Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.2 LAccepted-AOC 72 USMAN ENCAVE SECTOR O ALIGANJ LUCKNOW 226004 UP | LUCKNOW | LUCKNOW | UTTAR PRADESH | 226004 | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹24.1 L+₹1.2 L (5.40%)Rejected-Finance | L2 | Rejected-Finance Not Being Lowest |
Tender Value
₹24.9 L
EMD Value
₹49,800
Closing Date
28 Oct 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE LUCKNOW
229 MG Road Lucknow-226002
MAINTENANCE AND REPAIR TO 11 KV GODs INSULATORS LIGHTING ARRESTORS BUS BAR AND OTHER CONNECTED WORKS AT VARIOUS LOCATION OF CANTT AREA UNDER GE E/M LUCKNOW.
2021_MES_478367_1
CA NO CWE/LKO/EM/T-46 OF 2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
CANTT LUCKNOW
Class E and cat b(ii)
8 documents required · 8 mandatory
₹500
GE EM LUCKNOW
₹49,800
Yes
27 Nov 2021
28 Sept 2021
30 Oct 2021
28 Sept 2021
28 Oct 2021
16 Oct 2021
60 days
Amount
Dismantling air break gang operated switches vertical/horizontal mounted including insulators and operating machanisum for repapir/replacement of broken/worn out components and insulators for replacement etc ecomplete all as specified and directed.
Supply, fix, testing and commissioning of air break gang operated switch (pactel make), triple pole mechanically operated out door type with all fittings/accessories mounted on and including 11 KV HT 9 Nos porcelain insulators and steel channel frame, GI operating rod 25mm dia of suitable length with operating mechanism worked form ground level, vertically operated including locking arrangement & operating handle, with and including 7 levers lock of Navtal make complete suitable for current rating of 400 Amps HT 11 KV working pressure complete all as specified and directed.
Supply, fix, testing and commissioning of air break gang operated switch (pactel make), triple pole mechanically operated out door type with all fittings/accessories mounted on and including 11 KV HT 9 Nos porcelain insulators and steel channel frame, GI operating rod 25mm dia of suitable length with operating mechanism worked form ground level, vertically operated including locking arrangement & operating handle, with and including 7 levers lock of Navtal make complete suitable for current rating of 200 Amps HT 11 KV working pressure complete all as specified and directed.
Supply and fix drop out fuse unit expulsion type for out door air break gang operated switch, single pole, mounted on and including insulators for 11 KV working pressure, fixed to and including MS channel with nuts, bolts, washers etc synthetic bounded fuse carrying tube complete with line taps and suitable for current carring capacity upto 50 Apms only complete all as specified and directed.
S&F lighting arrestor explusion type complete with all fitting, transmission class, discharge capacity 65 kilo amps suitable for 11000 volts complete all as specified and directed.
Disconnecting the all existing electrical connection from four pole structure & taking out unserviceable droput fuse and lighting arrestor etc complete all as specified and directed.
Preperation of old painted surface and painting with 4 pole/two pole structure of HT steel tubular pole 11 mtr long from bottom to top incl all iron structure with asian aluminium paint and painting to bottom up to 1.5 mtr height from top of PCC coping with asian synthetic enamel paint one coats in Red /ylloow/blue alternate strip incl numbering in 8 cm height of number with black paint dully approved by Engineer-in-charge and complete all as specified and directed.
M & L MS plate made of 1.6mm thick of size 30cmx30cm fixed with suitable size ms flat iron with nut,bolt & washer and painted with red colour synthetic enamelled paint and write 8 cm height letter in white colour (feeder Name) as directed.
M & L Danger notice plate made of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S clamps, bolts and nuts of approved size, for HT, 25mmX20mmX 1.6mm size complete all as specified and directed.
Disconnecting all existing electrical connection from four pole structure & taking out unserviceable/ burnout HT jumpher cable/conductor with nut,bolt,washer and M&L PVC insulated sheathed unarmoured stranded aluminium conductor single core cable of size 95 sqmm incl cutting, thimbling, & new aluminium lugs, GI nut,bolt and washer etc complete as directed. Note- (i) Length of cable should not be less than 2.5 mtr. (ii) 3 core cable jumper measured as one job
S&F Cold shrinkable, in door type, cable termination kit with all accessories suitable for 11 KV (earth) HT XLPE Cable of size 50 to 95 Sqmm 3 core incl disconnecting/connecting the cable in RYB phase sequence in pole/RMU incl cutting the unserviceable portion and testing after connection in all respect etc complete all as specified and directed.
S&F cold shrinkable, in door type, cable termination kit with all accessories suitable for 11 KV (earth) HT XLPE Cable of size 120 to 185 Sqmm 3 core incl disconnecting /connecting the cable in RYB phase sequence in RMU/pole incl cutting the unserviceable portion and testing after connection in all respect etc complete as specified and dierected.
S&F Cold shrinkable,outdoor type, cable termination kit with all accessories suitable for 11 KV HT (earth) XLPE Cable of size 50 to 95 sqmm, 3 core incl disconnecting /connecting the cable in RYB phase sequence in RMU/pole including cutting the unserviceable portion and testing after connection in all respect etc complete all as specified and directed.
S&F Cold shrinkable,outdoor type, cable termination kit with all accessories suitable for 11 KV (earth) HT XLPE Cable of size 120 to 185 sqmm, 3 core incl disconnecting /connecting the cable in RYB phase sequence in RMU/pole incl cutting the unserviceable portion and testing after connection in all respect etc complete all as specified and directed.
S&F Cold shrinkable straight through joint kit with all accessories suitable for 11 KV (earth) HT XLPE cable of size 50 to 95 sqmm, 3 core incl cutting the userviceable portion and jointing cable in RYB phase sequence and testing complete all as specified and directed.
S&F Cold shrinkable straight through joint kit with all accessories suitable for 11 KV (earth) HT XLPE cable of size 120 to 185 sqmm, 3 core incl cutting the userviceable portion and jointing cable in RYB phase sequence and testing complete as specified and dierecd .
Hiring of cable fault detector machine to detect exact position of faulty XLPE /PVC HT cable, 11000 Volts grade heavy duty aluminium conductor of any size and any length including excavation, relaying of protection cable cover, & removing and earth filling etc complete all as specified and directed. Note : If any defect occurred at any place of Lucknow cantt area, the contractor will provide mechanic & fault locator with material within one hours for rectification of defects. If the contractor not provide the mechanic and material with schedule time, the amount will be deducted @ Rs1000/hrs after receiving phone/massage/ whatsapp /email etc complete all as specified and directed.
Supply and fixing fire retardant electric insulation synthetic mat INSULATICA 2000" for 11 KV 3.0 mm thick +10% conforming to BIS DOC No ETD -02 (5231) P dt 2003. meeting requirement of IS 3043, IS: 5216 (Part 1,2,3) IS : 8437 and IEC 479 pub-1 IEC 61111 & 61112 tested for brake down strength tensile /elongation ageing properties. Insulation resistance, affects of acid, alkaline, Diesel & transformer oil, leakage current test fire test etc. having min width of 1000m + 20 mm complete as required suitable and using adhesive and allied chemical and scaling of all joints and border ends and fixing decorative taps the installed sheet complete as specified and directed.
Disconnecting the all electrical connection and taking out the unserviceable cable from trenches/duct/pole/ wall any type/capacity/make complete all as specified and directed.
Supplying, laying, jointing, testing and commissioning in replacement HT under ground electric power cable Crossed linked polyethylene (XLPE) insulated, screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor, 11000 Volts grade suitable for earth system of 3 core 150 Sqmm cross sectional area size, ISI marked as per IS 7098 Part-2, laid in trenches/ laid under floor/ laid in ducts or fixed on poles etc. complete all as specified and directed.
Supplying, laying, jointing, testing and commissioning HT under ground electric power cable Crossed linked polyethylene (XLPE) insulated, screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor, 11000 Volts grade suitable for earth system of 3 core 120 Sqmm cross sectional area size, ISI marked as per IS 7098 Part-2, laid in trenches/ laid under floor/ laid in ducts or fixed on poles etc. complete all as specified and directed.
Supplying, laying, jointing, testing and commissioning HT under ground electric power cable Crossed linked polyethylene (XLPE) insulated, screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor, 11000 Volts grade suitable for earth system of 3 core 95 Sqmm cross sectional area size, ISI marked as per IS 7098 Part-2, laid in trenches/ laid under floor/ laid in ducts or fixed on poles etc. complete all as specified and directed. Note for item 20,21&22 :- Excavation/ boring of raod/ pipe shall be measured and paid separately under respective items.
Cleaning the sub station in side & out side building/fencing of transformer /two/four structure and also incl around 2 m radius out side of fencing in every month duly taking down unwanted material/grass/vegetable roots/small tree incl spraying the chemical (Roundup) in sub station in the ratio 1: 3 for burning the grass as specified and directed.
M&L for disconnecting burnt end or portion of 25 sqmm to 185 sqmm 3 ½ core cable removing the cable from loop including necessary excavation, earthwork, removing brick protection and relaying the same, and reconnecting the cable by removing burnt portion of cable and preparing fresh terminals of LT/HT cable to transformer/panel/pole etc complete all as specified and directed.
S&F in repairs copper bus bar any rating incl cutting/drilling of suitable size holes as required at site and also copper nut,bolt,washer etc complete all as specified and directed.
S&F in repairs aluminium bus bar any rating incl cutting/drilling of suitable size holes as required at site and also GI nut,bolt,washer etc complete all as specified and directed.
Material,labour and T&P for disconnecting the HT/LT connection of the transformer from pole/in side sub station/plinth and taking out the trnasformer from poles/plinth/inside the sub sation and shifting the same at directed place with the help of hydraulic/crane and making the connection of the HT & LT side as directed at any location in the cantt area incl testing complete all as specified and directed.
M&L for construction of plinth of size 1.8x1.8x 2.1 M (LXBXH) with PCC 1:3:6 type C2 using 40mm graded stone aggregate incl brick works with old size sub class B bricks straight or curved on plan exc 6 m means radius build in CM 1:6 incl rendering for mounting of transformer over all height 2.4 M (0.60m below the ground level and 1.8 m over the ground level) suitable for upto 500 KVA TRF complete all as specified and directed. Note- Drg will be approved by Engr-in-charge
M&L for earthing with galvanized steel earth plate electrode 600mm x 600mm x 6mm buried directly in ground (earth pit not less than 2.25 metre deep below ground level) vertically, with top edge of the plate not less than 1.50 mtr below normal ground level, connected to galvanized iron wire 32x6mm dia by means of nuts, bolts, washers of GI steel all as shown on electrical plate No 3 of MES Schedule Part I connected to earthing test point and testing on completion with and including necessary excavation and earth work, earth electrode, earthing lead from electrode to equipment/substation, adequate quantity of charcoal dust and common salt, test point, PCC (1:3:6) type C-1 (using 20mm graded black trap/granite/Basalt stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, pre cast RCC (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate) 40mm thick cover, reinforced with 6mm dia bars 3 Nos both way with 12mm dia round bar handle, GI light grade watering pipe 20 mm dia with funnel and wire mesh, and 15 mm dia GI light grade earth lead protection pipe, complete all as specified and directed. Contd......
Note : (i) Main earthing lead from earth plate electrode to test point upto length of 7.50 mtr shall be deemed to be included in the unit rate quoted by the tenderer against this item. (ii) GI protection pipe and earthing strip beyond 7.5 mtr long shall be measured and paid separately . (iii) Test result should be less than 1 ohms or satisfaction of user. if result not found less than 1 ohm the contractor do the earthing as disired result at own cost. (iv) Quantiy of coal 60 Kg and quantiy of salt shold be 100 Kg for each earthing
M&L for servicing of GOD mounted on pole with cleaning the moving and fixed contact and removing the old grease and greasing the moving and fixed contact of GOD with new grease incl tighting of nut,bolt and washer of GOD complete all as specified and directed.
Material and labour for cross arms, bracings, supports, clamps & back plates fabricated from structural steel sections including galvanised nuts & bolts, washers welding, bending cold or hot, drilling holes for bolts, in any shape or size as specified and including one coat of primer, one under coat and finishing coat with aluminium paint complete all as specified and directed.
Supply, install and erect in true vertical position (or to be fixed in an inclined position as strut pole) steel tubular swaged welded poles complete with C.I. base plate of 6 mm thick of size 300mmx300mm, B 118 finial taper plug, pole cap, bolts, nuts and washers and screwed, pole made out of MS tubing conforming to IS-2713 Part II, type 410-SP-55 ( 11 meters long) H.T poles including drilling of holes of required size and Nos for fixing of cross arms, painting with one coat of red oxide primer and two coats of black bituminous paint for portion embeded in concrete, painting three black/red/bands at lower portion of pole each of 300mm height at 300mm spacing, painting pole No with black paint at suitable height, complete all as specified and directed incl taking down old one complete all as specified and directed.
M&L pin type insulator porcelain, vitreous white, brown or green insulator incl one galvanised mild steel spindle two galvanised iron washer and one galvanised iron nut, 150mm height, 155 mm dia suitable for 11000 volt grade complete all as specified and directed.
M&L Disc type porcelain insulator, vitreos, white, brown or green insulator incl galvanised mild steel strap of size 31x3 mm washer insulator bolts 12 mm dia washer and nuts, 145mm height 255 mm dia ball and socket type max dia for 1100 volts grade working pressure with galvanised steel fitting complete all as specified and directed.
Supply, strining, streching and fixing and strengthening on insulators, ACSR conductor, including aluminium binding wire of of suitable cross sectional area (but not less than 16 SWG)Including line connectors vice type having two brass plates, bolts and nuts etc or compression crimping type sleeve joints for jointing conductors of equal or unequal size or for jumpers connections, including jelly complete all as specified and directed.
Renewal of existing earthing (GI plate earthig) with provision of new layers of charcoal and salt all as specified in electrical plate No 3 of SSR Part-I, including cleaning of existing GI earth plate, strip/wire etc and connecting with new bolts, nuts and washers complete and testing on completion in all respect as directed. Note: - (i) Excavation, PCC for earth pit and cover, watering pipe, funnel with wire mesh, earth lead and protection pipe shall be measured and paid separately. (ii) Salt 100 Kg and coal -60 kg should be minimum
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth and getting out for earthing and earth lead complete all as specified and directed.
All as per item No 37 above but depth exceeding 1.5 and not exceeding 3 metres
Returning, filling in and including spreading, levelling, watering and well ramming in layers n. exe 25 cm each in any type of soil all as specified and directed.
Removing excavated material to a distance not exc 50 metre and depositing where directed at a level not exc 1.5 metre above the starting point complete all as specified and directed.
S&F in repair CI funnel made as specified in SSR Part -I electrical plate No 3 fixed with GI pipe for watering by welding or threading etc complete all as specified and directed.
S&F galvanised steel tubing 20 mm bore light grade with all fittings in earthing for watering the earth including taking down old steel tubing complete all as specified and as directed.
S&F galvanised iron strip as earth continuity conductor or main earthing lead fixed to walls or burried in ground of size 32x6 mm complete all as specified and directed.
S&F GI plate of size 60cmx60cmx6mm suitable for earthing & fixed with 3 Nos GI nut bolt and washer incl making holes for nut & bolt including brazing & taking down old one etc complete all as specified and directed.
M&L for pre cast RCC (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate) 40mm thick cover, reinforced with 6mm dia bars 3 Nos both way with 12mm dia round bar handle, earth pit cover as per existing size including necessary formwork complete all as specified and directed.
M&L for Earth pit chamber PCC (1:3:6) type C-1 (using 20mm graded black trap/granite/Basalt stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, pre cast RCC (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate) 40mm thick cover, reinforced with 6mm dia bars 3 Nos both way with 12mm dia round bar handle as specified in SSR 2009 Part I Electrical Plate No 3 incl taking down old one and deposited broken pit cover as directed place etc complete all as specified and directed.
Servicing of air circuit breaker (MDO/EDO type) and disconnecting the electrical connection from unserviceable parts and taking out the unserviceable material from the ACB and fix the new material as per existing make/model/capacity incl cleanding and greasing fixed and movement parts etc complete all as specified and directed. Note :- (i) The rates quoted by the contactor shall include cost of any other spare parts not mentioned herein after but essentially required for functioning of the system. (ii) Unit rates quoted by tenderers shall deem to be included for, bolts, washers, lugs, thimble, wires and petty items required for efficient and smooth functioning of the equipment without any extra cost to the Govt. (iii) Material required in this item shall be measured as supply only in respecteive items.
Supply only Shunt release
Supply only Under voltage release
Supply only Earth fault release
Supply only Remote fault indicator
Supply only Microswitch for indication
Supply only lockable trip push botton
Supply only locking ACB in isolating position
Supply only locking ACB in any position
Supply only racking interlock
Supply only door interlock
Supply only mechanical operation counter
Supply only Mounting kit for front mounted counter
Supply only sspring charge indication micorswitech
Supply only racking pad lock assembly
Supply,install,testing and commissioning of LT distribution board cubical & indoor type factory made CPRI tested, dust and vermin proof fabricated to 2 mm thick CRCA sheet size of panel as per manufacturer norms and mounted on angle iron and tee section frame of size 50x50x6mm and double door front/rear opening and locking arrangment floor mounted, bus bar chamber with 1000 amps capacity aluminum bus bar fixed on post insulator inclduing painting with powder coated as specified and pre-wired with suitable size PVC insulated sheathed copper conducotr cable duly incl taking down old one LT panel and earth & PCC works complete in all respects and including the following :- (a) One No - Air circuit breaker electrical 4 pole draw out with microprocessor release with ITD,STD instantaneous, ground fault & IED indication, auxillary switch, main CTs for polyester resin cast CTs-800/5, ATB 064 for 3 phase & ATB-060 for neutral, safety shutter, 36 way auxillary isolating contacts, AC/DC charging motor, closing coil, shunt trip, anti-pumping relay, micor switches as required for electrical operation under voltage trip device (UVT coil with 500 msec time delay upto 1600 Amp) with spare parts as per manufacturer list complete of capacity 630 amps Make C&S or equivalent in Siemens/L&T/ABB
Prime power system
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .