Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.8 LAccepted-AOC FLAT NO 203 SEC 14 PLOT NO 142 SHIVSRUTI PARK APARTMENT E WING 1ST FLOOR MOSHI PRADHIKARAN TAL HAVELI DIST PUNE 412 105 | PUNE | MAHARASHTRA | 412105 | L1 | Accepted-AOC THE LOWEST TENDERER | |
| 2 | L2₹27.9 L+₹4.0 L (17.0%)Rejected-Finance | L2 | Rejected-Finance NOT THE LOWEST TENDERER | |
| 3 | L3₹38.1 L+₹14.3 L (60.1%)Rejected-Finance | L3 | Rejected-Finance NOT THE LOWEST TENDERER |
Tender Value
Refer Docs
EMD Value
₹70,000
Closing Date
14 Mar 2023, 6:00 pmClosed
GE MH AND RH KIRKEE
Military Engineer Services Garrison Engineer MH and Range Hills Range Hills Road Kirkee Pune 411003
REPAIR/MAINT OF PUMP MOTORS SUBMERSIBLE PUMP MOTOR AND EXTERNAL WATER SUPPLY INCOMING AND DISTRIBUTION SYSTEM AT DIFFERENT LOCATION AT AUNDH AND MH KIRKEE UNDER GE MH AND RH KIRKEE
2023_MES_581214_1
8397/E8
Open Tender
Civil Works - Water Works
Item Rate
180 days
GE MH AND RH KIRKEE
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE MH AND RH KIRKEE
₹70,000
27 Mar 2023
15 Feb 2023
16 Mar 2023
15 Feb 2023
14 Mar 2023
2 Mar 2023
15 Feb 2023 - 7 Mar 2023
Amount
M & L for dismantling, transporting to civil workshop centrifugal pump coupled with electric motor, split opening of following capacities pumpset including cleaning with kerosene/petrol for removing dirt supply and replacement of minor parts like impeller nut, lock, washer, packing, gasket greasing, oiling and reassembling, connecting in position testing, commissioning the pumpset complete all as directed. Note : Major part shall be measured and paid seperately under relevant Items of this BOQ as supply only.
75 HP Motor
60 HP Motor
40 HP Motor
30 HP Motor
25 HP Motor
20 HP Motor
15 HP Motor
7.5 HP Motor
M & L for taking down carefully electric motor 3-phase 415v,50Hz,AC from foundation/ coupling, transporting to civil workshop, opening the motor,Checking the insulation value of the windings, insulating the winding with same class of insulation varnish,Oiling Greassing of bearing and busing , painting with one coat of synthetic enamel paint as per color code and back to site for re-installing the motor and connecting to the pump, testing the motor for satisfactory performance all as directed by Engineer -in-Charge and all as specified for the following capacity. Note : Major part shall be measured and paid under relevant items of this BOQ as supply only
75 HP Motor
60 HP Motor
40 HP Motor
30 HP Motor
25 HP Motor
20 HP Motor
15 HP Motor
7.5 HP Motor
Supply only following bearings required as directed:-
75 HP Motor
60 HP Motor
40 HP Motor
30 HP Motor
25 HP Motor
20 HP Motor
15 HP Motor
7.5 HP Motor
Supply only terminal block for the following capacities:-
75 HP Motor
60 HP Motor
40 HP Motor
30 HP Motor
25 HP Motor
20 HP Motor
15 HP Motor
7.5 HP Motor
Supply only bush for pump suitable for the following capacity of pumps:-
75 HP Motor
60 HP Motor
40 HP Motor
30 HP Motor
25 HP Motor
20 HP Motor
15 HP Motor
7.5 HP Motor
Dismantling and taking out pump motor ,transporting the same work shop opening the motor, removing burnt winding and cleaning winding slots and rewinding of motor using suitable gauge/ size with supper enamelled copper wire, replacing insulation paper of class F and fire proof sleeves, varnishing complete, oiling, greasing, replacing old rear/ front bearings with new and reassembling complete motor including testing at site all as directed by Engr- in -charge
75 HP Motor
60 HP Motor
40 HP Motor
30 HP Motor
25 HP Motor
20 HP Motor
15 HP Motor
7.5 HP Motor
Disconnecting electrictrical and mechanicaly and taking out submersible motor pump set of following capacity complete from installed position/ sump , disconnecting of motor, transporting the motor to local workshop ,Split opening of the motor, removing burnt winding and cleaning the slots and rewinding of motor using new super enameled copper winding wire of suitable gauge / size, replacing paper insulation of suitable class and fire proof sleeves, varnishing etc. complete with oiling, greasing, replacing unsv thrust bearing and bushes after repairing, reassembling complete pump and motor after repairing lowering in existing position and testing all as specified and directed .
25 HP Motor
10 HP Motor
5 HP Motor
3 HP Motor
M& L for CI pipes with both ends flanged centrifugally cast, class -'B', conforming to IS 8329/ 2000, in any length suitable for flange joint of following sizes including taking down old existing unserviceable cast iron pipe complete all as specified & directed. Note : CI fitting and jointing shall be measued & paid seperately under relevant item of this BOQ
CI pipe 300 mm dia
CI pipe 200 mm dia
CI pipe 150 mm dia
CI pipe 100 mm dia
CI pipe 80mm dia
M&L for joint with rubber or fibre board gasket complete with suitable size nuts, bolts and washers etc as directed for flanged pipes & fittings for followings sizes including taking down fiber board gasket joint complete all as specified & directed:-
300 mm dia
200 mm dia
150 mm dia
100 mm dia
80 mm dia
M&L for cast iron fitting (any type radius and angle) taper any type (Straight) bend increasing decreasing or double socket etc Tee pieces, single branch ‘Y’ junction double branch, coller, capacity and plugs for up to 150 mm bore CI pipe conforming to IS-1538- 1976 including taking down unserviceable CI/DI/ fitting of any description complete all as specified and directed.
M&L for cast iron fitting (any type radius and angle) taper any type (Straight) bend increasing decreasing or double socket etc Tee pieces, single branch ‘Y’ junction double branch, coller, capacity and plugs for exc 150 mm to 400 mm bore CI pipe conforming to IS-1538- 1976 including taking down unserviceable CI/DI/ fitting of any description complete all as specified and directed.
Taking down unserviceable foot valve and supply and fixing foot valve of followingsizes including jointing materials all as specified and directed
150 mm Dia
100 mm Dia
80 mm Dia
S & F in repair tyre coupling of following sizes with existing alignement including taking down unserviciable tyre complying complete all as specified and directed.
A 18 Size
A 42 Size
A 60 Size
Supply and fix in repair 3 pole power contactor 2 NO +2 NC, ML 4 three phase, AC 440 volts, 50Hz, 100 Amps AC-1, 70 Amps AC3. Make - L&T CAT part No. SS90910 or equivalent rating of make given under list of make
Supply and fix in repair 3 pole power contactor 2 NO +2 NC, ML 6 three phase, AC 440 volts, 50Hz, 100 Amps AC-1, 70 Amps AC3 . Make - L&T CAT part No. SS90910 or equivalent rating of make given under list of make
Supply and fix in repair thermal overhead relay MN-5 with start and off/reset of Amps range 66-110 Amps Make- L& T Cat No SS94137 or equivalent in C& S or equivalent rating of make given under list of make
Supply and fix in repair thermal overhead relay for 30 to 40 HP motor alongwith with start and off/reset of Amps range 30-50 Amps Make- L& T or equivalent rating of make given under list of make
Supply and fix in repair thermal overhead relay for 7.5 to 25 HP motor alongwith with start and off/reset of Amps range 30-50 Amps Make- L& T or equivalent rating of make given under list of make
Supply and fix in repair ST timer 100 range 3-30 Sec coil voltage 240/360/415 Volt AC Make - L&T CAT part No. ST803280000 or equivalent rating of make given under list of make
Supply and fix in repair 3 pole power contactor MNX 25 AC-1 rating 25 A and AC 3 rating 45 A three phase, AC 440 volts, 50Hz, Make - L&T Cat part No. CS14110 or equivalent rating of make given under list of make
Supply and fix in repair 3 pole power contactor AC 3 rating 32 to 40 A three phase, AC 440 volts, 50Hz, Make - L&T/Seimense / BCH or equivalent rating of make given under list of make
Supply and fix in repair 3 pole power contactor AC 3 rating 16 to 25 A three phase, AC 440 volts, 50Hz, Make - L&T/Seimense / BCH or equivalent rating of make given under list of make
Supply and fix in repair or replacement ML 4 FASD Starter complete including disconnectioin of old termination, removal of old starter from the panel and fixing of new starter with all connection complete all as specified and directed
Supply and fix in repair or replacement MN 16 DOL Starter complete including disconnectioin of old termination, removal of old starter from the panel and fixing of new starter with all connection complete all as specified and directed
Supply and fix in repair or replacement MN MN 32 DOL Starter complete including disconnectioin of old termination, removal of old starter from the panel and fixing of new starter with all connection complete all as specified and directed
Supply and Fixing in replacement Water pressure gauge of capacity 5 Kg/mm2 gauge 8 " or 6" (size of dial) all as directed Make- ISI Make
Supply and fix in repair NRV of size of following size, Class PN 1.6, hydrodynamically guided, closing non return valve with gray Cast iron body, synthetic rubber coated reinforced ball, flanged type including 6mm thick rubber gasket, MS nuts, bolts and washers and dismantling the unserviceable NRV all as directed.
300 mm Dia
200 mm Dia
150 mm Dia
80 mm Dia
Supply and laying in replacement PVC insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area of following size:-
185 Sqmm 4 Core
95 Sqmm 3.5 Core
50 Sqmm 3.5 Core
35 Sqmm 3.5 Core
10 Sqmm 4 Core
Supply and fix in repair sluice valve cast iron body double flanged type PN1.6, with SS Spindle, ISI Mark of following capacities:-
400mm dia
300 mm dia
200 mm dia
150 mm dia
100 mm dia
80 mm dia
Supply and fix in repair air release valve cast iron body flanged type double acting type, ISI Mark of 80/100 mm size
Supply & fix in repair SS wire rope with PVC coating of size 10mm dia complete all as specified
Supply and fix in repair rubber gland packing suitable for sluice valve of following sizes
400 mm dia
300 mm dia.
200/150 mm dia.
100/80 mm dia.
Repair of NRV of size 200 mm flanged type by opening and cleaning inner plate spendle replacement of 6mm thick rubber gasket, MS nuts, bolts and washers after repairing refixing the same in existing position all as specified and as directed.
M&L for preparation of old painted steel surfaces of motor complete set including base plate, of capacity up to 40 HP motors & applying two coat of synthetic enamel paint all as directed by Engineer-in-Charge.
M&L painting of pump,motor complete set including base plate, of capacity 60 HP to 75 HP motor with two coat of synthetic enamel paint complete all as directed by Engineer-in-Charge.
Cleaning of MES electric supply installations/campus by surface dressing or trimming of natural ground to remove small unequalities not exc 15 cm deep (including removing vegetation/ shrubs/brush wood/ under growth) and carrying away the rubbish to a distance of not exc 50 mtr away complete for the various sub stations. Note: (a) Spray of herbsite deemed included in quoted rate. (b) Measurement for removing vegetation/ shrubs/brush shall be measured once only for entire period of completion.
Supply and fix in replacement only RYB indicator lamp LED type (Set of three lamp) for incoming and outgoing supply as per existing sizes all as directed by Engr-in-Charge.
Supply and Fix in replacement of CTs of 200/5 current rating AC, 415 V, three phase including connecting to supply as per existing all as directed by Engr-in-Charge.
Supply and fix in replacement Ammeter three phase digital type 50 HZ, AC as per existing sizes/ range all as directed by Engr-in-Charge.
Supply and fix iin replacement voltmeter three phase digital type 0-500 V, 50 HZ, AC as per existing sizes all as directed by Engr-in-Charge.
S& F single phase preventor relay SPPR type Sz5(6 wire) 415 V 50 Hz Make Siemens or equevelent approvd make
M&L for replacement of submersible cable round/flat of 3 core 6 Sqmm with multistanded copper coundecter all as directed.
S & F hot rolled medium and high tensile structural steel of grade E 165 as per IS 15911: 2010 as in framed work such as grills, grating, etc., with ends of bars of shouldered and/or riveted, or forged into spikes, framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework water tanks and similar work and applying one coat of red oxide primer and two coat of black paint (one coat before fixings and one coat of black paint after fixing ) complete all as specified and directed.
M&L for 75mm thick PCC M-10 grade (nominal mix) using 20mm graded stone aggregate as in Plinth, Path, floor with fair finish surface with out using extra cement complete all as specified.
S & F hot rolled medium and high tensile structural steel of grade E 250 quality C conforming to IS 2062: 2011 as in 5mm thick plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment complete all as specified and as directed.
Supply only PPM testing kit for portable/ drinking water measuring range 0.2 PPM to 5 PPM all as specified and directed. Make : Any approved Coy from Govt Lab.
S&F Multicore PVC insulated, PVC unsheathed industrial cable withflexible bright annealed copper conductor for voltage grade up to 1100 volts conformimg to IS 694 for following size:-
10 Sqmm 3 Core
16 Sqmm 3 Core
35 Sqmm 3 Core
S & F Integral decorative LED bollard with polycarbonate diffuser square shaped with IP 65 protection suitable for 9 watts LED bulb with necessary MS base box made out of MS sheet of 2 mm thick of suitable size embbed in PCC M-15 grade (nominal mix) using 20mm graded stone aggregat base, elecrical connections with adequate size including removal of old unserviceable one complete as all specified and as directed. Make: Bajaj Cat part No BGBOS 600 9W LED, Philips Cat Part No BCP 150 LED 150 WW or its equavalent in Wipro.
Taking down of existing unsearviceable water meter 300 mm dia by disconnecting of all nuts bolts and repair the same by replacing all unserviceable parts and calibration / testing the same from MIDC water works authority complate all as specified and as directed
Supply laying testing cable xlpe insulated Screened PVC Bedded Galvanised steel strip or wire armoured elctric power cable heavy duty 1100 V grade with stranded aluminium conductor of size 6.0 sqmm 2 core
S & F MCCB TP/TPN of following sizes suitable for fixing on Panel/ Starter of pump and motor with extended terminals complete all as specified.
MCCB 25 to 100 Amps, 3 pole, 36 KA
MCCB 160 Amps, 4 pole, 36KA
MCCB 350 Amps, 4 pole, 36/50 KA
MCCB 400 Amps, 4 pole, 36/50 KA
Labour only to attending the complaints for fault of motor, electric panel, pumps, sluice valve, NRV, float valve, foot valve on call basis as and when required with in the 04 hours and make the item serviceable by means of repair or replacement of relevant item all as specified and directed. Note : i) Spare part used in complaint is measured and paid seperately under relavant item. ii) Cost of Tools and special equipments used to attend the complaint is included in quotated rate. iii) In case not attended the complaint with in the 04 hours after intimation Rs. 500/- penalty will be levied to the contractor. iv) Normal hardware, like nuts, bolts, washers, cotton west, gland dori, grease, oil, anti rust spray, rubber gasket packing, should be used in complaint is included in quotated rate.
Labour only to visit the monthly basis to all pump house of entire area of GE (MH & RH) to check all sluice valve for leakage or any mechanical problem in operating of valve (spindal problem or gate problem) make it good and proper serviceable upto entire satisfaction complete all as specified and directed. Note : i) Spare part used in complaint shall be measured and paid seperately under relavant item of this BOQ. ii) Cost of Tools and special equipments used to attend the complaint is included in quotated rate. iii) Normal hardware, like nuts, bolts, washers, cotton west, gland dori, grease, oil, anti rust spray, rubber gasket packing, used in complaint is deemed to be included in unit rate quoted.
M/S. OM ENTERPRISES
K.K.Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .