Tender Value
₹28 L
EMD Value
₹56,000
Closing Date
17 Aug 2022, 6:00 pmClosed
GE AF Subroto Park
GE AF Subroto Park c o 56 APO
REPAIR/ MAINT OF INTERNAL ELECTRIC SUPPLY INCLUDING REPAIR OF CEILING FAN/ EXHAUST FANS/ PEDESTAL FANS AND SUB MAIN WIRING SWITCH SOCKETS, FITTINGS DBs MCBs AND CERTAIN ALLIED WORKS OF CAMERO OFFICERS MESS
2022_MES_540035_1
GE/SP/ TOKEN-16/2022-23
Open Tender
Civil Works
Item Rate
120 days
Subroto Park Delhi Cantt
Please refer Tender documents.
10 documents required · 10 mandatory
₹500
GE AF Subroto Park
₹56,000
Yes
22 Oct 2022
22 Jul 2022
24 Aug 2022
22 Jul 2022
17 Aug 2022
5 Aug 2022
Amount
Taking down carefully copper/aluminium point wiring( light ,fan, socket or power) complete, fitting such as switches, ceiling roses, pendents, regulators, sockets etc.removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditioned separately) and making good disturbed surface of walls, floors etc. Complete all as specified and directed by Engineer-in-Charge.
M&L for point wiring with single core of FRLS PVC insulated unsheathed ISI marked 1100 V grade cable multi stranded copper conductor of size 1.5 sqmm drawing through in and including PVC conduit size of not less than 20 mm including conduit fittings and accessories concealed in wall / ceiling wiring terminated in flush metal box alongwith outer cover plate for mounting modular/piano switch, socket and electronic regulator along with provn of earth wire of PVC insulated, unseathed, 1100 V grade cable multi stranded FRLS ISI marked copper conductor of size 1.5 sqmm all as specified and directed by Engr-in-Charge. For One light point controlled by one switch one way.
All as per srl item 2 above but for one ceiling fan / Exhaust fan point controlled by one switch regulator.
All as per item No 2 above but for one 3 pin 5 amps socket outlet on indipendent board with other switchs.
All as per item No 2 above but for one 3 pin 5 amps socket outlet on the same board with other switchs.
All as per item No 2 above but for Call bell controled by one push button in indipendent board .
All as per item No 2 above but with 2.5 Sq mm cable for Independent one 3 pin 15 Amps socket outlet In and including S/C 2.5 Sq mm PVC insulated copper conductor unsheathed 1100 v grade IS -694 FR cable for continuous earth wire.
M&L for point wiring for one light fitting / one fan point controled by one switch with 1.5 Sq mm PVC insulated copper conductor cable drawing in and including PVC Casing/capping or surface conduit with 1.5 Sq mm PVC insulated copper conductor cable for continuous earth wire connected to main earth dolly with 3mm thick plastic laminated sheet cover complete for one light point controlled by one switch complete all as specified and directed by Engineer in Charge.
All as per srl item 8 above but for one fan point controlled by one switch through regulator.
All as per srl item 8 above but for one 5 pin 5 amps socket outlet on the independent board.
All as per item No 8 above but for one 3 pin 5 amps socket outlet on the same board with other switchs.
All as per item No 8 above but for Call bell point.
All as per item No 8 above but with 2.5 Sqmm PVC insulated stranded copper conductor cable for one 3 pin 15 Amps socket outlet. In and including S/C 2.5 Sq mm PVC insulated copper conductor unsheathed 1100 v grade IS -694 FR cable for continuous earth wire.
M&L for point wiring with 1.5sqmm PVC insulated unsheathed multi stranded copper conductor cable drawing in existing steel/PVC conduit with 1.5 Sq mm PVC insulated copper conductor cable for continuous earth wire connected to main earth dolly excluding 3mm sheet metal box and hylam sheet complete for one light point controlled by one switch complete all as specified and directed by Engineer in Charge.
All as per srl item 14 above but for one fan point controlled by one switch through regulator.
All as per srl item 14 above but for one 5 pin 5 amps socket outlet on the independent board.
All as per item No 14 above but for one 3 pin 5 amps socket outlet on the same board with other switchs.
All as per item No 14 above but for Call bell point.
All as per item No 14 above but with 2.5 Sq mm PVC insulated stranded copper conductor cable for one 3 pin 15 Amps socket outlet. In and including S/C 2.5 Sq mm PVC insulated copper conductor unsheathed 1100 v grade IS -694 FR cable for continuous earth wire.
S&F switch piano, flush type single pole, one way, 6 Amps, 240 volts all as specified and directed by Eng-in-charge.
S&F Socket outlet 2 in 1, 3 pin,6 A, 240 volts all as specified and directed by Eng-in-charge.
S&F switch piano, flush type single pole, one way, 16 Amps, 240 volts all as specified and directed by Eng-in-charge.
S&F socket 16 Amps, 2 in 1, flush type all as specified and directed by Eng-in-charge.
Supply & fix in replacement bell push, flush type, 5 Amps, 240 volts all as specified and directed by Eng-in-charge.
S&F Fan Regulator step type 120 watt, 240 volt complete.
S&F Modular Fan step regulator, 120W step type 120 watt, 240 volt complete.
S & F Modular switch 1 way 6A, 1 modules suitable for 240 volt AC Complete all as specified and directed by Engineer-in-Charge.
S & F Modular Socket, 6A - 2/3 pin combined 2 module, suitable for 240 volt AC Complete all as specified and directed by Engineer-in-Charge.
S & F Modular switch 2 way 6A, 1 modules suitable for 240 volt AC Complete all as specified and directed by Engineer-in-Charge.
S&F Modular switch 1 way 16A, 1 modules suitable for 240 volt AC Complete all as specified and directed by Engineer-in-Charge.
S & F Modular Socket, 16A 2/3 pin combined 2 module, suitable for 240 volt AC Complete all as specified and directed by Engineer-in-Charge.
Supply and fix Modular bell push 1 Module 5 Amps suitable for 240 volt Complete all as specified and directed by Engineer-in-Charge.
Supply and fix White cover plate with frame,2 module Complete all as specified and directed by Engineer-in-Charge.
Supply and fix White cover plate with frame,3 module Complete all as specified and directed by Engineer-in-Charge.
Supply and fix White cover plate with frame,4 module Complete all as specified and directed by Engineer-in-Charge.
Supply and fix White cover plate with frame,6 module Complete all as specified and directed by Engineer-in-Charge.
Supply and fix White cover plate with frame,8 module Complete all as specified and directed by Engineer-in-Charge.
S & F Modular metal flush box 3 module Complete all as specified and directed by Engineer-in-Charge.
S & F Modular metal flush box 4 module Complete all as specified and directed by Engineer-in-Charge.
S & F Modular metal flush box 6 module Complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement ceiling roses, surface bakelite 65x50mm ,3 terminals 3 phase, PVC/Polycarbonate, isolated body all as specified and directed by Eng-in charge
Taking down the old white hylium sheet from the existing flash metal box and replacing new supper quality white hylium sheet of size 9" x 13" complete all as specified and as directed by Engineer-in-Charge.
All as per srl item 42 above but of size 8" x 5" complete all as specified and as directed by Engineer-in-Charge.
All as per srl item 42 above but of size 7" x 5" complete all as specified and as directed by Engineer-in-Charge.
All as per srl item 42 above but of size 5" x 5" complete all as specified and as directed by Engineer-in-Charge.
Taking down rusted sunkan metal box and fixing new metal box of 3 mm thick of size 9''x13'' with finishig of disturbed surfaced as directed by Engineer in charge.
Taking down rusted sunkan metal box and fixing new box of 3mm thick of size 8''x5'' with finishig of disturbed surfaced as directed by Engineer in charge.
Taking down rusted sunkan metal box and fixing new box of 3mm thick of size 7" x 5" with finishig of disturbed surfaced as directed by Engineer in charge.
Taking down rusted sunkan metal box and fixing new box of 3mm thick of size 5" x 5" with finishig of disturbed surfaced as directed by Engineer in charge.
S&F in repair of sub main wiring with 2 single core 04 Sq mm PVC insulated unsheathed 1100 V grade copper conductor cable drawing in existing rigid non- metallic PVC/metallic conduit incl 4.0 Sq mm PVC insulated single core copper conductor cable for continuous earth wire complete all as specified and directed by Engr-in-charge.
S&F in repair of sub main wiring with 2 single core 06 Sq mm PVC insulated unsheathed 1100 V grade copper conductor cable drawing in existing rigid non metallic PVC conduit incl 6.0 Sq mm PVC insulated single core copper conductor cable for continuous earth wire complete all as specified and directed by Engr-in-charge.
S&F in repair of sub main wiring with 2 single core 04 Sq mm PVC insulated unsheathed 1100 V grade copper conductor cable drawing in and incl rigid non metallic PVC conduit 25 mm dia incl 04 Sq mm PVC insulated single core copper conductor cable for continuous earth wire complete all as specified and directed by Engr-in-charge.
S&F in repair of sub main wiring with 2 single core 06 Sq mm PVC insulated unsheathed 1100 V grade copper conductor cable drawing in and incl rigid non metallic PVC conduit 25 mm dia incl 6.0 Sq mm PVC insulated single core copper conductor cable for continuous earth wirecomplete all as specified and directed by Engr-in-charge.
S&F in repair of sub main wiring with 2 single core 10 Sq mm PVC insulated unsheathed 1100 V grade copper conductor cable drawing in and incl rigid non metallic PVC conduit 32 mm dia incl 10 Sq mm PVC insulated single core copper conductor cable for continuous earth wire complete all as specified and directed by Engr-in-charge.
M & L for rigid non metalic PVC medium grade conduit including junction boxes, tee, bends, elbows, reducers bell mouth tube ends,fixing accessories such as couplers, lock Nuts, saddle pipe hook etc for 25 mm dia.ISI Marked complete all as specified and directed by Engr-in-charge..
Supply & fix in replacement of Casing capping double lock type supper quality size 20 mm width ISI marked with fixing accessories complete all as specified and directed by Engineer in Charge.
Taking down of LED/Tube light/CFL fitting of any type of make and removing material to store for keeping in safe costudy or for reuse or taking credit and making good distrub surface of walls,floor etc complete all as specified and directed by the Engineer- In- Charge.
Supply and fixing wall mounted LED batten extruded aluminium heat shrink provided for efficient heat dissipation and integrated electronic driver ,20 watt LED fitting with 100 lumen/watt, 6000K , 230 Volts, diffused optics ,etc complete with all accessories , connecting up with twin core twisted flexible copper conductor cable from ceiling rose to fitting, and testing complete all as specified and directed by the Engineer- In- Charge.
Supply and fixing wall mounted LED batten extruded aluminium heat shrink provided for efficient heat dissipation and integrated electronic driver ,10 watt LED fitting with 100 lumen/watt, 6000K , 230 Volts, diffused optics ,etc complete with all accessories , connecting up with twin core twisted flexible copper conductor cable from ceiling rose to fitting, and testing complete all as specified and directed by the Engineer- In- Charge.
Supply and fixing decorative LED wall light Nickel fitting premium opal glass for reduced glare designed for use with energy saving light bulbs suitable for 9/10 watt LED with 100 lumen/watt complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable from ceiling rose to terminal block, and testing complete all as specified and directed by the Engineer-In- Charge.
Supply and fixing ultra slim surface decorative 8/9 watt with 100 lumen/watt, 6000 K ,230 volt, LED ceiling fitting, complete with all accessories , connecting up with twin core twisted flexible copper conductor cable from ceiling rose to fitting, and testing complete all as specified and directed by the Engineer-In- Charge.
All as per item No 61 above but size 15 W complete all as directed by Engr-in-charge.
All as per item No 61 above but size 18W complete all as directed by Engr-in-charge.
S&F ultra modern design architectural design 34 watt 2x2 recess LED, 6000 K luminaire having glare free symmetrical illumination Complete all as specified and directed by Engineer-in-Charge.
S&F in replacement electronic driver suitable for ultra modern 24 to 48 watt 2x2 recess LED, 6000 K luminaire Complete all as specified and directed by Engineer-in-Charge. .
All as per item No 65 above but Suitable for 9 to 18W complete all as directed by Engr-in-charge.
S&F in replacement Highly efficient mid power LED street light 60 W with pressure die cast aluminium housing, reflector and enclosed with toughened glass IP65. with 2 single cable PVC insulator unsheathed 2.5 Sq mm with stranded copper conductor fixed on pole/wall/building complete all as specified and as directed.
S&F in replacement heavy duty industrial batten with pre-coated CRCA body decorative type ,suitable for retrofit LED 1X18/20W LED tube complete all as specified and as directed.
Supply and fix in replacement lamp holder PVC/Poly Carbonate type suitable for LED Bulb with ISI mark complete all as specified and as directed by Eng-in-charge.
Taking down carefully ceiling fans of any size for repair/service/rewinding/greasing and refixing in its original position after necessary repair/rewinding/servicing/greasing etc including connecting up with flexible twin core cable 23/0.0076 from ceiling rose or connector to fan complete and to ensure that ceiling fan should be fix in position in all respect all as directed by Engineer in Charge.
M& L for minor repair/service and greasing of bearings, cleaning of dust on ceiling fans with blades and canopys and reconnecting the electrical conections and with regulators complete all as specified and as directed by Engineer-in-Charge. Note: All required Materials are deemed to be included in the unit rate quoted.
M & L for repair to Ceiling fan of of any size by replacing unserviceable ball bearing of suitable size including neccessary greasing complete all as specified and directed by Engineer-in-Charge.
M&L for Rewinding of ceiling fan of sweep 1200mm/1400 mm sweep of any make and model with super enameled copper winding wire of same size as per old winding wire and confirming to relevent IS including replacement of insulation material, varnishing, greasing and lubricating, ball baring, GM bushes and replacement of suitable capacity of condenser and testing complete all as specified and directed by Engineer in Charge.
S&F in replacement of fan capacitor with copper wire plastic body 2.5 mfd.
S&F in replacement of fan capacitor with copper wire plastic body 3.15 mfd.
S&F in replacement of rubber real for ceiling fan complete all as specified and directed by Engineer in Charge.
S&F in replacement of mild steel U clamps including 10 mm dia but, nuts, washers and split pin for ceiling fan complete all as specified and directed by Engineer in Charge.
S&F in replacement of mild steel fan hook made out of 12 mm dia mild steel round bar of suitable size as per existing hook as directed by Engineerin Charge.
S&F in replacement of upper louver conopy of ceiling fan of any sweep, make, modles & size as per existing complete as specified and directed by Engineer in Charge.
S&F in replacement of ceiling fan heady duty 1200 mm sweep including necessary fixing arrangement for proper fixing as per site requirement complete all as specified and as directed by Engineer-in-Charge.
Taking down carefully Exhaust fans of any size for minor repair/service/rewinding/greasing and refixing in its original position after necessary repair/rewinding/servicing/greasing etc including connecting up with flexible twin core cable 23/0.0076 from ceiling rose or connector to fan complete and to ensure that ceiling fan should be fix in position in all respect all as directed by Engineer in Charge.
M& L for minor repair/service and greasing of bearings, cleaning of dust on exhaust fan fans with blades and reconnecting the electrical conections and with regulators complete all as specified and as directed by Engineer-in-Charge.
M & L for repair to exhaust fan/ of of any size ( 200 to 600 mm sweep) by replacing unserviceable ball bearing No 6201/6202/6203 including neccessary greasing complete all as specified and directed by Engineer-in-Charge.
M&L for rewinding of exhaust fan pvc of 200 mm sweep with super enamelled copper winding wire of same size as per old winding wire and confirming to IS including replacement of insulating material, warnishing, greasing lubricating, ball bearing, GM bushes and replacement of suitable capacity of condenser and testing complete all as specified and directed by Engineer in Charge.
All as per item No 84 above but size of exhaust fan metal 200/225/250 mm sweep complete all as directed by Engr-in-charge.
All as per item No 84 above but size of exhaust fan metal 300 mm sweep complete all as directed by Engr-in-charge.
All as per item No 84 above but size of exhaust fan 450 mm sweep complete all as directed by Engr-in-charge.
All as per item No 84 above but size of exhaust fan 600 mm sweep complete all as directed by Engr-in-charge.
S&F in replacement of fan capacitor with copper wire plastic body 1.5 mfd suitable for exhaust fan
S&F in replacement of fan capacitor with copper wire plastic body 4. mfd suitable for exhaust fan
S&F in replacement of exhaust fan heavy duty plastic body 200 mm sweep including necessary fixing arrangement for proper fixing in wall and making hole as per site requirement complete all as specified and as directed by Engineer-in-Charge.
S&F in replacement of exhaust fan heavy duty metal body type 225/230 mm sweep including necessary fixing arrangement for proper fixing in wall and making hole as per site requirement complete all as specified and as directed by Engineer-in-Charge.
All as per item No 92 above but size of exhaust fan 250 mm sweep complete all as directed by Engr-in-charge.
All as per item No 92 above but size of exhaust fan 300 mm sweep complete all as directed by Engr-in-charge.
All as per item No 92 above but size of exhaust fan 450 mm sweep complete all as directed by Engr-in-charge.
All as per item No 92 above but size of exhaust fan 600 mm sweep complete all as directed by Engr-in-charge.
S&F in replacement of wall mounting fan heavy duty 450 mm sweep including necessary fixing arrangement for proper fixing on wall as per site requirement complete all as specified and as directed by Engineer-in-Charge.
S&F in replacement of exhaust fan louvers fan suitable for 225/230/250 mm sweep including necessary fixing arrangement for proper fixing on wall as per site requirement complete all as specified and as directed by Engineer-in-Charge.
All as per item No 98 above but size of exhaust fan 300 mm sweep complete all as directed by Engr-in-charge.
Cutting of existing surface/wall for making hole suitable for fixing of exaust fan of required size including 04 Nos hold fastner and making good the disturbed surface all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement MCB distribution board with Bus bar 200A neutral link , earth bar made out of CRCA mild steel sheet surface mounting SPN 8 way 230 volts double door type regal gray horizontal type complete all as specified and as directed by Engineer-in-Charge. Note :- MCB shall be measured and paid seperately.
Supply and fixing in replacement MCB distribution board with Bus bar 200A neutral link , earth bar made out of CRCA mild steel sheet surface mounting SPN 12 way 230 volts double door type regal gray horizontal typecomplete all as specified and as directed by Engineer-in-Charge. Note :- MCB shall be measured and paid seperately.
Supply and fixing in replacement MCCB four Pole 125 Amps, 415 volt thermal release bearing cap 16 KA suitable for the MCB DB above comlete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement MCCB four Pole 100 Amps, 415 volt thermal release bearing cap 16 KA suitable for the MCB DB above comlete all as specified and as directed by Engineer-in-Charge.
S&F MCCB FP 16 to 63 Amps 16 KA, 440/415 volt 50 Hz all as specified ans directed by engineer in- charge.
S&F MCB TP 25 to 63 Amps 10 KA, 440 volt 50 Hz all as specified ans directed by engineer in- charge.
S&F MCB TP 100 Amps 16 KA 440 volt 50 Hz all as specified ans directed by engineer in- charge.
S&F MCB TP 125 Amps 16 KA 440 volt 50 Hz all as specified ans directed by engineer in- charge.
Supply and fixing in replacement MCBs 10 KA breaking capacity, single pole, 240 volts, 6 to 40 amps C Curve capacity.
Supply and fixing in replacement MCBs 10 KA breaking capacity, single pole, and neutral, 240 volts, 40/63 amps C Curve capacity.
Supply & fix in replacement of brass screw 3/18, long threaded suitable for fixing switch boards. ( 100 Nos in one packet)
Supply & fix in replacement of brass screw 9/11, long threaded suitable for fixing switch boards. ( 100 Nos in one packet)
Supply & fix in replacement of stainless steel screw 1/2" long. ( 200 Nos in one packet)
Supply & fix in replacement of stainless steel screw 1" long.( 200 Nos in one packet)
Supply and fix in replacement of flexible wire twin core 23/.076 complete all as specified and as directed by Engr-in- Charge.
Supply & fix in replacement PVC FRLS Flexible cable copper conductor, unsheathed , 1100 volts grade confirming to IS:694/1990 of size 1.5 sqmm complete all as specified and as directed by Engineer in Charge.
Supply & fix in replacement PVC FRLS Flexible cable copper conductor, unsheathed , 1100 volts grade confirming to IS:694/1990 of size 2.5 sqmm complete all as specified and as directed by Engineer-in- charge.
Supply & fix in replacement PVC FRLS Flexible cable copper conductor, unsheathed , 1100 volts grade confirming to IS:694/1990 of size 4.0 sqmm complete all as specified and as directed by Engineer-in- charge.
Supply & fix in replacement PVC FRLS Flexible cable copper conductor, unsheathed , 1100 volts grade confirming to IS:694/1990 of size 6.0 sqmm complete all as specified and as directed by Engineer-in- charge.
Supply and fix in replacement of twin core aluminium flexible wire conductor of size 6 sq mm 2 core complete all as specified and as directed by Engr-in- Charge.
Supply and fix in replacement of twin core aluminium flexible wire conductor of size 10 sq mm 2 core complete all as specified and as directed by Engr-in- Charge.
Supply and fix tape insulation PVC 25 mm wide in various colours of standard length complete all as specified and as directed by Engineer-in-Charge.
Excavation in trenches in hard and dense soil n exc 1.5 mtr wide and n.exc 1.5 mtr in depth for laying of pipe,foundation for poles, stay, laying cables etc and getting out complete all as directed by engineer-in-charge.
Returning filling in including spreading, leveling watering and well ramming in layers n. exc 25 cm in hard/dense soil complete all as directed by engineer-in-charge..
Removing excavated material n.exc 50 meters and depositing where directed at a level n.exc 1.5 meter above the starting point copmlete all as directed by engineer-in-charge.
M&L for Sand cushioning of cables provided with a layer of sand 8 cm deep before laying the cable and 15 cm depth after punning down and stretching the cable complete all as directed by engineer-in-charge.
Supply and laying well burnt sub class ‘B’ bricks old size as mechanical protection to under ground cables laying across the cable copmlete all as directed by engineer-in-charge.
M&L for precast cement concrete block masonry with solid blocks,exceeding 10 cm in width and setting in mortar type B1, 1:2:4 using 20 mm graded aggrigate complete all as specified and as directed.
Material and labour for cutting of road/ hard standing up to a size not exceeding 20cm width and not exceeding 60cm in depth for laying of cable protection pipe including making good the disturbed road/hard standing by providing PCC (1:2:4) type B1 and block top with black bituminous upto existing surface level complete all as specified and as directed by Engineer-in-charge.
Supply and laying in replacement GI pipe light grade galvanized with all fittings laid in trenches or fix on wall for cable protection of 80 mm bore copmlete all as directed by engineer-in-charge.Make-Jindal/Swastik/Tata
All as per srl item No 130 above but size 50 mm bore complete all as directed by engineer-in-charge.
Disconnecting,removing & taking out faulty U/G cable off sizes from trenches,wall and ducts complete all specified and as directed
Supply, Laying, Testing and connecting cable XLPE insulated armoured heavy duty electric cable with stranded aluminium conductor 1100 volts grade cross section area of 300 sqmm x 3.5 core copmlete all as directed by engineer-in-charge.
All as per srl item No 133 above but size 185 Sq mm x 3.5 core copmlete all as directed by engineer-in-charge.
All as per srl item No 133 above but size 120 Sq mm x 3.5 core copmlete all as directed by engineer-in-charge.
All as per srl item No 133 above but size 95 Sq mm x 3.5 core copmlete all as directed by engineer-in-charge.
All as per srl item No 133 above but size 70 Sq mm x 3.5 core copmlete all as directed by engineer-in-charge.
All as per srl item No 133 above but size 50 Sq mm x 3.5 core copmlete all as directed by engineer-in-charge.
All as per srl item No 133 above but size 35 Sq mm x 3.5 core copmlete all as directed by engineer-in-charge.
All as per srl item No 133 above but size 16 Sq mm x 4 core copmlete all as directed by engineer-in-charge.
All as per srl item No 133 above but size 10 Sq mm x 2 core copmlete all as directed by engineer-in-charge.
Supply and fixing in replacement of aluminium thimble stud type suitable for size of cable 240 to 400 sq mm all as specified and directed by engineer-in-charge.
Supply and fixing in replacement of aluminium thimble stud type suitable for size of cable 16 to 180 sq mm all as specified and directed by engineer-in-charge.
M & L in replacement FRP juction box including MCBs with front cover fixed with locking arrangement with suitable clamp/fixture on pole complete all as specified and directed by Engineer-in-Charge.
Material and labour for cleaning of Electric panel at rusted portion with sand paper and painting with synthetic enamel paint suaitable for metal complete all as specified and as directed by Engineer-in-Charge
M&L for preparation of old painted surface of steel tubular swaged poles (9 to 11 meter long) with good neck brackets including junction box, GI pipe and light fittings i.e HPSV/HPMV any rating and painting with one coat of aluminium paint including cleaning the acrylic cover and painting with black to 1.5 mtr height from top of PCC coping and marking pole numbers with one coat of synthetic enamel paint complete all as specified and as directed by Engineer-in-Charge.
M&L for earthing complete with GI earth plate electrode 60cmx60cmx6.3mm thick buried directly in ground (earth pit not less than 2.25 meter deep below normal ground level) with top edge of the plate not less than 1.5 meter below normal ground level, connected to galvanized earth lead wire 4 mm dia by means of GI bolts, nuts, check nuts and washers earth pit surrounded by picked layer of coal dust and 15 mm thick mixture in equal ratio of magnesium sulphate & copper sulphate in all around bottom and top and watering pipe 20mm bore of GI medium grade with funnel all as shown in electrical plate NO 5 of SSR Part I (1991) and connecting to earthing test point, including CI cover, frame and PCC (1:3:6) type C-2 using 20mm graded stone aggregate as in earthing pit with CI cover and framing including necessary earth work etc, complete all as specified Note 01 : PCC chamber shall be constructed at least one meter away from building shall be provided in slanting manner. 02 :- PCC pit cover shall be precast of RCC 1:2:4 type B-I 80 mm thick reinforced with XPM weighting not less than 4 Kg (sqm in liew of CI)
All as per item No 147 above but using galvanised iron strip 25x4mm as earthhing lead
S&F in replacement 4mm dia GI wireas per site requirement complete all as specified and directed by Engr-in-charge.
Material and labour for galvanised iron strip 25 X 4 mm with saddles and fixing screws and connected as per site requirement comlete all as specified and as directed by Engineer-in-Charge.
Disconnecting to worn out cable off size from main control panel /LT over head line/UG line cutting worn out portion and reconnecting including suitable size of aluminium lugs & thimbles ,nuts, bolts & washers comlpete (excavation of necessary earth work shall be measured and paid separately complete all as specified and as directed by Engineer-in-Charge.)
Taking down four/three runs of ACSR Conductors from overhead poles after disconnecting all connections and depositig in the store complete all as specified and directed by Engr-in-charge.
M&L for cutting/trimming of branches of tree tuching/aproaching LT over lines of various spans(having 40 to 45 mtr) up to 3 mtr width on each side from different site of grith up to 10 cm with cutting equipments hacksaw,axe,ladders,rope and safety measures etc including disposal of trimmed branches 500 mtr away inside the cantonment area and cleaning the area complete all as specified and directed by Engineer-in-charge.
M&L for re-streaching of loose LT over head line,aluminium conductor,GI guard wires and credals etc complete at various location and difrent span of 2 to 7 conductors with the help of rope and pullar etc complete all as specified and directed by Engineer-in-charge.
S&F in replacement of pin type,porcelain,vitreous,white,brown or green insulator including one galvanised mild steel spindle,two galvanised iron washers and one galvanised iron nut, 100 mm height,65 mm dia for 1100 volts grade complete all as specified and as directed.
S&F in replacement of shackle type,porcelain,vitreous,white,brown or green insulator 1100 Volts LT of size 100 mm high and 115 mm dia including galvanised mild steel straps of size 31x5 mm,washers,insulator bolts 14 mm dia,washers and nuts etc complete all as specified and as directed.
S&F in replacement of ACB 630 Amps FP 415 volts 3 phase 50 HZ with Adjustable Thermal & adjustable Magnetic setting of rapturing capacity 36 KA.
S&F in replacement of MCCB 400 Amps FP 415 volts 3 phase 50 HZ with Adjustable Thermal & adjustable Magnetic setting of rapturing capacity 36 KA.
S&F in replacement of MCCB 250 Amps FP 415 volts 3 phase 50 HZ with Adjustable Thermal & adjustable Magnetic setting of rapturing capacity 35 KA.
S&F in replacement of MCCB 200 Amps FP 415 volts 3 phase 50 HZ with Adjustable Thermal & adjustable Magnetic setting of rapturing capacity 35 KA.
S&F in replacement of MCCB 160 Amps FP 415 volts 3 phase 50 HZ with Adjustable Thermal & adjustable Magnetic setting of rapturing capacity 35 KA.
Supply and fixing in repairs amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of SP 5 To 32 AMP in the MCB DB/ junction box complete with connection testing and commissioning.
M& L for Fabricate, supply and install cubicle type, CPRI approved LT panel board,outdoor type, totally enclosed,dust & vermin proof (protection class IP 65) front opening with self locking arrangment made out of MS angle iron frame work, MS flat iron and CRCA sheet of 3.15 mm thick as per IS 5039 duly painted with powder coated paint of approved shade. The panel shall be suitable for 415 volts,50 Hz, 3 phase 4 wire system and shall be complete with 800 amp capacity copper bus bar, wiring the panel board with suitable size of PVC insulated, multi stranded copper cables and all connected acessories required for functioning of panel board such as thimbles,glands, bolts, nuts,washers etc including supply and fixing following acessories: (a) ACB, 4 pole, 800 amp current carrying capacity, 50 Hz, 415 volt with rupturing capacity 36 KA - 01 No ( Incoming) (b) Digital type volt meter - set 01 (c) Digital type ammeter with suitable rating CTs conforms to relevent IS specification,- set 01 (d) LED type indicator lamp set of red , yellow and blue - set 01 Outgoings:- (a) MCCB 4 pole, 250 Amp current carrying capacity, 50 Hz, 415 volt with rupturing capacity 36 KA - 07 Nos
M& L for Fabricate, supply and install cubicle type, CPRI approved LT panel board,outdoor type, totally enclosed,dust & vermin proof (protection class IP 65) front opening with self locking arrangment made out of MS angle iron frame work, MS flat iron and CRCA sheet of 3.15 mm thick as per IS 5039 duly painted with powder coated paint of approved shade. The panel shall be suitable for 415 volts,50 Hz, 3 phase 4 wire system and shall be complete with 400 amp capacity copper bus bar, wiring the panel board with suitable size of PVC insulated, multi stranded copper cables and all connected acessories required for functioning of panel board such as thimbles,glands, bolts, nuts,washers etc including supply and fixing following acessories: Incoming:- (a) MCCB, 4 pole,400 amp current carrying capacity, 50 Hz, 415 volt with rupturing capacity 36 KA - 01 No ( Incoming) (b) Digital type volt meter - set 01 (c) Digital type ammeter with suitable rating CTs conforms to relevent IS specification,- set 01 (d) LED type indicator lamp set of red , yellow and blue - set 01 Outgoings:- (a) MCCB 4 pole, 200 Amp current carrying capacity, 50 Hz, 415 volt with rupturing capacity 36 KA - 2 Nos (b) MCCB 4 pole, 160 Amp current carrying capacity, 50 Hz, 415 volt with rupturing capacity 16 KA - 02 Nos
M & L in replacement LED display board made of iron frame of size of 1.5mx1mx0.1m covered with display sheet including LED lighting inside the frame with fitting/fixture acessories suitable for ousideand connecting all as specified and directed by Engineer-in-charge.
M/S LADPURIA ENTERPRISES
CHAUHAN ENTERPRISES
J.P. Enterprises
sheetal engineering
shakti construction
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .