Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.8 LAccepted-AOC H NO 01 MADINA BAGH MEHJOOR NAGAR NEAR HOTEL RAFADA SRINAGAR 190015 J K | BUDGAM | JAMMU AND KASHMIR | 190015 | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹17.0 L+₹1.3 L (7.96%)Rejected-Finance HOUSE NO 102 LANE NO 4 C ANAND NAGAR BOHRI JAMMU 180002 J K | JAMMU | JAMMU AND KASHMIR | 180002 | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹17.7 L+₹1.9 L (12.3%)Rejected-Finance | L3 | Rejected-Finance Other than lowest | |
| 4 | L4₹21.6 L+₹5.8 L (37.0%)Rejected-Finance | L4 | Rejected-Finance Other than lowest |
Tender Value
Refer Docs
EMD Value
₹48,000
Closing Date
3 May 2021, 6:00 pmClosed
GE (I) 873 EWS
Garrison Engineer (Indep) 873 Engineer Works Section PIN 913 873 C/O 56 APO
PROVN OF CERTAIN E/M WORKS AT CHANDERKOT, KISHTWAR AND PATNITOP UNDER GE (I) 873 EWS
2021_MES_434117_1
NIT-73 of 20-21
Open Tender
Miscellaneous Works
Item Rate
180 days
Bhaderwah
As per NIT
7 documents required · 7 mandatory
₹500
GE (I) 873 EWS
₹48,000
Yes
11 May 2021
3 Apr 2021
6 May 2021
3 Apr 2021
3 May 2021
19 Apr 2021
Amount
Excavating in trenches, not exceeding 1.5metre wide and not exceeding 1.5metre depth for foundation, laying of cables etc., and getting out in any type of soil, complete all as specified and directed.
Excavating in trenches, not exceeding 1.5metre wide and exceeding 1.5metre depth but not exceeding 3.0metre depth for foundation, etc., and getting out in any type of soil, complete all as specified and directed.
Sand cushioning to underground cables using new dry river sand laid in trenches 8cm thick below the cable and 15cm thick above the cable after laying and stretching the cable complete, punned to 18cm, complete all as specified and directed Note : Punned thickness of 18cms shall be measured for payment.
Supply and laying brick covering with width equal to length of bricks as mechanical protection to underground cable using old size sub class 'B' bricks, laid flat size 230mm x 115mm x 75 mm with width of brick perpendicular to length of cable, all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick any type of soil, complete all as specified and directed.
Removing excavated soils to a distance exceeding 50m but not exceeding 100m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
Cement concrete type C-2 1:3:6(using 40mm graded crushed stone aggregate) as in foundation filling and mass concrete, complete all as specified and directed.
Cement concrete type D-2 1:4:8 (using 40mm graded crushed stone aggregate) as in foundation filling and mass concrete, complete all as specified and directed.
Cement concrete type B-1 1:2:4 (using 20mm graded crushed stone aggregate) as in coping of poles, complete all as specified and directed.
Stay assembly complete with accessories as shown in Electrical Plate No.1 of SSR 2009 Part-I using stay rod of 20 mm dia, stay bow 14 mm dia, 400 mm long, MS Plate of size 300 x 300 mm x 6mm thick, stay GI wire 7/4mm dia, loop type insulator 90x140mm clearance of hole 16mm, stay clamp (Excavation and concrete shall be measured and paid separately) complete all as specified and directed.
Steel Tubular swaged poles type 410 SP-31 (9.0 mtr long) conforming to IS : 2713 Part-I to III 1980, complete with 6 mm thick mild steel base plate, finial taper plug, MS bolts, nuts, screws including painting upto 1.5metre above PCC coping in black and white strips 05 Nos of 30cms each starting from the bottom of the pole and two coats epoxy based paint aluminium grade finish to the remaining external surface over one coat of primer complete including taking down old unserviceable pole all as specified and as directed.
Sheet metal enclosure for DBs, SPN 2 Way 240 Volts complete with and including MCB SPN 6 Amps, 240 Volts, 10 KA complete and fixed including taking down old all as directed by Engr-in-Charge.
Sheet metal enclosure for DBs, SPN 2 Way 240 Volts complete with and including MCB SPN 6 Amps, 240 Volts, 10 KA complete and fixed all as directed by Engr-in-Charge.
XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade ISI marked cross sectional area 16 Sqmm 4 core laid in trenches/ fixed to poles etc., complete all as specified and as directed.
XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade ISI marked cross sectional area 16 Sqmm 4 core laid in trenches/ fixed to poles etc. including taking down old unserviceable cable, complete all as specified and as directed.
XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade ISI marked cross sectional area 16 Sqmm 2 core laid in trenches/ fixed to poles etc., complete all as specified and as directed.
XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade ISI marked cross sectional area 35 Sqmm 4 core laid in trenches/ fixed to poles etc., complete all as specified and as directed.
Steel pipe galvanised light grade, 40 mm bore laid in trenches or under ground/floor or road of fixed with pole for protection of cable including GI clamps with bolts nuts and washers complete all as specified and directed.
1100 Volt grade heavy duty cable PVC Insulated aluminium conductor, served with inner sheathing of PVC tape and over all PVC sheathed in service connection suspended by insulating hanger not more than 1 mtr apart including 4 mm suspension wire, one twin core cable flat or circular 16 sqmm stranded conductor including taking down old, complete all as specified and directed.
1100 Volt grade heavy duty cable PVC Insulated aluminium conductor, served with inner sheathing of PVC tape and over all PVC sheathed in service connection suspended by insulating hanger not more than 1 mtr apart including 4 mm suspension wire, one twin core cable flat or circular 10 sqmm stranded conductor, complete all as specified and directed.
1100 Volt grade heavy duty cable PVC Insulated aluminium conductor, served with inner sheathing of PVC tape and over all PVC sheathed in service connection suspended by insulating hanger not more than 1 mtr apart including 4 mm suspension wire, one twin core cable flat or circular 10 sqmm stranded conductor including taking down old, complete all as specified and directed.
Street Light fitting 60 Watts LED made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having top opening separate driver compartment with IP66 protection and impact resistance of IK07 with 10KV built-in surge protection device including including street light bracket made out of 40mm bore GI tubing medium grade 1.2m long bend to shape by welding fixed with 02 Nos clamps made out of MS flat iron 40x5mm, complete all as specified and as directed. Make : Havells 'Endura Pearl Plus' Cat Part No SL60WLED757SASYTOPC or equivalent in Wipro / Philips / Crompton / Syska
PVC copper conductor cable 1.5sqmm twin core fixed as in connection to street light from DB, complete all as directed.
Supply, installation, testing, Commissioning of reverse Osmosis+Voilet Purifying system for capacity 250 ltrs/Hrs, Duty Cycle 16 Hours (max) mounted on steel frame heavy duty structure as per manufacturer instructions, with following parameters:- (a) Pre Filteration (b) Granular activated carbon filter (c) Carbon block filter (d) RO Membrane (e) Ultra Voilet rays (f) Post carbon filter (g) Dosing system of suitable capacity to dose anti-scalant chemical to protect the scaling formation on RO membrane of RO plant Make:- Renuka Water Treatment, Model: RWT-ROS-C250/ Kent elite Mineral RO/Declibac
Supply and installation, testing and commissioning voltage stablizer for automatic operation, single phase, naturally air cooled indoor type and designed for input variation between 90V to 230V with output voltage stablized at 230 V with accuracy of +- 2.5% and of capacity 5 KVA, complete all as specified and as directed.
Steel stagging made out of 65x65x6mm thick angle iron compete including necessary cutting, welding, grinding, earth work and grounting with PCC 1:3:6 in a four legs of staging at size 450x450x600mm thick for mounting of 1000 ltrs tank and complete installation all as specified and directed.
Rotational moulded polyethylene water storage tanks triple layer (cylindrical vertical with closed top) hoisted and fixed in position, including over flow and drain out pipe complete of 1000 litre capacity complete all as specified and directed.
Steel water tubing medium grade galvanised with all fittings including short lengths, fixed to walls, concealed in wall and ceiling or laid in floor complete with all fittings of nominal bore dia 20mm, complete all as specified and as directed.
Gate valve, cast copper alloy screwed down high pressure, with crutch or butterfly handle, screwed down both ends for iron pipe or for unions of 20mm bore and fixed , complete all as specified
Bib taps, cast copper alloy, screwed down high pressure, with crutch or butterfly handle, for bore of pipe 20mm, complete all as specified
Socket outlet combination universal type, 2 in 1, 6 pin 5 and 15 Amp, piano flush type, 230 volts, complete all as specified and as directed.
Cutting & screwing existing steel tubing of 20mm bore for addition/alteration or lengthening screw on pipe from connecter and done in position without taking down, complete all as directed.
Earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick buried directly to ground vertically to a depth not less than 2.25 Mtr below the ground level with top edge of earth plate not less than 1.65 Mtr below normal ground level connected to GI strip 25 x 4 mm size and earthing lead protected with 50 mm bore GI pipe, light grade, filling around with charcoal dust and salt including excavation, returning, filling of earth and disposal of surplus soil to a distance not exceeding 50 mtr and connected to GI strip by means of GI nuts, bolts and washers strip connected to earth plate including chamber PCC 1:3:6 type C-1 using 20mm graded crushed stone aggregate in concrete pit pre-cast RCC 40 mm thick reinforced with 6 mm dia round at 75 mm C/C both way with 12 mm dia mild steel plain bar lifting handle 2 Nos funnel with wire mesh 20 mm dia GI pipe light grade watering pipe and frame work complete all as shown in electrical plate No. 3 of SSR Part-I 2009 including testing on completion complete all as specified and as directed.
Earthing complete with galvanized mild steel earth plate electrode size 600mm x 600mm x 6mm thick buried directly in ground (preferably in vertical position) earth pit not less than 2.25 meter below normal ground level with top edge of the earth plate not less 1.5 meter (BGL) connected to galvanized iron earth lead wire 4mm dia by means of bolts, nuts, check nut and washer of galvanized iron including PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, excavation and earth work in any type of soil, 20mm bore “medium grade” galvanized iron water tubing fixed with cast iron funnel and wire mesh and 15mm bore “light grade” galvanized iron protection pipe for earth lead wire upto 5m length, charcoal, common salt, complete all as shown in EP No 3 of SSR 2009 Part-I, connected to test point complete, all as specified and testing on completion.
Supply, installation, Commissioning and Testing of Feeder Pillar Box, Kiosk outdoor type, CPRI type tested, LT 440 Volts, 50 Hz, TP, 4 wire supply, Floor mounted factory fabricated weather and vermin proof made out of 3 mm thick MS Sheet CRCA Sheet on angle iron 50 x 50 x 6mm frame of size 0.90 x 0.60 x 0.50 mtr suitable any capacity with front and rear opening doors, handle type locking arrangement powder coated internally and externally shall have channel base of appropriate size and mounted on PCC foundation of size as required or approved by manufacturers in PCC 1:3:6 Type C-2 including earth work complete with bus bar chamber comprising 4 Nos copper strip bus bars PVC insulated made of copper strip of size 40 x 5mm, PVC sheathed with colour coding, complete all as specified and directed with and including following fitments:-
(A) Incoming (i) MCCB 160 Amps, breaking capacity 35 KA, FP, 415 Volts with microprocessor release complete with spreader links – 01 No (B) Outgoing (i) MCCB 100 Amps, breaking capacity 35 KA, FP, 415 Volts with microprocessor release complete with spreader links – 02 No (ii) MCCB 63 Amps, breaking capacity 35 KA, FP, 415 Volts with microprocessor release complete with spreader links – 02 No (iii) Multifunctional digital panel meter with LCD display flush mounting type of size 96x96mm, accuracy class 1, including suitable CTs with secondry current 5A, with display volt, Amp, Frequency, KWH- 01 No (iv) All accessories pre-wired with suitable size PVC insulated copper conductor cables for control wiring and PVC insulated copper strips of appropriate size for power circuits as per standard engineering practice.
Supply, installation, Commissioning and Testing in replacement of Feeder Pillar Box, Kiosk outdoor type, CPRI type tested, LT 440 Volts, 50 Hz, TP, 4 wire supply, Floor mounted factory fabricated weather and vermin proof made out of 3 mm thick MS Sheet CRCA Sheet on angle iron 50 x 50 x 6mm frame of size 0.90 x 0.60 x 0.50 mtr suitable any capacity with front and rear opening doors, handle type locking arrangement powder coated internally and externally shall have channel base of appropriate size and mounted on PCC foundation of size as required or approved by manufacturers in PCC 1:3:6 Type C-2 including earth work complete with bus bar chamber comprising 4 Nos copper strip bus bars PVC insulated made of copper strip of size 40 x 5mm, PVC sheathed with colour coding, complete all as specified and directed with and including following fitments:-
(A) Incoming (i) MCCB 160 Amps, breaking capacity 25 KA, FP, 415 Volts (adjustable thermal and magnetic release) – 01 No (B) Outgoing (i) MCCB 100 Amps, breaking capacity 16 KA, FP, 415 Volts (adjustable thermal and magnetic release) – 02 Nso (ii) MCCB 63 Amps, breaking capacity 16 KA, FP, 415 Volts (adjustable thermal and magnetic release) – 01 No (iii) Multifunctional digital panel meter with LCD display flush mounting type of size 96x96mm, accuracy class 1, including suitable CTs with secondry current 5A, with display volt, Amp, Frequency, KWH- 01 No (iv) Lock pedestal (v) All accessories pre-wired with suitable size PVC insulated copper conductor cables for control wiring and PVC insulated copper strips of appropriate size for power circuits as per standard engineering practice.
Makes for Serial Item No '33 & 34' : Make of Panel : DV Electromatics Private Limited / Simon Fabricators / Electricfield Co / Adhunik Switchgear / Universal Switchgear Make of MCCB : L&T / Legrand / Schneider / Havells Make of Voltmeter / Ammeter / Multifunction Meter : SECURE / L&T (RISHAB) / C&S ELECTRIC / MECO
SUMEET TRADING CORPORATION
RAVI KUMAR
M/S Builders Indias
Bidder Name
M/S BALI CONSTRUCTIONS
M/S Builders Indias
SUMEET TRADING CORPORATION
RAVI KUMAR
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .