| Sl No | Description | Qty | Unit | Srinivasa Consructions L4 | SUN LIGHT HOUSE L3 | Srinivash Engineers L1 | M Shyam Sunder L2 |
|---|---|---|---|---|---|---|---|
| 1.00M&L in replacement for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area laid in trenches / duct or fixed to wall / passing through pipe on pole with suitable size cable glands, crimping type cable lugs for stranded aluminum conductor of following sizes complete all as specified and directed :- | |||||||
| 1.01 | 4 Core X 25 Sqmm | 200 | RM | 322 ₹64,400 | 220 ₹44,000 Lowest | 245 ₹49,000 | 230 ₹46,000 |
| 1.02 | 3.5 Core X 35 Sqmm | 200 | RM | 360 ₹72,000 | 240 ₹48,000 Lowest | 268 ₹53,600 | 250 ₹50,000 |
| 1.03 | 3.5 Core X 50 Sqmm | 250 | RM | 480 ₹1,20,000 | 300 ₹75,000 Lowest | 355 ₹88,750 | 310 ₹77,500 |
| 1.04 | 3.5 Core X 70 Sqmm | 250 | RM | 635 ₹1,58,750 | 380 ₹95,000 Lowest | 457 ₹1,14,250 | 392 ₹98,000 |
| 1.05 | 3.5 Core X 95 Sqmm | 200 | RM | 800 ₹1,60,000 | 500 ₹1,00,000 | 570 ₹1,14,000 | 490 ₹98,000 Lowest |
| 1.06 | 3.5 Core X 120 Sqmm | 150 | RM | 1,000 ₹1,50,000 | 600 ₹90,000 | 680 ₹1,02,000 | 590 ₹88,500 Lowest |
| 1.07 | 3.5 Core 150 Sqmm | 100 | RM | 1,200 ₹1,20,000 | 700 ₹70,000 Lowest | 830 ₹83,000 | 710 ₹71,000 |
| 1.08 | 3.5 Core 185 Sqmm | 100 | RM | 1,550 ₹1,55,000 | 850 ₹85,000 Lowest | 900 ₹90,000 | 885 ₹88,500 |
| 1.09 | 3.5 Core 240 Sqmm | 50 | RM | 1,940 ₹97,000 | 950 ₹47,500 Lowest | 1,000 ₹50,000 | 990 ₹49,500 |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
31 Jan 2026, 6:00 pmClosed
GE (UTILITY) SECUNDERABAD
GE UTILITY SECUNDERABAD MUDFORT SECUNDERABAD-500003
MISCELLANEOUS REPAIRS TO ELECTRIC SUPPLY SYSTEM, CAPACITOR PANEL, HIGH MAST, AMF PANEL AND ALLIED WORKS AT MCEME, DEPOT BN, EME RECORDS, NML, OHL ECOS FALAKNAMA, AGAMAN AND ADJOINING AREA UNDER AGE EM NO II OF GE(U) SECUNDERABAD
2026_MES_747974_1
GE (U)/SEC/TOKEN/70 OF 2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
SECUNDERABAD
All as per Tender documents
8 documents required · 8 mandatory
₹500
GE (UTILITY) SECUNDERABAD
₹80,000
Yes
26 Mar 2026
10 Jan 2026
7 Feb 2026
10 Jan 2026
31 Jan 2026
24 Jan 2026
M&L in replacement for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area laid in trenches / duct or fixed to wall / passing through pipe on pole with suitable size cable glands, crimping type cable lugs for stranded aluminum conductor of following sizes complete all as specified and directed :-
4 Core X 25 Sqmm
3.5 Core X 35 Sqmm
3.5 Core X 50 Sqmm
3.5 Core X 70 Sqmm
3.5 Core X 95 Sqmm
3.5 Core X 120 Sqmm
3.5 Core 150 Sqmm
3.5 Core 185 Sqmm
3.5 Core 240 Sqmm
Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth, for foundation of PCC/Steel pole, laying of cable in trenches etc and getting out in hard / dense soil complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm in soils complete all as specified and directed.
Removing excavated material (soils) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed.
M&L filling riddled earth in trenches for cushioning of laying of cables to the full width of excavated trench 8 cm thick before laying the cable and 10 cm above the cable, gently punned down, stretching and testing of cable on transformer yard etc complete all as specified and directed. Note :- Thickness of riddle earth cushion after punning down only shall be measured for payment.
M&L brick protection with common burnt brick sub class ‘B’ of size 230 x115 x75 mm for cable protection complete all as directed by Engr-in-charge.
Supply and Lay reinforced precast concrete cable cover LV, Type I,flat, size 250x150x40 mm complete all as specified and directed.
Supply, lay, commissioning and testing of cable jointing Kit Heat shrinkable type for 1100 V grade cable for straight through joint with jointing material and accessories suitable for LT UG cable of size 16 to 50 Sqmm, 3.5 Core complete all as specified and directed.
All as per item No 8.00 above but suitable for aluminium conductor cable of size from 70 sqmm, 3.5 Core to 95 Sqmm, 3.5 Core
All as per item No 8.00 above but suitable for aluminium conductor cable of size from 120 sqmm, 3.5 Core to 150 Sqmm, 3.5 Core
All as per item No 8.00 above but suitable for aluminium conductor cable of size from 185 sqmm, 3.5 Core to 240 Sqmm, 3.5 Core
Supply, lay, commissioning and testing of cable jointing Kit for 1100 V grade cable for outdoor End termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 16 to 50 Sqmm, complete all as specified and directed.
All as per item No 12.00 above but suitable for aluminium conductor cable of size from 70 sqmm, 3.5 Core to 95 Sqmm, 3.5 Core
All as per item No 12.00 above but suitable for aluminium conductor cable of size from 120 sqmm, 3.5 Core to 150 Sqmm, 3.5 Core
All as per item No 12.00 above but suitable for aluminium conductor cable of size from 185 sqmm, 3.5 Core to 240 Sqmm, 3.5 Core
Cutting the existing road/PCC surface straight by manual, depth and width not less than 1 mtr below ground level for passing of underground cable and filling back with excavated soil upto 75% road portion and 25% shall be made with cement concrete 1:2:4 (using 20 mm graded aggregate stone complete all as specified and directed.
Supply & lay in repairs Galvanised Iron tubing 40 mm bore, light grade in protection of cable at road crossing/hard standing/pole protection fixed with MS clamps of size 40 X 4 mm, nut bolts and washer as per site requirement including taking down old unserviceable pipes complete all as specified and directed.
Supply & lay in repairs Galvanised Iron tubing 50 mm bore, light grade in protection of cable at road crossing/hard standing/pole protection fixed with MS clamps, nut bolts and washer as per site requirement including taking down old unserviceable pipes complete all as specified and directed.
Supply & lay Galvanised in repairs Iron tubing 80 mm bore, light grade in protection of cable at road crossing/hard standing/pole protection fixed with MS clamps, nut bolts and washer as per site requirement including taking down old unserviceable pipes complete all as specified and directed.
Trimming/pruning and removing of tree branches or any other foreign objects from HT/LT over head conductor and clearing the OH Line of any type and size for one span of any length in 2 way /4 way/6 way conductor system. Notes: (i) Insulators of any type, connectors and ACSR conductor of any size required at site will be measured and paid separately under relevant item of this schedule. (ii) The contractor is responsible for provision of Necessary T & P including crane and safety equipments to complete the job.
Cutting unaxious green growth and grass by manual labour or by machine at all 11 KV Electric Installation premises/around 2/4 Pole structure/ along the boundary fencing and removing rubbish from the site of work complete all as specified and directed.
Supply, Installation, test and Commissioning in replacement of factory fabricated, out door type, LT Panel Board made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof, Double door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embeded with 50X50X6mm Mild Steel Angle Iron Frame and 600 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20mm Graded Stone Aggregate) and Testing after Installation complete all as specified and comprising of the following :–
Supply, Installation, test and Commissioning in replacement of factory fabricated, outdoor type, LT FEEDER PILLAR BOX made out of 3.15 mm thick CRCA Sheet of suitable size with projected Globe roof for rain water protection Dust and Vermin Proof, Double door with both side opening including Neoprene Rubber Gasket,, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Mild Steel Angle Iron Frame and 600 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs, and cable glands PCC Foundation in Cement Concrete 1:3:6 (20mm Graded Stone Aggregate) and Testing after Installation complete all as specified and comprising of the following :– (a) Aluminium bas bar of 200 Amps - 04 Nos in 3 phase and half neutral fashion, supported with suitable size of heavy duty porcelain stand lock with suitable size of brass nut, bolts and washer with heat shrinkable PVC sleeving. The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral. (b) MCCB 100 amps, 415 volt,16 KA Breaking capacity 4 pole Electromagnetic release duly connected to Bus Bar as INCOMING - 01 Nos
Supply , fixing , connecting and commissioning and testing of outdoor type (automatic and manual operation) power factor improvement panel of capacity 100 Kvar including interconnection with LT panel with appropriate size of electric cable for transformer (Outdoor/Indoor) type panel factory made, weather proof , dust and vermin proof suitable for 1100 V/440 V grade 3 phase 50 HZ AC supply floor mounted , fabricated out of 3.15mm thick CRCA sheet and having four Nos angle iron legs made out of 50 x 50 x 6mm 90 cm long angle iron below frame with front door and Side/Back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 sq mm / extension strips and connected with suitable size thimbles , lugs duly painted with siemens grey epoxy powder coating after suitable chemical treatment , legs duly embedded in ground upto 45 Cms in PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting , with required sheet metal enclosures, thimbles with on line monitring of Power Factor on web based application as specified and directed by Engr-in-Charge.
Incoming feeder:-
A. Incommer MCCB 160- Amp , Three Pole, Termal based release with adjustable O/L ,Adj S/C Setting Front Face, 16 KA rupturing capacity, Ics=100%Icu, Isolation with Positive Break Indication with Double Break Contacts, Standard Extended Rotary Handle, Spreaders, Phase Barrier.- 1 No
B.Metering Section- Digital Ammeter (0-150)Amps, digital Volt Meter (0-500)Volts , RYB Indicating Lamps ,1 Set Control fuses, CTs. 3
C. Insulated Busbar of Aluminium of 150A Capacity for 3 phase,, fixed on Insulators, Busbar Should be PVC Sleeved with red. Yellow. Blue Colour, Busbar Support should be of smc/dmc - 1 set.
D. Multi 10 Step 440V, 5A (144 x 144) microprocessor based power factor controller provided in the command module for target power factor setting, automatic adjustment of dead bank ratio, digital power factor display.
Outgoing feeder :-
H. Ventilating fans of required size to dissipate the heat liberated by capacitor unites complete with automatic switching on/off of fans depending upon the temperature of the pane; 230vac 1500rpm, 160cu.m/h flying leads
J. 10 Stpes Automatic Power Factor controller steps Relay Micro proccessor based for switchting ON and OFF of capacitors to Display of voltage ,current,Active power ,apparent Power display of COS Ø ,THD voltage ,THD current,alarm indication for defective step,low power factor and axcess temperature.The relay having volt free c/o contact,automatic detection and uses of optimum capacitor capable of 4 Quadrant operation and any phase offset requirement.Switching programm :LIFO combi Filter ,manual mode built in under and over voltage release with auto reset large voltage input band of 90V to 440 volt ,45 to 65 HZ,current measuring 10MA-5A suitable for CT x/1A andx/5A commissing without additional setting and programming.Three decimal power reading .Phasing out of fault capacitor bank Automatically .
K. All accessories prewired with suitable size copper Wire with stand high temperature, housed in cubical panel made out of 3.15mm thick CRCA Sheet factory made duly powder coated front and rear door open able with locking arrangement complete with foundation as required or recommended by manufacturer. Note: APFC Panel shall be manufactured by original manufacturer only. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted.
Supply , fixing , connecting and commissioning and testing of outdoor type (automatic and manual operation) power factor improvement panel of capacity 80 Kvar including interconnection with LT panel with appropriate size of electric cable for transformer (Outdoor/Indoor) type panel factory made, weather proof , dust and vermin proof suitable for 1100 V/440 V grade 3 phase 50 HZ AC supply floor mounted , fabricated out of 3.15mm thick CRCA sheet and having four Nos angle iron legs made out of 50 x 50 x 6mm 90 cm long angle iron below frame with front door and Side/Back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 sq mm / extension strips and connected with suitable size thimbles , lugs duly painted with siemens grey epoxy powder coating after suitable chemical treatment , legs duly embedded in ground upto 45 Cms in PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting , with required sheet metal enclosures, thimbles with on line monitring of Power Factor on web based application as specified and directed by Engr-in-Charge.
Incoming feeder:-
A. Incommer MCCB 160- Amp , Three Pole, Termal based release with adjustable O/L ,Adj S/C Setting Front Face, 16 KA rupturing capacity, Ics=100%Icu, Isolation with Positive Break Indication with Double Break Contacts, Standard Extended Rotary Handle, Spreaders, Phase Barrier.- 1 No
B.Metering Section- Digital Ammeter (0-150)Amps, digital Volt Meter (0-500)Volts , RYB Indicating Lamps ,1 Set Control fuses, CTs. 3
C. Insulated Busbar of Aluminium of 150A Capacity for 3 phase,, fixed on Insulators, Busbar Should be PVC Sleeved with red. Yellow. Blue Colour, Busbar Support should be of smc/dmc - 1 set.
D. Multi 10 Step 440V, 5A (144 x 144) microprocessor based power factor controller provided in the command module for target power factor setting, automatic adjustment of dead bank ratio, digital power factor display.
Outgoing feeder :-
K. Ventilating fans of required size to dissipate the heat liberated by capacitor unites complete with automatic switching on/off of fans depending upon the temperature of the pane; 230vac 1500rpm, 160cu.m/h flying leads
L. 10 Stpes Automatic Power Factor controller steps Relay Micro proccessor based for switchting ON and OFF of capacitors to Display of voltage ,current,Active power ,apparent Power display of COS Ø ,THD voltage ,THD current,alarm indication for defective step,low power factor and axcess temperature.The relay having volt free c/o contact,automatic detection and uses of optimum capacitor capable of 4 Quadrant operation and any phase offset requirement.Switching programm :LIFO combi Filter ,manual mode built in under and over voltage release with auto reset large voltage input band of 90V to 440 volt ,45 to 65 HZ,current measuring 10MA-5A suitable for CT x/1A andx/5A commissing without additional setting and programming.Three decimal power reading .Phasing out of fault capacitor bank Automatically .
M. All accessories prewired with suitable size copper Wire with stand high temperature, housed in cubical panel made out of 3.15mm thick CRCA Sheet factory made duly powder coated front and rear door open able with locking arrangement complete with foundation as required or recommended by manufacturer. Note: APFC Panel shall be manufactured by original manufacturer only. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted.
Supply , fixing , connecting and commissioning and testing of outdoor type (automatic and manual operation) power factor improvement panel of capacity 120 Kvar including interconnection with LT panel with appropriate size of electric cable for transformer (Outdoor/Indoor) type panel factory made, weather proof , dust and vermin proof suitable for 1100 V/440 V grade 3 phase 50 HZ AC supply floor mounted , fabricated out of 3.15mm thick CRCA sheet and having four Nos angle iron legs made out of 50 x 50 x 6mm 90 cm long angle iron below frame with front door and Side/Back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 sq mm / extension strips and connected with suitable size thimbles , lugs duly painted with siemens grey epoxy powder coating after suitable chemical treatment , legs duly embedded in ground upto 45 Cms in PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting , with required sheet metal enclosures, thimbles with on line monitring of Power Factor on web based application as specified and directed by Engr-in-Charge.
Incoming feeder:-
A. Incommer MCCB 160- Amp , Three Pole, Termal based release with adjustable O/L ,Adj S/C Setting Front Face, 16 KA rupturing capacity, Ics=100%Icu, Isolation with Positive Break Indication with Double Break Contacts, Standard Extended Rotary Handle, Spreaders, Phase Barrier.- 1 No
B.Metering Section- Digital Ammeter (0-150)Amps, digital Volt Meter (0-500)Volts , RYB Indicating Lamps ,1 Set Control fuses, CTs. 3
C. Insulated Busbar of Aluminium of 150A Capacity for 3 phase,, fixed on Insulators, Busbar Should be PVC Sleeved with red. Yellow. Blue Colour, Busbar Support should be of smc/dmc - 1 set.
D. Multi 10 Step 440V, 5A (144 x 144) microprocessor based power factor controller provided in the command module for target power factor setting, automatic adjustment of dead bank ratio, digital power factor display.
Outgoing feeder :-
H. Ventilating fans of required size to dissipate the heat liberated by capacitor unites complete with automatic switching on/off of fans depending upon the temperature of the pane; 230vac 1500rpm, 160cu.m/h flying leads
I. 10 Stpes Automatic Power Factor controller steps Relay Micro proccessor based for switchting ON and OFF of capacitors to Display of voltage ,current,Active power ,apparent Power display of COS Ø ,THD voltage ,THD current,alarm indication for defective step,low power factor and axcess temperature.The relay having volt free c/o contact,automatic detection and uses of optimum capacitor capable of 4 Quadrant operation and any phase offset requirement.Switching programm :LIFO combi Filter ,manual mode built in under and over voltage release with auto reset large voltage input band of 90V to 440 volt ,45 to 65 HZ,current measuring 10MA-5A suitable for CT x/1A andx/5A commissing without additional setting and programming.Three decimal power reading .Phasing out of fault capacitor bank Automatically.
J. All accessories prewired with suitable size copper Wire with stand high temperature, housed in cubical panel made out of 3.15mm thick CRCA Sheet factory made duly powder coated front and rear door open able with locking arrangement complete with foundation as required or recommended by manufacturer. Note: APFC Panel shall be manufactured by original manufacturer only. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted.
M&L for preparation of old painted surfaces for outdoor/indoor Amf panel/LT Panel of any size with applying two coat of synthetic enamelled grey paint after removing all dust & rust and paint shall confirm to IS 2032 complete all as specified .
Supply & Replace in replacement MCCB along with both side spreader link and nut bolts of appropriate size in exisitng LT Panel box/ Feeder Pillar boxes (KIOSK),in MCCB DBs of capacity 315-400 Amps, 4 Pole, 35 KA, 415 Volt including disconnecting/taking out existing old unsv/burned MCCB complete all as specified and directed.
All as per item No 30.00 here in before but of capacity 250 Amps, 4 pole, 36 KA
All as per item No 30.00 here in before but of capacity 200 Amps, 4 pole, 36 KA
All as per item No 30.00 here in before but of capacity 160 Amps, 4 pole, 36KA
All as per item No 30.00 here in before but of capacity 125 Amps, 4 pole, 16 KA
All as per item No 30.00 here in before but of capacity 100 Amps, 4 pole, 16 KA
All as per item No 30.00 here in before but of capacity 63 Amps, 4 pole, 16 KA
Supply & Replace in replacement MCCB along with both side spreader link and nut bolts of appropriate size in exisitng LT Panel box / Feeder Pillar boxes (KIOSK),in MCCB DBs of capacity 250 Amps, 3 Pole, 35 KA, 415 Volt including disconnecting/taking out existing old unsv/burned MCCB complete all as specified and directed.
All as per item No 37.00 here in before but of capacity 200 Amps, 3 pole, 36 KA
All as per item No 37.00 here in before but of capacity 160 Amps, 3 pole, 36 KA
All as per item No 37.00 here in before but of capacity 63 Amps, 3 pole, 16 KA
S& F in replacement of MCB , SP 6-32 Amps ,C curve with breaking capacity 10 KA, including disconnecting / taking out existing old unsv/burned isolator complwte all as specied and directed
S&F in replacement MCB, TP 25-63 Amps, 'C' Curve with breaking capacity 10KA, including disconnecting/taking out existing old unsv/burned Isolator complete all as specified and directed.
S&F in replacement MCB, SPN 32 Amps, 'C' Curve with breaking capacity 10KA, including disconnecting/taking out existing old unsv/burned Isolator complete all as specified and directed.
M& L in repairs Advance Maintenance Free G.I. SAFE EARTHING Electrode with PIPE of not less than 50 mm outer dia) and two meter length, The electrode should be of galvinised (80 -100 micron) along with earth lead as Galvanised steel strip of size 32 X6 mm 7.5 m . The GI Electrode shall be pre-filled with Crystalline Conductive Material (CCM). The GI electrode shall be surrounded with 25 kg Backfill compound to provide maximum contact between the electrode and Back Fill Compound.connected to earthing test point including excavation, earth work, PCC pit, RCC cover 50 mm thick, lifting rod and testing on completion, complete all as specified and directed. Make: ASHLOK/GRAVIN/TRUE POWER/JVM
S&F in replacement of Galvanised Iron Strip 32x6mm with Saddles and fixing Screws for Roof/Earth Conductors and Down Conductors above Ground including taking down unserviceable Strip, complete all as specified and as directed. NOTE : All Joints should be joined by Brazing or by using of nuts and bolts& washers.
S&F in replacement of Galvanised Iron Tubing/Pipe 40mm bore (dia), light grade for Strip Protection, fixed in Walls/Floors with suitable type of Clamps, etc. including taking down unserviceable GI Tubing/Pipe, complete all as specified and as directed.
S&F in repairs cable route indicator for LT UG cable of 1100 volts bolted with 25x5 mm flate iron member of height 0.60 mtrs and 80 mm CI plate embeded in PCC 1:3:6 type C2 of size 15x15x20 cm block complete all as specified.
Repair/maintenance, excluding major spares but including regualr maintenance of the Automatic Power factor correction panel capacity up to 200 KVARs and upto 12 stages installed at various locations at MCEME area including carrying out complete maintenance/ repairs as required of all the sub systems viz. based control panels, feeder pillar, APFC relay, Power capacitor bank, Power contactors, Control wiring, Monitoring CT, MCBs/ MCCBs for isolation (with all the accessoires) any breakdown maintenance and replacement of unserviceable parts, refixing of old serviceable parts/ new parts if any project completion and trouble shooting responsibility also lies with contractor including following provisions complete all as specified and directed. Notes:- (i) Rate quoted by tenderer is deemed to be inclusive of checking of system fortnightly, replacement of defective control wiring, small part such as Push button, lugs any auxilary contact, auto selctor switch etc and necessary servicing repair by expert technician and register will be maintaned for the same. (ii) The scope of work includes the labour charges required for removing, repairing, refixing, carrying out electrical termination, capacitors bank, APFC relay, power contactor, contol CT, MCBs/ MCCB and fixing/installing/testing and commissioning the complete system. (iii) Capacitors bank, APFC relay, power contactor, control CT, MCBs/ MCCB shall be measured and paid seperatly.
S&F in replacement of On-Load changeover switch (In sheet steel enclosure), (Side Handle), 4 pole of capacity 615 Amps, 415 Volts, 50 Hz, complete all as specified and directed.
S&F in replacement of off-Load changeover switch (In sheet steel enclosure), (Side Handle), 4 pole of capacity 200 Amps, 415 Volts, 50 Hz, complete all as specified and directed.
S&F off-Load changeover switch (In sheet steel enclosure), (Side Handle), 4 pole of capacity 100 Amps, 415 Volts, 50 Hz, complete all as specified and directed.
Supply and fix power contactor MCX-42 of having capcity 360 Amps 4 pole 2NO+2NC complete all as specified and directed. Make :- L&T Cat part No CS97022 or equivalent HPL / Schneider
Supply only of aluminium cable lugs of following sizes :-
16 to 25 Sqmm Size
35 to 50 Sqmm Size
70 to 95 Sqmm Size
120 to 150 Sqmm Size
185 to 240 Sqmm Size. Make : Dowell/Jaison.
Supply and fix in replacement of power factor correction capacitor, 5 KVAR, heavy duty 440 volts 50 Hz complete including taking down old unserviceable capacitor complete all as specified and directed.
All as per item No 59.00 here-in-before but 10 KVAR Capacitor Bank
All as per item No 59.00 here-in-before but 15 KVAR Capacitor Bank
All as per item No 59.00 here-in-before but 20 KVAR Capacitor Bank
All as per item No 59.00 here-in-before but 25 KVAR Capacitor Bank
S&F in replacement APFC relay with auto-set functiont 7/8 stage APFC relay Make:- L&T/ HPL/HAVELLS
Supply and fixing in replacement only capacitor duty contactor suitable for rating 5 kVAR ,50Hz,440v,3-ph,3-pole in existing panel including including necessary wiring & misc accessroies for satisfactory completion of job taking down old unserviceable one complete all as directed by Engineer-in-Charge. Make: Schnieder/L&T/Seimens
All as per item No 65.00 above but 10 KVAR capacitor duty contactor
All as per item No 65.00 here-in-before but 20 KVAR capacitor duty contactor
All as per item No 65.00 here-in-before but 25 KVAR capacitor duty contactor
M&L in repairs Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size Complete all as specified and as directed
M&L for shingle or gravel, levelled and consolidated to gradient required of 50 to 75 mm spread thickness as specified for tranformer yards etc all as specified and directed.
Supply & Laying of Insulating mats 2.5mm thick made of Elastomer (a generic term that includes rubbers, latex and elastomeric compounds that may be natural or synthetic or a mixture or a combination of both) for use as floor covering for the protection of workers on ac and dc installations with the system voltages up to 11 kV ac and 240 V dc and as per Cl 5 of IS15652 latest Class B Cat II of Size 1m X 2m complete with Relevant Test Reports and fixing on floor with suitable adhesives complete all as specified and as directed Note:- the mat should be permanently pasted with the help of suitable adhesive/resin. All joints and comers shall be filled/covered with insulating material of matching colour. Matching colour and matching designed tapes should be used to maintain an aesthetic look of the installation.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.16 MB
T70_8587_Tender.pdf
Tender Documents • 0.45 MB
BOQ_837625.xls
BOQ • 0.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .