Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Infra Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | Ist₹12.9 LAccepted-AOC | Ist | Accepted-AOC L-1 Bidder | |
| 2 | IInd₹13.0 LRejected-Finance 145 1 0 NEAR OLD LIC SHIV NAGAR VILLAGE TOWN MODIPURAM CITY MEERUT MEERUT UTTAR PRADESH 250110 INDIA | MEERUT | UTTAR PRADESH | 250110 | IInd | Rejected-Finance L-2 Bidder | |
| 3 | IIIrd₹14.0 LRejected-Finance | IIIrd | Rejected-Finance L-3 Bidder | |
| 4 | IVth₹14.4 LRejected-Finance | IVth | Rejected-Finance L-4 Bidder | |
| 5 | Rejected-Technical | - | Rejected-Technical Due to no experince as per PQR. |
Tender Value
₹14.3 L
EMD Value
₹15,000
Closing Date
1 Dec 2023, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE, ETC-I, Varanasi
Bhikaripur, DLW, Varanasi
INSTALLATION OF 1X40MVAR CAPACITOR BANK ALONGWITH OTHER ASSOCIATED WORKS
2023_UPTCL_861195_1
E-tender no. 48/2023-24/ETC-I/VNS
Open Tender
Electrical Works
Item Rate
45 days
400KV Substation Sarnath
Fee/EMD/PAN/GST Registration and experience for execution of work as per specification
2 documents required · 2 mandatory
₹590
SE, ETC, Varanasi
₹15,000
15 Apr 2024
10 Nov 2023
2 Dec 2023
10 Nov 2023
1 Dec 2023
25 Nov 2023
Amount
Following works are to be Carried out at 400KV Sub Station Sarnath, Varanasi for the Work of Installation of 2x40MVAR Capacitor Bank alongwith other associated Works including all cost of men, material, misc. consumables, T&P etc. to complete the job satisfactorily as per site requirement & direction of the Supervising Engineer :
Supply of Bolted type Single Tension Fitting Assembly, suitable for Single ACSR Panther Conductor & 70KN Disc Insulator, complete with Hardware Fittings, D-Shackle, Socket Eye, Ball Link, Tension Clamp etc., as per Drawing / Sample.
Supply of Single Suspension Fitting Assembly Free Centre Type suitable for ACSR Panther Conductor & 70 KN Disc Insulator consisting of Suspension Clamp, J-Hook, Ball Hook complete with Split Pin, G.I. Bolts, Nuts, Plain & Spring Washers etc. as per Drawing / Sample.
Supply of PG Clamp duly Made of LM-6 Aluminium Alloy, suitable for ACSR Moose to ACSR Panther Conductor, Complete with 4 No. 16×90 mm size HDG Bolts, Nuts, Spring & Plain Washers, as per Sample.
Supply of PG Clamp duly Made of LM-6 Aluminium Alloy, suitable for ACSR Panther to ACSR Panther Conductor, Complete with 4 No. 16×90 mm size HDG Bolts, Nuts, Spring & Plain Washers, as per Sample.
Supply of 40 mm M.S. Round Bar alongwith Carriage of the same from designated place to 400KV S/S Sarnath, Varanasi.
Supply of 40 mm dia M.S. Electrode of 3 Meter length alongwith Carriage of the same from designated place to 400KV S/S Sarnath, Varanasi.
Hot dip Galvanised, Hexagon Round head transmission Nut Bolts & Washer of following sizes
16 mm x 45 mm
16 mm x 50 mm
Supply of MS Flat of following Sizes alongwith Carriage of the same from designated place to 400KV S/S Sarnath, Varanasi :
Laying of Earth Mat in 132KV Switchyard alongwith Connecting the newly laid Earth Mat with existing Earth Mat as per details below :
Fabrication of 3 Meter Long Electrode with 36 mm dia. M.S. Round Bar having 150 mm Long Conical Shape by due Cutting, Straightening etc. and then Piercing it Vertically, inside the Ground with Top 700 mm below the Ground Level including Shifting of M.S. Round Bar from Storage Place at the Sub Station to Switchyard.
Laying of 40 mm dia. M.S. Round Bar, 700 mm below the Ground Level by due Cutting, Straightening, Welding, Painting, Excavation of Trench, Back Filling of Trench after Laying of Earth Mat including Shifting of M.S. Round Bar from Storage Place at the Sub Station to Switchyard.
Making of 150 mm Long Lap Joint of above laid 36 mm dia. Round Bar by due Cutting, Straightening, Welding etc. on both sides of Joint.
Making of 150 mm Long Lap Joint of above laid 36 mm dia. Round Bar to Connect with existing Earth Mat of the Sub Station by due Cutting, Straightening Welding etc. on both sides of Joint.
Making of Cross Joint of above laid 36 mm dia. M.S. Round Bar, 700 mm below the Ground Level by due Welding at all 4 Corners including Providing & Welding of suitable size 2 No. M.S. Angle Pieces on Opposite Corners of the Cross Joint.
Making of End Joint of above laid 36 mm dia. M.S. Round Bar with Top of the already Vertically Pierced M.S. Electrodes, 700 mm below the Ground Level by due Welding.
Cutting, Straightening & Laying 500 mm below inside Ground & above Ground of M.S. Flats 50 mm x 6 mm (to be Provided by Department as per Requirement) for Diagonal / Double Earthing of the Main & Aux. Structures, Equipments (CB, Isolators, CTs, PTs, C&R Panel, Junction Boxes etc.) including Welding with Main Earth Mat and with Object to be Earthed, back filling of Soil to completing the Job satisfactorily.
Earthing of Grounded Cable racks in the cable trenches of 132KV Capacitor Bank Bay. The work covers earthing of angle Iron Cable Rack by means of 25 mm x 6 mm M.S. flat including Cutting, Straightening, Laying & Welding on Racks, which will run continuous on each and every Bottom, Top & Middle Rack of Trench and it should be connected at distance of every 750 mm on the continuous running Bottom MS Flat.
Fabrication of 3 Meter long Electrode with 40 mm dia M.S. Rod having 150 mm long conical shape and then its piercing vertically in the ground with top 500 mm below ground level, its welding with 75x10 mm size M.S. Flat for making of Shielding Mesh for LAs and finally, connecting the Shielding with Main Earthmat at 2 places, with due digging of Earth /Trench, its back filling and painting etc. with all other associated works for satisfactory completion of the job of Shielding Mesh for 132 KV LAs. as per technical specification.
Painting of following sizes M.S. Earthing Strips by Rubbing with Sand Paper & Wire Brush, then Painting with 1 coat of Red Oxide Primer & 2 coats (The 2nd coat of Paint shall be applied at the gap of 48 hrs. when 1st coat of Paint is done & Checked by concerned A.E. / J.E.) of 1st quality Synthetic Enamel Paint of Asian / Berger / Nerolac make in Bus Green Colour :
50 × 6 mm size M.S. Earthing Strip.
25 × 6 mm / 25 × 5 mm size M.S. Earthing Strip.
Loading, Carriage and unloading of Galvanized Sub Station Structure from EFU, Naini (Allahabad) / Designated Place to 400KV Sub Station Sarnath, Varanasi.
Sorting, Weighing and Loading of Galvanized Sub Station Structures on private Truck to be arranged by the Contractor at EFU Naini, Allahabad / Designated Place.
Safe Transportation of Galvanized Sub Station Structures by Private Truck arranged by the Contractor from EFU Naini, Allahabad / Designated Place to 400KV Sub Station Sarnath, Varanasi (Distance 150 Km. approx.) including Toll charges.
Unloading, Sorting & proper Stacking of Galvanized Sub Station Structures from Private Truck arranged by the Contractor at store yard 400KV Sub Station Sarnath, Varanasi.
Safe Loading of Approx. 1.5 Km. (1 Drum) ACSR Panther Conductor on Suitable Vehicle, Shifting from storage place to Loading place at designated 220KV or 132KV Sub Station, Safe Carriage of above Conductor Loaded on Vehicle to be arranged by the Contractor from designated 220KV or 132KV Sub Station to 400KV S/S Sarnath, Varanasi (Approx. Distance 50 - 60 Km.), Safe Unloading of above Conductor Loaded on Vehicle, Shifting of same to safe storage place at 400KV S/S Sarnath, Varanasi with all other associated works, with all cost of men, misc. consumables and T&P etc. required for satisfactory completion of the job.
Erection of following Structures (to be Provided by Department as per Requirement) including their Shifting from Storage Place at the Sub Station to Erection Site :
Lattice type Main Structures.
Lattice type Auxiliary Structures.
Making hole in Auxiliary Structures / Main Structures as per site requirement by Gas Cutter & Grinding Machine.
Erection of following Equipments (to be Provided by Department as per Requirement) including their Shifting from Storage Place at the Sub Station to Erection Site :
2x20MVAR Capacitor Bank Unit
Control Panel for 2x20MVAR Capacitor Bank
145KV SF6 C.B.
145KV C.T. Junction Box
145KV Bus Isolator with associated PIs
145KV Tandem Isolator with associated PIs
145KV Bus Post Insulators
132KV Series Reactor
132KV Neutral C.T.
Erection of AC Power Cubical for Breaker / Isolator.
Laying of following size Armoured Control Cable in Control & Relay Panel in Control Room and various equipment such as C.T., J.B., C.B. Isolators etc. in switch yard making the hole of proper size fixing of glands and providing of ferrules and then wiring the same as per drawing, including dressing of control cable and numbering on cables.
Interconnection & Termination of various sizes above Laid Control Cables between 132KV Capacitor Bank Feeder C&R Panel to various Equipments & Equipments to Equipments in 1 No. 132KV Capacitor Bank Feeder Bay including Extending D.C. Supply from DCDB and A.C. Supply from ACDB to C&R Panels and various Equipments including Making necessary Holes in Gland Plates, wherever Required alongwith Providing & Fixing of Appropriate sizes Cable Glands, Providing of Ferrules for each Core of the Cables, then Termination with Crimping type Copper Lugs alongwith Preparation of Inter-Connection Drawing and Commissioning of the Panel / Feeders in Co-ordination with T&C Wing including Providing of 2 Sets of Hard Copies of as Executed Inter-Connection Drawing. (1 Job for each Bay)
Termination of already laid 3.5 Core x 400 mm2 Power Cable by providing suitable size aluminium dowell make lugs its crimping and connecting with equipment including cost of lugs and all other associated work to complete the job.
Laying & Stringing of 132KV 3f Jack Bus Bars of 36 / 24 Meter Length of Single ACSR Panther Conductors including Hoisting of Disc Insulator Strings, Tension Fittings etc. alongwith Shifting of the Conductor / Materials from Storage Place at the Sub Station to Erection Site.(1 Job for each Phase of each Section of the Bus Bar)
Jumpering with Single ACSR Panther Conductors of 132KV Capacitor Bank Bays between 132KV Main Bus-I to 132KV Jack Bus, 132KV Jack Bus to 132KV TI, 132KV Main Bus-II to 132KV SI, 132KV SI to 132KV TI, 132KV TI to 132KV CB, 132KV CB to 132KV CT, 132KV CT to 132KV LA, 132KV LA to 132KV Jack Bus, 132KV Jack bus to 132KV SI, 132KV SI to 132KV PI, 132KV PI to Capacitor Cell, Capacitor Cell to 132KV Reactor, 132KV Reactor to 132KV NCT . (1 Job for each Jumper)
Fabrication of Metallic Display Board by 16 SWG 600 x 300 mm size M.S. Sheet Board, covering the outer periphery on both sides by M.S. Strip of size 25 x 6 mm, fixing of ½” dia. 4” long M.S. Pipe on centre of outer edges of the M.S. Sheet Board, then covering the outer most periphery by 1.5” dia. M.S. Pipe and finally, fixing of 1 Meter long 50 x 50 x 6 mm size M.S. Angle Support Legs on both sides of the M.S. Board, grouting of above Metallic Display Boards in 132KV switchyard 132KV Capacitor Bank Bay by digging of earth of size 30 x 30 x 50 mm for each leg of the Display Board, then concreting of Plinth of size 30 x 30 x 60 mm with the help of Cement, Sand, Brick Ballast mixture in the ratio of 1 : 3 : 6 & 12 mm thick plastering over it, Painting of above Metallic Display Board by applying 1 coat of Red Oxide Primer, then applying 2 coats of Black colour Synthetic Enamel Paint on M.S. Angle / Pipe / Strip portion and 2 coats of Golden Yellow colour Synthetic Enamel Paint on M.S. Sheet Board with the help of good quality Brush & Spray Painting Machine. Finally, writing of Bay details on both sides of the Display Board with Black colour Synthetic Enamel Paint as per direction of Supervising Engineer, with all cost of men, material and T&P etc. required for the job.
Providing & Fixing of 150 Watt LED Street Light Luminary Fitting (CCT : 5700 – 6500K, CRI>70, Rated Voltage : 220V-240V AC, PF>0.9), Epoxy powder coated pressure die casted aluminum housing with bright anodized aluminum reflector and enclosed with Heat Resistant and toughened Glass front visior for Protection with 5KV Surge Protection with Constant current driver suitable for 140-280 VAC working range including Pole side mounting suitable upto 60mm OD pipe and IP66 Degree of Protection of Havells / Syska make Complete in all Respect with Electrical Connections, on Periphery Lighting Poles / Gantry already Installed in Switchyard of 400KV S/S Sarnath, Varanasi alongwith other associated Works including Cable Terminations, with all Cost of Men, Materials, Misc. Consumables, T&Ps etc. Required for Satisfactory Completion of the Work as per Technical Specifications & Direction of the Supervising Engineer. Original Warranty / Guarantee Card should also be submitted along with above material. (1 Job per LED Street Light Fitting)
Hi-tech power transmission
M/S PRABHATT ENGINEERING WORKS
Meena Elect & Engg. Works
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .