Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹1.2 Cr
EMD Value
₹2.1 L
Closing Date
31 Jul 2025, 1:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Above/Below/Par
TECHNICAL
15 conditions · 4 needing a document upload
Clause Regarding GST: (a) All the Bidders/tenderers should ensure that they are GST Compliant and their quoted tax Structure are as per GST LAW.(b) Tenderer Should Furnish their GSTIN numbers representing the States in Which they are registered GST, along with address of Registered Office.(c)The Contract is under GST Act and rules as applicable time to time.
Financial Eligibility Criteria: The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. Annual Contractual Turnover Data for the Previous 3/4 Years should be submitted as per Annexure-IX.(AnnexureVIB of Tender Documents).
41 conditions · 12 needing a document upload
Check List: The tenderer(s) would fill up the check list, as per Annexure-XXIII to ensure that they are submitting the complete tender offer.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Upgradation of Goods Yard Lighting with provision of HM Tower after dismantling of old Lattice type tower along with Internal wiring improvement at NTSK, JT & FKG Goods.
LV-T-14-TSK-901-R
LV-T-14-TSK-901-R
Open
Works - General
14 Months
Tinsukia, Assam
₹0
₹2.1 L
31 Jul 2025
9 Jul 2025
82 items across 2 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 90,89,710 | ||
| — | 14.00 | — | — | ||
| Dismantalling of old Lattice fabricated High mast tower and deposition of all materials to Concerned Power House in challan. The tower to be dismantalled part wise with help of welding/gas cutting and suitable Machinery(Hydra Crane) Proper Safety precaution to be observed during dismantallling as per direction of Engineer incharge at Site. | — | — | — | 2,80,070 | |
| — | 10.00 | — | — | ||
| Supply, fitting, fixing of 200 Amps outdoor type cable junction box, angle frame mounted, dust & vermin proof, complete with rain cap, aluminium basbar of suitable size for TPN, 200 Amps, 415 V made out of 16 SWG CRCA sheet duly painted, Cable Junction Box Size: (lxbxh=450x 450x600 mm). | — | — | — | 89,390 | |
| — | 4.00 | — | — | ||
| Supply, installation , testing and commissioning of 16 Mtrs high mast tower hot dip galvanized as per IS 875 (construction as per BS EN 10025 - 1993 or equivalant IS) with lantern carriage for 8 Nos of Nos of Light, pulley and cables with 8 Nos 150 W LED Flood Light with secondary lens for illumination . The mast shall also include accessories for highmast including headframe,steel wire rope 6mmdia (7/19 construction),trailling cable,double drum winch,galvanised lantern carriage arrangement suitable for 8 Nos Of Luminarie. The structure shall be of 16 Mtr height in two sections, hot dip galvansied both inside and outside (conforming to IS4759- 1984,IS2629-1985, IS2633-1972) and suitable for wind speed as per IS875 Part III , including base plate of size 610X610X30 mm, Lightning protection final with GI single spike of suitable length, provision for 3 nos of earthing terminals at base of mast, Twin dome LED avaiation obstruction light at top of mast, 12 nos of 900mm/30mm(min.) size steel E6.8 grade foundation bolts and Anchor plate of 510 PCD . The Construction of Foundation is included in scope of work as per manufacturers recomendation.The Mast shall also have raising and lowering system, head frame, hot dip galvanised steel lantern carrige (using 50mm dia B class GI pipe) suitable for fixing 8 nos of LED high mast luminaires symmetrically, trailing cable of 24Amp rating EPR insulated and PVC sheathed 5core X 2.5 sq.mm copper conductor cable and other wiring materials for luminaires, integral power tool (415V, 3phase, 1HP - 2mtr per minute single speed motor reversible) installation inside the base compartment, 2 nos of continuous 6mm stainless steel wire ropes(7/19 construction), double drum winch (manual and electrical both) as per IS 807, Feeder type control panel for operation of luminaires with astromical ON/OFF timers with suitable MCBs, contractors for automatic control of luminairs, power tool control and raise lower push button etc., complete as required. . The mast shall have thickness of 3mm top and 4 mm bottom, No of faces: 20, Across face dia: Top-150 mm, Bottom-410 mm, Base plate: 610x 30 mm, PCD: 510 MM, Bolts: 12 Nos of 30x900 mm. 3 Nos earthing to be provided for the High Mast with 50 mm dia GI pipe 3 Mtrs Long and 32x5 mm GI flat strip of required length.. | — | — | — | 16,00,400 | |
| — | 11.00 | — | — | ||
| Supply, installation , testing and commissioning of 12 Mtrs high mast tower hot dip galvanized as per IS 875(construction as per BS EN 10025 - 1993 or equivalant IS) with lantern carriage for 8 Nos of Nos of Light, pulley and cables with 8 Nos 150 W LED Flood Light with secondary lens for illumination . The mast shall also include accessories for highmast including headframe,steel wire rope 6mmdia (7/19 construction),trailling cable,double drum winch,galvanised lantern carriage arrangement suitable for 8 Nos Of Luminarie. The structure shall be of 12 Mtr height in two sections, hot dip galvansied both inside and outside (conforming to IS4759- 1984,IS2629-1985, IS2633-1972) and suitable for wind speed as per IS875 Part III , including base plate of size 545X545X20mm, Lightning protection final with GI single spike of suitable length, provision for 3 nos of earthing terminals at base of mast, Twin dome LED avaiation obstruction light at top of mast, 06 nos of 900mm/20mm(min.) size steel E 6.8 grade foundation bolts and Anchor plate of 445 PCD . The Construction of Foundation is included in scope of work as per manufacturers recomendation. The foudation should be as per Approved Drawing of manufacturer.The Mast shall also have raising and lowering system, head frame, hot dip galvanised steel lantern carrige (using 50mm dia B class GI pipe) suitable for fixing 8 nos of LED high mast luminaires symmetrically, trailing cable of 24Amp rating EPR insulated and PVC sheathed 5core X 2.5 sq.mm copper conductor cable and other wiring materials for luminaires, integral power tool (415V, 3phase, 1HP - 2mtr per minute single speed motor reversible) installation inside the base compartment, 2 nos of continuous 6mm stainless steel wire ropes(7/19 construction), double drum winch (manual and electrical both) as per IS 807, Feeder type control panel for operation of luminaires with astromical ON/OFF timers with suitable MCBs, contractors for automatic control of luminairs, power tool control and raise lower push button etc., complete as required. . The mast shall have thickness of 3 mm top & Bottom, No of faces: 12, Across face dia: Top-100 mm, Bottom-360 mm, Base plate: 545x 20 mm, PCD: 445 MM, Bolts: 06 Nos of 20x900 mm. 3 Nos earthing to be provided for the High Mast with 50 mm dia GI pipe, 3 Mtrs Long and 32x5 mm GI flat strip of required length.. | — | — | — | 37,52,100 | |
| — | 250.00 | — | — | ||
| Supply, laying, connection , testing of 6 SQ mm 4 core PVC insulated and PVC Round Sheathed, Multicore Annealed Bare Copper Conductor (flexible) industrial cable for Voltage Grade 1100 Volt, Conforming to IS 694 : 2010 | — | — | — | 1,09,750 | |
| — | 2000.00 | — | — | ||
| Supply, laying, connection with necessary cable lugs, testing and commissioning of LT XLPE Insulated, Cores Laid Up, PVC Inner sheathed, Armoured stranded aluminum conductor cable Size : 25 SQ MM 4 Core having Galvanized steel Strip, Extruded PVC Type ST2 Sheathed, 650/1100V Grade As Per IS 7098(Part 1) 1988 . Cable laying by excavation of earth depth 0.75 Mtrs. into breadth 0.508 Mtrs. below the ground level and a layer of course sand of 7.5 CM thickness shall be spread over the ground before laying the cable and the cable shall be covered with a layer of course sand of 7.5 CM thickness. The bottom of cable trench shall be leveled and got rid of any sharp material. Above the Layer of Course Sand 3 inch Size Brick is to be provided for protection of cable. Cable route markers to be provided at an interval not less than 50 Mtrs. All conditions to be fulfilled as per DRG No : PCEE/ELG/DRG/2024/2 Dtd 04.10.2024. | — | — | — | 13,28,000 | |
| — | 500.00 | — | — | ||
| Supply, laying, connection with necessary cable lugs, testing and commissioning of LT XLPE Insulated, Cores Laid Up, PVC Inner sheathed, Armoured stranded aluminum conductor cable Size : 95 SQ MM 4 Core having Galvanized steel Strip, Extruded PVC Type ST2 Sheathed, 650/1100V Grade As Per IS 7098(Part 1) 1988 . Cable laying by excavation of earth depth 0.75 Mtrs. into breadth 0.508 Mtrs. below the ground level and a layer of course sand of 7.5 CM thickness shall be spread over the ground before laying the cable and the cable shall be covered with a layer of course sand of 7.5 CM thickness. The bottom of cable trench shall be leveled and got rid of any sharp material. Above the Layer of Course Sand 3 inch Size Brick is to be provided for protection of cable. Cable route markers to be provided at an interval not less than 50 Mtrs. All conditions to be fulfilled as per DRG No : PCEE/ELG/DRG/2024/2 Dtd 04.10.2024. | — | — | — | 8,62,000 | |
| — | 300.00 | — | — |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .