directed by Engineer-in-charge.
S&F Modular socket flush type 6 pin,15/16 Amps, 230 volts, complete all as specified and directed by Engineer-in-charge.
S&F Modular bell push piano flush type 6 Amps single pole, one way, complete all as specified and directed by Engineer-in-charge.
S&F Modular electronic step type fan regulator suitable for ceiling fan of 1200mm / 1400mm sweep,2 Module complete all as specified and directed by Engineer-in-charge.
S&F sheet metal plug & socket DB, SP, with a two pin and earth plug with socket, 230 Volts with & including one MCB SP ‘C’ Curve 10 kA, 20 Amps complete all as specified and directed by Engineer-in-charge.
M&L for point wiring complete with 1.5 Sqmm (nominal cross section area) FRLSH PVC insulated multistranded unsheathed copper conductor cable drawn in existing conduit including replacement of sunken pressed steel terminal boxes and making good the disturbed surfaces of wall with all jointing accessories including provision of pressed steel sunken terminal boxes made of 1.2mm thick pressed steel sheet, 60mm deep of suitable length and painted with red oxide primer including 1.5 Sqmm PVC insulated multistranded unsheathed copper conductor wire as earth continuity to common earth and connecting to earth dolly for one light point, fan point, bell point controlled by one switch complete all as specified and directed by Engineer-in-Charge.
All as per serial item No. 12 here-in-before but for One light point controlled by Two 2- way switches.
All as per serial item No. 12 here-in-before but for One bell or buzzer point controlled by by one push button on same board with other or independent switches
M&L for point wiring complete with 2.5 Sqmm (nominal cross section area) FRLSH PVC insulated multistranded unsheathed copper conductor cable drawn in existing conduit including replacement of sunken pressed steel terminal boxes and making good the disturbed surfaces of wall with all jointing accessories including provision of pressed steel sunken terminal boxes made of 1.2mm thick pressed steel sheet, 60mm deep of suitable length and painted with red oxide primer including 2.5 Sqmm PVC insulated multistranded unsheathed copper conductor wire as earth continuity to common earth and connecting to earth dolly for One 3 pin 5 Amp socket outlet on the same board with other switches complete all as specified and directed by Engineer-in-Charge.
All as per serial item No. 13 here-in-before but for One 3 pin 5 Amp socket outlet on independent board.
All as per serial item No. 13 here-in-before but for one socket outlet 3 pin, 15/16 Amps on independent board & sheet metal plug & socket DB
S&F switch piano flush type 6 Amps single pole, one way, complete all as specified and directed by Engineer-in-charge.
S&F socket outlet 2 / 3 pin, 6 Amps, 230 volts, complete all as specified and directed by Engineer-in-charge.
S&F switch piano flush type 6 Amps single pole, two way, complete all as specified and directed by Engineer-in-charge.
S&F switch piano flush type, 15 Amps, 240 volts, flush type complete all as specified and directed by Engineer-in-charge.
S&F socket outlet 3/5 pin, 5/15 Amps, 230 volts, flush type complete all as specified and directed by Engineer-in-charge.
S&F electronic step type fan regulator suitable for ceiling fan of 1200mm / 1400mm sweep,2 Module complete all as specified and directed by Engineer-in-charge.
S&F bell push, flush type, 5 Amp, 230 Volts grade complete all as specified and directed by Engineer-in-charge.
S&F Lamp holder, insulated body with back plate etc complete all as specified and as directed by Engineer-in-Charge.
S&F ceiling rose surface bakelite 65mmx50mm with two or three terminal complete all as specified and directed by Engineer-in-charge.
S&F electric bell (ding - dong), AC, 230 Volts, Single pole & connecting up complete all as specified and directed by Engineer-in-charge.
S&F as in replacement flush mounting factory made SPN DB 8 way, 240 Volt,Double door, IP-43 protection, IK-09 with metal door with 100 Amps copper bus bar, with neutral bar, earth bar and cables ties for cable management fully insulated bus bar complete all as specified and directed by Engineer-in-charge.
S&F as in replacement flush mounting factory made TPN DB 4 way, 240 Volt, Double door, IP-43 protection, IK-09 with metal door with 100 Amps copper bus bar, with neutral bar, earth bar and cables ties for cable management fully insulated bus bar complete all as specified and directed by Engineer-in-charge.
S&F as in replacement flush mounting factory made VTPN DB 4 way, 240 Volt, Double door, IP-43 protection, IK-09 with metal door with 100 Amps copper bus bar, with neutral bar, earth bar and cables ties for cable management fully insulated bus bar complete all as specified and directed by Engineer-in-charge.
S&F as in replacement of MCCB, 125 Amp,4 Pole,16KA, 415 volts with fixed thermal magnetic release complete all as specified and directed by Engineer-in-charge.
S&F as in replacement MCB 40 to 100 Amps, four pole 415 Volts, 10 KA, ‘C’ Curve, complete all as specified and directed by Engineer-in-charge.
S&F as in replacement MCB 25 to 63 Amps, TP 415 Volts, 10 KA, ‘C’ Curve, complete all as specified and directed by Engineer-in-charge.
S&F as in replacement MCB 40 - 63Amps, Single Pole & neutral 240 Volts, 10 KA, ‘C’ Curve, complete all as specified and directed by Engineer-in-charge.
S&F as in replacement MCB 6 to 32 Amps, Single Pole 240 Volts, 10 KA, ‘C’ Curve, complete all as specified and directed by Engineer-in-charge.
M&L for Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6mm thick burried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth of not less than 1.5 metre below ground level, earth plate surrounded by 15cm thick and packed layer of charcoal dust and common salt, connected to earth lead of GI wire 4 mm dia (8 SWG) by means of bolts, nuts and washers of the earth wire galvanised iron or steel and thimbles and other end of the earth wire connected to earthing test point and protected by galvanised iron pipe light grade 15mm dia and water pipe 20mm dia GI light grade top of pipe with funnel & wiremesh, and bottom connected to earth plate by slit and two bolts/nuts/washers, PCC chamber in cement concrete (1:2:4) type B-1 and 40mm thick RCC cover, excavation & earth work complete all as shown in electrical plate No. 3 of MES Schedule Part-I of SSR-2009 including taking down old eathing complete all as specified and directed by Engr-in-charge. Notes :- (i) Cost of GI wire upto 7.5m is included in this item. (ii) PCC 1:2:4, Excavation, earthwork is included in the quoted rate of this item. (iii) Cost of GI tubing upto 7.5m is included in the quoted rate of this item. (iv) Outer edge of earth pit chamber shall be 1.5 metre away from the outer edge of PCC chamber. (v) Minimum weight of reinforcement for RCC cover shall be 1 KG.
S&F Energy efficient decorative ultra slim prewired 9 / 10watt (600mm length) LED light fitting (Mirror light) (Day cool light), surface and wall mounted LED batten, extruded aluminium housing with polycarbonate diffuser & integrated electronic driver and all accessories fixed on wall / hanging complete all as specified and as directed by Engineer-in-charge.
S&F Energy efficient decorative ultra slim, prewired, lumiline 18 watt LED light fitting (Day cool light), batten type with drive & polycarbonate housing including tube rod and all accessories prewired fixed on wall / hanging complete all as specified and as directed by Engineer-in-charge.
Supply and fixing LED lamp minimum 3 star rated 10W LED B-22 base complete all as specified and directed by Engr-in-Charge with following specifications (a) Lumen system efficacy of lamp should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 45°C (d) Power factor : Minimum 0.90 (e) CRI : Morethan 80
Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and as directed.
S&F in repair/replacement Bulk Head wall light fixture 9/10 Watt Environment Friendly Energy saving Edge Lit LED luminare of high brightness IP 65 Protection wall mounted, complete all as specified and as directed by Engineer-in-charge.
Supply, fixing and testing LED Bldg / Security light fitting of 35 Watt, 5700K - 6500 K (including LED drive and internally prewired) complete with body robust, corrosion resistant, superior finish and without any cracks or through holes, made in a single piece by high pressure die cast aluminum alloy. The luminaries shall be monolithic construction totally enclosed dust and water proof with IP -65 / 66 protection as per IS - 10322-1982(Part -I) with latest amendments and input voltage range 140 - 300 V, AC, frequency 50 - 60 Hz ,P.F should be more than 0.9 with Total Harmonic Distortion THD(I) less than 15% ,cool white colour and lamp starting time should not be more than 10 second including 10 KV surge protection in built or external. Driver should be constant current constant voltage driver. Driver should have high voltage withstanding capacity upto 300 V, AC. Driver should also have double phase protection, no load , open circuit and short circuit protection .LED light fitting should be suitable for ambient temperature from -10 degree Centigrade to 50 degree Centigrade and humidity level 10% to 90 % RH. Covers should be polycarbonate/toughened glass to ensure minimum IP 65 degree protection. Cover should not degrade due to heating and ageing. The efficiency of LED luminaries system shall be more than 100 lumens per watt and must be certified by the LM-79 test report and including connection for street light from pole box with 2.5 Sqmm, 3 core PVC insulated stranded copper conductor FRLSH cable, 1100 Volts grade ISI marked including addition / alteration in bracket (if required) for fixing light fitting complete all as specified and directed by Engineer-in- charge.
S&F as in repair street light bracket made out of 32mm dia GI pipe light grade 1.2m long , bent to shape at 120 degree angle from vertical fixed along pole with and including required number of clamp made out of Flat iron 25mm x 6mm with nuts, bolts ,washers etc. duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and as directed by Engineer-in-charge.
Supply and fixing LED flood light 100 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and as directed.
M&L for Sub main wiring complete with 2 single core 6 Sqmm (Nominal area) multi stranded copper conductor PVC insulated unsheathed cable FRLSH drawn in medium duty PVC conduit ISI marked not less than 25mm dia concealed including single core multistranded copper conductor 6 Sqmm size cable as earth continuity wire drawn in same conduit including taking down old unserviceable complete all as specified and directed by Engineer-in- charge Note : Two runs of 6 Sqmm single core cable and one run of 6 sqmm copper wire earth continuty conductor and conduit with fittings shall be measured as one length.
M&L for Sub main wiring complete with 4 single core 10 Sqmm (Nominal area) multi stranded copper conductor PVC insulated unsheathed cable FRLSH drawn in medium duty PVC conduit ISI marked not less than 25mm dia concealed including single core multistranded copper conductor 10 Sqmm size cable as earth continuity wire drawn in same conduit including taking down old unserviceable complete all as specified and directed by Engineer-in- charge Note : Four runs of 10 Sqmm single core cable and one run of 10 sqmm copper wire earth continuty conductor and conduit with fittings shall be measured as one length.
Supplying, laying, jointing, commissioning and testing in replacement PVC insulated screened PVC bedded, armoured, heavy duty underground electric cable with stranded aluminium conductor 1100 volts grade of cross sectional area 25 sq mm 4 core confirming to IS-7098 (Part-I-1988) laid in trenches, along poles through pipes including taking down old unserviceable etc complete all as specified and directed by Engineer-in-charge. Note : Excavation and earthwork, Brick protection and sand cushioning shall be measured and paid seperately
(a) All as per item No 43 above but cable of cross sectional area 16 sq mm 4 core.
(b) All as per item No 43 above but cable of cross sectional area 16 sq mm 2 core.
(b) All as per item No 43 above but cable of cross sectional area 10 sq mm 2 core.
Excavation in trenches n.exc 1.5 m wide and n. exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and as directed by Engineer-in-Charge.
Returning, filling in approved soft/loose soil including spreading, leveling, watering and well ramming in layers each n.exc 25cm complete all as specified and as directed by Engineer-in-Charge.
Removing surplus soil to a distance n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and as directed by Engineer-in-Charge.
M&L for dry sand (Tibba sand) and punning for cushioning to underground cable complete all as specified and directed by Engineer-in-charge. Note: - For payment purpose thickness after punning shall be measured.
M & L for brick protection with old size sub class 'B' bricks laid flat, abutting each other with gap between adjacent bricks not exc. 10mm, length of bricks across the route of underground cable complete all as specified and directed by Engineer-in-Charge.
Supplying and laying for GI pipe light grade 40 mm bore (ISI marked) laid in trenches/ road crossings/ fixed to poles /walls/ path /drain/floors with and including all necessary clamps, nut bolts and washers etc all fitting as required including taking down old unserviceable pipe , complete all as specified and as directed by Engineer-in-Charge.
SHIVA BUILDERS (BID ID -3392695)
godara construction company (BID ID -3392764)
S.K BUILDERS AND ENGINEERS (BID ID -3392703)
SRI SAI CONSTRUCTION COMPANY (BID ID -3384420)
MAJOR REFREGERATION AND ELECTRICALS (BID ID -3392289)
Truly Technos LLP (BID ID -3384101)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .