REPAIR / MAINT OF 33 KV POWER TRANSFORMERS, SWITCHGEAR AND SOLAR POWER PLANT AND CONNECTED ITEMS UNDER GE (A) SURATGARH
2024_MES_690714_3
CA No CWE BKN-Token No 87/2024-2025
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (A) Suratgarh
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE (A) Suratgarh
₹25,040
Yes
15 May 2025
6 Mar 2025
3 Apr 2025
6 Mar 2025
27 Mar 2025
13 Mar 2025
Amount
Dismantling the Potential Transformer (PT) 33 KV Oil Cooled from installed position on steel structure after disconnecting electric supply from both sides for necessary repairs like replacement of washers, replacement of cork sheet, refilling of oil, etc after checking and make fully functional the Potential Transformer (PT) and installing in its original position and making all electric connections and testing complete all as specified and as directed. Notes : (i) Labour component required for the replacement of unserviceable parts shall be deemed to be included in the unit rate quoted against this item. (ii) Transformer oil shall be measured & paid separately under relevant item. (iii) T&P and minor parts will be arranged by the contractor and the cost thereof shall be deemed to be included in the unit rate quoted against this item.
Dismantling the Current Transformer (CT) 33 KV Oil Cooled from installed position on steel structure after disconnecting electric supply from both sides for necessary repairs like replacement of washers, replacement of cork sheet, refilling of oil, etc after checking and make fully functional the Current Transformer (CT) and installing in its original position and making all electric connections and testing complete all as specified and as directed. Notes : (i) Labour component required for the replacement of unserviceable parts shall be deemed to be included in the unit rate quoted against this item. (ii) Transformer oil shall be measured & paid separately under relevant item. (iii) T&P and minor parts will be arranged by the contractor and the cost thereof shall be deemed to be included in the unit rate quoted against this item.
M&L for taking down carefully existing serviceable switch air break, gang operated outdoor, any type of capacity 33 KV, servicing to the operating mechanism, greasing etc of all joints for smooth operation, with & including replacement of burnt male/female contact where required, re-fixing the switch air break, gang operated outdoor, testing, complete all as specified and as directed.
S&F in replacement 12/24 Volts 10 Amps heavy duty automatic float cum booster trickle battery charger, control wiring and stand operating on 230 volt single phase 50 Hz supply by replacing unserviceable charger complete all as specified and directed.
Supply, installation, testing for single phase, outdoor type, hermetic sealed, Voltage Transformer (PT) 36 KV grade with following ratio/ protections :- (a) HSV :- 36 KV (b) IL:- 36 KV/70 KV/170 KVP (c) Primary Voltage (V) :- 33000/3 (d) Secondary Voltage (V) :- 110/3 (e) Output (VA) :- 200 (f) Accuracy Class :- 1.0 (g) Frequency :- 50 Hz (h) Insulation Class :- A, complete all as specified and directed by Engineer-in-Charge.
Supply, installation, testing for single phase, outdoor type, hermetic sealed, Current Transformer 33 KV grade with following ratio/ protections :- (a) Ratio :- 100/1-1A (b) HSV :- 36 KV (c) IL:- 36 KV/70 KV/170 KVP (d) Core1 :- 30 VA, Class1 (e) Core2 :- 30 VA, Class 5P10 (f) STC :- 13.1 KA/1 Sec. (g) Frequency :- 50 Hz (h) Insulation Class :- A, Complete all as specified and directed by Engineer-in-Charge.
S&F in replacement of Oil Temperature Indicator (OTI) 0-150 degree Celsius suitable for power/ distribution transformer complete all as specified and as directed.
S&F in replacement of Winding Temperature Indicator (WTI) 0-150 degree Celsius suitable for power/distribution transformer complete all as specified and as directed.
S&F in replacement of Preset Electric timer switch (Selec 800XA) operated at 12 Volts to 240 Volts, AC for 33 KV VCB to operated spring charging motor complete all as specified and directed.
S&F in replacement valve regulated Lead Acid Battery bank 24 Volts, 200 AH (2 Volts, 200 AH - 12 Nos) for proper functioning of HT breakers including control wiring and stand complete all as specified and as directed.
S&F in replacement of PG Clamp/ T-Connector complete all as specified & as directed.
S&F in repair spring charging motor suitable for existing 33 KV VCB complete all as specified and as directed. Make :- Alstrom / CG / ABB / Areva
S&F in repair DC power pack 24 Volt/ 110 Volt 22 AH supply built with battery and auto battery charger complete all as specified and as directed.
Supply and fixing in repair PVC control copper cable multi strand of size 4.00 sqmm 8 core complete all as specified and directed.
Supply only SF-6 Gas suitable for 33 KV VCB complete all as specified & as directed.
S&F in repair master relay suitable for existing 33 KV VCB complete all as specified and as directed.
Supply and fixing in repair ELITE 500 multi function meter, 35-500 VAC (L-L), Ib 1 to 5 Amps, Imax 6 Amps, Class 0.5s, TFT, Aux 85-300V AC/ 48-300V DC, MODBUS on RS, SW configuration-1, 96x96 complete all as specified & as directed. Make : Secure/L&T/AVV other equivalent make as approved by the GE.
M&L for Earthing complete with galvanised steel earth plate electrode of size 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than 2.25 m below normal ground level) with top edge of the earth plate at a depth not less than 1.5 m below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to & including galvanized iron strip 25x4mm as earth lead, including nuts, bolts, check nuts & washers of galvanized iron or steel and riveted/welded to earth plate at one end and other end of strip connected to test point with two Nos nuts bolts or welding with steel structure, GI earth strip encased in and including 40mm bore GI light grade pipe with all fittings from upper edges of earth plate upto 7.5 metre above ground level fixed with and including 25x3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from earth pit to top of electrode and including funnel, wire mesh, copper lugs etc complete with earth pit in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate and 40mm thick pre-cast RCC (1:2:4 type B1) cover with 40x40x3mm MS angle iron fram complete all as specified and shown in electrical plate No 3 of SSR Part-I including necessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance not exc 50m complete all as specified and as directed including dismantling & taking out old existing unserviceable earthing. Note : PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode and pipe for watering shall be provided in slanting manner.
Material and Labour for calibration, setting, servicing of repair/replacement of burnt/ unserviceable wiring duly lugged of existing 33 KV VCB/RMU relay of any make including setting of over current, earth fault, auxillary, master relay etc complete all as specified and as directed.
S&F in repair CGI 14N (electronic relay) suitable for 33 KV VCB complete all as specified and as directed.
S&F in repair CGV 24N (Over Voltage and Under Voltage) relay electronic type suitable for 33 KV CR Panel complete all as specified and as directed. Make : Alstrom/ CG/ ABB/ Areva
S&F in repair closing coil or tripping coil for 33 KV VCB (24 Volts/110 Volts DC) complete all as specified and as directed. Make :- Alstrom / CG / ABB / Areva
S&F in repair TNC switch suitable for 33 KV VCB complete all as specified and as directed. Make :- Alstrom / CG / ABB / Areva
Dismantling the power transformer 33 KV/11 KV oil cooled copper wound of capacity 1600 KVA to 3150 KVA from installed position on four pole/two pole/platform, after disconnecting electric supply from HV and LV sides to carry out necessary repairs as on required basis on ground, providing all insulating material like sleeves, tapes, kerb tapes, cork sheet and any lead broken both side, etc reassembling, after checking and make functional of WTI & OTI including replacement of unserviceable item (if required) as directed and installing in its original position and making all electric connections with thimbles/PG clamps, commissioning including refilling of transformer oil after dehydration with required dielectric strength (min 50 KV) and testing complete all as specified and as directed.
Supply and fixing in replacement of HT bushing assembly 33 KV including brass nuts and bolts but inclusive of insulation washer etc with accessories for transformer of capacity 1.6/3.15 MVA complete all as specified and as directed.
Supply and fixing in replacement of Breather assembly complete including silica gel for transformer of capacity upto 1600 KVA to 3150 KVA complete all as specified and as directed.
Supply and fixing in replacement of Silica Gel blue in crystal complete all as specified and as directed.
Material and labour preparation of new steel surfaces of any description over 10 cm width or girth not otherwise described and applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified.
M&L for preparation of external surfaces of distribution transformer of capacity 1600 KVA to 3150 KVA including cleaning and removing oil spots from the body and painting with one coat of synthetic enamel paint (grey first quality of approved by GE with gun sprayer including marking of SM/MES No etc. on transformer with synthetic enamel paint (white) complete all as specified and as directed.
Supply only Transformer oil confirming to IS:335 (1993) having dielectric strength not less than 60 KVA complete all as specified and as directed. Note : Transformer oil shall be supplied in sealed barrels with test certificate. Cost of barrel shall be deemed to be included in the unit rate quoted by the contractor and empty barrel will be the property of the Department and same shall be deposited to the AGE E/M Store Yard. Nothing extra shall be paid on this account.
Supply and Topup Transformer oil confirming to IS:335 (1993) having dielectric strength not less than 60 KVA complete all as specified and as directed.
M&L for filtration / dehydration of old/existing transformer oil including topping up of transformer oil as required in the transformers of different capacity, installed at various locations with suitable capacity of filtration machine to achieve dielectric strength minimum 60 KV complete all as specified and as directed. Notes: (i) All necessary T&P / testing equipment shall be provided by the contractor at his own cost. No extra payment shall be made to the contractor. (ii) New Transformer Oil required for topping up shall be paid for separately under relevant item of this Schedule as ‘Supply only’.
Supply only Cork sheet gasket 5 mm thick superior quality of size 1m x 1m on top cover plate of the transformer capacity 1600 KVA to 3150 KVA complete all as specified and directed.
Supply , laying, jointing, commissioning and testing in replacement of PVC insulated screened PVC bedded, heavy duty underground electric DC Solar cable with stranded copper conductor 1500 volts grade of cross sectional area 6 sqmm single core multistranded conductor conforming to IS-7098 (Part-I-1988) laid in trenches, along with poles through pipes etc complete all as specified and directed. Make : Havells/ Gloster / Finolex / Polycab
Material and labour for cutting of vegetation surrounding transformer, two poles structures, Four Pole structures at various sub stations/ E&M installation and remove to a distance, not exc 250 mtr complete all as per direction of Engineer-in-Charge.
M&L for 40mm graded crushed stone aggregate, deposited, spread around the outdoor electrical installations, complete all as specified and as directed. Note : for all BoQ items, all old unserviceable valuable material retrieved from the above is deposited to AGE E/M Yard.
M/s Rohit Construction Co. (BID ID -3267457)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .