| Sl No | Description | Qty | Unit | R.S.ASSOCIATE L3 | alfa engineering L1 | SARASWAT ELECTRICALS L2 |
|---|---|---|---|---|---|---|
| 1.00 | Providing of Numerical Differential Relay Protection relay of following make ABB/SIEMENS/SCHNEIDER MAKE SUITABLE FOR 40 MVA 132/33 KV Power Transformer with following features. (i) CT Secondary 1A, PT Secondary-110 VAC, 50Hz (ii) Inbuilt event logger, disturbance recorder for alteast 200 disturbance (iii) Auxiliary supply 110 VDC (iv) Differential 2 Winding Protection (v) Over fluxing, Over/Under Voltage, Neutral voltage, Displacement, Over/Under Frequency, Under Current, open circuit- VE phase sequence over current, Thermal Over load, Instt. Phase fault O/C, Instt. E/F Time delayed phase fault O/C & time delayed E/F (iv)Communication interface RS-485 facility. The Work of Retrofitting of new differential relay by making proper cutting the MS Sheet of relay's size and mounting it with proper drilling and tightening with nut bolt and painting the used MS Sheet with same colour as panel of 40 MVA T/F-II, required rewiring in C&R Panel with proper dressing, ferruling and termination and carrying out all its associated work which are essential to complete the job in all respect. Work of commissioning, configuration and testing of new installed differential numerical relay. Testing must necessarily be carried out with the help of electronic secondary relay testing kit. All the required test related to above differential relay should be done exactly in accordance with the electrical norms and standards as per the guidance of T&C wing. This Job also includes Work of dismantling of old electromechanical type relay and its associated wires etc. from concerned C&R panel of 40 MVA T/F-II at 132 KV S/S Jahanabad. Contractor will arrange all labour, and T&P and testing kit along with all other charges at his own cost. | 1 | Job | 2,50,000 ₹2,50,000 | 1,65,000 ₹1,65,000 Lowest | 1,71,500 ₹1,71,500 |
| 2.00 | Supply of numeric based directional over current & E/F (IDMT) RELAY (50/51N) also time delayed O/C, E/F feature of ABB/SIEMENS/SCHNEIDER make for 132 KV/33KV 40MVA T/F-II C&R Panel at 132 KV S/S Jahanabad. Transformer C&R panel relay required (i) at least 6BI, 7BO with one alarm output, (ii) having auxiliary current 1A suitable for 110V auxiliary voltage, (iii) communication interface RS-485/USB (iv) Having inst. E/F & O/C and also time delay O/C & E/F Features. Retrofitting of new directional over current & E/F (IDMT) relay (50/51N) by making proper cutting the MS Sheet of relay's size and mounting it with proper drilling and tightening with nut bolt and painting the used MS Sheet with same colour as panel of 40 MVA T/F-II, required rewiring in C&R Panel with proper dressing, ferruling and termination and carrying out all its associated work which are essential to complete the job in all respect. Work of commissioning, configuration and testing of new installed differential numerical relay. Testing must necessarily be carried out with the help of electronic secondary relay testing kit. All the required test related to above differential relay should be done exactly in accordance with the electrical norms and standards as per the guidance of T&C wing. This Job also includes Work of dismantling of old electromechanical type relay and its associated wires etc. from concerned C&R panel of 40 MVA T/F-II at 132 KV S/S Jahanabad. Contractor will arrange all labour, and T&P and testing kit along with all other charges at his own cost. | 2 | Job | 42,000 ₹84,000 Lowest | 56,000 ₹1,12,000 | 53,000 ₹1,06,000 |
Tender Value
₹3.3 L
EMD Value
₹4,000
Closing Date
8 Aug 2025, 5:00 pmClosed
Suprintending Engineer
Superintending Engineer Electricity Transmission Circle I 57 George Town Prayagraj 211002 PH- 0532-2256499/9415311005
Dismantling of old electromechanical type relay of 40 MVA-II C R Panel and its retrofitting of Numerical type relay at 132 KV Substation Jahanabad, under Electy. Trans. Division-Fatehpur.
2025_UPTCL_1061632_1
11-ETC-I(A)/ 2025-2026
Open Tender
Electrical Works
Item Rate
60 days
Fatehpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
SE ETC-I PRAYAGRAJ
₹4,000
14 Aug 2026
31 Jul 2025
9 Aug 2025
31 Jul 2025
8 Aug 2025
31 Jul 2025
Amount
Providing of Numerical Differential Relay Protection relay of following make ABB/SIEMENS/SCHNEIDER MAKE SUITABLE FOR 40 MVA 132/33 KV Power Transformer with following features. (i) CT Secondary 1A, PT Secondary-110 VAC, 50Hz (ii) Inbuilt event logger, disturbance recorder for alteast 200 disturbance (iii) Auxiliary supply 110 VDC (iv) Differential 2 Winding Protection (v) Over fluxing, Over/Under Voltage, Neutral voltage, Displacement, Over/Under Frequency, Under Current, open circuit- VE phase sequence over current, Thermal Over load, Instt. Phase fault O/C, Instt. E/F Time delayed phase fault O/C & time delayed E/F (iv)Communication interface RS-485 facility. The Work of Retrofitting of new differential relay by making proper cutting the MS Sheet of relay's size and mounting it with proper drilling and tightening with nut bolt and painting the used MS Sheet with same colour as panel of 40 MVA T/F-II, required rewiring in C&R Panel with proper dressing, ferruling and termination and carrying out all its associated work which are essential to complete the job in all respect. Work of commissioning, configuration and testing of new installed differential numerical relay. Testing must necessarily be carried out with the help of electronic secondary relay testing kit. All the required test related to above differential relay should be done exactly in accordance with the electrical norms and standards as per the guidance of T&C wing. This Job also includes Work of dismantling of old electromechanical type relay and its associated wires etc. from concerned C&R panel of 40 MVA T/F-II at 132 KV S/S Jahanabad. Contractor will arrange all labour, and T&P and testing kit along with all other charges at his own cost.
Supply of numeric based directional over current & E/F (IDMT) RELAY (50/51N) also time delayed O/C, E/F feature of ABB/SIEMENS/SCHNEIDER make for 132 KV/33KV 40MVA T/F-II C&R Panel at 132 KV S/S Jahanabad. Transformer C&R panel relay required (i) at least 6BI, 7BO with one alarm output, (ii) having auxiliary current 1A suitable for 110V auxiliary voltage, (iii) communication interface RS-485/USB (iv) Having inst. E/F & O/C and also time delay O/C & E/F Features. Retrofitting of new directional over current & E/F (IDMT) relay (50/51N) by making proper cutting the MS Sheet of relay's size and mounting it with proper drilling and tightening with nut bolt and painting the used MS Sheet with same colour as panel of 40 MVA T/F-II, required rewiring in C&R Panel with proper dressing, ferruling and termination and carrying out all its associated work which are essential to complete the job in all respect. Work of commissioning, configuration and testing of new installed differential numerical relay. Testing must necessarily be carried out with the help of electronic secondary relay testing kit. All the required test related to above differential relay should be done exactly in accordance with the electrical norms and standards as per the guidance of T&C wing. This Job also includes Work of dismantling of old electromechanical type relay and its associated wires etc. from concerned C&R panel of 40 MVA T/F-II at 132 KV S/S Jahanabad. Contractor will arrange all labour, and T&P and testing kit along with all other charges at his own cost.
SARASWAT ELECTRICALS (BID ID -5411184)
R.S.ASSOCIATE (BID ID -5412051)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].