| 1 | L1₹13.0 LAdmitted-Finance | L1 | Admitted-Finance | |
| 2 | L2₹13.5 L+₹51,438.56 (3.95%)Admitted-Finance | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | A.S.ENTERPRISES L1 | M.B. Enterprises L2 |
|---|---|---|---|---|---|
| 1.01 | Disconnecting of HT supply from main HT panel after proper switching off 11 KV VCB discharging the supply. Complete drain out of transformer oil from transformer to empty oil drum by oil machine, dismantling of conservator tank all protection relays cable end boxes vent pipes and other items as required | 2 | Jobs | 46,640 ₹55,035.2 Lowest | 46,800 ₹55,224 |
| 1.02 | Cleaning of transformer oil tank and removing of sludge settled in the bottom with the help of vacuum pressure cleaning machine thoroughly, cleaning of core and winding of transformer with hot oil and proper safety precaution to prevent the winding damage as required, cutting of old overheated insulation of winding and re-insulation of weak point with the help of HT insulation material and proper taping etc. | 2 | Jobs | 1,41,560 ₹1,67,040.8 Lowest | 1,44,000 ₹1,69,920 |
| 1.03 | Replacement of top cover gasket vertical vent gasket & missing hardware to stop the oil leakage. | 2 | Jobs | 52,030 ₹61,395.4 Lowest | 52,200 ₹61,596 |
| 1.04 | Repairing of tape Changer | 1 | Jobs | 22,000 ₹25,960 Lowest | 22,500 ₹26,550 |
| 1.05 | Replacement of silica gel | 2 | Jobs | 6,600 ₹7,788 Lowest | 6,660 ₹7,858.8 |
| 1.06 | Checking & matching of control wiring of all protection relays and calibration of bucchlaz relay and protection relays testing the same. | 2 | Jobs | 32,670 ₹38,550.6 Lowest | 33,300 ₹39,294 |
| 1.07 | Complete assembling of transformer cleaning of complete transformer tightening of all connection of incoming and outgoing side and testing & checking of IR test with megger of winding & cable of both sides with HI pot machine | 2 | Jobs | 60,500 ₹71,390 Lowest | 60,660 ₹71,578.8 |
| 1.08 | Repairing of LT Copper bolt and Pam, remettaling and finishing the same as per original shape and size | 8 | Jobs | 1,72,000 ₹2,02,960 Lowest | 1,80,000 ₹2,12,400 |
| 1.09 | Filling of T/oil to up to top up level as required to make power | 836 | Ltrs. | 1,24,146 ₹1,46,492.28 Lowest | 1,27,908 ₹1,50,931.44 |
| 1.10 | P/Fixing of winding protection pad | 2 | set | 32,670 ₹38,550.6 Lowest | 33,300 ₹39,294 |
Tender Value
Refer Docs
EMD Value
₹26,100
Closing Date
19 Nov 2025, 11:15 amClosed
EE ENM M 4
DELHI JAL BOARD C BLOCK SECTOR-19 BPS ROHINI DELHI-89
Repair Servicing Dehydration of Kirloskar make 1600 KVA Transformer No 1 and 2 at Sanjay Gandhi Transport Nagar BPS in AC 05
2025_DJB_281076_20
NIT No. 16(2025-26)M-4
Open Tender
Miscellaneous Works
Item Rate
90 days
EE ENM M 4
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Account No SB 50448339804
₹26,100
Yes
22 Nov 2025
12 Nov 2025
19 Nov 2025
12 Nov 2025
19 Nov 2025
12 Nov 2025
Disconnecting of HT supply from main HT panel after proper switching off 11 KV VCB discharging the supply. Complete drain out of transformer oil from transformer to empty oil drum by oil machine, dismantling of conservator tank all protection relays cable end boxes vent pipes and other items as required
Cleaning of transformer oil tank and removing of sludge settled in the bottom with the help of vacuum pressure cleaning machine thoroughly, cleaning of core and winding of transformer with hot oil and proper safety precaution to prevent the winding damage as required, cutting of old overheated insulation of winding and re-insulation of weak point with the help of HT insulation material and proper taping etc.
Replacement of top cover gasket vertical vent gasket & missing hardware to stop the oil leakage.
Repairing of tape Changer
Replacement of silica gel
Checking & matching of control wiring of all protection relays and calibration of bucchlaz relay and protection relays testing the same.
Complete assembling of transformer cleaning of complete transformer tightening of all connection of incoming and outgoing side and testing & checking of IR test with megger of winding & cable of both sides with HI pot machine
Repairing of LT Copper bolt and Pam, remettaling and finishing the same as per original shape and size
Filling of T/oil to up to top up level as required to make power
P/Fixing of winding protection pad
Repair of cooloinf fins, replacement of cooling fins gasket and oil seal for stopping the leakage
Dehydration and filtration of complete transformer oil and checking the die electric strength up to 50 KV at site as required.
Complete cleaning and chemically washing of oily and muddy trransformer body and painting of transformer with enamel paint.
Insulating the bus bar
M.B. Enterprises (BID ID -1640269)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.88 MB
BOQ_371267.xls
BOQ • 0.26 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .