Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.2 LAccepted-AOC | ₹23.2 L Quoted ₹23.6 L | L1 | Accepted-AOC Being L1 |
| 2 | L2₹24.7 LRejected-AOC GROUND FLOOR 281 1 D SHIVRAI NAGAR SAI MIRACLE ROAD RAHATNI PUNE 411 017 | PUNE | PUNE | MAHARASHTRA | 411017 | ₹24.7 L | L2 | Rejected-AOC Being L2 |
| 3 | L3₹25.6 LRejected-AOC S NO 261 1 D SAI MIRACLE ROAD SHIVRAI NAGAR RAHATANI PUNE 411 017 | PUNE | PUNE | MAHARASHTRA | 411017 | ₹25.6 L | L3 | Rejected-AOC Being L3 |
| 4 | L4₹26.1 LRejected-AOC | ₹26.1 L | L4 | Rejected-AOC Being L4 |
| 5 | L5₹26.7 LRejected-AOC 704 SILVER DEAL DAFFODIL WING 1 B T KAWADE ROAD PUNE 411 001 | PUNE | PUNE | MAHARASHTRA | 411001 | ₹26.7 L | L5 | Rejected-AOC Being L5 |
| Sl No | Description | Qty | Unit | M/S - KRUPA ELECTRICALS L5 | SOURABH ENGINEERS L6 | om sai enterprises L9 | ASHA ASSOCIATES L8 | MAYUR ELECTRIC SERVICES L1 | Star Electrical L4 | MUDDAM CONSTRUCTIONS L11 | YOGESH ELECTRICALS L2 | ISHITARAJ ENTERPRISES L3 | AN-ICON Engineering Technologies and Infrastructure Developments Pvt. Ltd. L10 | GANGA ENTERPRISES L7 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply and laying, connect, test and commissioning of LT underground cable XLPE insulated, armoured heavy duty electric cable with multi stranded aluminium conductor heavy duty 1100 Volts grade in trenches/on wall/poles laid in ducts/inside protection pipe of the following sizes including cable glands, lugs and suitable size of MS saddle clips (where ever cable laid in ceilings/walls without cable duct) complete including taking down existing unserviceable cable all as specified and directed by the Engr-in-Charge for the following :-
Notes : (i) Excavation, sand cushioning, cable protection shall be measured and paid separately. (ii) Cost of jointing material e.g. lugs, thimbles, nut bolt, glands and washers is deemed to include in the rate quoted.
(a) 120 Sqmm 3.5 core | 150 | Running Metre | 775 ₹1.2 L | 818 ₹1.2 L | 900 ₹1.4 L | 750.75 ₹1.1 L | 640 ₹96,000 | 710.45 ₹1.1 L | 650 ₹97,500 | 672.75 ₹1.0 L | 698.75 ₹1.0 L | 930 ₹1.4 L | 800 ₹1.2 L |
| 2.00 | (b) 50 Sqmm 3.5 core | 160 | Running Metre | 300 ₹48,000 | 386 ₹61,760 | 550 ₹88,000 | 462 ₹73,920 | 390 ₹62,400 | 437.2 ₹69,952 | 350 ₹56,000 | 414 ₹66,240 | 430 ₹68,800 | 450 ₹72,000 | 500 ₹80,000 |
| 3.00 | (c) 35 Sqmm 3.5 core | 150 | Running Metre | 275 ₹41,250 | 285 ₹42,750 | 450 ₹67,500 | 334.95 ₹50,242.50 | 280 ₹42,000 | 316.97 ₹47,545.50 | 250 ₹37,500 | 300.15 ₹45,022.50 | 311.75 ₹46,762.50 | 350 ₹52,500 | 360 ₹54,000 |
| 4.00 | (d) 25 Sqmm 4 core | 180 | Running Metre | 245 ₹44,100 | 251 ₹45,180 | 400 ₹72,000 | 288.75 ₹51,975 | 250 ₹45,000 | 273.25 ₹49,185 | 225 ₹40,500 | 258.75 ₹46,575 | 268.75 ₹48,375 | 300 ₹54,000 | 320 ₹57,600 |
| 5.00 | (c) 16 Sqmm 4 core | 170 | Running Metre | 180 ₹30,600 | 191 ₹32,470 | 250 ₹42,500 | 231 ₹39,270 | 200 ₹34,000 | 218.6 ₹37,162 | 200 ₹34,000 | 207 ₹35,190 | 215 ₹36,550 | 250 ₹42,500 | 250 ₹42,500 |
| 6.00 | Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for taking out/laying for HT/LT under ground cables and getting out in:-
(a) Soft / loose soil. | 109.35 | Cubic Metre | 300 ₹32,805 | 200 ₹21,870 | 129.25 ₹14,133.49 | 127.05 ₹13,892.92 | 110 ₹12,028.50 | 120.23 ₹13,147.15 | 300 ₹32,805 | 113.85 ₹12,449.50 | 118.25 ₹12,930.64 | 325 ₹35,538.75 | 150 ₹16,402.50 |
| 7.00 | (b) Hard / dense soil. | 847.13 | Cubic Metre | 315 ₹2.7 L | 350 ₹3.0 L | 800 ₹6.8 L | 277.2 ₹2.3 L | 240 ₹2.0 L | 262.32 ₹2.2 L | 400 ₹3.4 L | 248.4 ₹2.1 L | 258 ₹2.2 L | 350 ₹3.0 L | 280 ₹2.4 L |
| 8.00 | (C) soft desintigrated rock | 18.23 | Cubic Metre | 450 ₹8,203.50 | 900 ₹16,407 | 658 ₹11,995.34 | 646.8 ₹11,791.16 | 560 ₹10,208.80 | 612.08 ₹11,158.22 | 750 ₹13,672.50 | 579.6 ₹10,566.11 | 602 ₹10,974.46 | 600 ₹10,938 | 660 ₹12,031.80 |
| 9.00 | Returning filling in including spreading leveling watering and well ramming in layers not exceeding 25cms in soil complete all as specified and directed by Engr-in-Charge | 887.16 | Cubic Metre | 90 ₹79,844.40 | 85 ₹75,408.60 | 52.87 ₹46,904.15 | 51.97 ₹46,105.71 | 40 ₹35,486.40 | 49.18 ₹43,630.53 | 90 ₹79,844.40 | 46.57 ₹41,315.04 | 48.37 ₹42,911.93 | 100 ₹88,716 | 40 ₹35,486.40 |
| 10.00 | Removing excavated materials not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and directed. | 87.54 | Cubic Metre | 120 ₹10,504.80 | 100 ₹8,754 | 52.87 ₹4,628.24 | 51.97 ₹4,549.45 | 40 ₹3,501.60 | 49.18 ₹4,305.22 | 150 ₹13,131 | 46.57 ₹4,076.74 | 48.37 ₹4,234.31 | 140 ₹12,255.60 | 50 ₹4,377 |
Tender Value
Refer Docs
EMD Value
₹80,000
Closing Date
9 Dec 2025, 6:00 pmClosed
GE RnD Pashan
GE RnD Pashan
REPAIRS TO VARIOUS UTILITY SERVICES INCLUDING EXTERNAL ELECTRIFICATION SERVICES AT GANESHKHIND AREA UNDER GE(I) RnD PASHAN
2025_MES_733490_2
GERD/PSN/TOKEN/45 OF 2025-26
Open Tender
Electrical and Maintenance Works
180 days
GE RnD Pashan
As per tender documents
9 documents required · 9 mandatory
₹500
GE RnD Pashan
₹80,000
Yes
28 Jan 2026
18 Nov 2025
11 Dec 2025
18 Nov 2025
9 Dec 2025
2 Dec 2025
18 Nov 2025 - 25 Nov 2025
Amount
Supply and laying, connect, test and commissioning of LT underground cable XLPE insulated, armoured heavy duty electric cable with multi stranded aluminium conductor heavy duty 1100 Volts grade in trenches/on wall/poles laid in ducts/inside protection pipe of the following sizes including cable glands, lugs and suitable size of MS saddle clips (where ever cable laid in ceilings/walls without cable duct) complete including taking down existing unserviceable cable all as specified and directed by the Engr-in-Charge for the following :- Notes : (i) Excavation, sand cushioning, cable protection shall be measured and paid separately. (ii) Cost of jointing material e.g. lugs, thimbles, nut bolt, glands and washers is deemed to include in the rate quoted. (a) 120 Sqmm 3.5 core
(b) 50 Sqmm 3.5 core
(c) 35 Sqmm 3.5 core
(d) 25 Sqmm 4 core
(c) 16 Sqmm 4 core
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for taking out/laying for HT/LT under ground cables and getting out in:- (a) Soft / loose soil.
(b) Hard / dense soil.
(C) soft desintigrated rock
Returning filling in including spreading leveling watering and well ramming in layers not exceeding 25cms in soil complete all as specified and directed by Engr-in-Charge
Removing excavated materials not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and directed.
Supply and lay in trenches reinforced precast concrete cable cover class LV, Type I, flat, size 250mm x150mm x 40mm for cable protection complete all as specified and directed by the Engr-in-Charge.
Material and labour for riddled earth filling in trenches to required width at bottom and top of cable cushioning including spreading leveling and consolidation complete all as specified and as directed. Note : Punned thickness shall measured and paid.
On load filteration of transformer oil by continueous circulation of transformer oil through mechanical filters to achive the desired dielectric strength of 35 KV for one minute at 4 mm gap complete all as specified. Note: 1.Oil samples are to be collected from top and bottom of oil tank and test results to be recorded for each sample before and after filteration.
Supply and topping up transformer oil of dielectric strength 60 KV at 2.5 mm gap in transformers of various capacity installed in various locations complete all as specified and directed. Notes : (a) New Transformer oil shall be filled in the transformer only after filteration and dehydration of existing transformer oil of the transformer. (b) Transformer oil shall be supplied in sealed barrel with test result and test certificate.
Supply and fix in repair breather assembly transparent plastic body with top and bottom portion pressed with metallic cover, filled with silica gel blue in colour and suitable for fixing on existing pipe of size 15/20/25 mm dia with suitable reducers/connectors etc as per site requirement /capacity of transformer complete all as specified and directed. Note : Rate quoted shall be deemed to include the cost of modification if any required to fix on existing MS Pipe.
Repair to gang operated air brake switch device upto 100 Amps,22 KV capacity including greasing/oiling of all moving contacts, renewal of nut bolts,washers of suitable sizes,unserviceable spares and jumper connections in all phases for smooth functioning of the devices all as directed by Engr-in-charge. Note : Unserviceable spares and jumper connections replaced shall be measured and paid separately as "Supply only"
Supply only the following items : (a) Male contact/moving contact with blade arcing horn of gang operated AB switch devices suitable for 22 KV
(b) Female contact /fix contact jaw arcing horn for gang operated AB switch devices.
(c) Tinned copper flexible jumper 200/200 Amps
(d) Post top Polymer insulators of gang operated AB switch devices.
(e) Middle post Polymer insulators of gang operated AB switch devices.
(f) Bottom post Polymer insulators of gang operated AB switch devices.
(g) MS jumper carrier.
(h) Back connector plate.
GI pipe, heavy grade 25 mm dia made to shape for gang operating from ground.
Repairs to drop out fuse complete upto 400 Amps,22 KV capacity including renewal of worn out nut bolts,washers,of suitable size /unserviceable spares and jumper connections for smooth functioning of the devices all as directed by Engr-in-charge. Note : Unserviceable spares and jumper connections replaced shall be measured and paid separately as "Supply only"
Supply only the following items (to be incorporated under Item No 26 above) a) Fix top contact/ contact for drop out fuse.
b) Fix lower contact for drop out fuse.
c) Post insulators of drop out fuse.
Supply, install, testing and commissioning of 22 KV outdoor type Polymer based gang operated air brake switch triple pole, suitable for verticle mounting complete , GI operating rod of suitable length for operating mechanism worked from ground level complete in both OFF and ON positions, for current rating upto 200 Amps,each pole consist of galvanised steel base HT insulators 9 Nos as per BSS/ISS non ferrous knife and spring loaded contacts, arcing horns of adequate section to brake magenetizing current of the transformers. All ferrous parts hot dipped galvanised and non ferrous parts suitably tinned to with stand weather complete all as specified and directed.
Supply and fix in repair Polymer Pin type insulator of 22 KV including necessary hardware complete all as specified and directed.
Supply and fix in repair Polymer disc type insulator, ball and socket type, white brown or green suitable for 22KV including necessary hardware complete all as specified and directed
Supply and Fix in repair defective lightining distribution surge arrestor, complete set non linear type MCOV, 18 KV, 5 KA with all fittings bolts nuts and washers etc complete all as specified and directed.
Material and labour for preparation of old painted steel surface of 6/4/2 pole structure HT/LT street light/HT steel tublar poles 8.5/9.0/11/13 mtr long above GL/coping including cross arms,channels,Flat iron,Clamps in LT/HT OH line by scraping with wire brush/ sand paper and applying one coat of aluminium paint including pole numbering all as specified and directed by Engr-in-charge for the following types:- a) HT 4 Pole structure 11 metre long
b) HT 2 Pole structure 11 metre long
c) HT pole 11 metre long
d) LT pole 8.5/9 metre long
Disconnecting the transformer outdoor type from HT/ LT system and opening carefully by draining out transformer oil upto HT/LT boxes for rectifying the leakage by replacing the unserviceable spare parts of capacity 50 to 750 KVA transformer, refilling the transformer oil and complete assembling after repairs including testing for any oil leakages and connecting the HT/LT system after the leakages have been rectified and tested on available electric load complete all as specified and directed. Note : Defective parts replaced will be measured and paid separately as "Supply only" under respective items here in after.
Supply only LT bushings with brass studs of existing specification.
Supply only top cover gasket set.
Supply only HT bushing with stud 22 KV of existing specification.
Material and labour for preparation of old painted surfaces of transformer, removing rusted scale/oil & painting of transformer with one coat of synthetic enamel paint of approved make duly Marking/ writing MES/SM No. complete all as specified and directed by Engr-in-charge for : (a) 160 to 250 KVA capacity of transformer.
(b) 300 to 500 KVA capacity of transformer.
Re-Stringing of HT/LT over head conductor and earth conductors, unwinding and visual testing of insulator, rewinding of ACSR and GI earth wire guard/ earth conductors rigidly with winding wire complete all as specified and directed.
Material and labour for disconnecting from existing main taking out from LT panel board for servicing & overhauling LT ACB of any make 800 to 1600 Amp, 50Hz 415V AC Draw out type including taking out existing mechanism complete with servicing of operating mechanism triping mechanism and spring charging mechanism complete to make it funtioning smoothly and including replacement of unserviceable spares and fixing in its original position with all connections and testing complete all as specified and directed. Note : Spare parts shall be paid separately under respective items here in after, however cost of minor spares except mentioned in item no 46 to 49 below shall be deemed to be included in item rate.
Supply only Following spare parts suitable for LT ACB suitable 800A-1600 A Capacity :- (a) Main isolating contact (Male and Female) jaw type complete including fixing accessories
(b) Shunt Trip coil/ Closing coil 415 VAC suitable for 800 amps ACB
(c) Under voltage tripping divice (UVT) 415 volts
(d) Single phae CTS at rating 800/5A
Supply and fixing in repair MCCB 3pole, 320 Ampere, 36 KA, 415 volts, over load and short circuit protection, adjustable thermal -magnetic release type complete all as specified and directed
Supply and fixing in repair MCCB 3pole, 250 Ampere, 36 KA, 415 volts, over load and short circuit protection, adjustable thermal -magnetic release type complete all as specified and directed
Supply and fixing in repair MCCB 3pole, 200 Ampere, 36 KA, 415 volts, over load and short circuit protection, adjustable thermal -magnetic release type complete all as specified and directed
Supply and fixing in repair MCCB 4pole, 100 Ampere, 25 KA, 415 volts, over load and short circuit protection, adjustable thermal -magnetic release type complete all as specified and directed
Supply and fix Pin type, porcelain, vitreous white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100 mm height, 65mm dia suitable for 1100 volts grade including taking out existing unserviceable insulator all as specified and as directed.
Supply and fix insulator shackle type, porcelain, vitreous, white, brown or green insulator including galvanised and mild steel straps of size 31x5mm, washers, insulator bolts, washers and nuts, size of insulator 100 mm height, 115 mm dia with 14 mm dia bolts for 1100 Volts grade including taking out existing insulators complete all as specified and as directed.
Material and labour for PCC 1:3:6 type C-2 using 40mm graded aggregate as in foundations of stays and poles, copping of poles etc complete including necessary form work weathering, slightly rounded or chamfered angles and throating complete all as specified and directed.
Supply and fix in repairs LED street light /road way luminaries 70 watts with pressure die cast housing heat shrink with IP 66 protection, interchangeable electronic driver high efficiency longer life, protection against high surges , high /low voltage cutoff, open/short circuit protection and high power factor LEDs as light source including fitted on existing street light pole bracket complete all as specified and as directed.
Supply and fix in repair LED street light /road way luminaries 90 watts with pressure die cast housing heat shrink with IP 66 protection, interchangeable electronic driver high efficiency longer life, protection against high surges , high /low voltage cutoff, open/short circuit protection and high power factor LEDs as light source including fitted on existing street light pole bracket complete all as specified and as directed.
Supply and fix in repairs pole junction box sheet moulded compound (SMC) type with hinged door and locking arrangement of size 140x140x100mm (internal) comprising, one No MCB single pole of capacity 6 Amps 240 volts and one No terminal for loop in & loop out suitable for single phase street light system including nuts and bolts and connecting up complete MS clamp fabricated from 25x3mm MS flat iron all as specified and directed.
Supply and fix in repair Automatic Street Light Switch using NATURE SWITCH for automatic switching of Street Lights based on LUX level of Natural Light. The Sensor (Nature Switch) along with suitable Power Contactor, MCB and Support Terminals should be enclosed in pole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, Termite proof and FR grade special moulding compound (Sintex make SMC Junction box) conforming to IP54.The Contactor, MCB and Circuit Wiring should suitable enough to take load of 8 kW single-Phase load .Contactor Rating: 40.Amps ( 2-pole ).MCB (single-pole) Rating:63.Amps (2 nos.) Nature Switch: Kakatiya Energy Systems Pvt. Ltd. Hyderabad (EnC Approved) Contactor: BCH/L&T/Schneider or equivalent MCB: Havells/Schneider/Legrand/L&T. complete all as specified and directed.
Supply, install, testing and commissioning of LT Panel Board CPRI approved cubical with Kiosk type made out of 3.15 mm thick outdoor type with IP 65 grade of protection CRCA sheet, powder coated, with support of 50 mm X 50 mm X 6 mm angle iron bottom frame with double hinged front openable shutters of each feeder control unit with locking arrangement in front and back openable inspection doors heat shrink PVC sleeved aluminum bus bar of capacity 800 Amps, 3 Phase, 4 wire, for each phases and neutral fixed on suitable insulator all housed in suitable bus bar chamber and provision and fixing of multifunction meter, CTs of suitable ratio, and LED pilot indication lamps complete along with provision of necessary cable entry/ exit boxes for all incoming and out going cables with provision of hoes for cable glands etc fixed on suitable PCC foundations, testing on completion complete all as specified and directed and shall be comprising of the following:- Incomer MCCB with thermal magnetic Release range 250 Amps, 4 Poles, 36 KA breaking capacity - 01 No, Outgoing MCCB with thermal magnetic Release range 125 Amps, 4 pole, 36 KA breaking capacity - 02 No, coloured heat shrinkable PVC insulated aluminium bus bar 400 amps 3 phase wire LED Pilot lamps (R Y & B) - 01 Set, LED Digital multi function meter with CTs-01 Set extended rotary handles and spreader terminals for all MCCBs excavation and PCC foundation
Material and labour for earthing with galvanised steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground earth pit not less than 2.25 M deep below ground level with top edge of the plate not less than 1.5 M below normal ground level connected to galvanised earth lead wire 4.0 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 5 of SSR Part I connected to earthing test point including excavation/ earth work in any type of strata, removal of surplus excavated material, GI pipe for watering and funnel, PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B0 in cover slab GI funnel with GI watering pipe 20mm dia med grade, wire mesh, protection pipe 20mm dia GI pipe light grade for earth lead upto 7.50 m long complete all as specified and directed by Engineer-in-Charge.
Material and labour in repair for earthing with and including galvanised steel earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground earth pit not less than 2.25 metre deep below ground level with top edge of the plate not less than 1.5 metre below normal ground level connected to galvanised strip 32mm x 6 mm by means of nuts, bolts, check nuts, washers of galvanised iron or steel all as shown in electrical plate No. 03 of SSR Part I connected to earthing test point including excavation/ earth work in any type of strata, removal of surplus excavated material, GI pipe for watering and funnel, PCC 1:3:6 type C1 (using 20mm graded crushed stone aggregate) chamber including necessary formwork / mould for fair and even surfaces, precast RCC 1:2:4 type B0 ( using 12.5 mm graded crushed stone aggregate) chamber cover slab, GI funnel, with GI watering pipe 20 mm bore medium grade, wire mesh, protection pipe 40 mm bore GI pipe light grade for earth lead upto 7.50 metre long including testing & charcoal and salt complete all as specified and directed by Engineer-in-Charge. Note : Test report shall be prepared and submitted by the contractor in triplicate duly obtaining signatures of MES JE / AGE & PMG / user. Test results are to be written in letters of 20mm height in white colour on black paint back ground.
Material and labour for 63 Amp, 4 pole, 6 way busbar chamber, busbar made of ETP grade copper, wall mounted type suitable for 415 volt, Ac including fixing arrangements clamps, glands, nuts and bolts complete all as specified and as directed by Engr-in-Charge.
Material and labour for straight through joint,heat shrinkable,type,for HT OH AB cable including joint kits and labour complete for making joints suitable for aluminium conductor cable XLPE,3 core,95 to 120 sqmm,22 KV all as specified and directed by Engineer-in-charge.
Material and labour for outdoor type end termination joint, heat shrinkable, type, for under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable XLPE, 3 core, 95 sqmm, 22 KV all as specified and directed by Engr-in-charge
Cutting the tree branches which touches the LT/HT OH lines and cleaning the same 2.5 mtr away from centre line of HT/LT OH line span not exceeding 60 mtrs between poles and deposting the tree branches/leaves at 30 m distance away from site complete all as specified and directed Note : Any number of tree branches cut in one span will be measured as one length for payment purpose.
(b) Over head Tank of capacity 100000 Glns
Material and labour for painting 40 to 75 HP motorwith one coat of synthetic enamel paint by using brush to motor and pump set including cleaning and preparing surface duly scraping old paint and writing SM/MES No.all as specified and directed by Engineer-in-charge
Material and labour for painting of old painted surfaces of pipe 100 to 150 mm dia including preparation of surfaces and applying one coat of synthetic enamel paint complete all as directed and required at site.
Material and labour for painting of old painted surfaces with one coat synthetic enamel paint by using brush to sulice valve and wheel of size 100 to 200 mm dia including cleaning with chemical agent and preparing surface duly scraping old paint all as specified and directed .
Material and labour for Overhauling of centrifugal pump sets by dismantling the pump set,opening,cleaning,greasing including renewal of spare parts and reassembling after repairs including,metaling,grinding etc transpotation, reinstalling back to position and testing complete for 30 HP to 75 HP Pump DSM 4 RR/DSM 4 RM/DB 65/20. Note:-Spares parts renewed shall be measured and paid seperately as "Supply only".
Supply only spares for 30 to 75 HP Pump DSM 4RR/DSM4 RM /DB 65/20, Pumps(Make:-Kirloskar pumps) (a) Shaft sleeve
(b) Shaft sleeve nuts ( set of 4)
(c) Bearing cartridge DE/NDE
(d) Bearing cover DE/NDE (set of 2) Split gland coupling
(e) Bearing cap (set of 2)Wear Ring
(f) Bearing lock nut
(g) Throat bush (set of 2)
(h) Gland packing 10Sqmm
(j) DSM 100/36 set of Gaskets
(k) DSM 100/36 set of 'O' rings
(l) Impeller 1st/ 2nd stage
Disconnecting the electrical and mechnical connection of burnt electrical motors from the site/location including transporting to and from workshop, rewinding of electrical motors by dismantling and removing the burnt out copper winding wire,cleaning the slots of stator with petrol and brushes,winding with polyster based super enameled copper wire of same guage of original one with proper class of insulation including varnishing and heating the coil and remove the air bubbles complete,stator/rotor after rewinding,reassembling all parts including reinstalling,connection to original position and testing on full load all as directed by Engineer-in-charge for capacity of motor as per following:- (a) 30 HP three phase motor 415 V
(b) 75 HP three phase motor 415 V
Supply only roller ball bearing/Double ball bearing thrust ball bearing of pumps/motor of following sizes:- (a)6309
Supply and fix power contactors MCE 110 Amp type with 2NO+2NC ,CP No.CS94137 in existing pumping set starter panel including necessary testing complete all as specified and directed.
Supply and fix in repair unserviceable pressure guage range 0 to 14 Kg/cm2 with 100 mm dia with one stainless steel cock.
Supply and Fix rubber packing sheet 3 mm thick complete all as specified and directed.
Supply and fix in repair rubber bush for pin type coupling for any type of pump and motor complete all as specified and directed.
Material and labour for lead pig for repair of leaking joints complete all as specified and directed.
Material and labour for spun yarn for repair of leaking joints complete all as specified and directed.
Material and labour for lead wool for repair of leaking joints complete all as specified and directed.
Dismantling the disturbed valve chambers and construction of brick masonry valve chamber of the following sizes(internal dimensions) including necessary earth work excavation in any type of soil,PCC(1:4:8),type D2 in foundation,brick masonry of wall thickness of 230 mm in CM(1:6) rendering CM(1:6) internally and externally including to a depth of 15 cm below GL,3 mm thick hinged MS iron cover as specified in IS-3950-1979 embeded in PCC with locking arrangment and painting with two coats of distinctive color synthetic enamel paint over a coat of red oxide primer PCC(1:2:4) B1,50 mm thick coping and locking arrangment etc complete all as specified and directed:- (a) 900x900x1200 mm
(b) 1200x1200x1200 mm
Burning out leaking lead joints in position including removing of old lead for following size of pipes complete all as specified and directed by Engineer-in-charge. (a)80 mm bore of pipe
(b)100 mm bore of pipe
(c)150 mm bore of pipe
Material and labour for run lead joints for CI pipes complete with necessary jointing material such as pig lead and spun yarn, fire wood for jointing of pipes complete all as specified and directed by Engineer-in-charge for the following sizes:- (a)80 mm bore of pipe
(b)100 mm bore of pipe
(c)150 mm bore of pipe
Taking up or down GI water tubing including removing of all necessary connections/fittings as specified and directed by Engineer in Charge. (Note : excavation and earth work will be measured & paid separately) (a) 15 mm dia
(b) 20 mm dia.
(c) 25 mm dia
(d) 40 mm dia
(e) 50 mm dia
(f) 80 mm dia
Relaying and refixing the GI pipe after descaling / cleaning complete with the help of water & brush of the following size / bore obtained from Sl item No 109 to 114 above and connect in old / new positions, laid in trenches/fixed on wall/on floor including provision of new fittings such as bends, tee, unions, elbows, sockets etc complete all as specified and directed. (a) 15 mm dia.
(b) 20 mm dia.
(c) 25 mm dia
(d) 40 mm dia
(e) 50 mm dia
(f) 80 mm dia
Supply and fix GI tubing medium grade ISI marked fixed on wall, roof, floor complete with necessary accessories such as Tees union , bend ,elbow nipple reducer etc , all as required at site for branch connection including cutting threading complete all as specified and directed by Enginner-in-Charge. (a) Bore of pipe 15 mm dia
(b) 20 mm dia.
(c) 25 mm dia
(d) 40 mm dia
(e) 50 mm dia
(f) 80 mm dia
Supply and fix galvanized iron water tubing medium grade ISI marked in trenches complete with all accessories such as Tees union,bend,elbow nipple reducer etc all as required at site for branch connection including cutting threading complete all as specified and directed. (a) dia of pipe 15 mm dia
(b) 20 mm dia.
(c) 25 mm dia
(d) 40 mm dia
(e) 50 mm dia
(f) 80 mm dia
Disconnecting/taking down unserviceable worn out CI sluice valve with SS Spindle and supply and fix new CI sluice valve PN 1.6 with SS spindle as required at site and as directed by Engineer-in-charge:- (a) Sluice valve 100 mm dia
(b) Sluice valve 150 mm dia
(c) Sluice valve 200 mm dia
Supply and fix Foot valve ball type heavy duty suitable for 150 mm dia pipe line complete all as specified and directed.
Material and labour cutting of Roads / Plinth to width n exc 300mm and depth n exc 300 mm complete all as specified and directed. Note: PCC will be measured and paid separetely.
Material and labour PCC in 1:2:4 type B 1 by using 20 mm graded stone aggregate for making good road/foot path/hard standing/drain/ bldg plinth protection and foundation for motors, pumps and starters all as per site requirement and as directed by Engr-in-Charge.
Disconnection of existing water storage tank any type at 3.0mtr height and above, removal of water if any from the tank and cleaning the bottom and internal periphery of the tank by using wire brushes to remove the Mud, Algae, fungus etc without damaging the water tank and finally rinsing the tank by using chlorine/bleaching powder/altoc GP or any other similar type of disinfectent chemical as directed by Engr-in-Charge complete all as specified or as directed at site. Note : Date of cleaning shall be written after cleaning in format DD/MM/YY with synthetic enamel paint after removing the earlier date if found exisitng. (a) Capacity upto 1000 litre
Supply and fix in repairs ball valves high pressure of PTMT with epoxy coated luminium rod & highdensity plastic ball screwed for iron pipe and fixed for the following sizes at any height of building complete all as specified and directed :- Note : All T&P required for complete the work shall be arranged by the contractor and no any extra payment will be admissible on this account. (a) for 15mm dia
(b) for 20mm dia
(c) for 25mm dia
Repair to water supply line (Fresh water) with mechanical joint, of CI pipe line of size150 mm including taking out the leaked /puncture/cracked existing pipe , cutting of damaged portion of pipe through welding, making rough surfaces smooth and champhered by grinding and then connected through GI pipe jointing material adequate size complete as per site requirement. Note : Testing/commissioning the pipe line on full pressure after complete the job will be carried out and payment will made of this job if found satisfactory other wise the same shall be done against and no extra payment will be made on this account.
Supply and fixing of CI/DI fitting for spigot socketed pipes such as Bends (any type, radius an angle) Tapers any tpe, (straight, bend, increasing, decreasing or double socket etc.) Tee pieces single branch, `Y' junction, double branch, cross (all sockets or flanged ) collars, caps and plugs, Connecting pieces one end flanged and other socket or spigot and bell mouth pieces one end flanged other end tapering as bell mouth Upto150 mm bore complete all as specified and directed.
Routine maintenance consisting of normal repairs with periodical routine maintenance and testing of DG set of 75 KVA complete (i.e. Engine, Alternator etc) under GE(I) R&D Pashan as below including all cosumables like cotton, waste cloth, kerosene oil etc. Maintenance will be carried out as and when ordered in writing by Engineer-in-Chagre, complete all as specified and directed :- (a) Change of engine oil, (b) Check clearance of suction and exhaust valves and adjust if required, (c ) Changing of oil filter, fuel filters, screen filters assembly (d) Changing of water filter element, (e) Topping up of coolent, (f) Change of Hydraulic governer oil, (g) Tightening of all nut bolts, (h) Greasing of all points, (j) Checking of any leaking in fuel and oil lines, (k) Cleaning of fuel tank by taking out the dirt and sludge, cleaning the tank thoroughly, (l) Repair of battery terminal made of Brass with necessary brazing to cable each set of 2 NOTE 1 : Labour charges for dismantling / taking down and replacement / refixing new parts required is deemed to be included in unit rate quoted. NOTE 2 : Spare parts like oil filter, fuel filter, screen filter by pass filter etc. will be measured and paid separately as supply only. 75 KVA DG Set at pump house GaneshKhind Area
Supply of Engine oil 20W40 for DG set complete all as specified and directed. Make : castrol or techno commercial equivalent make of others.
Supply and top up of Premix Ethylene Glycol coolent for Engine Radiator complete all as specified and directed. Make : castrol or techno commercial equivalent make of others.
Material and labour for battery terminals made out of brass with nut bolts & washers and necessary brazing to cable complete all as specified and directed.
Supply and fix flexible braided high pressure hydraulic pressure pipe including both ends chromium plated connections check nuts and washers suitable for fuel tank to FIP complete all as specified and directed.
Supply only by pass filter element with 'O' ring suitable for DG Sets of 75 KVA complete all as specified and directed.
Supply only fuel filter primary and secondary with 'O' ring for DG Sets of 75 KVA complete all as specified and directed.
Supply only oil filter with 'O' ring for DG Sets complete all as specified and directed.
Material and labour for valve chamber cover with black paint with two coats of asian paint including preparing surface duly scraping old paint complete all as specified and directed by Engr-in-Charge.
Supply and fix fan belt for DG Sets complete all as specified and directed. Make : Fenner / Dunlop or techno commercial equivalent.
Material and labour for cleaning of radiator,external cleaning by vaccum cleaner,petrol washing and taking out the carbon deposits from cooling fins and internal cleaning by using restor plus liquid and inhibitor corrosion of 75 KVA DG Set complete all as specified and directed by Engineer-in-charge.
Supply install testing and commissioning of Electromagnetic Digital water flow meter along with UPS back up suction/delivery size 600 mm dia on existing CI/DI water supply pipe line 600 mm Metering details as follow :- Type : Flow Sensor JT122SSL Electrodes : SS316 Process connection : DIN PN 16 Flanges : Carbon Steel Area classification : Non‐Hazardous Protection class : IP 68 Mounting : Remote with 10 Mtr Cable Type : Microprocessor Based Output : 4 ‐ 20mA + MODBUS RS 485 Accuracy : ± 0.5% of measured value for velocity Display : LCD Display Parameters : Actual flow rate, totalized flow (8 digit) Power supply : 230V AC Housing : Aluminium Note : The rate shall be including PMC / MITC lab testing.
Supply and fix in replacement Led Acid Battery of 180 AH ,12 V DC for DG Set complete all as specified and directed.
YOGESH ELECTRICALS (BID ID -3492997)
ISHITARAJ ENTERPRISES (BID ID -3493133)
Star Electrical (BID ID -3493358)
M/S - KRUPA ELECTRICALS (BID ID -3490654)
SOURABH ENGINEERS (BID ID -3491036)
GANGA ENTERPRISES (BID ID -3493418)
ASHA ASSOCIATES (BID ID -3491963)
om sai enterprises (BID ID -3491508)
AN-ICON Engineering Technologies and Infrastructure Developments Pvt. Ltd. (BID ID -3492857)
MUDDAM CONSTRUCTIONS (BID ID -3492227)
stage.html
html • 0.08 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.58 MB
8626.pdf
Tender Documents • 1.68 MB
BOQ_829073.xls
BOQ • 0.67 MB
Download all tender documents and submit your bid