REPAIR/MAINT OF HT UG CABLE, LT DISTRIBUTION SYSTEM, HT INSULATOR, GANG OPERATED DEVICES FOR 2 POLE STRUCTURE, 4 POLE STRUCTURE AND CONNECTED ALLIED WORKS AT JAFFARPORE, BARASSAT, KPA AND LOS DUM DUM UNDER GE (AF) BARRACKPORE
2024_MES_673855_1
8304/BKP/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
CWE AF KALAIKUNDA
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (AF) BARRACKPORE
₹30,000
Yes
30 Apr 2025
11 Sept 2024
16 Oct 2024
11 Sept 2024
15 Oct 2024
25 Sept 2024
Amount
Disconnection of all HT/LT connection of the defective distribution transformer 11/0.433 KV out door / indoor any make taking down / out from plinth / pole / platform with the help of crane and transporting the same carefully to workshop for repair/rewinding and taking back after repair to its existing position, upto 315 KVA and repairing of tank body, denting/ painting of full body afer preparation and 2 coats zinc chromite primer over 2 coats anti corrosive synthetic enamel paint on body by using spary gun and compressor to transformer, re-assembling of transfomer, testing of copper loss, iron loss, core loss, insulation test of all HT/LT windings, topping up of transformer, testing of di-electric strength of transformer oil and achieving upto 40MV to 60MVcomplete all as directed by Engr-in-Charge. Note:- (i) The rate quoted is deemed to be inclusive of necessaryTesting/ Painting/ Crane / vehicle charges for shifting and installation of the transformer. (ii) The items covered shall be executed immediately during the break down period and the work will be executed as directed by Engr-in-Charge. (ii) All the materials such as Transformer Oil, Copper winding wire, insulating papers, core plates, assembling accessories etc are mesured and paid saperetely in relevent item.
M&L for Making LT/HT coil suitable gauge of super enamelled copper solid conductor wound in the shape of helical/disc/cylindrical/crossover or as per existing to generate maximum MMF and insulation of winding wrapped with kraft paper/press board, cotton insulating taps and insulating materials shall be of Class A type to withstand 105 degree celicius temperature, including making of coil as required of upto 315 KVA capacity of transformer complete all as directed by Engr-in-Charge.
Opening of the 11 KV / 0.433 KV transformer up to 315 KVA by removing the inspection cover / top cover, decanning of the transformer oil up to the required level for replacement of LT/HT bush complete from the shell and renewal for burnt out LT/HT bush to avoid leakage of oil refilling back to existing oil into the transformer complete testing & commissioning complete all as directed by Engr-in-Charge. Note : HT/LT bush will measured and paid separately under relevant item.
Supply only of HT bushing including metal parts and washer made M12 type complete for any make of plinth/pole mounted transformer of 100 to 315 KVA capacity complete all as directed by Engr-in-Charge.
Supply only of LT rod / studs made of brass with nut and washers fittings etc as per size and shape of original of 100 to 315 KVA complete all as directed by Engr-in-Charge.
S&F in repair rubber cork sheet gasket complete kit for transformer top cover of capacity 100KVA to 315KVA of existing size, shape and thickness complete all as specified and as directed.
S&F in repair cable jointing kit for 11 KV (Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and as directed.
S&F in repair cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and as directed.
S&F in repair cable jointing kit for 11 KV (Earthed) grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and as directed. (Note: Contractor has to arrange cable fault locating machine, vehicle and manpower and the cost of the same shall deemed to be included in the unit rate.)
S&F in repair Eletrical Insulation Mat as per IS-15652/2006 coded of Size 1 metre x 2 metres x 2.5mm thick, Grip Pattern Blend of Synthetic polymers material, Sock proof, Colors : Black/Blue, Class B (Suitable for upto 11 KV) complete all as specified ad directed by Engr-in-Charge Note- Test report and warranty 2 Years shall be submitted on payment
Supply and install in replacement of HT 11 KV outdoor gang operated air-break switch suitable for horizontal or vertical mounting with drop out fuse having 12 insulators of rating upto 200 Amps including taking down old unserviceable complete all as specified and directed.
S&F in repair Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo Amp 11000 Volt including taking down old unserviceable complete all as specified and directed.
M&L for Servicing / Greasing of HT Switch air break ( GOD) 11 KV TP with replacement of Corroded nut Bolts Male Female contact, ACSR Jumpers, making alignment of operating Mechanism for Proper ON / OFF operation of GOD and male contact including greasing complete all as specified and as directed. Note- Male Female contact shall be measured & paid separetely
Supply only Male and Female contacts 400A suitable for 11 KV Air Break switch complete all as directed by Engr-in-Charge.
Supply and fixed in replacement for MS Channel/ Angle/Cross arms 'C' type, dimension and thickness as per existing fitted at site including making hole for clamping arrangements, drilling holes in any dia at any length, welding fabrication,, bending including all kind of nuts/bolts/washers and MS clamps of 5 mm thick and not less than 5 cm width suitable for mounting/fixing MS 'C' Channels on 4 pole/3 pole/2 pole or HT/LT poles including painting of complete structure including existing one by applying two coats of alumium paint over a coat of metalic primer after preparing the pole surfaces complete all as specified and as directed.
M&L for cement concrete (1:3:6) type C1 using 20 mm graded stone aggregate in coping of poles including necessary work finished the exposed surface even without using extra cement complete all as directed by Engineer-in-Charge.
M&L for cement concrete (1:4:8) type D2 using using 40 mm graded stone aggregate in foundation, filling and mass concrete. complete all as directed by Engineer-in-Chrage.
Removal of foreign material /vegitation from yard and depositing a side for 2/4 pole structure yard approx 1000 Sqm for filling of sand layer in yard complete all as directed by Engr-in- charge. Note- Sand paid through under relevent item
Supply and spread grade stone aggregate 40 mm in structure yard of 2/4 poles complete all as directed by Engr-in-charge.
Supply and spread grade stone aggregate 20 mm in structure yard of 2/4 poles complete all as directed by Engr-in-charge.
Dehydration including filtration cleaning of transformer oil in transformer indoor / outdoor type at different location DMRL area by contrifusion / machine having minimum capacity 1000 to 30000 ltrs / hrs including testing oil before and after dehydration for each and di-electric strength not less than 40MV in 2.5 gap complete all as directed by Engr-in-Charge.
Supply and topping up of new transformer oil of existing type having di-electric strength not less than 60MV complete all as directed.
Supply and fix in replacement Silica gel alongwith breather assembly of existing size of transformer capacity 100KVA to 315KVA including minor repair works in breather assembly, if required, complete all as specified and as directed.
M&L for preparation of HT Steel Tubular Two pole structure including cross arms, MS channels, clamps after scrapping thoroughly the existing rust / dirt / dust and corroded paint from the old steel surfaces and applying two coats aluminum paint over a coat of red oxide primer, complete all as specified and as directed.
M&L for preparation of HT Steel Tubular Four pole structure including cross arms, MS channels, clamps after scrapping thoroughly the existing rust / dirt / dust and corroded paint from the old steel surfaces and applying two coats aluminum paint over a coat of red oxide primer, complete all as specified and as directed.
M&L for ACSR conductor, proper jointing with suitable clamps and termination with the help of suitable lugs in GODs, Drop Out units, insulators and cable end terminations etc of weasel with permissible sag as per IS rules etc including taking down old unserviceable ACSR conductor of any type and size complete all as specified and as directed.
S&F in repair Disc type insulator, porcelain, vitreous 145mm high and 255 mm dia ball and socket type, white, brown or green single disc assembly for tension with tension clamps for couductor, working pressure 11000 Volt, complete all as specified and as directed.
M&L in repair Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut150mm height, 150mm dia for 11000 volts grade, complete all as specified and as directed.
M&L for disconnecting and taking out existing HT 11 KV VCBs of any make from housing and cleaning, rubbing and overhauling the mechanical parts and Servicing of 11KV indoor VCB, checking of quality of vacuum interrupter, insulation resistances, static contact resistance, Testing ( IR value, Ratio test, Polarity test) and connection verification of 11 KV Current transformer( Set of three) by PRIMARY CURRENT INJECTION KIT ,and Testing and calibration of relay( set of two Over current and one earth fault) by SECONDARY CURRENT INJECTION KIT including all other functional tests of the VCB, C&R panel and CTs, PTs complete all as specified and as directed. [Note:(i) Contractor shall be liable for arrangement of transportation. (ii) Contractor has to arrange suitable technician after getting shutdown permission from this office, atleast one week through proper channel.]
Supply, connecting and testing of copper tripping coil and closing coil 24V DC or 110V DC or as per existing voltage for 11 KV VCB including dismantling of old unserviceable one complete all as specified and as directed.
Supply, connecting and testing indicator lamp LED type, 30/110/220 volt DC (RED/YELLOW/BLUE) for each Phase, including taking down old unserviceable one, complete all as specefied and as directed. (Make: L&T/RAAS/SIEMENS)
S & F in repair three phase Voltmeter square type Digital of size 96mm x 96mm of capacity 0 to 15 KV PT Ratio 11KV/110 Volt for panel complete all as specified and as directed.
S&F in replacement Supply, installation, testing and commissioning of Micro processor based relay IDMT type (02 O/C + 01 EF) for 11 KV VCB panel, rating 5 Amps, Auxiliary supply 20-110 Volt DC complete all as specified and as directed. Note: (i) Testing of all kind of faults with minimum and maximum fault level shall be carried at site. (ii) Contractor has to arrange primary and secondary current injecting device alongwith expertised technician at his own cost.
S&F in repair HT 11KV VCB resin & Copper bound Bus bar Spout 3 phase, Industrial grade complete assembly, as per existing model / size, complete all as specified and as directed.
S & F in repair VCB Bus bar support insulator 11KV grade red colour with complete assembly, complete all as specified and as directed.
Excavation in trenches in soft/loose soil not exceeding 1.5 m wide and not exceeding 1.5 m in depth, n.exc 10 sqm on plan, for foundation or for laying of cable/ pipe lines etc. and getting out complete all as specified and as directed .
Returning, filling in, including spreading, leveling, watering and well ramming in layers n.exc 25cm as in soft loose soil complete all as specified and as directed.
Removing excavated soil to a distance n.exc 50m and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and as directed.
Supply and spread clean dry river sand as cable cushioning for prtection of cable to be laid in treaches/transformer yard/two pole structure as per SSR part I complete all as specified and directed by Engineer - in - Charge.
S&F burnt clay bricks, sub class B, old size, in trenches on cable as cable protection across the length of the cable (width wise) complete all as specified and as directed.
Supplying and laying un-reinforced precast concrete cable cover but class HV, Type 1, flat, size 300mmx l80mm x 40mm complete all as specified and as directed.
Supply, laying & testing and connecting cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade, of size 95 sq mm 3 core, (earth grade) ISI marked including taking down old unserviceable cable of any description complete all as specified and directed.
Supply and lay cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armored, electric power cables ( heavy duty ) 1100 volts grade with stranded aluminium conductor of size 95 Sqmm 3.5 core including taking down old unserviceable cable of any description complete all as specified and directed.
Supply and lay cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armored, electric power cables ( heavy duty ) 1100 volts grade with stranded aluminium conductor of size 70 Sqmm 3.5 core including taking down old unserviceable cable of any description complete all as specified and directed.
Supply and lay cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armored, electric power cables ( heavy duty ) 1100 volts grade with stranded aluminium conductor of size 50 Sqmm 3.5 core including taking down old unserviceable cable of any description complete all as specified and directed.
Supply and lay cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armored, electric power cables ( heavy duty ) 1100 volts grade with stranded aluminium conductor of size 35 Sqmm 3.5 core including taking down old unserviceable cable of any description complete all as specified and directed.
S&F in replacement MCCB 4 pole, 415 Volts, 63 Amps with breaking capacity 25 KA (Adjustable Thermal Magnetic Release Setting) complete all as specified and as directed.
S&F in replacement MCCB 4 pole, 415 Volts, 100 Amps with breaking capacity 25 KA (Adjustable Thermal Magnetic Release Setting) complete all as specified and as directed.
S&F in replacement MCCB 4 pole, 415 Volts, 160 Amps with breaking capacity 25 KA (Adjustable Thermal Magnetic Release Setting) complete all as specified and as directed.
S&F in replacement MCCB 4 pole, 415 Volts, 200 Amps with breaking capacity 36 KA (Adjustable Thermal Magnetic Release Setting) complete all as specified and as directed.
S&F in replacement MCCB 4 pole, 415 Volts, 400 Amps with breaking capacity 36 KA (Adjustable Thermal Magnetic Release Setting) complete all as specified and as directed.
M & L for cutting/excavating the road/hard standing (hard rock) for the laying of cable crossing pipe complete all as directed by Engr-in-charge.
M&L for PCC (1:3:6) type C-2 (using 40 mm graded stone aggregate) as in foundations, filling and mass concrete complete all as specified and as directed.
S&F in repair GI tubing of size 50 mm bore, light grade, with all fittings for protection of cables, to cross under road, hard standing, pavements etc and making good the disturb surfaces complete all as specified and directed.
M&L for preparation of old painted steel and iron surfaces of LT panel board, feeder pillar box and AMF panel board/PFC panel etc over 10cm width or girth and applying two coats of anti corrosive synthetic enamel paint over one coats of metallic zinc chrome primer complete all as specified and as directed.
S&F power pack of AC input 230V and output DC 24V - 110 Volt complete with weather proof enclosure, connecting cables, fixing accessories, inbuilt battery for 4 hr backup to operate relay and VCB charging mechanism complete
M&L for complete disconnecting APFC panel from all incoming/outgong connection of any capacity, checking the serviceability of all components i.e existing capacitors, contactors, MCB's, indicator lights-03Nos, replacement of burnt out PVC insulated copper wire-40RM, copper thimble - 08 Nos, MCB's SPN C Series (6-25Amp) - 02 Nos and re-connect the same after thoroughly clean including testing complete all as specified and as directed. (Note:- Power factor controller shall be measured and paid separately).
Supply installation, commissioning and testing including providing all necessary electrical connection, LT feeder panel board of size (CPRI Approved), outdoor type, double door,factory made out of 3 mm thick MS sheet of size 1.5 m x 1.3 m x 0.5 m deep having hinge opening arrangement in front and back side and bottom frame made out of angle iron of size 40x40x5mm thick and 04 nos legs 0.45 meter length with cable entry and exit circular hole with cable gland & gasket at bottom complete RYB PVC colour coated heat shrink sleeves aluminium bus bar of capacity 1000 Amp with inslulator supported including painting to all internal and external exposed steel surfaces with powder coating paint (7 stage process) with duly fixed in ground with necessary PCC foundation (1:2:4) type B1 upto a height of 0.5 mtr from ground level with danger notice plate of 1.6mm thick mild steel sheet, vitereous enamelled (white), with letters, figures and conventional skull and bones in signal red colour, fixing lugs, bolts, screws etc complete and comprising of the following accessories including necessary excavation work for taking out cable loop and refilling the trenches including taking down old unsv existing panel all as directed by the Engr-in-Charge:- Incoming(a) Onload changover 400A (open execution type) (b) MCCB 630A, 415 Volts 4 pole, 50 KA (Thermal Megnetic release) Rotary handle- 01 No Make: Legrand/L&T/Havells Outgoing (a) MCCB 100A, 415 Volts 4 pole, 25 KA (Thermal Megnetic release) Rotary handle- 08 Nos Make: Legrand/L&T/Havells (b) Phase Indicating lamp (neon) LED type (set of three Red,Yellow,Blue)----01 Set. (c) 3 Ph Digital Amps incl CTs 600/5A and Voltmeter for protection/ controlling MCB 6 Amps SP 10 KA- 01 Set
Dismantling and shifting of indoor/outdoor type LT Panel Board of ( Appx size min 1.2 m x 1.00 m x 0.5 m and max 2.0 m x 1.5 m x 0.6 m) with all accessories after disconection of outgoing & incomming cables, earth strips etc. and taking away from existing location and re-installation on the P.C.C./ brick platform duly grouted in the new platform constructed within 15 mtr from the existing location and reconnection of all outgoing and incomming cables, all as specified & as directed.
Supply and fixing tamper proof intelligent power factor controller with digital multi function meter display of capacity 8 Step 440 volt, 3 phase 50 Hz. complete all as specified and as directed.
S&F in repair HDPE pipe of 150mm dia, PN 10, heavy grade, fixed on 2 pole/4 pole structure for cable protection etc. complete all as specified and as directed.
M&L for cleaning of HT/LT Electric supply installation by spraying of weeds herbicide for kill unwanted vegetation around near and around electrical power house installation, around all LT panel boards and feeder pillar boxes, cutting grass, removing unwanted bushes, removing debris etc and making good of undulated ground by filling fresh soil and levelling the area to existing ground level, removing unwanted debris from the premises at a distance above 50m from site complete all as specified and as directed. [Note: (i) Locations - (a) Jaffarpore, approx area - 2800 SQM. (b) Kancharapara AF Camp, approx area - 3600 SQM (c) LOS Dum Dum AF Camp, approx area - 1600 SQM (ii) In case of damage to any existing assets such as UG cables, Pipelines or any type of things, contractor has to make good as per the existing.]
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .