CE, TMC on behalf of Director, TMC
Engineering Department 6th floor Service Block
CivilHVACWorksRTBunkersHBB
2024_TMC_814140_1
TMC/ENG/HBBRTBunker2425eNIT10
Open Tender
Civil Works
Item Rate
56 days
TMH Parel
As per tender document
6 documents required · 6 mandatory
₹0
₹4.9 L
Engineering Department 6th floor Service Block
10 Dec 2024
1 Jul 2024
7 Aug 2024
1 Jul 2024
5 Aug 2024
15 Jul 2024
1 Jul 2024 - 8 Jul 2024
9 Jul 2024
Amount
Civil Works (BoQ2)
Electrical Works (BoQ3)
Mechanical (Boq4)
Fire Fighting (Boq5)
Lan Cabling (Boq6)
Description of Work / Item(s)
Amount
Civil- Interior Works Dismantling of existing false ceiling, wall panelling, skirting, flooring, brick wall, HVAC high and low side along with all electrical conduits, fittings and fixtures, backing and bedding mortar, ducts, diffusers, grills, etc. complete and removal of the debris from site.
Providing and laying Vitrified Floor Tiles and skirting in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3kg/sqm including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm (Basic Rate 800-900/ sqm)
Providing and laying Vitrified Tiles having height 100 mm for Skirting in required position with readymade adhesive mortar of approved quality on plaster of 1:2 cement mortar including joint filling with white/ colour cement slurry cleaning curing complete. (Basic Rate 800-900/ sqm)
Providing & applying plaster at an average thickness of 12 to 15 mm in exact line & level in the proportion of 1 : 4 cement and sand mortar by manual mixing, with addition of waterproofing chemical on the walls to act as backing for the tiles to be fixed
Providing and installing false ceiling system of metal suspension type, non perforated fireproof aluminum panel tiles of size 600*600, thickness 0.5 mm with integrated acoustic lining along with 15 mm suprafine or relevant grid system,edging angles, accessories etc. The provision for cut outs for electrical fittings, fixtures, & AC ducts, grills and other fittings to be provided as per the requirements. The periphery of the cut out will be strengthened with necessary frameworks.
Providing and applying Plastic Emulsion Paint of approved make and colour conforming to IS in two coats (surface and finish acceptable to the EIC must be achieved by the contractor and any additional coats if required shall be at the cost of the contractor); including preparing surfaces, filling up with gypsum or approved crack filler, binder; cleaning and making the surface dust-free, applying a sealer or primer coat of paint as recommended by approved paint manufacturer, applying two coats of paint (of approved make and shade), required scaffolding, cleaning and protecting till the handing over of site to the employer all complete to entire satisfaction of the EIC.
M 25 Grade Concrete to raise floor upto 300 mm in Linac room for fixing baseframe with required shuttering
Laying of 3Nos. PVC pipes on sand bed
Brick work with bricks of class designation 75 in super structure above plinth for all heights in cement mortar 1:6 (1 cement : 6 coarse sand)
Supplying of height adjustable revolving chairs, medium-back with hand rest. Godrej, Featherlite or equivalent make.
Providing and fixing solid core flush door shutter in commercial type ply with single leaf 32mm thick with / without ventilator as per detailed drawings with wrought iron hold fast, stainless steel fixtures, hinges, locks and handles on both sides with 1mm laminate complete. Cost to include door frame with polish.
Constructing cable trenches 300mm wide and 310mm deep as per the drawings
Preparing and fixing openable covers of 19 inch plywood with ability to sustain a load of 200kgs to be placed on the trenches 300 mm wide, all works complete
Providing and applying pest control against rodent and termite.
Core-Cutting of existing Bunker Walls
Providing & supplying storage units of required length with required height. Made up of BWR "AA" Grade Ply with white, Ply for sides, Shutters, shelves, top, bottom and vertical portions. Shutters shall be fixed with 75 mm long SS cut hinges, tower bolts and magnetic catchers at top/ bottom and locks as required. Handles shall be 316 SS grade. All external surfaces shall have 1.0 mm laminate of approved shade, and 0.8 mm white laminate inside.
Depth of 400 mm with open / closed shelves
Depth of 600 mm with open / closed shelves
Providing making fixing work station 800mm deep and 800mm high with providing required framing/supports with one pedestal unit drawer and shutter, pvc cable manager,CPU stand, etc. work station should be made of 19mm thk ply board make century ply/green ply, with 1 mm thk laminate over the all outer surface and 0.8mm thk white lamuinate on all inner surface cost shall be included of all necessory hardware like hinges, handle, locks, etc. complete in all respect.
Providing & fixing of load hooks with testing certificate - Refer services drawings
Providing and fixing laminate finish panelling with aluminum framing 25 x 25 mm fixed to the wall at 600 mm c/c with 12mm plywood and 1 mm thick laminate of approved shade on single side. Rate to include that for all necessary hardware, adhesive, etc.
Providing and installing false ceiling system of gypsum board as per approval with galvanized steel framework and suspenders. The provision for cut outs for electrical fittings, fixtures, & AC ducts, grills and other fittings to be provided as per the requirements. The periphery of the cut out will be strengthened with necessary frameworks.
Providing and fixing PVC corner guard (stretcher protection)
Providing and fixing PVC patient railing.
Providing & fixing soft board with approved fabric with wooden framework for display of drawings and documents.
Providing and fixing mirror of size (0.6x0.8m)
Providing and fixing coat hooks
Providing & supplying shoe rack of size (0.6x0.8m)
Providing 3D views of interior
Supply and fixing of artificial vitronite slab over the counter of console table
Supply and fixing of room signage
Supply and fixing of radiation safty logos
Providing & fixing of Cubical curtain 1 m wide for change room. The cost to include that for all necessary hardware & fixtures such as curtain rod,etc.
Providing and fixing laminate finish partition with aluminum framing 25 x 25 mm fixed to the wall at 600 mm c/c with 8mm plywood and 1 mm thick laminate of approved shade on both side. Rate to include that for all necessary hardware, adhesive, etc.
Providing and laying P.C.C M15 (1:2:4) grade concrete for chiller foundation including all necessary formwork, batching, etc. complete including wet curing for specified time frame.
Providing and fixing Skylight (decorative light) with design of natural view having best resolution made from printed acrylic, by fixing ceiling interlocked aluminum profile.
Providing and Fixing temporary sealed partition of regd. Height covering up the work area from the usable area or for any other the use with salwood frame work or light weight Aluminium frame work whicever is convenient as per site condition & with 6mm thick commercial plywood from both sides, making openable door shutter in it etc.etc. with all other necessary allied works ,later removing the same after completion of the work & storing it in proper place so as to use it against for other areas.
Civil - Structural Works Carefully removing or chiseling, existing plaster of thickness up to 22 mm from the surface , including collecting, stacking & carting away the debris from the working area upto stagging point. (stagging point distance should be 50 mtr from working area)
Breaking existing RCC / PCC by mechanical breaker / cutter without disturbing the adjacent structure including cutting reinforcement by means of chisel / hammer carefully and carting away of debris
Carefully excavating in any kind of soil, in existing building in or out sides, and carting away the debris upto 50 mtr stack point
Backfilling in the pits/trenches excavated for foundation of RCC walls and tie beams with earth available at site or with earth brought from outside.
Providing and erecting MS /wooden / bamboo props and fixing (100x100) mm wooden blocks at the top of props wherever required to support the existing slab and shall be secured properly in position
Providing and laying P.C.C. M15 (1:2:4) concrete in foundation as leveling course 100-150 mm thick including necessary form work, batching, mixing, placing, consolidating etc. complete including wet curing for specified time period.
Supplying, Providing and placing in position M25 Reinforced cement concrete with 20mm downgraded aggregates for walls/foundations including vibrating, curing, providing construction joints, leaving cut-outs/ pockets for placing of inserts/ embedment, etc., complete, including cost of providing steel centering and shuttering form work with plywood lining for all shapes (including scaffolding(Upto 3 mtr), centering, etc.), but excluding the cost of providing reinforcement all as per specifications.
Supply & fabricating and fixing reinforcement for RCC work with high yield strength ribbed cold twisted tor steel of various diameters and all lengths of grade Fe 500 conforming to BIS specification including cutting, bending, fabricating, welding, wastage and placing in position according to drawings and binding the reinforcement with the use of 16 gauge galvanized binding wire of double fold and providing precast cement cover blocks for main reinforcements to ensure specified cover according to relevant IS code. The measurements will be in accordance with IS code 1200.
Providing and laying brick work with bricks of class designation 75 in super structure above plinth for all heights in cement mortar 1:6 (1 cement: 6 coarse sand)
Providing and laying microconcrete for RCC walls with necessary formwork and stagging
Providing & fixing shear pins , anchoring in the existing concrete up to 200mm length with necessary grouts/epoxy resins & further protruding up to 200 mm to embed in the proposed RCC section including cutting, bending, welding etc. complete as instructed by the consultant
For 10mm dia
For 16mm dia
For 20mm dia
Providing & fixing shear connectors up to 25mm dia re-bar & 500mm in length, embedding in the first layer of concrete up to 200mm depth & maintaining in position till completing the concreting operations to further embed in the second layer of concrete to facilitate the necessary bonding between the pours including cutting, bending, welding etc. complete as instructed by the consultant
Providing and fixing M.S. double leaf door of size 1.6m wide x 2m height with duco spray paint, door frame and hardware complete. The door to include 5% borated polyethylene sheet -25mm, 1mm + 1mm lead sheet
Description of Work / Item(s)
Amount
ELECTRICALS WORKS POINT WIRING :- Point wiring for light/fan/bell with ISI mark 3 x 1.5 sq.mm (P+N+E). FRLS PVC insulated copper conductor of Polycab / RRK /Finolex in surface/ recessed heavy class pvc casing capping/conduit of Presto-plast/sunwood /Precision make with Modular switch of Legrand-Myrius/MK-Blenze & Anchor make-ceiling rose/batten holder/slanting holder Boxes etc. with circuit labling/marking/ferruling complete.
Primary point upto 4 mtrs length
Primary point length 4 mtrs to 7 mtrs
Primary point length 7 mtrs to 10 mtrs
Secondary point Extending from Primary point upto 4 m
Dimmable Led light point with 100W - with Regulator in 2 module box , 7 to 10 meter length
DISMANTLING :- Carrying out assigned jobs of dismantling the existing electrical installation like light, fan, bell, independent plug point wiring of all types with accessories and cable /switchgear in an approved mannerwith tools and tackles as per instruction of Engineer Incharge
Supply & installation of Power point Legrand-Myrius/MK-Blenze (inclusive of 2No.of 5/15 Amp switch socket, back box, face plate & wiring,accesories etc)
Supply & installation of Power point Legrand-Myrius/MK-Blenze (inclusive of 1 No.of 5/15 Amp switch socket, back box, face plate & wiring, Circuit naming accesories etc)
Telephone outlet :- Supplying and instllation of telephone outlet point inclusive of Telephone instrument panasonic KX TS 500 B Telephone socket with back box ,plate, laying two pair 0.5 mm gauge unarmoured telephone wire (30 meter from TT box to telephone outlet in PVC conduit of suitable size) D.O.T approved, make Dlink/Finolex/Digilink/Polycab through conduit/casing caping up to nearesr Telephone TT box.
Supplying and laying 2 core,0.5 sqmm Microphone Cable make-RR Kable ,Polycab,Finolex through conduit/casing caping/cable tray in proper manner.
Supplying,installation of Indicator type call bell with acceptance push button with concealed two module box face plate, make Legrdand
Supplying,laying,connection, termination of 15 meter length High speed HDMI cable, CL3 rated support 4K,UHD,HD.
SUB Mains :- Providing concealed,surface finished Heavy duty conduit ISI mark or Casing capping as per site requirement with Supplying and erecting mains with copper conductor PVC insulated FRLS of 1100 V AC grade Polycab/RRK/Finolex make wire with circuit labling/marking/ferruling complete.
2 x 1.5 sq mm -+ 1.5sqmm Earth wire
2 x 2.5 sq mm -+ 1.5sqmm Earth wire
2 x 4 sq mm -+ 2.5 sqmm Earth wire
LIGHT Fixtures Supply and installation of LED fixtures - Surface /Suspended / Recessed Mounted luminaires Philips / Orient / Bajaj Make
LED Light fixture Duraslim 15 watt, Round 6500K,
LED Light Fixture Full Glow 2FT X 2FT 6500K
Dimmable LED Light Fixture, 10 watt ,Warm-white
Distribution Boards Supply, installation, testing & commissioning DBs
SPN DB with Metal door, 12 way, IP 43, inclusive of required rating MCB,RCBO
TPN DB with Metal door, 8 way, IP 43, inclusive of required rating MCB,RCBO
Fabricate Supply and Fixing of Stainless steel 306 Trunking /covering 16 Gauge of similar to Ω shape or as per sample
To cover casing capping of 25 mm
To cover casing capping of 50 mm
Earthing Conductor:- Supplying, fixing with saddling of following flexibles copper conductor 1100 V a.c. grade cables with green colour insulation ,Polycab/RRK/Finolex make with proper connection at both the ends as directed by Eng --in -chrg.
1 x 10 sq.mm
1 x 95 sq.mm
Earthing Station Providimg chemical earthing with drilling in soil by means of proper drilling equipments in soil by means of proper drilling equipment as per requirment of site condition and providing earth electrode Cu bounded Steel Rod 17.2 mm dia X 3000 mm length (100 Microns) as per IEC 60364/62561 ECO safe carbon based backfill compound 50 pounds with Gun Metal Clamp and providing ECO friendly rust proof heavy duty wheather proof Polyethylene Earth Pit Chamber with dimensions 254 mm dia (top), 330 mm dia (bottom) and 260 mm (height) with submission of test report as per directions of EIC and making the site clear by removing debris.
Addressable FA System Supply ,installation, testing & commissioning of intelligent addressable smoke detector with base complete in all respect with connection in existing FA loop with activation and testing at FA panel (Make-Honeywell)
Removing and reinstallation, testing & commissioning of intelligent addressable smoke detector complete in all respect with connection and activationin existing FA loop (Make-Honeywell)
Supplying & laying with saddle of 2x1.5 sqmm fire survival armoured cable, 1000V rated with copper conductor Xlpe insulation, armoured outersheathed Zero Halogen .Colour-Red
Description of Work / Item(s)
Amount
Replacement of AHU & FCU and associated ancillary works S.I.T.C of Horizontal/ Vertical double decker type Integrated factory fabricated Eurovent / AHRI certified Double skin Air handling units. Frame work construction : Frame work of Extruded aluminum alloy section with Thermal Break for AHU. It shall be made out of 1 mm pre coated galanised steel sheet outside & 1 mm thick Aluzinc sheet inside, with 50 mm thick Rock wool insulation with density not less than 96 + 4 kg /cum sandwiched between them. Drain Pan: Drain pan made out of 1.2mm stainless steel (SS Grade 304) sheet instulated with 25mm thick closed cell insulation nitrile rubber with thermal brake profile. AHUs to be provided with marine lamps on both sides and view ports. Installation of new AHU with all new foundations, vibration isolator pads etc shall be in vendors scope. Make - Stulz, System Air, Flaktwood, DRI , Euroclima. Filter Section - Return Air Section shall be provided with Washable type of Box type Combination Filter EU-5. Coil Section : Chilled water coil of 6 row deep constructed with Aluminium fins of minimum 0.15 mm, thickness with Anti corrisive coating and copper tubes of minimum 20 gauge thickness. Copper tube shall be 1/2'' mm diameter. The coil face area shall not exceed 2.5m/sec. The coil section shall be equipped with factory fitted Mist eliminator of PVC. Space provision for UV lamps before cooling coil. Fan Section: Direct drive backward curved Radial EC fan (Electronically commutated) with permanent magnet brushless DC motor for stepless variation of speed of fan based on temperature/pressure sensor Inputs. The fan section shall be provided with limit switch for safety to shut off fan during Opening of access door. Supply air outlet damper provided. Minimum Two nos. or more fans with 50% redundancy as per CFM should be considered for each AHU.Fan Make - Ebm, Zeil abegg Electrical starter : Built in starter panel with Auto /Manual switch and incomer power terminal provisions must be provided as Integral part of the AHU. AHU to be provided with individual fan run status.
Removing of old AHU along with connected piping, old connected ducting, power and control cabling and foundation. Installation of new AHU along with supply installation of new chilled water piping with insulation of TF quality 50 mm thick thermocole section covered with hessain cloth, SS wire mesh and 12 mm thick sand cement plaster in finished condition. New foundation blocks required for installation of new AHU shall be in vendors scope. Removing of old insulation material, taking out of TMH premises and disposing it in proper manner is in vendors scope. Size of the AHU is very critical factor. Vendor should visit the site before submitting their quote to check the size of the existing AHU and the available space for the proposed AHU. HBB Ground floor LA wating Hall (12000 CFM, 45TR 65mm Static)
S.I.T.C of Ceiling concealed Fan Coil Unit, constyruct with 24 G double skin GI Pre coated sheet with 3 row deep cooling coil (9.5 mm OD & tube thickness 30 G) aluminum fins, blowers, single phase direct driven motor, 12 mm thick pre filters and drain pan constructed out of 22 G stainless Steel, 24 G, Gi as covering sheet & sandwiched insulation of 25 mm thick thermocole in between. FCU with thermostat controller supply and return chilled water insulated copper piping approx 5 mtrs each, valve station with 2 way PICV valve and controller and control wiring. FCU Make : Zeco, Trox, Systemair PICV valves & controller make : Oventrop, Belimo
SITC of Chilled water piping out of M.S. heavy class ERW C -class pipe (pressure rating PN 16) confirming to relevant IS 1239 Code upto 150 mm dia pipes, from 150 mm and above upto 2S0 mm dia 6 mm thick pipes and above 250 mm dia 6-8 mm thick pipes, with necessary fittings, teak wood gutties for indoor and hard puff blocks for outdoor pipes, elbows, tees, reducers. Suitable GI supports as specified. Pipe make - Tata / Jindal / SAIL Supply & Installation of Chilled Water Piping Insulation In Building Area of Nitrile Rubber self adhesive properties having a K value of not more then 0.033º W/m k at an average temperature of 0 deg C. Density shall be between 40 to 60 Kg/M³ +/- 2% Temperature range : 5 to 12 deg. C, 25 mm thk. Insulation for pipe dia 0 to 80 mm & 32 mm thk for pipe dia 100 & above as per technical specifications covered with UV Glass cloth covering system for the protection of existing nirtrile insulation 205 GSM thick applied on the nitrile insulation with proper adhesive and 26g Al cladding. Insulation Make - Armafex / K flex
80 mm dia pipe
65 mm dia pipe
50 mm dia pipe
40 mm dia pipe
32 mm dia pipe
25 mm dia pipe
SITC of insulated Butterfly Valves with extended neck of Pressure Rating PN 16, with extended stem complete with gaskets, suitable flanges, nutbolts as per relevent standards and specification. Make- Kitz/Audco/Danfoss
80 mm dia.
65 mm dia.
50 mm dia.
40 mm dia
32 mm dia
25 mm dia
S.I.T.C of two way pressure independent Dynamic control and balancing valve shall be self balancing type with help of Diaphragm in valve body for maintaining DP at all the time. Valve should have capacity to adjust flow in running condition without hampering the operation of unit. Actuator should have capacity to accept 0-10 volts / on off input signals from thermostat or control system. Actuator must be Electromechanical type with automatic anti blocking function so that actuator will open and close the valve once in 24hrs if FCU / AHU remains idle for more than 24hrs/ Or Electro thermal for on/off type PIBCV. Unique design of PIBCV consists of precisely machined valve components coupled with a self-contained differential pressure regulator (Diaphragm) should be installed in the single valve body and not in cartridge. The machined valve components result in high range ability performance while the self-contained pressure regulator (Diaphragm unit) maintains a constant differential pressure across the control valve irrespective of the change in system pressure during partial load condition. Changes in flow through the PIBCV will not occur due to system pressure changes but due to control signal from room thermostat or from BMS. Valve should have capability to set the baseline flow without any chart and should have flow indication on its body in l/h or in m3/h. Flow setting should be done at site without any hassles. Prestting of flow must be done in valve and not in actuator. Make- Oventrop, Belimo Actuator - Modulating and electromechanical , > 150 N or as per Manufacturers design for valve, IP 54, 60-180 seconds fully close to fully open, Must be with anti blocking function. Actuators must be capable of closing valve fully in case of power failure Thermostat - Thermostat should be compatible to work with AHU. Thermostat must display percentage opening of actuator on screen in percentage. Power cabling, Control cabling from panel to actuator and thermostat to be carried out by vendor any modification addition in the existing electrical panel if required will be in vendors scope.
65 mm dia
Supplying and installing of 6" dia Pressure gauges with SS Ball valve. Make- H GURU / Dwyer / Gandhi
Supplying and installing of 6" dia Temperature guage with SS thermowells. Make- H GURU / Dwyer / Gandhi
Supply and Installation of 5 mm wall thickness PVC drain piping for Air handling unit with all fittings and supports, saddle, pressure clamps etc with 9 mm thick tubular type nitrile insulation wrapped with glass cloth dipped in adhesive recommended by manufacturer.
50 mm dia
Supply, installation, balancing and commissioning of factory fabricated 180 GSM GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. Make- Jindal / Sail / Tata
22Gauge GI ducting
20 Gauge GI ducting
18 Gauge GI ducting
Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc Make- Dynacraft, Systemair, Carryair.
Supply, installation, testing and commissioning of Motorized ( ON/OFF Type) GI volume control duct damper with enthalpy sensor and control wiring (minimum 1.5 sqmm) neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc Make- Dynacraft, Systemair, Carryaire
Supply, installation, testing and commissioning of Motorized ( ON/OFF Type) GI volume control duct damper actuator.Make - Danfoss, Belimo.
Supply and Fixing of Extruded AL powder coated Four way Diffuser with removable core, 4 side flanges and AL Box Damper. Make- Dynacraft/Ravistar/Caryaire/Ductocraft
Supply and Fixing of Extruded AL powder coated Four way Diffuser with removable core,4 side flanges. Make- Dynacraft/Ravistar/Caryaire/Ductocraft
Supply and Fixing of Extruded AL powder coated Supply Air Grills with AL volume control damper. Make- Dynacraft/Ravistar/Caryaire/Ductocraft
Supply and Fixing of Extruded AL powder coated Return Air Grills with louvers but without AL volume control damper.Make- Dynacraft/Ravistar/Caryaire/Ductocraft
Design, S.I.T.C. of Heater bank in the existing ducting. Heaters should operate to maintain the humidity in the 3 nos. LA's between 45% to 50%. A separate panel should be considered for the heaters with MCCBs, contactors, humidity stats, overload and all safety as required for the heater bank.
Supply and Installation of AHU/Duct mounted UV based Advance Oxidation Plasma (AOP) cell. The AOP cell is powered by High Energy Ultaviolet Photochemistry (UVC-254 nm), just like action of sun.The system shall be able to kill 99% of bacteria, virus, molds and other pathogens in the air as well as on surfaces using oxidation technology, it should be able to comprehensively remove harmful mocrobial contamiation as well as odors, VOC's. The system should be suitable for operation on 220 volts, single phase, 50 Hz, A.C. supply with an adaptor connection, complete as per specification. Make - Ultrapure, Aeropure
SITC of single duct Variable Air Volume (VAV) terminal units suitable for 4000 CFM air flow units shall be rated in accordance with Ashrae standard 36-72 . Unit shall be of the pressure independent type throughout the entire range and shall be capable of resetting the air flow to +5% of the nominal air flow regardless of the change in the system pressure. The unit shall be capable of being reset to any airflow between zero and the maximum, air volume automatically to compensate for duct pressure fluctuations. The air velocity sensor shall measure the true velocity across the inlet of the unit and be unaffected by changes in duct air temperature and humidity. The sensor shall be field replacable without opening the associated ductwork. The entire package shall be calibrated and factory set for the maximum and minimum flow rates as specified but shall be capable of easy re adjustment in the field. Each terminal box shall be provided with factory calibrated, direct reading air flow indicator. Seperate gauge tap shall be provided for field recalibration and commissioning. The velocity controller and damper actuator shall be of an integral part directly mounted on to the damper shaft. The actuator shall be capable of operating in stalled position without overheating or mechanical damage. The damper shall remain in a fixed position when electric power source is interrupted. The damper shall be of heavy gauge Galvanised steel with peripheral gasket, pivoted in self lubricating bearing.VAV type shall be with single outlet short attenuation and communicable BacnetMS/TP controller. Supply and Fixing of control wiring is in Vendor scope. Make- Trox/Trane/Haltron (With Belimo Controller)
Supply ,Installation of Thermal Insulation of Nitrile Rubber Insulation 25 mm thick with self adhesive properties & all the joints sealed & finished with self adhesive tape. & as per technical specifications. For Supply Air Duct Make : Armaflex, K Flex, Aeroflex.
Supply, Installation Acoustic insulation of duct with 25 MM thick open cell nitrile rubber ,Adhesive,GI Bending Wire,Screw,washer etc as per technical specifications. Make : Armaflex, K Flex, Aeroflex.
Supplying and fixing TP sheet steel enclosure on surface/recess along with 16/25/32 A 415 V ''C'' curve TP MCB complete with connections, testing and commissioning etc as required. Make : Legrand
SITC of 1100 V a.c. grade FRLS PVC armoured CU cabling along with appropriate size of saddles,spacers complete with GI conduit in approved manner. Make- Polycab/RRK/Finolex
4 Core x 6 Sqmm CU Cable
4 Core x 4 Sqmm CU Cable
SITC of GI earthing of 6 SWG including end connections complete in all respect.
S.I. of MS fabrication along with I beams, C channels, angles, plates, bars, anchor fastners etc as required.
Supply of direct drive backword curved Radial EC fan (Electronically Commutated) with permanent magnet brushless DC motorfor stepless variation of speed of fan based on temperature/ pressure sensor Inputs. Two fans of Each model used in the AHU to be supply as approved by Engineer In Charge
SITC of DOL startrer with enclosure siutable for above Exhaust Fan or 10 HP load, with O/L & SPP
Process Chiller-LS Work Supply, installation, testing & commissioning of 18G 13/8" hard Copper pipes for supply and return lines of chiller including all necessary fittings, elbows, tees, clamps, supports chanel, cable tray, etc. The complete length of the pipe to be duly insulated with 19mm nitrile insulation with tapes etc. as per standard practice.
Supply, installation, testing of UV treatment including 1 layer of UV Glass cloth and 2 Layers of Starbond 30-36 for exposed length of copper pipe open to atmosphere.
Installation, testing & commissioning of chiller inlet & outlet flange union
Supply, installation, testing & commissioning of following valves, gauges, accessories etc.
Pressure gauges, size 3 inch dia, Make Remax (Or, Equivalent) range 0 to 100 psig
Temperature gauges, size 3 inch dia, Make Remax (Or, Equivalent), range 0 to 100 degree celcious
25 mm brass drain valve with 10 mtr pvc piping with all fittings and support hardware Make: zoloto/Sant (Or, Equivalent)
40mm brass Ball valves (Make - Sant Or, Equivalent)
Auto Air vent
Supply and refilling of DM / Minaral water
Supply & commissioning of water panel with brass nut, copper pipe, welding with all fittings,etc.
Buy Back Items
Buy-Back (ie minus)Amount of old AHU as in where is basis along with old ducting, piping.(Dismantling, removing and shifting out of TMH premises is in vendors scope. Insulation material removed of old ducting and piping, old foundations to be taken out by vendor.) Buy back Amt to be paid in advance by vendor before taking out the material.
Buy-Back (ie minus) Amount of existing, FCUs as in where is basis along with old ducting, piping.(Dismantling, removing and shifting out of TMH premises is in vendors scope. Insulation material removed of old ducting and piping, old foundations to be taken out by vendor.) Buy back Amt to be paid in advance by vendor before taking out the material.
Description of Work / Item(s)
Amount
Supply, Installation, Testing & Commissioning of Novec 1230 /FK-5-1-12 or Equivalent with Zero Ozone depleton potential and very low Global Warming Potential of 1 with 20 years Blue Sky Warranty against any regulatory bans and Restictions. Fire Protection Fluid, OEM Factory Filled per Kgs.
Supply, Installation, Testing & Commissioning of UL Listed Discharge hose with Manifold Check Valve for Multi Cyilnders System including all type of fittings complete in all respect as per instruction of EIC Make- CRYPTZO/Intime/Tyco/Kidde/Equivalent
Supply, Installation, Testing & Commissioning of UL Listed Electromegnetic Actuator, Manual Actuator, Pneumatic Actuator for Multi Cylinder System including all type of fittings complete in all respect as per instruction of EIC Make- CRYPTZO/Intime/Tyco/Kidde/Equivalent
Supply, Installation, Testing & Commissioning of UL Listed Low Pressure Switch and Discharge Pressure Switch for Multi Cyilnders System including all type of fittings complete in all respect as per instruction of EIC Make- CRYPTZO/Intime/Tyco/Kidde/Equivalent
Supply, Installation, Testing & Commissioning of Warning Sign Board with Marking "GAS DISCHARGE. DO NOT ENTER" and "GAS DISCHARGE. EVACUATE IMMEDIATELY" Shall Operate on 24V DC, Driven Through Gas Release Panel. (for use outside room) Make- CRYPTZO/Intime/Tyco/Kidde/Equivalent
Supply, Installation, Testing & Commissioning of MS Seamless Pipes as per ASTM A106 Gr B, Schedule 40 including all fittings like elbow, Tee, Barrel Nipple, Flange and Supports, Etc. incuding one coat of primer and two coat of paint complete in all respect as per instruction of EIC. Carrying out associated Civil works, lifting,shifting, loading, unloadiing, Houskeeping and Disposing all type of generated debris and scrap out of TMH is deemed to be included in this item cost. Pipe Make: Tata, Jindal, sail, MSL Paint Make: Asian, Burger, Nerolac etc. Location 1:- HBB Triology Machine room & UPS Room Location 2:- HBB Novalis Machine room & UPS Room
Design, Supply, Installation, Testing & Commissioning of Two zone Gas Release Panel facility to connect Manual Abort/Release switches. The Panel shall provide Potential free contacts for Trouble / Fault Status. The Panel shall be Complete with Red Colour Housing, Monitored Power supply units for Notification devices & warning signages of the system, including Battery charger & batteries. This shall include conventional detectors along with the panel to fulfill the system requirements. Make- Ravel/Agni/Simens/Honeywell
Supply, Installation, Testing & Commissioning of UL Listed Manual Abort Stations with DPDT Relay, The Abort will be monitored simultaneously by Fire Alarm and BMS System. Complete with required mounting accessories. (Make- Microm/Simlex or Equivalent)
Supply, Installation, Testing & Commissioning of UL Listed Manual Release Stations with DPDT Relay, The Release switch will be monitored simultaneously by Fire Alarm and BMS System. Complete with required mounting accessories. (Make- Microm/Simlex or Equivalent)
Supply, Installation, Testing & Commissioning of UL Listed Service Disconnect Switch with flush mount and indicator lamps 24 VDC. The Service Disconnect switches shall be controlled by keyswitch and should initiate a supervisory condition to fire panel when in disconnect/disable position. (should be with Aux PF Contact). Complete with required mounting accessories. (Make- Microm/Simlex or Equivalent)
Supply, Installation, Testing & Commissioning of 2 Core x 1.5 mm2, Multistranded Annealed Tinned Copper, Shielded FRLS, Armoured cable, RED in Colour. The cable shall be laid on surface with hot dip GI Saddels and spacers every 0.3 meters. Complete with GI Junction Box, lugs, cable compression glands, cable tags and Ferruling. (Make- KEI/RR Kable/Caliplast)
Supply installation testing & commissioning of Hooter cum flasher.
Description of Work / Item(s)
Amount
Lan Cabling work DISMANTLING & REPAIRING:- Providing quilified Wireman and a helper with tools for carrying out assigned jobs day to day Maintanance such as repairing /dismantling the existing light ,fan,bell,independent plug point wiring of all types with accessories and cable /switchgear in an approved manner as per instruction of Engineer Incharge(reqd material will be provided by TMC) Medical Physicist Room (Removing old data point , data wire , rack etc )=4 manday, Novalis Console=2 manday, Triology Console=1 manday, 4D CT Console=1 manday,
Concealing of 6"X 6" Box or lower size with surface finish. Medical Physicist Room=10 Rmt, Novalis Console + Lab=5 Rmt, Triology Console + Lab=3 Rmt, 4D CT Console + Lab=3 Rmt,
Supply and Fixing Rigid PVC conduit Medium Mechanical Stress (MMS) with all fitings & fixing accessories Precision make
20 mm Medical Physicist Room=100Rmt, Novalis Console + Lab=50Rmt, Triology Console + Lab=50Rmt, 4D CT Console + Lab=50Rmt,
25mm Medical Physicist Room=500Rmt, Novalis Console + Lab=400Rmt, Triology Console + Lab=200Rmt, 4D CT Console + Lab=200Rmt,
Supply and Fixing Flexible Conduits Poly Proplyne (PP) with all fitting & fixixng accessories Precision make
20 mm Medical Physicist Room=50Rmt, Novalis Console + Lab=30Rmt, Triology Console + Lab=30Rmt, 4D CT Console + Lab=30Rmt,
25mm Medical Physicist Room=100Rmt, Novalis Console + Lab=50Rmt, Triology Console + Lab=50Rmt, 4D CT Console + Lab=50Rmt,
Supply & Fixing PVC Casing Caping with all fittings & fixing accessories Precision make
1 inch dia 25mm x 12mm Medical Physicist Room=50Rmt, Novalis Console + Lab=30Rmt, Triology Console + Lab=20Rmt, 4D CT Console + Lab=20Rmt,
1 inch dia 25mm x 16mm Medical Physicist Room=50Rmt, Novalis Console + Lab=30Rmt, Triology Console + Lab=20Rmt, 4D CT Console + Lab=20Rmt,
Supply and Fixing PVC Casing Caping with all fitting & fixing accessories Precision make
100 x 50 mm PVC trunking Medical Physicist Room=15Rmt, Novalis Console + Lab=10Rmt, Triology Console + Lab=10Rmt, 4D CT Console + Lab=10Rmt,
50 x 50 mm PVC trunking Medical Physicist Room=10Rmt, Novalis Console + Lab=10Rmt, Triology Console + Lab=10Rmt, 4D CT Console + Lab=10Rmt,
Information tech Section: Supply, Installation & Testing and commissioning of following:
Cat - 6 copper cable in existing conduit / Trunking Medical Physicist Room=1000Rmt, Novalis Console + Lab=900Rmt, Triology Console + Lab=500Rmt, 4D CT Console + Lab=500Rmt Make / Model: D-link, Quicksand, Polycab
I/O for CAT - 6 Medical Physicist Room=36Nos, Novalis Console + Lab=16Nos, Triology Console + Lab=20Nos, 4D CT Console + Lab=16Nos, Make/ Model: D-link, Malson
Surface mounting box Medical Physicist Room=18Nos, Novalis Console + Lab=8Nos, Triology Console + Lab=10Nos, 4D CT Console + Lab=8Nos, Make / Model: D-link, Anchor
Supply & Installation of Metal boxes Medical Physicist Room=10Nos, Novalis Console + Lab=5Nos, Triology Console + Lab=3Nos, 4D CT Console + Lab=3Nos,
Dual face plate for MS concealed box Medical Physicist Room=18Nos, Novalis Console + Lab=8Nos, Triology Console + Lab=10Nos, 4D CT Console + Lab=8Nos, Make/ Model: Dlink
RJ45 Connectors Medical Physicist Room=2Nos, Novalis Console + Lab=2Nos, Triology Console + Lab=2Nos, 4D CT Console + Lab=2Nos, Make/ Model: Dlink
Supply and installation of 42U Double section Rack Medical Physicist Room Rack= 1 Nos. Make/ Model: D-link, Valrack, DataRack
24 port jack panel for CAT - 6 Medical Physicist Room Rack= 15 Nos Make / Model: D-link, Malson, Crometek
Fibre fixing and termination Medical Physicist Room Rack= 5 Nos
Network cable removing Medical Physicist Room Rack= 8 Nos.
Fibre Scanning and testing Medical Physicist Room Data Point = 10 Nos
I/O Fixing and termination Medical Physicist Room Data Point = 100 Nos
Installation, removal, replacement of rack Medical Physicist Room Rack= 3 Nos
Cat 6 Patch cord 3 feet Medical Physicist Room Rack= 96 Nos. Make/ Model : D-link
Cat 6 Patch cord 7 feet Medical Physicist Room Rack= 88 Nos. Make/ Model : D-link
C9200L-48T-4X-E Network Switch 48 port (With 1/10G SFP) with one year warranty Medical Physicist Room Rack= 2 Nos Make/ Model : Cisco
C9200-24T-A Network POE switch 24 port with one year warranty Medical Physicist Room Rack= 1 No. Make/ Model : Cisco
Aruba 505 Wireless Access Point with mounting kit and neccessary Licenses like Wireless FW and IPS License, Policy Enforcement Firewall (AP) License, RF Protect License including WIP and Spectrum (AP Support) with one year warranty Medical Physicist Dept= 7 Nos Make/ Model : Aruba
3in3 interior
3in3 interior
maxcool solutions pvt ltd
3in3 interior
maxcool solutions pvt ltd
maxcool solutions pvt ltd
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.06 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .