| 1 | 1₹3.7 CrAccepted-AOC 143 RAM GALI HAJINDER NAGAR II KANPUR UP PIN 208007 | KANPUR NAGAR | UTTAR PRADESH | 208007 | ₹3.7 Cr | 1 | Accepted-AOC Being lowest and overall reasonable bid. |
| 2 | 2₹3.8 Cr+₹10.6 L (2.88%)Rejected-Finance 1630 SECTOR 7C CHANDIGARH 160019 | CHANDIGARH | CHANDIGARH | CHANDIGARH | 160019 | ₹3.8 Cr+₹10.6 L (2.88%) | 2 | Rejected-Finance Being other than lowest bidder. |
| 3 | 3₹4.1 Cr+₹43.2 L (11.7%)Rejected-Finance 5037 5038 URBAN ESTATE PH 1 PATIALA 147002 PUNJAB | PATIALA | PATIALA | PUNJAB | 147002 | ₹4.1 Cr+₹43.2 L (11.7%) | 3 | Rejected-Finance Being other than lowest bidder. |
| 4 | Rejected-Technical | - | - | Rejected-Technical Not enlisted in category (b)(ii). |
Tender Value
Refer Docs
EMD Value
₹4.5 L
Closing Date
24 Dec 2021, 6:00 pmClosed
CE (AF) NAGPUR
O/O HQ CHIEF ENGINEER (AF) VAYUSENA NAGPUR 440007
PROVISION OF WORK SERVICES FOR MAFI POWER SUB STATION AND ALLIED WORKS AT AF STN CHAKERI KANPUR
2021_MES_476034_1
AF_CHK_801183
Open Tender
Electrical and Maintenance Works
Lump-sum
540 days
GE(AF) E/M KANPUR, GE(AF) B/R KANPUR
For MES Enlisted Contractors- Class A Category b (i) and b(ii) For other Contractor meeting enlistment Criteria of MES for Class A Category b (i) and b (ii)
8 documents required · 8 mandatory
₹2,000
Yes
GE(AF) E/M CHAKERI
₹4.5 L
Yes
4 Feb 2022
9 Nov 2021
30 Dec 2021
9 Nov 2021
24 Dec 2021
6 Dec 2021
9 Nov 2021 - 23 Nov 2021
Amount
SCH 'A' PART XII (MISC B/R & E/M ITEMS) Note:-(i) Excavation and earthwork to the extent required for execution of relevant item under this schedule unless otherwise specified shall be measured and paid under relevant items of Schedule 'A' Part-II.
INTERNAL ELECTRIFICATION
Supply and fixing surface & wall mounted decorative ultra slim linear LED lighting fixture with co extruded polycarbonate body environmental friendly energy efficient 10 W 2 '(feet) with electronic driver, suitable for 240 volts AC input, and prewired with copper wire to be connected with the ceiling rose complete hanging/fixing arrangement with all accessories complete all as specified and as directed.
Supply and fixing modern suspended type LED fitting 20 W 4 '(feet) long with extruded aluminium housing and robust construction with electronic driver, suitable for 240 volts AC input, and prewired with copper wire to be connected with the ceiling rose complete hanging/fixing arrangement with all accessories complete all as specified and as directed.
Supply and fixing of building security light LED aesthetically designed IP 65 protection complied to IEC 60598 and IS 10322 high power LED cool white, with integral driver, 35 Watt power consumption pressure die cast aluminium body including reduced glare impact resistant polycarbonate cover prewired complete with light bracket made out of GI pipe light grade 32 mm OD, 1.2 mtrs long bent to shape fixed with two set of clamps nut bolts washer etc. complete all as specified and as directed.
Supply and fixing ceiling fan 1200 mm sweep air delivery 210 CFM single phase 230 V 50 Hz , white in colour copper wound including condensor, connector, canopy, down rod, clamps, etc. complete with all acessories internally pre wired and including connecting up with suitable size of flexible 3 core stranded copper conductor cable complete as per BEE standard ISI marked complete all as specified and as directed.
Material and labour for point wiring (concealed) for socket outlet 3 pin 15 Amps on independent board in and including rigid non metallic PVC medium grade conduit 20 mm dia size including cutting chases for conduits, sinking for boxes for concealed conduit wing with 2.5 sqmm PVC insulated unsheathed FRLS multi stranded copper conductor cable with flush type metal boxes modular type suitable for fixing modular switches, sockets,fan regulator etc. with white colour cover plate with brass screw and including PVC insulated unsheated multi stranded copper conductor cable 2.5 sqmm as an earth wire connected to common earth and dolly as per IS specification complete all as specified and as directed ( Rates shall be deemed to be including mounting concealed boxes and modular cover plates of suitable module)
Material & Labour for sub main wiring (concealed) complete with two single core 4 Sqmm FRLS PVC insulated unsheathed stranded copper conductor cable drawn through in and including 25 mm dia rigid non-metallic PVC conduit and conduit accessories including one single run of 4 Sqmm FRLS PVC insulated unsheated stranded copper earth cable connected to common earth dolly complete and including cutting chasing in walls for concealed wiring using machine cutting and making good the disturbed surface complete all as specified and as directed. Note : 2 runs of 4 Sq.mm & 1 run of 4 Sq.mm and one run of 25 mm dia PVC Conduit will be measured as one unit
Material & Labour for sub main wiring (concealed) complete with four single core 4 Sqmm FRLS PVC insulated unsheathed stranded copper conductor cable drawn through in and including 25 mm dia rigid non-metallic PVC conduit and conduit accessories including two single run of 4 Sqmm FRLS PVC insulated unsheated stranded copper earth cable connected to common earth dolly complete and including cutting chasing in walls for concealed wiring using machine cutting and making good the disturbed surface complete all as specified and as directed. Note: 4 runs of 4 Sq.mm & 2 run of 4 Sq.mm and one run of 25 mm dia PVC Conduit will be measured as one unit
AIR CONDITIONING
Supply installation,commissioning and testing of copper wound automatic voltage stabilizer of capacity 5 KVA suitable for AC of upto 2 TR for automatic operation single phase naturally air cooled indoor type and designed for input variation between 170 volt to 270 volt with accuracy +/- 2.5% complete all as specified and directed
EXTERNAL WATER SUPPLY
Cutting of PCC/hard standing/WBM road not exceeding 30 cm in depth for passing of GI/CI pipeline all as specified and directed
EXTERNAL ELECTRIFICATION
Supply installation, commissioning and testing of11 KV VCB panel indoor type, made out of 2.0 mm thick CRCA sheet, dust and vermin proof , locking arrangement duly powder coated totally enclosed free standing floor mounting type, compartment based with truck mounted vacuum circuit breaker spring operated electrically and manually charged operating mechanism suitable for horizontal isolation, horizontal draw out type VCBs with copper bus bars, back entry type complete VCB panel confirming to IS and IP 4X class of protection comprising necessary bus-bars connections and following protective and control devices as specified below. The VCBs shall be tested for High voltage test, Primary injection test and Secondary injection test individually at site after erection before commissioning and the rate for the same is deemed to be to included in the quoted rate.
(III) Bus coupler Vacuum Circuit Breaker 630A, HT, 11KV three phase, AC supply, 350MVA ,18.3KA breaking capacity, short circuit ratings 1 second, complete:- without any protection and metering-02No Note : Both the buscoupler should be electrical and mechanical interlocked so as to avoid turning on of both VCBs simultaneously VCB PANEL SHOULD COMPRISE OF THE FOLLOWING FEATURES :- (a) Push buttons for accepting faults and reset. (b) LED indicating lamps for (duly control wired up (i) Auto trip (ii) Spring charge (iii) Fault Alarm (iv) Trip Circuit Healthy (v) Trip circuit Unhealthy (vi) Breaker ON (vii) Breaker OFF c) RS 485 communication d) Motor operated spring stored energy trip for closing and opening of the breaker in working on 230V AC e) Manual charging / operating arrangement. f) Fuses for metering and protection system g) One No. internal bus earthing with flat GI strip of size 50x 6mm h) one No. of space heater with thermostat i) One No. of inside lamp with switch ( 40W 230V) j) One No. of plug point with switch( 5A, 230V) k) Copper bus bar common for out going feeders with PVC sleeves (l)Shunt trip coil with 30 V DC (m) Closing coil with 110V/30V DC
n) Complete control panel wiring with copper wire of size not less than 2.5 sqmm o) Civil design for foundation should be done all as per instructions manual of manufacturer. (p) Extension of bus bar from existing panel to connect the stand along panel including necessary modification. Note:- (a) The VCB shall be tested for High Voltage test, Primary Injection test & Secondary Injection test individualy at site after erection before commissioning and the same is deemed to be to included in the quoted rate. (b) VCB shall be drawout type and their should be provision of extendable. (c) Whole scheme shall be as per schematic line diagram arranged by the contractor from manufracture and shall be approved by the GE before executed. (d) Unit rate shall included the cost of danger notice baord, 11KV grade 25 cm CRCA ISI Marked, 11 KV grade, chequred type rubber mat 1 meter width and length equivalent to the width of the panel, Two sets of operating and maintenence manual, spares list, periodical mainenance chart / manual, lay out of panel / wiring shall be included in the rate quoted, (e) Cost of any civil work required to install the panels shall be deemed to be included in the rate of panel
11 KV VCB panel Stand alone indoor type, made out of 2.0 mm thick CRCA sheet, dust and vermin proof , locking arrangement duly powder coated totally enclosed free standing floor mounting type, compartment based with truck mounted vacuum circuit breaker spring operated electrically and manually charged operating mechanism suitable for horizontal isolation, horizontal draw out type VCBs with copper bus bars, back entry type complete VCB panel confirming to IS and IP 4X class of protection comprising necessary bus-bars connections and following protective and control devices as specified below. The VCBs shall be tested for High voltage test, Primary injection test and Secondary injection test individually at site after erection before commissioning and the rate for the same is deemed to be to included in the quoted rate.
g) Trip circuit supervision relayh) Master trip relay .VCB PANEL SHOULD COMPRISE OF THE FOLLOWING FEATURES :- (a) Push buttons for accepting faults and reset. (b) LED indicating lamps for (duly control wired up) (i) Auto strip (ii) Spring charge (iii) Fault Alarm (iv) Trip Circuit Healthy (v) Trip circuit Unhealthy (vi) Breaker ON (vii) Breaker OFF c) RS 485 communication d) Motor operated spring stored energy trip for closing and opening of the breaker. e) Manual charging / operating arrangement. f) Fuses for metering and protection system g) One No. internal bus earthing with flat GI strip of size 50x 6mm h) one No. of space heater with thermostat i) One No. of inside lamp with switch ( 40W 230V) j) One No. of plug point with switch( 5A, 230V) (k) shunt trip coil with 30 V DC (l) closing coil with 110V/30V DC m) Copper bus bar common for out going feeders with PVC sleeves n) Complete control panel wiring with copper wire of size not less than 2.5 sqmm o) Civil design for foundation should be done all as per instructions manual of manufacturer. p) Extension of bus bar from existing panel to connect the stand alone panel including necessary modification.
Note:- (a) The VCB shall be tested for High Voltage test, Primary Injection test & Secondary Injection test individualy at site after erection before commissioning and the same is deemed to be to included in the quoted rate. (b) VCB shall be drawout type and their should be provision of extendable. (c) Whole scheme shall be as per schematic line diagram arranged by the contractor from manufracture and shall be approved by the GE before executed. (d) Unit rate shall included the cost of danger notice baord, 11KV grade 25 cm CRCA ISI Marked, 11 KV grade, chequred type rubber mat 1 meter width and length equvalent to the width of the panel, Two sets of operating and maintenence manual, spares list, periodical mainenance chart / manual, lay out of panel / wiring shall be included in the rate quoted, (e) Cost of any civil work required to install the panels shall be deemed to be included in the rate of panel
Supply, installation, testing and commissioning of indoor type oil cooled isolation transformer 100 KVA, three phase, metalic body, unbalanced type copper wound with standard fittings and accessories, input voltage of 415 volt +/- 5% output voltage 415 volt+/- 5% , frequency 50Hz, with IP-42 protection , conforming to latest IS and with following description including first fill of transformer oil:- (a) Method of cooling - Oil cooled. (b) Ratio - 1: 1 (c ) Insulation class -Class -E (d) Winding Temperature - Less than 55* C (e) Full load lossess- Less than 5% (f) No load lossess - Less than 0.5% (g) Mounting - On wheel detachable type (h) Potential difference between Earth to Neutral voltage - Less than 01 volt. Note :- (a) In addtion to the above all standard fittings to be provided as per ISI norms. (b) PCC foundation concrete and coping shall be as per OEM recommendation.
Supply, installation, testing and commissioning of indoor type oil cooled isolation transformer 630KVA, three phase, metalic body, unbalanced type copper wound with standard fittings and accessories, input voltage of 415 volt +/- 5% output voltage 415 volt+/- 5% , frequency 50Hz, with IP-42 protection , conforming to latest IS and with following description including first fill of transformer oil:- (a) Method of cooling - Oil cooled. (b) Ratio - 1: 1 (c ) Insulation class -Class -E (d) Winding Temperature - Less than 55* C (e) Full load lossess- Less than 5% (f) No load lossess - Less than 0.5% (g) Mounting - On wheel detachable type (h) Potential difference between Earth to Neutral voltage - Less than 01 volt. Note :- (a) In addtion to the above all standard fittings to be provided as per ISI norms. (b) PCC foundation concrete and coping shall be as per OEM recommendation.
Supply, installation, testing and commissioning of indoor automatic/servo voltage controller three phase, 50Hz (confirming as per BIS 9815 Part 1 :1994 reaffirmed 2009) Naturally oil cooled of 100 KVA , unbalanced type, copper wound, digital display type, Relay free smooth and silent operation with Ist filling of Transformer oil having following specification :-
(i) Input voltage 340-480V or as per ground requirement (ii) Output voltage stabilized at any designed/desired voltage 415 +/- 1% adjustable (iii) No distortion in wave form (iv) Response time not to exceed 10milli seconds (v) Sensitivity (+_ 1%) (vi) Rate of correction 8 volt/second for single phase and 20 volt/second for phase to phase (vii) No load losses less than 0.5% (viii) Full load losses less than 2.5% (ix) Duty cycle continuous 24 x 7, Efficiency more than 95% (x) Type of load 3 Phase, unbalanced type (xi) Digital display voltmeter and amp meter of suitable rating Protections (i) Over load/short circuit protection (ii) High/low voltage cut off (iii) By pass arrangement in case of emergency (iv) Single phase sequence change protection
Supply, installation, testing and commissioning of indoor automatic/servo voltage controller three phase, 50Hz (confirming as per BIS 9815Part 1:1994 reaffirmed 2009) Naturally oil cooled of 630 KVA , unbalanced type, copper wound, digital display type, Relay free smooth and silent operation with Ist filling of Transformer oil having following specification :-
(i) Input voltage 340-480V or as per ground requirement (ii) Output voltage stabilized at any designed/desired voltage 415 +/- 1% adjustable (iii) No distortion in wave form (iv) Response time not to exceed 10milli seconds (v) Sensitivity (+_ 1%) (vi) Rate of correction 8 volt/second for single phase and 20 volt/second for phase to phase (vii) No load losses less than 0.5% (viii) Full load losses less than 2.5% (ix) Duty cycle continuous 24 x 7, Efficiency more than 95% (x) Type of load 3 Phase, unbalanced type (xi) Digital display voltmeter and amp meter of suitable rating Protections (i) Over load/short circuit protection (ii) High/low voltage cut off (iii) By pass arrangement in case of emergency (iv) Single phase sequence change protection
Supply,testing and commissioning indoor L.T.Panel board factory fabricated indoor cubicle type totally enclosed made out of 2.00 mm thick sheet metal enclosure with angle iron frame of suitable size, CPRI approved, IP-42 for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel opening doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber/wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands of suitable size for cable entry and exit complete with necessary internal wiring with stranded copper conductor FRLS PVC insulated cables of adequate size, duly with painted one coat of red oxide primer and two coats of synthetic enamel paint of gray or any other approved colour and bus bar for three phase and neutral of 1800 Amp mounted on epoxy insulator-01 Set including connecting the following.
(i) Incoming ACB 4 pole , 415 Volts 50 KA microprocessor based with thermal magentic relase (Electrically Draw out type ) of capacity 1250 Amps - 02 Nos (Incoming from DG No 1 & from DG No 2) (ii) Incoming ACB 4 pole , 415 Volts,50 kA with inbuilt CTS and array for manual spring charging mechanism, microprocessor based with thermal magentic release ( Electrically Draw out type ) of capacty 1250 Amps - 01 Nos (Incoming from PS1 T fr) (iii) Outgoing ACB 4 pole , 415 Volts 50 kA microprocessor based with thermal magentic release (Electrically Draw out type ) of capacty 1250 Amps - 02 Nos (out going to isolation Transformer & spare for future expansion) (iv) Out going ACB 4 pole , 415 Volts,50 kA with inbuilt CTS and array for manual spring charging mechanism, microprocessor based with thermal magentic release ( Electrically Draw out type ) of capacty 1250 Amps - 01 Nos (use as a bus coupler) (v) Multi functional Meter-1 No. (vi) Timer switch, 20 Amps -1 No (vii) LED Phase indicator lamps(RYB) - 1 set (Note 1. Rate of All electrical and mechanical interlocked system between incoming ACB shall be deemed included in the quoted rate. 2. Schematic diagram/arrangement of LT Panel to be provided by the contractor from manufracture and shall be approved by the GE before executions. 3.PCC foundation concrete and coping shall be as per OEM
Supply, testing and commissioning outdoor weather & dust vermin proof L.T .Panel board factory fabricated indoor cubicle type totally enclosed made out of 2.00 mm thick sheet metal enclosure with angle iron frame of suitable size, CPRI approved, IP-42 for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel opening doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber/wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor FRLS PVC insulated cables of adequate size, duly with painted one coat of red oxide primer and two coats of synthetic enamel paint of gray or any other approved colour and bus bar for 3 phase and neutral of rating 1800Amp mounted on epoxy insulator-01 Set including connecting the following :-
(i) Incoming ACB 4 pole , 415 Volts, 50 KA with in built CTS and array for manual spring charging mechanism, microprocessor based with thermal magnetic release (Electrically Draw out type ) of capacity 1000 Amps - 01 Nos (Incoming from Isolation Transformer) (ii) Outgoing ACB 4 pole , 415 Volts, 50 kA with in built CTS and array for manual spring charging mechanism, microprocessor based with thermal magnetic release (Electrically Draw out type ) of capacity 630 Amps - 01 Nos (Outgoing to CCR) (iii) Outgoing MCCB 4 pole , 415 Volts, 25 kA fixed type with thermal magnetic release of capacity 63 Amps - 01 Nos (Outgoing to ATC) (iv) Outgoing MCCB 4 pole , 415 Volts, 25 kA fixed type with thermal magnetic release of capacity 32 Amps - 02 Nos (Outgoing to TACAN, SATC Loop 1 ) (v) Outgoing MCCB 4 pole , 415 Volts 16 KA fixed type with thermal magnetic release of capacity 25 Amps - 05 Nos (Outgoing to DVOR, GP, GCA, FP-PS1, R/W Hut 27, ) (vi) Outgoing MCCB 4 pole , 415 Volts 16 kA fixed type with thermal magnetic release of capacity 16 Amps - 04 Nos (Outgoing to RVR 1, RVR 2, Base Ops, & Spare ) (vii) Multi functional Meter-1 No. (viii) Timer switch, -1 No (ix) LED Phase indicator lamps(RYB) - 1 set (x) PCC foundation concrete and coping shall be as per OEM recommendation.
Supply testing and commissioning outdoor weather & dust vermin proof L.T .Panel board factory fabricated indoor cubicle type totally enclosed made out of 2.00 mm thick sheet metal enclosure with angle iron frame of suitable size, CPRI approved, IP-42 for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel opening doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber/wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor FRLS PVC insulated cables of adequate size, duly with painted one coat of red oxide primer and two coats of synthetic enamel paint of gray or any other approved colour and bus bar for 3 phase and neutral of rating 1800Amp mounted on epoxy insulator-01 Set including connecting the following :-
(i) Incoming ACB 4 pole , 415 Volts, 50 KA with in built CTS and array for manual spring charging mechanism microprocessor based with thermal magentic release (Electrically Draw out type ) of capacity 1250 Amps - 01 Nos (Incoming from Isolation Transformer) (ii) Outgoing ACB 4 pole , 415 Volts, 50 kA with in built CTS and array for manual spring charging mechanism microprocessor based with thermal magentic release (Electrically Draw out type ) of capacty1000 Amps - 02 Nos (Outgoing to LT Panel) (iii) Multi functional Meter-1 No. (iv) Timer switch, -1 No (v) LED Phase indicator lamps(RYB) - 1 set (vi) PCC foundation concrete and coping shall be as per OEM recommendation.
Supply,testing and commissioning L.T.Panel board factory fabricated indoor cubicle type totally enclosed made out of 2.00 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm , CPRI approved, IP-42 suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel opening doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber/wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor FRLS PVC insulated cables of adequate size, duly with painted one coat of red oxide primer and two coats of synthetic enamel paint of gray or any other approved colour and bus bar for 3 phase & neutral of 400 Amps capacity mounted on epoxy insulator-01 Set including connecting the following :-
(i) Incoming 100Amps 4 pole MCCB, 25 KA -01 (ii) Outgoing 32 Amps, 4 pole MCCB, 16 KA - 01 Nos (outgoing to S.ATC) (iii) Outgoing 25 Amps, 4 pole MCCB, 16 KA - 03 Nos (outgoing to LOC, FP-PS2 & R/W Hut 09) (iv) Outgoing 16 Amp 4 pole MCCB 16 KA - 02 Nos (outgoing to RVR3 & Building supply ) (iv) Multi function Meter-1 No. (v) LED Phase indicator lamps(RYB) - 1 set (vi) PCC foundation concrete and coping shall be as per OEM recommendation.
Supply,testing and commissioning L.T.Panel board factory fabricated indoor cubicle type totally enclosed made out of 2.00 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm , CPRI approved, IP-42 suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, with hinged panel opening doors (covers) on two sides with handles, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber/wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor FRLS PVC insulated cables of adequate size, duly with painted one coat of red oxide primer and two coats of synthetic enamel paint of gray or any other approved colour and bus bar for 3 phase & neutral of 400 Amps capacity mounted on epoxy insulator-01 Set including connecting the following :-
(i) Incoming 200Amps 4 pole MCCB, 25 KA -01 (ii) Outgoing 100 Amps, 4pole MCCB, 25 KA - 04No (Outgoing to LT Panel & spare 2 nos for future expansion) (iii) Multi function Meter-1 No. (iv) LED Phase indicator lamps(RYB) - 1 set (v) PCC foundation concrete and coping shall be as per OEM recommendation.
Supply installation, testing and commissioning of LT Feeder Panel board Indoor type with IP 55 protection , cubical shape, asthetically , designed factory fabricated CPRI approved firm, , outer body made of 2mm thick CRCA sheet and inner body with 2mm thick CRCA sheet with front and rear opening , dust & vermin proof, provision for ventilation incuding bus bar chamber for three phase and neutral , continuous GI Strip earth bus bar , panel confirming to IS 8623 rust proof , power coating with pure polyester powder coated 0.70 microns , as per IS-13871, 1993. Complete panel mounted on base frame made out from MC Channel of suitable size with four legs 4 feet height made out from angle iron of suitable size fixed with PCC 1:3:6 , 40mm graded aggregate type C2 and coping with PCC 1:2:4 type B1 using 20mm graded aggregate and embedded 15cm deep in PCC foundation , grouting properly and panel of suitable size to accomodate the items mentioned below
and having separate compartment/chamber for electric switch gear, bus bar & cable alley etc, including all incoming and outgoing electrical cable connection with proper lugs and glands complete all as specified and comprising with the following : - (a) Copper bus bar for extension of incoming and outgoing termination duly insulated with heat shrinkable colour coding sleeves TPN of capacity 1250 Amp for three phase & 625 Amp for neutral. Bus bar fixed in bus bar chamber on fibre /porcelean insulator of appropriate size, complete with nuts , bolts and washer . (b) ACB draws out type of cap 1250Amps , 50 KA 4 Pole with in built CTS and array for manual spring charging mechanism , IP 54 with manual and electrically operated protection thermal magnetic (DN-1) and Microprocessor release in built thermal memories self diagnostic protection release confirm to EMI/EMC standard mechanically interlock and confirming to IEC - 60947-2 complete - 01 No for incoming. (c) Complete control panel wiring with single core PVC insulated FRLS, multi stranded copper conductor cable of size 1.5 sqmm for volt meter , amp meter , frequency meter and indicating lamp for phase indication of ON/OFF indication complete. (d) Digital multifunctional meter for measuring ampere , voltage, frequency etc - 01 No (e) Phase indicator LED Based lamp in R,Y, B colours - 01 No
Supply and fix MCCB 4 Pole 200 Amp s capacity , 415 volts , 50 Hzs AC with rupturing capacity 36KA complete with sheet metal enclosure appropriate size made out from 2mm thick CRCA sheet including necessary fixing arrangement complete all as specified per directed
M&L for boring of holes under road, pavement, hard standing not less than 2mtr by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed .
Supply and fixing cable route indicator, consisting of 200mm dia 6mm thick cast iron to be painted with brown colour with inscription casting as HT Cable 11000 Volts grade,and fixed with and including hot dipped GI angle of size 40mm x 40mm x 6mm, 0.60m long, GI bolts, nuts embedded in ground in route of cable with and including PCC 1:3:6 type C2 of size 200mm x 200mm x 300mm all as directed
Supply and fixing CO2 type portable Fire extinguishers of 22.5 kgs. Capacity (trolley mounted) complete all as specified and directed
Supply and fixing CO2 type portable Fire extinguishers of 6.5kgs. Capacity (trolley mounted) complete all as specified and directed
Supply and fixing multifunctional meter with class 1 accuracy with following parameters i.e Volt, Amp, Frequency, PF, kW, kVA, kVAR, kWh, kVAh, kVARh,THD etc including fixing arrangement on sheet metal enclosure of suitable size and making necessary electrical connection for monitoring electric supply system complete all as specified and as directed.
Supply , laying and testing PVC insulated , PVC Sheathed cable galvanised steel strip or wire armoured electric control cables (Heavy duty) with stranded copper conductor of size 2.5 sq mm 3 core 1100 volts grade all as specified and as directed
M&L for cutting of PCC/Hard standing/WBM road not exceeding 20 cm in width not exceeding 30 cm in depth for passing of HT Cable and making good of disturbed surface to match with the existing surfaces by using old and new material i.e bitumen/PCC (1:3:6) type C-1 complete all as specified and directed.
EXTERNAL SEWAGE DISPOSAL
Construction of septic tank in any type of soil, foundation in PCC 1:2:4, brick work in CM 1:4, RCC precast manhole cover having 6mm plate embedded all around/fibre reinforced cover with angle iron frame, Vent shaft and sludge chamber complete for 10 users complete all as shown on TD drawing no CE(AF)/NGP/TD-77/2006 dated 17/11/2006 revised 18/11/2006 and all as specified and as directed.
Construction of soakage well with excavation in any type of soil foundation in PCC 1:3:6, wells of Honey combed brickwork and solid in M-25 Concrete, including intercepting chamber, screen chamber brick work in CM 1:4, RCC cover slab in M-25/ filling with brick bats, complete of size 1.80 M dia X 3.0M depth complete all as shown on TD drawing no CE(AF)/NGP/TD-43/2004 sheet 1/2 & 2/2 dated 09/01/2004,and all as specified and as directed.
Material and labour for fire stand suitable for 06 fire bucket and fire extinguisher complete all as specified and as directed
Total amount of Schedule 'A' Part XII carried over to General Summary
GENERAL SUMMARY
Lumpsum price worked out by the contractor for “BUILDING & STRUCTURE” as listed in Schedule ‘A' Part I representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part I on Srl Page No. 34(R)
Lumpsum price worked out by the contractor for “INTERNAL WATER SUPPLY" as listed in Schedule ‘A' Part II representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part II on Srl Page No.36(R)
Lumpsum price worked out by the contractor for “INTERNAL ELECTRIFICATION” as listed in Schedule ‘A' Part III representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part III on Srl Page No. 40(R)
Lumpsum price worked out by the contractor for “SITE CLEARANCE, EXCAVATION AND EARTHWORK” as listed in Schedule ‘A' Part IV above/below the lumpsum price as inserted by MES for Schedule ‘A’ Part IVon Srl Page No. 42(R)
Lumpsum price worked out by the contractor for “SHED FOR DG SET” as listed in Schedule ‘A' Part V above/below the lumpsum price as inserted by MES for Schedule ‘A’ Part V on Srl Page No. 44
Lumpsum price worked out by the contractor for “AIR CONDITIONING” as listed in Schedule ‘A' Part VI representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ PartVI on Srl Page No. 45
Lumpsum price worked out by the contractor for “ROAD / PATH/ CULVERT/ HARDSTANDING as listed in Schedule ‘A' Part VII representing above/below the lumpsum price inserted by MES for Schedule ‘A’ Part VII on Srl Page No. 48
Lumpsum price worked out by the contractor for “EXTERNAL SEWAGE DISPOSAL” as listed in Schedule ‘A' Part VIIIrepresenting above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part VIIIon Srl Page No. 51
Lumpsum price worked out by the contractor for “COMPOUND WALL, FENCING, GATE” as listed in Schedule ‘A' Part IX representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part IX on Srl Page No. 56
Lumpsum price worked out by the contractor for “EXTERNAL WATER SUPPLY” as listed in Schedule ‘A' Part X representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part X on Srl Page No 58.
Lumpsum price worked out by the contractor for “EXTERNAL ELECTRIFICATION, LIGHTENING ARRESTOR” as listed in Schedule ‘A' Part XI representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part XI on Srl Page No. 67
Total amount of SCHEDULE 'A' PART XII (MISC B/R & E/M ITEMS) brought forwarded from Serial Page No. 107(R)
SAGGI ELECTRIC COMPANY
Sant Construction Co.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .