Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance A 3 257 JANAKPURI NEW DELHI 110058 | WEST DELHI | DELHI | 110058 | Admitted-Finance |
| 2 | Admitted-Finance WZ 1000 B NANGAL RAYA PANKHA ROAD NEW DELHI 110046 | NEW DELHI | NEW DELHI | DELHI | 110046 | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | Admitted-Finance |
Tender Value
₹36.8 L
EMD Value
₹73,600
Closing Date
17 Mar 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
ARJUN PATRO,IDSE
GE U ELECTRIC SUPPLY
PROVISION OF AUGUMENTATION OF POWER SUPPLY SYSTEM AND MISCELLANEOUS SERVICES IN DEVELOPMENT ENCLAVE DELHI CANTT
2022_MES_508947_1
GE ELECT/D-100/2021-2022
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE U ELECTRIC SUPPLY
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE U ELECTRIC SUPPLY
₹73,600
Yes
21 Mar 2022
19 Feb 2022
19 Mar 2022
20 Feb 2022
17 Mar 2022
5 Mar 2022
60 days
Amount
Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 630 Amp, 25kA/3-sec, comprising of Out Going VCB Panel CAMS / Shankar Vihar Area Substation confirming toIEC-62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Insulated Copper busbars and droppers in all bus / breaker/ adaptor and cable chambers , 02nos. Rack-In-Rack-Out Handles, structure made from AluZinc/GI/ Powder Coated CRCA sheets to prevent corrosion and rusting. The complete panel incl. HT and LT chamber with FRLS wiring and acessories shall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products are not accepted .The Make of the VCB, Panel And Relay Shall be of the Same Make / OEM : Note: These HT pannels shall be clubbed in with the existing / fixed with the existing VCB and Bus Coupler of Make: Simens/schnider/ABB/Crompton Makes of Various Substations, and Rate Quoted Shall be inclusive of the Adapter Pannels/ connecting Copper Bus Links
(A) (i) 11kV, 630Amp, 25KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24VDC). (ii) Current Transformers 11kV, 300-150/1-1A, Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA - Set of 03 Nos. (iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs. Relay setting should be possible through inbuilt software or through addtional software supplied by the relay manufacturer. (iv) Metering Equipment including:- (a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy. (vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip (c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required (b) All Multi-function-meters shall be connected in a ModBus loop terminating into 01 No. ModBus-to-TCP/IP converter to be provided for sending data to SCADA console via networking switch.. (viii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation (e) Heater Switch with Thermostat - 01no. (f) 3-pin socket with ON/OFF switch - 01no. (g) LED Lamp with ON/OFF switch - 01no. (ix) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay, (x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel with existing VCB panel relay suituated in the 11 KV CRP for achieving the required protection.
Note for Item 01 (i) Cost of construction of foundation as per manufacturer design, including foundation frame (supplied by OEM), channels etc. for HT Panel as required at site are deemed to be included in the quoted rate. (ii) Each VCB panel being floor-mounted, air-insulated, fully-compartmentalizeds The OEM shall supervise and certify the commissioning/charging of equipment. (iii) Foundation frames shall be inclusive in the scope of supply of OEM. (iv) All Multi-function-meters shall be connected in a ModBus loop terminating into 01 No. ModBus-to-TCP/IP converter to be provided for sending data to SCADA console via networking switch. (v) All Outgoing VCBs will have inter-tripping logic in place to ensure that Incomer breaker immediately trips in case of failure of opening of outgoing VCB experiencing feeder fault. Special and dedicated Alarm shall be in place to issued the user. This facility should be implemented over soft-logic, and can be disabled by authorized personnel without requiring any on-site re-wiring.
Supply laying jointing commissioning and testing of XLPE insulated screened, PVC bedded, galvanized steel strip / wire armoured electric power cable FRLS PVC Sheated (Heavy duty) with multistranded aluminum conductors 11 KV grade of size 240 sqmm 3 core IS-7098 marked suitable for HT 11 KV (Earthed) system laid in Cable Ducts/ trays/ trenches/encased in GI pipes/RCC / DWC / HDPE pipes complete all as specified and directed. Note for Item No.2 (i) Each cable drum not less than 500 Mtr length (ii) The contractor will be responsible for taking permission from appropriate authority i.e. NHAI / IGL / Cantt board or other Units , if needed for the above said cable work. (iii) Manual Excavation has be carried out at the places of Services such as of near Existing HT/LT Cables, OFC/ Telecom Cables , Water / Gas Pipe/ Sewage Pipe Lines, Area Drinages and Contractor shall be responsible for rectification of damages immediately on priority to the damages of Services occured during exection of the cable / earth work.
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and as directed Engineer In Charge
Supply and fix cable jointing kit for 11 KV(Earthed) grade cable for indoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 240 sqmm to 300 sqmm
Excavation in trenches not exceeding 1.5 m wide and exceeding 1.5 m in depth and getting out Soft/loose soil for laying U/G cable, pipe pole foundation etc all as specified.
Removing excavated material (soils) to a distance n.exc 50 m and depositing where directed at the level n exc 1.5m above the starting point complete all as specified and directed.
Returning, filling in including spreading levelling watering and well ramming in layers not exceeding 25 cm thick each in soft/loose soil complete all as specified.
Supply & laying un- reinforced precast concrete cable cover class HVP type 1 with peak size 300 mm x180mmx40mm in trenches for protection to under ground cable complete all as specified.
Material and Labour for river washed and screened dry sand for filling in trenches below and around underground dry sand for filling in trenches below and around underground cable for cushioning of cables complete all as specified.
Supply and fix cable route indicator made of RCC(Nominal mix) type BO 1:2:4 (12.5 mm graded stone aggregate) with 8 mm TMT Bar 1.5 M height x 60 cm wide x 800 mm thick tapered on top visible above ground duly painted with synthetic enamel paint of Blue colour base and letters with black paint. The description for writing for HT cable 11000 volts will be given by Engr-in-charge/Accepting officer complete all as specified and as directed.
M&L for plate earthing complete with galvanised mild steel plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground vertically (in earth pit not less than 2.25 m below normal ground level) with the top edge of the earth plate at a depth not less than 1.5 m below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides and incl GI earth strip 32x6 mm bolted (with GI nuts, bolts & check nuts) and riveted to earth plate at one end and connected to metallic bodies of HT/LT equipments etc at the other, earth strip encased in and including 40mm bore GI grade pipe with all fittings from top of electrode to body of equipment fixed with and including 25x6mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 50mm bore GI pipe medium grade from bottom of earth pit to top of electrode complete with wire mash and funel earth pit in PCC 1:2:4 type B-O using 12.5 mm graded crushed stone aggregate excavation and earth work and RCC cover complete all as specified and shown in electrical plate No 3 of SSR Pt-I.
Supply, Designing, Engineering, Installation, Integration, Commissioning and Testing of Substation Automation System (SAS) for 11 kV substations as per proposed system architecture, suitable for minimum 1000 I/O points and to integrate the same with upper level SCADA/DAS complete with the following:- (i) Remote Terminal Unit (RTU) or Data Concentrator Unit (DCU) suitable for connecting Numerical relays on IEC 61850 protocol and Multi-Functional Meters (MFM) on Modbus protocol. RTU/DCU shall have following configuration as minimum:- (a) Processor (Industrial Grade) (b) Memory 64 MB (c) Communication Protocols IEC 60870-5-104, DNP3, IEC 61850 and Modbus (d) Ports 3 x RJ45 Ethernet, 1 x RS 485, and 2 x RS 232. (e) 8 Digital input (f) Operating Voltage Range 24 V DC, +/- 15% (g) Security Protocols IPsec, SSL and SRTP (h) Cyber Security as per IEC62351 & IEC62443 (j) Protection Degree IP 54 (k) Operating Temperature range -20degC to 60degC, Humidity upto 95% (l) Support two redundant physical channel communication to one control centre
RTU module shall be of industrial grade, continuous duty, EMC compliant substation management unit and act as a gateway for interfacing with relays over IEC 61850, meters on Modbus and upper-level SCADA/DMS on IEC-104 protocol. RTU shall obtain substation feeder data like breaker ON/OFF/TEST/SERVICE position, Spring charge, TCH etc on IEC 61850 protocol and energy parameters like current, voltage, kVA, kW, kWh, kVAR, pF, Hz etc. on Modbus protocol via daisy chain and shall integrate the same with upper level SCADA. (ii) Industrial grade managed type Ethernet networking switch for star-coupler connection to all IED’s over IEC 61850 platform and upper level scada on IEC 104, suitable with 24 V DC supply and have minimum 16x10/100/1000 Base-T RJ45 and 2xFO ports. (iii) LTE router/modem for transmitting data on IEC 104 protocol and having following configuration as minimum:- (a) Ethernet port RJ45, RS 232 (b) Communication Protocols - Modbus RTU to TCP support, Modbus master (c) Security - Zone based firewall, VLAN, DMZ, HTTPS local & remote connection, SIM PIN (d) Routing - DHCP, static routing, port forwarding, traffic routing, static / dynamic DNS, DNS proxy, NAT, STP (e) Operating Voltage Range 24 V DC, +/- 15% (f) Operating Temperature range -20°C to 60°C, up to 95% RH (g) Dual SIM (one standby) via two mini-SIM held in trays
(iv) Cabinet of minimum dimension 1000x800x300mm, made of 2 mm CRCA sheet, glass on front door, having multi-tier-arrangement, suitable ventilation and cable-entry/routing arrangement, IP 55, conforming to IEC 60529 and having following:- (a) Power Supply module 110-230/24V DC, 5A – 01 No (b) Power Supply redundancy module, 24V DC, 10A – 01 No (c) Door Limit Switch (d) Illumination Light (e) Control MCB (f) Space Heater with Thermostat (g) Air Filter Louver with Fan
(h) Panel wiring & other accessories as per OEM recommendation (v) LAN Cable (CAT5/CAT6) with sufficient number of RJ-45 terminals, suitably routed via substation trenches/ducts/walled-pipes including cable tray/conduit as per site conditions from 11 kVHT VCB Panel upto Ethernet switch / RTU module. (vi) PVC insulated and sheathed Copper control cable 1.0 Sqmm x 2 core for Modbus communication via daisy chain, with isolation MCBs and suitably routed via substation trenches/ducts/walled-pipes including cable tray/conduit as per site conditions from MFM to RTU module. (vii) Integration of all IEDs and MFMs with RTU module, tagging of data points as per requirement of upper level SCADA, integration with upper level SCADA control centre on IEC 104 complete all as specified and as directed. (viii) Any other item/service required for complete system delivery of SAS is deemed to be included in the present scope of work and no extra claim shall be entertained in this regard.
Supply installation & commissioning of 24V/20A Bank single phase Float cum boost battery charger unit including battery bank comprising 12 Nos of 2 volts 100 AH sealed maintance free battery. The CCCV battery charger consisting of diodes and SCRs , liberally rated mounted on heat sinke and complete with resistor/condensor network for surge suppression. during auto float mode to boost mode and vice versa ,01 set of solid state consant potential contoller to establise he DC output voltage of the float cum boost charger 01 nos , elecytonic controller , DC digital ammeter , DC digital Volt meter , potential meter , DC MCB for reerse battery potential.
The charger sshould have alarm , annuciation with visual and audibl alarm with manual reset facility with fuse fail alarm. Float cum Boost battery charger and DC distribution board shall be houst in porder caoted sheet steel cubical with pannel of 1.6 mm thickness, lowers for ventilation gland plate will be provied from canle entry from bottom. Th ebattery charger should be divided inti two compartment. The upper compartment shall house the battery charger an DCDB with all necessary control. The Lowwer compartmenet shall be suitable for housing the battery at Shankar Vihararea Control panel room. technical specification shall be as under:
(a) Input working voltage 180 - 270 Volts. (b) Nomonial input vltage 230 V , AC, 50 Hz, (c) On load input power factor >0.8 (d) On load unit watt efficiencies .80% (e) No load losses of complete chages < 10% (f) Ripple content on the load (RMS) = 1 to 5 % (g) Over load 110 5 for 30 Minutes and will give visual indication for overload condition (h)boost charging 2.4 V/Cell (j) Foat charging 2.15 V/ cell (k) Float cum boost charging automatically charges from give the visual indication for either float or boost based on charging mode (l) reverse polarity No damage will cause . A visual indication for reverse polarity will appear with an audio alarm (m) Short circuit MCB protection provided
NOTE :-(i)contractor should provide 50 % of the material as listed above within 15 days of the placing of work order and shall be verified by the Eng-in-charge.
M/s Adhikari construction co.
mayur enterprises
Vijay Electricals
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .