| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 CrAccepted-AOC A T ROAD EVERLITE HOUSE PANITOLA LAIPULI TINSUKIA ASSAM 786183 | TINSUKIA | ASSAM | 786183 | ₹1.3 Cr Quoted ₹1.1 Cr | L1 | Accepted-AOC L1 BIDDER |
| 2 | L2₹1.2 Cr+₹6.0 L (5.21%)Rejected-Finance OPPOSITE SWAHID BHAWAN VILL MIRZA P O MIRZA DIST KAMRUP 781125 | MIRZA | KAMRUP | ASSAM | 781125 | ₹1.2 Cr+₹6.0 L (5.21%) | L2 | Rejected-Finance L2 BIDDER |
| 3 | L3₹1.5 Cr+₹33.0 L (28.9%)Rejected-Finance GROUND FLOOR PURVI COMPLEX A T ROAD NEAR PANBAZAAR OVERBRIDGE KAMRUP ASSAM 781001 | KAMRUP METRO | ASSAM | 781001 | ₹1.5 Cr+₹33.0 L (28.9%) | L3 | Rejected-Finance L3 BIDDER |
Tender Value
Refer Docs
EMD Value
₹2.8 L
Closing Date
13 Dec 2024, 12:00 pmClosed
CGM PPnD
First Floor, Bijulee Bhawan, Paltanbazar, Ghy-01
Turnkey Construction of 01 (one) no. of 33kV Feeder Bay including Civil works at 132 kV AIIMS GSS, AEGCL
2024_AEGCL_40242_1
Tech-1137/Deposit/33kV Jericho Bay
Open Tender
Electrical Works
Turn-key
365 days
132kV AIIMS GSS
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,000
₹2.8 L
Yes
28 May 2025
8 Nov 2024
16 Dec 2024
8 Nov 2024
13 Dec 2024
2 Dec 2024
9 Nov 2024 - 16 Nov 2024
Amount
Supply of Equipments and accessories
36kV, 31.5kA/3sec, 1250A, Vacuum Circuit Breaker complete with mounting structure and accessories including Terminal connectors.
36kV,1250A,3 Phase Gang operated outdoor type double break centre post rotating motor operated Isolators without earth switch complete with all accessories and solid core post insulator with Terminal connectors.
36kV,1250A,3 Phase Gang opereated outdoor type double break centre post rotating motor operated Isolators with earth switch complete with all accessories and solid core post insulator with Terminal connectors.
33kV, 400-200/1-1A, 2-core Single phase CT complete with all fittings and accessories including with Terminal connectors (0.2s-5p20 class, live tank type)
CT Junction (Marshalling) Box
33kV Lightning Arrester complete with all fittings and accessories including Terminal connectors and surge counter.
33kV, 8kN post insulator with all fittings including Terminal connectors
Supply of Mounting Structures with mounting & foundation bolts as per drawing and technical specification.
33kV Motorised isolators without Earth Switch
33kV PI (BPI)
33kV Motorised isolators with Earth Switch
Mounting Structure for PI of 33 kV AI tube bus (HBPI)
Supply of Indoor floor mounted 33 kV Feeder control and relay panel (Simplex Type) with BCU, ethernet switch and all accessories suitable for SAS integration to existing SAS of iGrid make.
Supply of 3ph 4 wire Energy Meter (0.2S class, SAMAST Compliant ABT Meter)
Supply of Lattice type structural steel (for Column & Beam type)
Column type "C5"
Beam type "B5"
Supply of Terminal connectors, IPS AL Tube, conductor etc. of 33 kV Side.
3 inch IPS AL tube for 33 kV Bus as per GTP & Drawing
ACSR Panther Conductor
Terminal connector for Bus PI suitable for 3 inch IPS AL Tube
Tee connector suitable for interconnection of single ACSR Panther conductor to AI Tube
Terminal connector for 33 kV PI suitable for single ACSR Panther conductor
End caps and couplers/bends for 3 inch IPS AL Tube
Tee Clamp (Panther to Panther)
Supply of Earthmat Extension and grounding of equipments
Main earth mat (65x12 mm GI flat)
50x6 mm GI flat Earthing conductor for earthing of indoor L.T & control panels, Junction box, Marshalling boxes, cable trenches etc.
Earth electrode, 50mm dia, 3m long GI perforated pipe
GI steel wires (37/3.5mm)
Supply of PVC Armoured Control Cable (Copper)
19CX 1.5 sqmm
12CX 1.5 sqmm
7CX 1.5 sqmm
4CX2.5 sqmm
2CX2.5 sqmm
Supply of Armoured Power Cable (Aluminium)
4CX4 sqmm
Supply of 60W LED lights for switchyard Illumination, including fitting and fixing
Supply of 415 V AC Marshalling Kiosk including construction of foundation, installation & cable termination. a) 2nos. 63A, 4P (Incomer) b) 3nos. 25A, 4P (Outgoing) c) 3nos. 16A, 4P (Outgoing)
Supply of Mandatory Spares
33 kV , 25 kA, 1250 A Isolators Contacts (1 Male, 1 Female Contact= 1 Set)
Master Trip relay
Bay control unit
O/C & E/F relay
Tripping coil for 33kV VCB
Closing coil for 33kV VCB
Tee connector suitable for interconnection of single ACSR Panther conductor to AI Tube
Complete one no. of VCB pole (Spare) compatible to fitting in any phase of the VCB
Supply of GI Cable Tray
Perforated type 600 mm wide
Perforated type 300 mm wide
Supply of Earthing Stick (Discharge Rod) upto 132kV Level (Standard Length 15 meter) including installation and demo at site.
Supply of Portable Led Light Tower as per Technical Specification including installation and demo at site
Supply of Fire Fighting Equipment
22.5 kg FE CO2 type trolley mounted
DCP 5 kg capacity, wall mounted
Fire buckets (12 Nos with stand in one set)
Description of Work / Item(s)
Amount
F&I of Equipments and accessories
36kV, 31.5kA/3sec, 1250A, Vacuum Circuit Breaker complete with mounting structure and accessories including Terminal connectors.
36kV,1250A,3 Phase Gang operated outdoor type double break centre post rotating motor operated Isolators without earth switch complete with all accessories and solid core post insulator with Terminal connectors.
36kV,1250A,3 Phase Gang opereated outdoor type double break centre post rotating motor operated Isolators with earth switch complete with all accessories and solid core post insulator with Terminal connectors.
33kV, 400-200/1-1A, 2-core Single phase CT complete with all fittings and accessories including with Terminal connectors (0.2s-5p20 class, live tank type)
CT Junction (Marshalling) Box
33kV Lightning Arrester complete with all fittings and accessories including Terminal connectors and surge counter.
33kV, 8kN post insulator with all fittings including Terminal connectors
F&I of Mounting Structures with mounting & foundation bolts as per drawing and technical specification.
33kV Motorised isolators without Earth Switch
33kV PI (BPI)
33kV Motorised isolators with Earth Switch
Mounting Structure for PI of 33 kV AI tube bus (HBPI)
F&I of Indoor floor mounted 33 kV Feeder control and relay panel (Simplex Type) with BCU, ethernet switch and all accessories suitable for SAS integration to existing SAS of iGrid make.
F&I of 3ph 4 wire Energy Meter (0.2S class, SAMAST Compliant ABT Meter)
F&I of Lattice type structural steel (for Column & Beam type) as per drawing
Column type "C5"
Beam type "B5"
F&I of Terminal connectors, IPS AL Tube, conductor etc. of 33 kV Side.
3 inch IPS AL tube for 33 kV Bus as per GTP & Drawing
ACSR Panther Conductor
Terminal connector for Bus PI suitable for 3 inch IPS AL Tube
Tee connector suitable for interconnection of single ACSR Panther conductor to AI Tube
Terminal connector for 33 kV PI suitable for single ACSR Panther conductor
End caps and couplers/bends for 3 inch IPS AL Tube
Tee Clamp (Panther to Panther)
F&I of Earthmat Extension and grounding of equipments
Main earth mat (65x12 mm GI flat)
50x6 mm GI flat Earthing conductor for earthing of indoor L.T & control panels, Junction box, Marshalling boxes, cable trenches etc.
Earth electrode, 50mm dia, 3m long GI perforated pipe
GI steel wires (37/3.5mm)
F&I of PVC Armoured Control Cable (Copper)
19CX 1.5 sqmm
12CX 1.5 sqmm
7CX 1.5 sqmm
4CX2.5 sqmm
2CX2.5 sqmm
F&I of Armoured Power Cable (Aluminium)
4CX4 sqmm
F&I of 60W LED lights for switchyard Illumination, including fitting and fixing
F&I of 415 V AC Marshalling Kiosk including construction of foundation, installation & cable termination. a) 2nos. 63A, 4P (Incomer) b) 3nos. 25A, 4P (Outgoing) c) 3nos. 16A, 4P (Outgoing)
F&I of Mandatory Spares
33 kV , 25 kA, 1250 A Isolators Contacts (1 Male, 1 Female Contact= 1 Set)
Master Trip relay
Bay control unit
O/C & E/F relay
Tripping coil for 33kV VCB
Closing coil for 33kV VCB
Tee connector suitable for interconnection of single ACSR Panther conductor to AI Tube
Complete one no. of VCB pole (Spare) compatible to fitting in any phase of the VCB
F&I of GI Cable Tray
Perforated type 600 mm wide
Perforated type 300 mm wide
F&I of Earthing Stick (Discharge Rod) upto 132kV Level (Standard Length 15 meter) including installation and demo at site.
F&I of Portable Led Light Tower as per Technical Specification including installation and demo at site.
F&I of Fire Fighting Equipment
22.5 kg FE CO2 type trolley mounted
DCP 5 kg capacity, wall mounted
Fire buckets (12 Nos with stand in one set)
Description of Work / Item(s)
Amount
Erection of equipment mounting structure as per drawing & specification as per supervision of site engineer
33kV Vacumm Circuit Breaker
33kV Isolator
33 kV Post Insulator
Lattice Structure Column C5
Lattice Structure Beam B5
Mounting structure for PI of 33 kV Al Tube Bus
Erection, testing & commissioning of Equipment including laying & terminating of LT power and control cables, connection of terminal clamp connectors as required and equipment earthing.
33kV Vacumm Circuit Breaker
33kV Isolator with Earth Switch
33kV Isolator without Earth Switch
33kV Post Insulator
Installation of earthing system as per instruction of site incharge
Installation M.S. rod earth electrode (driven) with test link including making necessary connections and construction of CI covered earthpits
Construction of extended Earth mat using 65x12 mm GI Flat and connection to riser icluding painting of welding joints with bitumen paint and connecting to main earthmat as directed by site incharge
Erection of 50x6 mm GI flat
Erection of GI steel wires (37/3.5mm)
Installation, testing and commissioning of 33kV Feeder Control & Relay panel
Installation of C&R panel in control room including testing and commissioning including cable layout and termination as per directives of site incharge.
Integration of supplied C&R panel with existing SAS of iGrid make including testing & commissioning
Erection of Terminal connectors 33 kV Side.
3 inch IPS AL Tube for 33 kV Bus
ACSR Panther Conductor
Terminal connector for Bus PI suitable for 3 inch IPS AL Tube
Terminal connector for 33 kV PI suitable for single ACSR Panther conductor
Tee connector suitable for interconnection of single ACSR Panther conductor to AI Tube
End caps and couplers/bends for 3 inch IPS AL Tube
Tee Clamp (Panther to Panther)
Construction of cable trench and 100mm thickness precast RCC cover slab including supply of all materials and Labour etc. as per drawings & specification.
D-Type
C-Type
Switchyard PCC & Gravelling
Providing 80mm thick PCC base in prop 1:4:8 as per drawing, specification & site incharge instruction including supply of all materials and labour etc,
Providing switchyard gravelling (100mm Thickness), levelling etc. as per directive of site incharge.
Construction of Drain including supply of all foundation materials and Labour etc. as per drawings & specification.
Drain (700WX1000D)
Description of Work / Item(s)
Amount
Construction of Foundations for 33KV Bay extension at 132/33 KV AIIMS GSS
Site Clearence along with Jungle cutting & clearing, removal of debris, structures along with foundation and disposal the unserviceable material outside the campus as directed by site incharge.
Site Development by earth filling, levelling compacting in layers not exceeding 20 cm in depth, breaking clods, watering, rolling each layer with ½ tonne roller, or wooden or steel rammers, and rolling every 3rd and top-most layer with power roller of minimum 8 tonnes and dressing up etc. as per site requirement.
Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material as per direction of Engineer - in- charge.
For 3nos. CT Pile Foundation (Existing pile foundation drawing is shared with the tender document for referance)
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas including removal of stone boulders of any size by excavation, getting out, disposal of excavated earth, backfilling and compacting as directed by Engineer-in-charge. (For all kinds of soil)
Providing, driving with by Manual means/DMC/hydraulic piling rigs with power units and installing driven cast-in-situ reinforced cement concrete piles of grade M-25 of specified diameter and length below the pile cap, to carry safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of shoe and the length of pile to be embedded in the pile cap, boring for pile foundation, removal of stone boulders of any size during boring, disposal of boring earth as per instruction of Site Incharge etc. all complete. (Length of pile for payment shall be measured from top of shoe to\ the bottom of pile cap) : 400 mm dia piles
Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material as per direction of Engineer - in- charge. Pile cap demolition
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level as per drawing. For TMT Bar
RCC Work with Shuttering Providing and laying plain/reinforced cement croncrete works using cement, coarse sand & 20mm down graded stone aggregate with cost of necessary form work including dewatering if necessary, and curing for reinforced cement concrete work complete as directed (Reinforcement will be measured and paid separately) (A) In sub - structure up to plinth level N)Without using admixture, plasticiser M25 grade concrete
Plain cement concrete works with coarse aggregate of sizes 13mm to 32mm in foundation bed for footing steps, walls, brick works etc as directed and specified including dewatering if necessary, and curing complete (shuttering where necessary shall be measured and paid separately). (a) In prop 1:3:6 aggregate by volume.
For 1no. CB Pile Foundation (Existing pile foundation drawing is shared with the tender document for referance)
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas including removal of stone boulders any size by excavation, getting out and disposal of excavated earth, backfilling and compacting as directed by Engineer-in-charge. For all kinds of soil
Providing, driving with by Manual means/DMC/hydraulic piling rigs with power units and installing driven cast-in-situ reinforced cement concrete piles of grade M-25 of specified diameter and length below the pile cap, to carry safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of shoe and the length of pile to be embedded in the pile cap etc. all complete. (Length of pile for payment shall be measured from top of shoe to\ the bottom of pile cap) : 400 mm dia piles
Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material as per direction of Engineer - in- charge. Pile cap demolition
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level as per drawing. For TMT Bar
RCC Work with Shuttering Providing and laying plain/reinforced cement croncrete works using cement, coarse sand & 20mm down graded stone aggregate with cost of necessary form work including dewatering if necessary, and curing for reinforced cement concrete work complete as directed (Reinforcement will be measured and paid separately) (A) In sub - structure up to plinth level N)Without using admixture, plasticiser M25 grade concrete
Plain cement concrete works with coarse aggregate of sizes 13mm to 32mm in foundation bed for footing steps, walls, brick works etc as directed and specified including dewatering if necessary, and curing complete (shuttering where necessary shall be measured and paid separately). (a) In prop 1:3:6 aggregate by volume.
For 3nos. LA Pile Foundation (Existing pile foundation drawing is shared with the tender document for referance)
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas including removal of stone boulders any size by excavation, getting out and disposal of excavated earth, backfilling and compacting as directed by Engineer-in-charge. For all kinds of soil
Providing, driving with by Manual means/DMC/hydraulic piling rigs with power units and installing driven cast-in-situ reinforced cement concrete piles of grade M-25 of specified diameter and length below the pile cap, to carry safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of shoe and the length of pile to be embedded in the pile cap etc. all complete. (Length of pile for payment shall be measured from top of shoe to\ the bottom of pile cap) : 400 mm dia piles
Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material as per direction of Engineer - in- charge. Pile cap demolition
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level as per drawing. For TMT Bar
RCC Work with Shuttering Providing and laying plain/reinforced cement croncrete works using cement, coarse sand & 20mm down graded stone aggregate with cost of necessary form work including dewatering if necessary, and curing for reinforced cement concrete work complete as directed (Reinforcement will be measured and paid separately) (A) In sub - structure up to plinth level N)Without using admixture, plasticiser M25 grade concrete
Plain cement concrete works with coarse aggregate of sizes 13mm to 32mm in foundation bed for footing steps, walls, brick works etc as directed and specified including dewatering if necessary, and curing complete (shuttering where necessary shall be measured and paid separately). (a) In prop 1:3:6 aggregate by volume.
For 7nos. PI Pile Foundation (Existing pile foundation drawing is shared with the tender document for referance)
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas including removal of stone boulders any size by excavation, getting out and disposal of excavated earth, backfilling and compacting as directed by Engineer-in-charge. For all kinds of soil
Providing, driving with by Manual means/DMC/hydraulic piling rigs with power units and installing driven cast-in-situ reinforced cement concrete piles of grade M-25 of specified diameter and length below the pile cap, to carry safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of shoe and the length of pile to be embedded in the pile cap etc. all complete. (Length of pile for payment shall be measured from top of shoe to\ the bottom of pile cap) : 400 mm dia piles
Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material as per direction of Engineer - in- charge. Pile cap demolition
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level as per drawing. For TMT Bar
RCC Work with Shuttering Providing and laying plain/reinforced cement croncrete works using cement, coarse sand & 20mm down graded stone aggregate with cost of necessary form work including dewatering if necessary, and curing for reinforced cement concrete work complete as directed (Reinforcement will be measured and paid separately) (A) In sub - structure up to plinth level N)Without using admixture, plasticiser M25 grade concrete
Plain cement concrete works with coarse aggregate of sizes 13mm to 32mm in foundation bed for footing steps, walls, brick works etc as directed and specified including dewatering if necessary, and curing complete (shuttering where necessary shall be measured and paid separately). (a) In prop 1:3:6 aggregate by volume.
For 2nos. Isolator Pile Foundation (Existing pile foundation drawing is shared with the tender document for referance)
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas including removal of stone boulders any size by excavation, getting out and disposal of excavated earth, backfilling and compacting as directed by Engineer-in-charge. For all kinds of soil
Providing, driving with by Manual means/DMC/hydraulic piling rigs with power units and installing driven cast-in-situ reinforced cement concrete piles of grade M-25 of specified diameter and length below the pile cap, to carry safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of shoe and the length of pile to be embedded in the pile cap etc. all complete. (Length of pile for payment shall be measured from top of shoe to\ the bottom of pile cap) : 400 mm dia piles
Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material as per direction of Engineer - in- charge. Pile cap demolition
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level as per drawing. For TMT Bar
RCC Work with Shuttering Providing and laying plain/reinforced cement croncrete works using cement, coarse sand & 20mm down graded stone aggregate with cost of necessary form work including dewatering if necessary, and curing for reinforced cement concrete work complete as directed (Reinforcement will be measured and paid separately) (A) In sub - structure up to plinth level N)Without using admixture, plasticiser M25 grade concrete
Plain cement concrete works with coarse aggregate of sizes 13mm to 32mm in foundation bed for footing steps, walls, brick works etc as directed and specified including dewatering if necessary, and curing complete (shuttering where necessary shall be measured and paid separately). (a) In prop 1:3:6 aggregate by volume.
For 2nos. C5 Tower Pile Foundation (Existing pile foundation drawing is shared with the tender document for referance)
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas including removal of stone boulders any size by excavation, getting out and disposal of excavated earth, backfilling and compacting as directed by Engineer-in-charge. For all kinds of soil
Providing, driving with by Manual means/DMC/hydraulic piling rigs with power units and installing driven cast-in-situ reinforced cement concrete piles of grade M-25 of specified diameter and length below the pile cap, to carry safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of shoe and the length of pile to be embedded in the pile cap etc. all complete. (Length of pile for payment shall be measured from top of shoe to\ the bottom of pile cap) : 400 mm dia piles
Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material as per direction of Engineer - in- charge. Pile cap demolition
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level as per drawing. For TMT Bar
RCC Work with Shuttering Providing and laying plain/reinforced cement croncrete works using cement, coarse sand & 20mm down graded stone aggregate with cost of necessary form work including dewatering if necessary, and curing for reinforced cement concrete work complete as directed (Reinforcement will be measured and paid separately) (A) In sub - structure up to plinth level N)Without using admixture, plasticiser M25 grade concrete
Plain cement concrete works with coarse aggregate of sizes 13mm to 32mm in foundation bed for footing steps, walls, brick works etc as directed and specified including dewatering if necessary, and curing complete (shuttering where necessary shall be measured and paid separately). (a) In prop 1:3:6 aggregate by volume.
ARADHANA AGENCY (BID ID -250753)
P & S CONSTRUCTION (BID ID -249963)
ARADHANA AGENCY (BID ID -250753)
Everlite Engineering Industries (BID ID -249707)
P & S CONSTRUCTION (BID ID -249963)
ARADHANA AGENCY (BID ID -250753)
Everlite Engineering Industries (BID ID -249707)
ARADHANA AGENCY (BID ID -250753)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .