Chief Engineer Pune Zone
Chief Engineer Pune Zone Dakshin Kaman Marg CAMP, Pune PIN- 411001
PROVISION OF DUs FOR OFFICERS AT MUMBAI
2024_MES_642096_1
CA NO. CEPZ/MUM/TOKEN-21 OF 2023-24
Open Tender
Civil Works
900 days
Mumbai
Class SS category a(i)
Also refer NIT
8 documents required · 8 mandatory
₹3,000
GE (West) Colaba
₹15 L
Yes
HQ Chief Engineer Pune Zone
27 Jun 2024
13 Feb 2024
13 May 2024
13 Feb 2024
11 May 2024
4 May 2024
14 Feb 2024 - 24 Feb 2024
29 Feb 2024
Amount
Schedule ‘A’ Part I to XIII items which are Prepriced by MES, Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only.
Total amount of Sch ‘A’ Part I (Building & Structures)
Total amount of Sch ‘A’ Part II (Internal Water Supply)
Total amount of Sch ‘A’ Part III (Internal Electric Supply)
Total amount of Sch 'A' Part-IV (Lightening Protection)
Total amount of Sch ‘A’ Part V (Road, Path and Hard standing)
Total amount of Sch ‘A’ Part VI (Area Drainage)
Total amount of Sch ‘A’ Part VII (Sewage Disposal)
Total amount of Sch ‘A’ Part VIII (Compound Wall, Fencing and Gate)
Total amount of Sch 'A' Part-IX (External Water Supply)
Total amount of Sch 'A' Part-X (External Electric Supply)
Total amount of Sch 'A' Part-XI (Fire Safety System)
Total amount of Sch 'A' Part-XII (Site Clearance, Excavation and Earthwork)
Total amount of Sch 'A' Part-XIII (Demolition/Dismantling)
NOTE: Schedule ‘A’ Part II to XIII items, which are not Prepriced by MES are given hereunder, Bidders shall insert their rate in Column-7 only and the Estimated rate indicated as "0.0" are for that purpose.
SCHEDULE 'A' PART-XIV (MISC B/R, E/M, PILE FOUNDATION, FIRE SAFETY SYSTEM, MODULAR KITCHEN AND LIFT WORKS)
PILE FOUNDATION WORK
M&L Drilling into any type of soil strata lowering upto non-collapsible strata for 600mm dia cast in situ piles all as required and getting out and disposal of spoil outside MD land and depositing at a place including erecting pilling equipment of any type complete with all accessories, centering in position and removing on completion of each pile all as shown on drawing, as specified and as directed.
M&L Drilling into Soft/disintegrated/weathered rock lowering upto non-collapsible strata for 600mm dia cast in situ piles all as required and getting out and disposal of soft/ disintegrated/weathered rock outside MD land and depositing at a place including erecting pilling equipment of any type complete with all accessories centering in position and removing on completion of each pile all as shown on drawing, as specified and as directed
M&L Drilling into Hard rock lowering upto non-collapsible strata for 600 mm dia cast in situ piles all as required and getting out and disposal of hard rock outside MD land and depositing at a place including erecting pilling equipment of any type complete with all accessories centering in position and removing on completion of each pile all as shown on drawing, as specified and as directed
NOTES for Sr No 14.01 to 14.04 (a) Spoil shall be disposed off outside MD land. The unit rate quoted against item Nos 14.02 to 14.04 shall interralia be deemed to include for this operation and no extra payment shall be admissible on this account. (b) Drilling of piles shall be measured and paid from marked average ground level to bottom of pile.
M&L RCC or RMC M-40 design mix concrete and Tremie Concreting as per IS 456 of 2000 in piles cast in situ and pile caps of 600 mm dia piles of any length /depth using tremie pipe concrete method including cutting and knocking down waste concrete complete all as shown on drawings, as specified and directed. Note: RCC will be measured and paid from cutoff level and rate quoted shall be inclusive of cutting and knocking of RCC waste above cut off level.
M&L CRS TMT (Fe 500 D) with cover block, 10 mm dia & over, cut to length bent to shape required, including cranking, bending spirally for hoping for columns, hooking ends & binding with & including mild steel wire (annealed) not less than 0.9mm dia or securing with clips as in reinforcement of pile case and pile caps including lowering of pile cage into pile of 600 mm / 450 mm dia complete all as directed.
M&L CRS TMT (Fe 500 D) 5mm dia and over upto and including 10mm dia in stirrups, spacers, binders, cut to length bent to shape required, including cranking, bending spirally for hoping for piles, hooking ends & binding with & including mild steel wire (annealed) not less than 0.9mm dia or securing with clips for reinforcement of pile case and pile caps complete all as directed.
M&L Providing and installing 6 mm thick MS liner for bored cast in situ concrete piles 600mm dia with necessary stiffeners, driving shoe with continuous welding including cutting, welding, etc. conforming to Fe 410-W (Gde E-250 Quality A) including applying one coat of primer with two coats of epoxy as anticorrosive treatment on external surfaces of liner as per manufacturer's instructions, complete all as specified and as directed.
M&L Providing and installing 3 mm thick MS liner for bored cast in situ concrete piles 600mm dia (upto 6m depth) with necessary stiffeners, driving shoe with continuous welding including cutting, welding, etc. conforming to Fe 410-W (Gde E-250 Quality A) including applying one coat of primer with two coats of epoxy as anticorrosive treatment on external surfaces of liner as per manufacturer's instructions, complete all as specified and as directed.
Notes for item Nos 14.09 & 14.10: (i) Rates shall be inclusive of cutting the liner at cut off level. The rate is deemed to include for cutting, removal and salvage value of the material so obtained. (ii) MS liner will be measured and paid upto the cut off level of pile only. Additional MS liner if used for conveyance of construction shall be included in the rate quoted. No extra payment shall be made on this account. (iii) MS Liner shall be driven upto refusal level. The occurrence of refusal level will be decided by GE at site based on visual inspection of bailer samples from pile bore, past experience and laboratory test results. The decisions of GE in this regard shall be final and binding.
M&L High Strength Dynamic Load Test using capwac analysis as per ASTM 4945 and IRC 78 on 600mm dia piles in accordance with IS provisions for Initial Test including all necessary arrangements providing and setting up all necessary accessories and equipments carrying out the prescribed test as required/specified under the expert supervision, noting the result, taking out the accessories and equipment on completion of test, submitting the result in soft and hard copy quintuplicate all as directed.
M&L for Integrity Test on 600mm dia pile in accordance with IS provisions including all necessary arrangements providing and setting up all necessary accessories and equipments carrying out the prescribed test as required/specified under the expert supervision noting the result, taking out the accessories and equipment on completion of test, submitting the result in soft and hard copy quintuplicate all as directed.
M&L for High Strength Dynamic Load Test using capwac analysis as per ASTM 4945 and IRC 78 on 600mm dia pile in accordance with IS provisions for Routine Test including all necessary arrangements providing and setting up all necessary accessories and equipments carrying out the prescribed test as required/specified under the expert supervision noting the result, taking out the accessories and equipment on completion of test, submitting the result in soft and hard copy quintuplicate all as directed.
M&L High Strength Dynamic Load Test using capwac analysis as per ASTM 4945 and IRC 78 on 600mm dia pile in accordance with IS provisions for Lateral Test including all necessary arrangements providing and setting up all necessary accessories and equipments carrying out the prescribed test as required/specified under the expert supervision noting the result, taking out the accessories and equipment on completion of test, submitting the result in soft and hard copy quintuplicate all as directed.
INTERNAL WATER SUPPLY
S&F 15 mm CP bib taps cast copper alloy with crutch or butter fly handles screwed down for iron pipe complete all as specified and directed. Make : Cera Cart Part No- F1005152 or technocommercially equivalent in Jaquar/ Marc/ Kohler/ Player
S&F two way bib cock with wall flange quarter turn (Low-flow) 16 mm dia complete all as specified and directed. Make : Cera Cart Part No- F1005156 or technocommercially equivalent in Jaquar/ Marc/ Kohler/ Player
S&F Pillar Cock (Low-flow) 16 mm dia fixing complete all as specified and directed. Make : Cera Cart Part No- F1005452 or technocommercially equivalent in Jaquar/ Marc/ Kohler/ Player
S&F Hand shower (Health faucet) with 1.20 meter long easy ss chrome plated hose flex tube in chrome finish and wall hook with NRV (Back flow preventer) complete all as specified and directed. Make : Cera Cart Part No- F8030107AB or technocommercially equivalent in Jaquar/ Marc/ Kohler/ Player
S&F Overhead Shower Single function Square overhead shower 150 x 150 mm Flow with Air Effect (ABS Body & Face Plate Chrome Plated) with Rubit Cleaning System 16 mm dia. complete all as specified and directed. Make : Cera Cart Part No- F7010506AB or technocommercially equivalent in Jaquar/ Marc/ Kohler/ Player
S&F Wall Mixer 3 In 1 with flange provision for Overhead Shower with 115mm Long Bend Pipe on Upper Side, connecting legs & wall flanges complete all as specified and directed. Make : Cera Cart Part No- F1005402 or technocommercially equivalent in Jaquar/ Marc/ Kohler/ Player
S&F Wall mounted sink cock with swivel spout & flange complete with fitting & fixture complete all as specified and directed. Make : Cera Cart Part No- F1005501 or technocommercially equivalent in Jaquar/ Marc/ Kohler/ Player
S&F Gun metal globe or gate valve, 65 mm dia, ISI marked, confirming to IS-778 with iron wheel head, screwed both ends for Galvanised iron (GI) pipe as under and fixed complete all as specified and directed.
S&F Gun metal globe or gate valve, 100 mm dia, ISI marked, confirming to IS-778 with iron wheel head, screwed both ends for Galvanised iron (GI) pipe as under and fixed complete all as specified and directed.
S&F Stop valves, cast copper alloy, fancy type, chromium plated with long shank and cup (concealed type), screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed all as specified and directed for the following nominal bore of pipes:- Make : Cera/ Jaquar/ Marc/ Kohler/ Player.
(a) 15 mm nominal bore of pipes.
(b) 25 mm nominal bore of pipes.
S&F Angular stop cock 15 mm bore of pipe (16 mm outer dia) with wall flange, chromium plated (concealed type), screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron / CPVC pipe or for unions and fixed all as specified and directed. Make: Cera/ Jaquar/ Marc/ Kohler/ Player.
S&F Toilet Paper Holder of vitreous china fixed to wall with chromium plated (CP) brass screws complete all as specified and directed. Make : Cera Cart Part No- F5013109CH or technocommercially equivalent in Jaquar/ Marc/ Kohler/ Player
S&F Towel Rail 600 mm long of PTMT fixed with and including Chromium plated brass screws and wooden / plastic cleats. (Minimum weight 190gms) complete all as specified and directed. Make :Cera Cart Part No- F5014131CH or technocommercially equivalent in Jaquar/ Marc/ Kohler/ Player
Supply, installation, testing & commissioning of 32 mm outer dia of pipes bronze pressure reducing valve having stainless steel strainer screen, stainless steel stem, factory preset having SS adjustable bolt and locking nut, complete all as specified and directed.
Supply, installation, testing & commissioning of 50 mm outer dia of pipes bronze pressure reducing valve having stainless steel strainer screen, stainless steel stem, factory preset having SS adjustable bolt and locking nut, complete all as specified and directed.
Supply, installation, testing & commissioning of 65 mm outer dia of pipes bronze pressure reducing valve having stainless steel strainer screen, stainless steel stem, factory preset having SS adjustable bolt and locking nut, complete all as specified and directed.
INTERNAL ELECTRIFICATION
S&F Vertical triple pole & neutral, double door, metallic modular distribution board 4 way conforming to IEC 61439-3, suitable for flush / surface mounting with provision for MCCB up to 250 A as incomer and SP/TP MCBs as outgoing, reversible metal door, fully insulated 250 A copper busbar for each phase, two fully insulated & shrouded neutral bars, two earth bars, cable ties for cable management, prefitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified and directed. (Sub Station DB)
NOTE: FP MCCB & SP/TP MCBs shall be measured and paid separately.
S&F MCB for AC applications conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, sliding bottom clamp, colour coded on/off indication on dolly, bi-connect IP 20 protected lower terminals and sliding shutters, etc. complete all as specified in IS 732: 2019 and directed.
6- 32 A, 230 V, 50 Hz, SP MCB (C curve)
40- 63 A, 230 V, 50 Hz, FP MCB (C curve) for TPN DB at common area
6- 32 A, 230 V, 50 Hz, SPN MCB for 8 way DB(C curve),
Supply, installation, testing and commissioning of IP 54 rated sandwich type (3L+N+PE) busbar trunking 400 Amps capacity, 440 volt system complete with two runs of 50 mm X 6 mm aluminium earthing strip and accessories all as specified and directed.
Make : ABB, Legrand, L&T, Schneider, Siemens
The BTS shall conform to the following technical specifications:
[A] GENERAL
[i] The busbar trunking system (BTS), both feeder and plug-in, shall be of sandwich construction. All components and fittings (straight length, elbow, tee, flanged end, cable tap-off box and circuit breaker etc.) shall conform to IEC 61439-6:2012 or UL 857 and shall be procured from the OEM of BTS. The BTS shall have IP 65 protection with canopy for outdoor application and IP 54 protection for indoor application in accordance with IEC 60529: 1989.
[ii] The rated operation voltage of BTS shall not be less than 1.1 kV. The neutral conductor shall have the same cross-sectional area as the phase conductor and the earth busbar shall be provided on both sides of the housing.
[B] CERTIFICATE
[i] The busbar, of full range and each rating, shall pass full type tests specified in IEC 61439-6-2012. The certificate shall be issued by an international independent testing authority, e.g. ASTA. KEMA. UL, ERDA, CPRI etc.
[ii] A product safety mark, e.g. KEMA-KEUR, ASTA DIAMOND, UL and ERDA, CE, etc. shall be on the product offering a visual assurance of full product safety testing, factory inspection and ongoing surveillance under independent authority.
[iii] The BTS shall be certified for seismic tests conforming to IEEE 693-2018 for seismic zone V.
[C] SHORT-CIRCUIT RATINGS & TESTS
[i] The entire BTS (bus duct and plug-in box assembly) shall be capable of withstanding the short-circuit of electrical installation without undergoing any electrical, mechanical or thermal stress under fault condition at a service voltage of 1.1 kV at 50 Hz frequency. The minimum rated insulation voltage shall be 1 kV.
[ii] The minimum certified short-circuit withstand capacity for 800 A rating shall be 50 kA for 1 sec.
[D] HOUSING
[i] The busbar trunking housing shall be constructed of 1.6 mm thick electro-galvanised steel and shall be provided with a suitable protective finish of epoxy paint.
[ii] The busbar trunking housing shall be totally enclosed non-ventilated for protection against mechanical damage and dust accumulation and it shall be tested for its characteristics offering resistance against corrosion. It shall also pass at least 1000 salt spray test to ensure its anti-corrosion ability.
[iii] The totally enclosed housing shall be manufactured by the BTS OEM and modifications of busbar trunking to make it totally enclosed by housing other than the busbar trunking OEM shall be unacceptable without written consent of the OEM.
[E] BUSBARS
[i] The busbars shall be of aluminium with tin / silver plating at joint and conductivity of the joint shall be > 60% IACS
[ii] There shall be no bolts passing through the busbars of the BBT.
[iii] Each busbar shall be insulated with Class-F (155 ⁰C) multilayer PET insulation. Epoxy and Mica insulation shall be unacceptable.
[iv] The temperature rise at any point of busbar trunking enclosure shall not exceed 55 ⁰C above the ambient temperature of 40 ⁰C when operated at the rated current.
[F] JOINTS
[i] The busbar trunking joint shall be of one-bolt type utilizing high strength steel bolt(s) and Belleville washers to maintain proper pressure over a large contact surface area.
[ii] The bolt(s) shall be torque indicating and at earth potential.
[iii] The nut(s) shall be of two-headed design to indicate proper torque has been applied and shall require only a standard long handle wrench to be properly activated.
[iv] Access shall be required to only see one side of the busbar trunking to tighten joint bolts.
[v] It shall be possible to remove any joint connection assembly to allow electrical isolation or physical removal of a busbar trunking length without disturbing adjacent busbar trunking lengths.
[G] PLUG-IN OPENING
[i] The connecting jaw of a plug-in unit shall plug directly onto the busbar and have full contact with busbar itself. Welded tab at plug-in busbar is unacceptable.
[ii] All contact on joint and plug-in opening shall be of copper strip in order to avoid external force damage on busbar while plugging in or plugging out operation.
[iii] On plug-in busbar trunking there shall be three dead front, hinged cover type plug-in opening on each side.
[iv] All openings shall be usable simultaneously. Busbar trunking shall be installed in such a manner that plugs are side mounted to permit practical use of all plug-in openings.
[v] It shall be possible to inspect the plug-in opening and busbars prior to the installation of plug-in units.
[H] SUPPORT STRUCTURE
[i] Support structure shall be provided as per OEM's recommendation.
[ii] Indoor feeder and plug-in busbar trunking shall be approved for hanger spacing of up to 3 m for horizontally mounted run and 4.88 m for vertically mounted runs. Outdoor feeder busbar trunking shall be approved for spacing up to 1.5 m for horizontally or vertically mounted runs.
[I] VOLTAGE DROP
[i] The voltage drop (sending end voltage minus receiving end voltage) specified shall be based on the busway operating at full rated current and stabilized operating temperature in.
[ii] The 3- Phase line to line voltage drop shall not exceed 3.4 V per 100 feet length at 40% power factor concentrated load which may exist during motor starting.
[iii] The line to line voltage drop shall not exceed 4.1 V per 100 feet at the load power factor which produces the maximum voltage drop in the bus way.
[J] INSPECTION / SUPPORT OF INSTALLATION
[i] The installation of busbar trunking system (BTS) shall be executed by skilled professionals with minimum experience of 5 yrs. having sufficient installation base and pre-commissioning experience.
[ii] The entire installation shall be directly supervised by the OEM.
[iii] The OEM shall also furnish a commissioning report underlining satisfactory installation after the commissioning of BBT system.
Straight Run Feeder having IP 54 protection
Flange End with Equalizer / Shorting Plate
Horizontal / Vertical Bend
Plug-in Point (Without Switchgear)
Vertical Spring Hanger / Fix Hanger
End Cover
Expansion Joints
Tinned Copper Braided Flexibles with Hardware- Nuts & Bolts
Adapter Box
STANDARD PLUG-IN BOX / TAP-OFF UNIT WITH FP MCCB
PIB / TOU with 63 A, 415 V, 16 kA, 50 Hz, FP MCCB
END FEED UNIT WITH FP MCCB / ACB
End Feed Unit (EFU) with 400 A, 25 kA, 415 V , 50 Hz, FP EDO MCCB
SUPPORTING STRUCTURE
Horizontal Fixing Clips
Supply, fabricate and erect MS Structural steel for BBT support structure with painting as recommended by OEM.
NOTES :
The bidder shall furnish dimensional drawings of the items offered, indicating all the fittings, dimensional tolerances, typical GADs, etc. with details of insulation at each point and core construction, etc. for approval of the Garrison Engineer.
S&F Surface / wall mounted LED batten light fitting including LED light 20W capable of delivering 2000 lumen, having PC diffuser, luminous efficacy of > 90 lumen/W, CRI > 80, PF > 0.9, CCT 6500K, independent isolated SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in powder coated white extruded aluminium channel housing. white coloured ABS end caps, IP 20 protection, input voltage range 140- 270 V, input frequency 50- 60 Hz, including electrical connection with 3 core flexible copper conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed.
S&F Surface / wall mounted LED batten light fitting including LED light 10 W capable of delivering 1000 lumen, having PC diffuser, luminous efficacy of > 90 lumen/W, CRI > 80, PF > 0.9, CCT 6500K, independent isolated SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in powder coated white extruded aluminium channel housing. white coloured ABS end caps, IP 20 protection, input voltage range 140- 270 V, input frequency 50- 60 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed.
S&F LED Bathroom light fitting with LED lamp 10 W suitable for wall mounting & 220- 240 V, 50 Hz mains voltage with built-in LED & driver, power rating ≤ 10 W, including IP 20 protection as well as electrical connection with 3 core 1.0 mm² PVC insulated copper conductor unarmoured cable to the fixture complete all as specified.
S&F Surface mounted round slim LED surface light with premier diffuser 12W with integral fixed output driver having LED light source engine, luminous flux ≥ 1200 lm, rated luminous efficacy ≥ 100 lm/W, power consumption ≤ 11 W, power consumption tolerance ±10%, initial corrected colour temperature (CCT) 6500K, colour rendering index (CRI) > 80, SDCM < 5, THD < 10%, Power Factor ≥ 0.90, median useful life L70B50 @ Ta = 45 °C ≥ 30000 hrs, surge protection level ≥ 2.5 kV with aluminium pressure die cast housing and polycarbonate optical cover / lens material, IP 20 & IK 02 protection, safety class I, and suitable for mounting on normally flammable surfaces, 220- 240 V input voltage, 50 Hz line frequency, ambient temperature range 0 to 45 °C, overall diameter ≤ 7" (175 mm) and fixture height ≤ 60 mm along with mounting bracket and all necessary accessories complete all as specified and directed.
S&F Surface mounted round slim LED surface light with premier diffuser 18W with integral fixed output driver having LED light source engine, luminous flux ≥ 2000 lm, rated luminous efficacy ≥ 100 lm/W, power consumption ≤ 18 W, power consumption tolerance ±10%, initial corrected colour temperature (CCT) 6500K, colour rendering index (CRI) > 80, SDCM < 5, THD < 10%, Power Factor ≥ 0.90, median useful life L70B50 @ Ta = 45 °C ≥ 30000 hrs, surge protection level ≥ 2.5 kV with aluminium pressure die cast housing and polycarbonate optical cover / lens material, IP 20 & IK 02 protection, safety class I, and suitable for mounting on normally flammable surfaces, 220- 240 V input voltage, 50 Hz line frequency, ambient temperature range 0 to 45 °C, overall diameter ≤ 7" (175 mm) and fixture height ≤ 60 mm along with mounting bracket and all necessary accessories complete all as specified and directed.
S&F 25 W street light having high efficiency long life LED module with SMD LED package mounted on MCPCB with high LED efficacy of ≥ 2600 lumen/W, integral SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, IP 66 protection, high efficiency polycarbonate cover with integrated lens housed in pressure die-cast aluminium alloy heat sink for effective thermal management, sturdiness, excellent corrosion resistance, separate optical and control gear compartment & top opening for easy maintenance, suitable for side entry, pole mounting with bracket arm OD 35 mm to 42 mm including necessary electrical connection to the fixture with 3 core flexible Cu conductor cable of appropriate size and 1.5 m long bracket, having 40 mm diameter light grade GI pipe, including GI clamps, nuts, bolts & washers with two coats of synthetic enamel paint over a coat of red oxide primer complete in all respect as specified and directed.
S&F Wall-mounted bulkhead having LED light source engine, integral fixed output driver,120° luminaire light beam spread, luminous flux ≥ 700 lm, luminous efficacy ≥ 107 lm/W, power consumption ≤ 6.5 W, power consumption tolerance ±10%, initial corrected colour temperature (CCT) 6500K, colour rendering index (CRI) ≥ 80, SDCM < 5, power factor (fraction) > 0.90, median useful life L70B50 @ Ta = 45 °C ≥ 25000 hrs, surge protection level ≥ 2 kV with aluminum die cast housing, polycarbonate optical cover / lens, IP65 & IK08 protection, and suitable for mounting on normally flammable surfaces, 140- 270 V input voltage, 50 Hz line frequency, ambient temperature range 0 to 45 °C, class I safety, along with wall-mounting bracket and all necessary accessories complete all as specified and directed by the engineer-in-charge.(lift well light)
Supply and fixing Ceiling fan complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) complete all as specified and directed by engineer-in-charge.
S&F Energy efficient non-metallic fresh air fan having blade sweep 250 mm, air delivery not less than 860 CMH, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fresh-air fan complete all as specified and directed.
S&F Exhaust fan, steel body AC single Phase. 230V size 300 mm sweep heavy duty with, blades, and frame and louvers including electrical connection with 3 core flexible copper conductor cable of appropriate size from ceiling rose to the fresh-air fan complete all as specified and directed.
S&F Exhaust fan, steel body AC single Phase. 230V size 450 mm sweep heavy duty with, blades, and frame and louvers including electrical connection with 3 core flexible copper conductor cable of appropriate size from ceiling rose to the fresh-air fan complete all as specified and directed.
Supply, installation and commissioning of Electric Geyser having 25 litres storage capacity, temperature sensitive LED indicators with temperature sensing LED knob to control and indicate the temperature of water with enhanced safety for protection, high working pressure of 8 bar ideal for high rise building and over heat protection with auto off feature and integrated shock safe plug, 5 star rated, shock safe plug, PUF insulation, incoloy glass coated heating element, anode rod, adjustable knob, multi-functional safety valve with IP 4X protection all complete all as specified and directed.
Supply, installation, testing and commissioning Smart Three Phase Meter (AC Static watt hour Meter), AC Three Phase Four Wire, Tamper Proof, Smart meter (AC Static watt hour Meter) of Class 1.0, 415 volt 10 A-60 A, ISI marked marked with IS-16444:2015(reaffirmed 2020) and relevant IEC standards with inbuilt communication facility as per IS code through any mode and on demand display, billing data generation facility, anti-tamper features, Microprocessor and LED/LCD based circuitry. This shall include DCU, software and 02 years defects liability. Defects Liability shall include 02 years SIM network charges for data communication and all type of charges and GCC hosting charges.
Supply, installation, testing & commissioning concealed in wall transparent Polycarbonate three phase meter box for indoor application.
NOTES FOT ITEM NO 15.18 & 15.19:
(ii) The meter shall be compatible to other standard make of KWH meter and support to the centre server installed by department.
LIFT WORK
The lifts shall conform to the following technical specification:- [i] Type of Lift: Passengers Lift [ii] Load Capacity: 544 kg / 8 Passenger [iii] Speed: 2.0 m/s with single speed motor [iv] Power Supply: 3- Phase, 4 Wire, 415 V, 50 Hz AC [v] Type of Drive: VVVF Regenerative Drive (Variable Voltage and Variable Frequency Regenerative Drive) [vi] Type of Machine: Gearless PMSG Motor. [vii] Car Size: Not less than 1.43 m² [viii] Car & Landing Door at all Floors: Automatic center opening with VVVF door drive, opening size not less than 900 mm X 2100 mm sliding type, fabricated by stainless steel sheet not less than 16 gauge having hairline finish (N-304) [ix] Car Enclosure: Manufactured with stainless steel frame SS 304, luxury golden mirror etched finish of 1.2 mm thick (No cladding) not less than 16 gauge with honeycomb/glass with golden etched having stainless steel ceiling SS-304, luxury golden mirror etched finish, internal lighting arrangement with LED light fittings with auto cut-off system operated on commercial supply and one LED light fitting operated on battery with invertors as emergency light, complete internal ventilation system provided with concealed axial/cross flow fan with auto cut-off system and stainless steel grill / wire mesh for protection. [x] Handrail: Standard thickness 40 mm diameter stainless steel hand-rail all around inside the car cabin
(iii) Fire emergency operation (iv) Emergency operation for power failure. [b] The ARD actuation time shall be less than one second after failure of power supply and when ARD is operative the car shall stop at the nearest floor and then open [xxii] Civil work: Necessary Civil work viz. making good disturbed surfaces, modification to landing space to suit to car size, necessary foundation to machine as per OEM recommendation etc. complete. [xxiii] Mirror of suitable size to be provided above SS railing on the wall opposite to Centre opening stainless steel doors.
NOTES: [i] The lift shall work on microprocessor-based control system with self-diagnostic features, site programming, etc. to suit changing needs of the user. [ii] The lift shall be silent in operation & shall have smooth and controlled acceleration and de-acceleration with leveling accuracy of ± 5 mm. [iii] Potential free contacts for each floor position and up and down movement of the lift shall be provided in the controller. (iv) Contractor shall submit GA drawing for approval by AO (v) Contractor shall obtained necessary approval from local / state / central authority and make arrangement for inspection and testing as required. Contractor shall also submit required certificate / license from competent govt authority before commissioning / handing over of site or all as directed.
[i] Type of Lift: Stretcher / Fire Lift [ii] Load Capacity: 1088 kg / 16 Passenger [iii] Speed: 2.0 m/s with single speed motor [iv] Power Supply: 3- Phase, 4 Wire, 415 V, 50 Hz AC [v] Type of Drive: VVVF Regenerative Drive (Variable Voltage and Variable Frequency Regenerative Drive) [vi] Type of Machine: Gearless [vii] Car Size: Not less than 2.48 m² [viii] Car & Landing Door at all Floors: Automatic center opening with VVVF door drive, opening size not less than 900 mm X 2100 mm, sliding type, fabricated by stainless steel sheet not less than 16 gauge having honeycomb finish (SS-304). [ix] Car Enclosure: Manufactured with stainless steel frame not less than 16 gauge with honeycomb having stainless false ceiling with hairline finish, internal lighting arrangement with LED light fittings with auto cut-off system operated on commercial supply and one LED light fitting operated on battery with invertors as emergency light, complete internal ventilation system provided with concealed axial/cross flow fan with auto cut-off system and stainless steel grill / wire mesh for protection. [x] Handrail: Standard thickness 40 mm diameter stainless steel hand-rail all around inside the car cabin. [xi] Terminal Buffers: Special PU buffers / spring buffers as per OEM recommendation and approval of GE.
[xii] Door Opening (Inside): Centre opening stainless steel doors with hairline finish doors with clear opening of not less than 900 mm X 2100 mm and protected by infrared door protection system. [xiii] Car & Counter Weight Guide: Guide rails of MS 'T' section as per OEM design; counter weight shall be as recommended by OEM. [ixv] Flooring: Granamite flooring & toe guard of adequate depth / as per OEM design.
[xv] Signal System: Combined luminous hall push buttons with LCD TFT hall position indicators (IP-55) of stainless steel in ground floor, Dot matrix in rest in rest of the floors with stainless steel hairline face plate at all floors two sides, LCD colour display car position indicator in car and over load warning in the car, one car operating panel with stainless steel hairline with etched borders and luminous button in car, car direction indicator in car and landing, battery operated alarm bell and emergency light along with invertors of suitable capacity having fireman switch at ground floor, all signal features and COP shall have stainless steel face plate, 2D infra red sensor safety edge of door for entire height, built in announcing system without hand set. (a) Combined luminous hall buttons with LCD hall position indicators of stainless steel at all floors. (b) LCD car position indicators of stainless steel. (c) Car operating panel of stainless steel with luminous buttons in car. (d) Car direction indicator in car & landing. (e) Battery operated alarm bell & emergency light (rechargeable) along with suitable maintenance free battery (This system shall be separate from ARD batteries). (f) Overload warning feature in car cabin (display and announcing type both). (g) One fireman's switch to be installed at ground floor near landing door. (h) All signal fixture & car operating panel on hairline stainless steel face plate with hairline finish. (i) Infrared door sensor safety edge of door for entire height.
(j) Voice Synthesizer with MP3: MP3 based Voice Synthesizer consisting of electronic PCB enclosed in a PVC (IP 54) Box to be fitted in the controller and speaker unit to be mounted on the ceiling of the car for announcements of floor positions and other features like door opening, Overload, ARD, power failure, etc. [xvi] Stops & Opening:20-20 All opening on same side.
NOTES: [i] The lift shall work on microprocessor-based control system with self-diagnostic features, site programming, etc. to suit changing needs of the user. [ii] The lift shall be silent in operation & shall have smooth and controlled acceleration and de-acceleration with leveling accuracy of ±5 mm. [iii] Potential free contacts for each floor position and up and down movement of the lift shall be provided in the controller. [iv] Adequate number of earthing for electrical appliances, motor, control panel and machine room having earth resistance not more than 1 Ohm shall be provided by OEM/Contractor, rate for which shall be deemed to be included in item rate. [v] Adequate number of electric wiring or LED fittings shall be provided in machine room as well as lift shaft by OEM/Contractor, rate for which shall be deemed to be included in item rate. [vi] Contractor shall submit GA drawing for approval by AO [vii] Contractor shall obtained necessary approval from local / state / central authority and make arrangement for inspection and testing as required. Contractor shall also submit required certificate / license from competent govt authority before commissioning / handing over of site or all as directed.
M&L 1.1 kV grade XLPE insulated armoured copper cable conforming to IS 7098 (Part 1): 1988, having stranded compact shaped conductors as per Cl. 2 of IS 8130: 1984, PVC inner sheath, single armouring of galvanised steel strip/wire and PVC Type ST-2 outer sheath conforming to IS 5831: 1984, including necessary clamping / dressing with cable ties and termination complete of following sizes as all specified and directed:-
4 core 16 mm2 , 2XWY
4 core 10 mm2 , 2XWY
Supply, installation, testing and commissioning of factory made, CPRI / ERDA type tested, fully compartmentalized bolted type Vertical Transport (Lift) Feeder (design verified assembly- DVA) of suitable size conforming to IEC 61439-1 & 2 and IEC 61641 and having modular extensible design suitable for indoor mounting, internal arc compliance of minimum 70 kA for 0.3 s, made out of 2.0 mm thick mild steel CRCA sheet, having both sides openable with hinged doors and locking arrangement, IP 54 & IK 10 protection, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enameled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3-Phase, 4-Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete all as specified and directed. The VTF shall comprise of the following:- Make: ABB, Legrand, L&T E&A, Schneider, Siemens, BCH
[A] BUSBAR CHAMBER 01 Set (3L + N) of copper busbar of rated capacity 200 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection.
[B] INCOMING [i] Circuit Breaker (a) 125 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2: 2016, having thermal magnetic trip unit, adjustable overload setting, adjustable short-circuit setting, front indication LEDs, etc.- 01 No. [ii] Instrumentation & Measurement (a) CI 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interrupts- 01 No. (b) 160/5A Cl. 1.0 C.T. with 10 VA burden- 01 No. (c) 6A, 10kA, 415V, 50 Hz 4P MCB- 01 No. [iii] Indication & Annunciation (a) LED phase indicators (Red, Yellow, Blue)- 01 Set (b) LED status indicators (ON, OFF, TRIP)- 01 Set
[C] OUTGOING [i] Circuit Breaker 63 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz 3P MCCB, conforming to IEC 60947-2: 2016, having thermal magnetic trip unit, adjustable overload setting, adjustable short-circuit setting, front indication LEDs, etc for 8 passenger 2 Nos.- 03 Nos.(2W+1S). [ii] Instrumentation & Measurement (a) 50/5A Cl 1.0 CT having 5VA burden- 01 No. (b) 0-63 A ammeter- 01 No. [iii] Indication & Annunciation LED status indicators (ON, OFF, TRIP)- 01 Set
NOTES: [i] The busbars shall be of double deck arrangement for rating ≥ 2000A interleaved /non-interleaved design as per OEM. Separation of busbar shall be as per Form 4b. [ii] All the MCCBs up to 250 A shall be with thermal magnetic trip unit & above 250A shall be with microprocessor trip units. To ensure failsafe emergency tripping of the breakers (ACBs & MCCBs), it shall be supplied with continuous rated shunt trip coils. [iii] Necessary control and switching devices to execute the switching and control logic shall be deemed inclusive of the scope of supply irrespective of them being specified / not specified above or in the SLD. [iv] The Panel / Switchboard shall be tested to withstand vibration caused by an earthquake in accordance with IEC 60068-3-3:2013 or IS 1893 Zone V. [v] The Panel shall be purchased from the original equipment manufacturer (OEM) or OEM authorized franchises only. [vi] The Contractor shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, typical GADs, etc. to GE for approval of the MEP Consultant and thereafter A.O.
DG SET
Supply, installation, testing and commissioning of Outdoor type silent LT Diesel Generator set of 400 kVA rating, conforming to IS/IEC 60034-1 along with AMF cum synchronizing panel with associated switchgear, control panel and exhaust piping, Acoustic Enclosure as per latest CPCB norms (with amendments up to date at the time of execution), with necessary foundation, HSD oil storage & distribution system etc. with all necessary statutory approvals complete all as specified including control wiring from AMF to DG and directed. The diesel generator set shall conform to the following technical specifications:-
[A] Engine (i) Rating: 400 kVA (ii) Emissions / Fuel Strategy: Low Fuel Consumption (iii) Duty: Prime Power (iv) Overload: 10% for 1 hr in every 12 hrs (v) Site Output: Not less than 505 HP or as per the manufacturer specifications to generate sufficient torque to match the output capacity of 400 kVA alternator. (vi) Governor Type: Electronic-A1 (vii) Cooling System: Radiator water Cooled (viii) Silencer Type: Residential [B] Starting System (i) Type of Starting System: Battery Starting System (Ele.) (ii) Type of Battery: SMF VRLA type including battery charging system (iii) Battery Voltage: 12 V (iv) Number of Battery: AS recommended by OEM (v) Ah Capacity: As recommended by OEM [C] Fuel Oil System (i) Fuel tank capacity: for continue run of 12 hour (ii) Fuel tank thickness & MOC: 3 mm thick mild steel [D] Lube Oil System (i) Lube oil sump capacity: as per OEM (ii) Lube oil consumption: As per OEM
[E] DG Set Details (i) Mounting Type: AVM Pad [F] Alternator Details (i) Rating: 400 kVA (ii) Voltage: 415 V (iii) Power Factor (PF): 0.8 lag (iv) Connection: 3-Phase, 4-Wire (v) Degree of Protection: IP 23 (vi) Insulation: Class H (vii) Temperature Rise: Limited to Class H (viii) Excitation System: Separately Excited (ix) Frequency: 50 Hz (x) Voltage Variation: ±5% (xi) Voltage Regulation: ±0.5%
[G] Integrated DG Set Controller (1) Control: (i) Run/ Off / Auto Switch (ii) Emergency Stop (iii) Manual Run Stop Control Switch (iv) Idle / Run Mode Control (2) Metering (Engine): (i) Starting Battery Voltage (ii) Lube Oil Temperature & Pressure (iii) Engine coolant Temperature (iv) Coolant Pressure (v) Engine rpm (vi) Operating Hours (vii) Number of Starts
(3) Electrical: (i) Current (ii) Voltage (iii) Frequency (iv) kW (v) kWh (vi) PF (vii) kVA (4) Protection / Warning (Engine): (i) Over speed Shutdown (ii) Low Lube Oil Pressure Warning / Shutdown (iii) High coolant Temperature Warning / Shutdown (iv) Low coolant Temperature Warning (v) Low Coolant Level Warning / Shutdown (vi) Low and High Battery Voltage Warning (vii) Weak Battery Warning (viii) Over Crank Shutdown (ix) Fail to Crank Shutdown (x) Magnetic Pickup Failure Shutdown
(5) Alternator: (i) Over current (ii) High Voltage (iii) Low Voltage (iv) Under / Over Frequency (v) Reverse Power (kVA & kVAr) (vi) Phase Sequence
(6) Miscellaneous: (i) Digital AVR (ii) Amp Sentry Protection (iii) Sensor Failure Indication (iv) Programmable Idle Speed Control (v) Digital Synchronizing Function (vi) Sync Check (vii) Synchronoscope (viii) Auto Load Sharing (ix) Compatibility to Remote Monitoring (x) Smart Starting
[H] Exhaust System (i) Exhaust piping of size recommended by OEM to match latest CPCB rules with 75 mm thick glass wool / mineral wool insulation with wire chicken mesh over insulation and 24 gauge aluminium sheet cladding over the exhaust pipes from silencer to atmosphere including welding joint(s), bend(s), clamp(s), dash fasteners, flanges, nuts, bolts, etc. complete as required and as per specification (ii) Aluminium cladding for residential silencer with mineral wool 50 mm thick, density 64 kg/m3, wire mesh and 24 gauge aluminum cladding (iii) MS self-support structure for exhaust piping (iv) SS flexible bellows of suitable size as per the recommendation of OEM to match latest CPCB rules complete with counter flanges, heat resistant gaskets, nuts, bolts and washers, etc. complete as required.
[I] Power Cabling (i) LT cable of 1.1 kv grade 3.5 core, 300 mm2 A2XWY cable, shall be measured and paid specified separately.
[J] ACCOUSTIC ENCLOSURE: (i) Acoustic enclosure with insulation of resin bonded fibre glass wool roll of density appx 24 Kg/cum with factory laminated aluminium vapour barrier with and including mechanically fastened nylon / steel/ straps of suitable size. Thickness of insulation shall be as per manufacturer / OEM recommendation to maintain CPCB norms.
[K] FUEL PIPE (i) 50 mm NB MS Class C pipe of required length (ii) Fuel pipe fittings, viz. bends, flanges, valves, tees, elbows, etc as required
AVIATION LIGHT
S&F LED aviation/obstruction light having intensity > 40 cd, die-cast aluminium body, UV stabilized optical lens for 360◦ illumination, inbuilt on-off photo cells, IP 65 rated operating on 90- 270 V, 50 Hz, 1- Ph AC supply complete as specified and directed. Make: Bajaj Cat-Part No. 110731 BGAV 302 LED or equivalent model of Havells, Wipro
M&L Cable 2 core, 1.5 mm² stranded copper conductor (as per IS 8130), XLPE insulated, extruded PVC type ST-2 (as per IS: 5831) sheathed, single layer of galvanized steel flat strip armoured cable of 1.1 kV grade, conforming to IS 7098 (Part-2), including cable termination and cable glanding complete as specified and directed.
S&F Single pole & neutral 2 way, modular type, double door, metallic distribution board conforming to IEC 61439-3, suitable for flush / surface mounting with provision for DP RCCB / RCBO / Isolator / MCB as incomer and SP MCBs as outgoing, reversible metal door, 100 A copper busbar, fully shrouded neutral bar, earth bar, wire set & cable ties for cable management, pre fitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified in IS 732: 2019 and directed. (It shall be connected from common DB). Note: DP RCCB / RCBO / Isolator / MCB & SP MCBs shall be measured and paid separately.
S&F 10 A, 230 V, 50 Hz, SPN/DP MCB for AC applications conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, sliding bottom clamp, colour coded on/off indication on dolly, bi-connect IP 20 protected lower terminals and sliding shutters, etc. complete all as specified in IS 732: 2019 and directed.
S&F Modular type 1 module RJ 45 TV socket complete with GI box, modular plate and cover all as specified and directed. Make: Legrand Arteor, L&T Englaze, Honeywell MK, Schneider Unica Pure
S&F RG 11 coaxial cable having solid electrolytic grade annealed plain copper central conductor of 1.63 mm nominal diameter, gas injected physical polyethylene foam insulated, wrapped with aluminium mylar tape aluminium alloy wire braided, jelly flooded and PVC jacketed including termination complete . cable shall be laid up to outside building / duct as directed all as specified.
S&F Modular type 1 module RJ 11 telephone socket with shutter complete with GI box, modular plate & cover all as specified and directed. Make: Legrand Arteor Cat. Part No. 5734 26 or equivalent model of MK or Havells
EXTERNAL WATER SUPPLY
Supply, installation, testing and commissioning of horizontal split-casing single stage single suction pump having flow rate ≥ 11.2 litre/s @ 80 mWC head in 1 W + 1 S configuration and conforming to IS 6595 (Part 2): 1993 and having horizontal axially split volute type CI delivery casing, suction and discharge nozzles and supporting feet cast integral with lower half casing, enclosed balanced bronze impeller, high tensile steel (CS) shaft supported by antifriction bearing and protected by bronze shaft sleeves in stuffing box area sealed by mechanical seal, deep groove ball / roller bearing, standard drilling flanges etc. suitable for direct coupling with TEFC squirrel cage induction motor suitable for operation on 3-Ph, 415 V±10%, 50 Hz AC supply and conforming to IS 12615: 2018, base plate, mounting channel frame, accessories and fittings, viz. pressure gauge, drain, coupling, coupling guard, vibration isolation arrangement by means of spring / rubber type mounting and foundation as per manufacturer's recommendation and other necessary accessories complete all as specified and directed.
Make: Grundfos, Kirloskar, KSB, Wilo NOTES: [i] Necessary civil work viz. foundation for placement of pump and pump accessories shall be covered in the scope of work. [ii] Pressure gauges & drains shall be measured and paid for separately. [iii] The contractor shall verify pump head before placing the purchase order of pumps.
M&L PN 1.6 rated 100 mm NB swing type foot valve cum strainer, conforming to IS 4038: 1986, suitable for vertical installation and having cast iron body, guide & strainer, soft grade iron plunger, SS spring, bronze seat ring, CS fasteners, flange drilling standard end connection and accessories complete all as specified and directed.
S&F 4" Bourdon tube pressure gauge conforming to EN 837-1, having copper alloy process connection & pressure element, plastic black pointer & case, plastic crystal-clear window, snap-fitted in case, accuracy class 2.5, scale range 0- 25 bar complete with accessories, etc. as specified and directed. Make: General, WIKA, TSI
Supplying, installing ,testing and commissioning of MS air vessel for each delivery header, conforming to IS 4736: 1968, fabricated from 6 mm thick MS plate, 250 mm in diameter and 1 m in height with dished ends fabricated from 8 mm thick MS plate having flanged inlet connection and drain arrangement with 25 mm NB valve, pressure gauge & gun metal stop cock complete as specified and directed.
M&L 1.1 kV grade copper conductor, XLPE insulated unarmoured cable 3 core 10 Sq.mm, 2 XWY, conforming to IS 7098 (Part 1): 1988, having stranded copper compact shaped conductors as per Cl. 2 of IS 8130: 1984, PVC inner sheath and PVC Type ST-2 outer sheath conforming to IS 5831: 1984, including necessary clamping / dressing with cable ties and termination complete all as specified and directed.
S&F 100 mm X 50 mm X 1.6 mm (L X D X T) size of perforated painted with powder coating MS cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with MS suspenders including bolts, etc. complete all as specified and directed. Make: Elcon, Aravali Engineers, Grent
S&F Heavy duty chemical dosing system plunger type suitable to inject solution upto 25 LPH working pressure 10 Kg/cm2 comprising dosing pump coupled with three phase electric motor of capacity 0.5HP, 1440 RPM assembly with agitator in one motor, agitator with SS sweep blade duly FRP coated, FRP tank 150 Ltrs capacity, complete unit mounted on heavy duty MS fabricated frame duly anti corrosive paint complete with chemical grade PVC NRV along with control panel for dosing pump made of powder coated MS fabricated box consisting of LED indicator, digital Volt meter, Amp meter, single phase preventer, high voltage protection unit complete all as specified and directed.
EXTERNAL ELECTRIFICATION
Supply, installation, testing and commissioning of indoor type 3-Ph, 400 A, 12 kV, 50 Hz dead front, floor-standing, fully compartmentalized, metal-clad, dust, damp and vermin-proof VCB module conforming to IS/IEC 62271, having 13.1 kA short time withstand current (for 3 sec) & internal arc tested for 13.1 kA (1 sec) with provision of bolting to the floor, suitable for severe tropical climate conditions (IEC 60068-2-30: 2005), having separately earthed IP 67 rated HV and busbar compartments and IP2X rated LV compartment made of 2.0 mm thick CRCA sheet steel, indoor type motor operated spring closing vacuum circuit breaker (VCB) having SCADA compatible facilities and necessary metering and protection arrangement (including but not limited to surge protection, short-circuit, earth fault, phase sequence or phase balancing, frequency etc.), for rupturing capacity of 250 MVA with all necessary accessories complete as specified and directed. The VCB module shall conform to following technical specifications:-
[i] The VCB shall be inside a hermetically sealed stainless steel tank, filled with SF6 gas, with a service life of 30 yrs for the main circuit without maintenance.
[v] CTs shall be double core window / bar primary and the CT ratio shall be 100-50/5 A. Maximum VA burden shall be 10 VA and rated for full short circuit current for 1 s. CTs shall be of a minimum accuracy of class 0.5/5P10 and CT Secondary rating shall be 5 A unless otherwise specified.
[vi] PT shall be 3-Phase, 3-Limb type with 50 VA per phase of class 0.5/3P accuracy with system voltage 11KV, Ratio 11KV/√3 / 110V/√3 and shall be mounted on incomer breaker truck. The same shall be mounted in a separate withdrawable truck in a separate vertical panel for bus connected PT.
[vii] Control supply for closing and tripping shall be 110 / 220 V DC through an external battery source including suitable battery and battery charging system. 230 V, 50 Hz 1-Ph AC supply shall be also be available for the operation of spring charging motor and cubical space heater. Wattage rating of closing and tripping coils shall be within 250 W.
[viii] All other secondary wiring in the panel shall have high quality PVC insulation and the same shall have conductor size of not less than 1.5 m2 copper.
NOTES:
[a] Necessary control and switching devices to execute the switching and control logic shall be deemed inclusive of the scope of supply irrespective of them being specified / not specified above or in the SLD.
[b] The VCB module shall be tested to withstand vibration caused by an earthquake in accordance with IEC 60068-3-3:2013 or IS 1893 Zone V.
[c] The VCB module shall be purchased from the original equipment manufacturer (OEM) or OEM authorized franchises only.
[d] All the necessary noble components (viz., structural, Door noble like hinge, Bush, Door alignment gauge and Bus bar noble - Bus bar support, Close profile structure - horizontal & vertical) of the Panel shall be supplied by the OEM.
[e] The Contractor shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, typical GADs, etc. to the engineer-in-charge for approval of the MEP Consultant and thereafter A.O. / representative.
[f] The Contractor shall intimate the Engineer-in-Charge of the routine tests in accordance with IEC 62271-200 & IEC 62271-100 in the OEM factory in presence of a representative nominated by the Engineer-in-Charge before dispatch.
Supply, installation, testing, commissioning of 3-Phase 11/0.433 kV, 50 Hz liquid immersed, ONAN cooled 500 kVA indoor step-down distribution transformer having energy efficiency level 3 and conforming to IS 1180-3: 2021, including first filling of natural ester oil conforming to IS 16659: 2017, having dielectric breakdown strength ≥ 50 kV, CRGO bolt-less prime grade core (M4 or better) ensuring high endurance; HV & LV windings wound from paper insulated electrolytic grade copper conductor with tapping on the HV winding for variation of HV voltage within range of +7.5% to -7.5% in steps of 2.5%, hermetically sealed corrugated tank, HV cable box and suitable for LV bus duct complete with all standard fittings / accessories as specified, as per manufacturer’s recommendation and directed. The transformer shall conform to the following specifications:-
[i] Transformer Rating: 500 kVA
[ii] Highest System Voltage: 12 kV
[iii] Rated Voltage (HV/LV): 11 kV / 433 V
[iv] Frequency: 50 Hz ± 3%
[v] No. of Phases: 3
[vi] Connection (HV / LV): Delta / Star (neutral brought out)
[vii] Vector Group: Dyn11
[viii] Type of Cooling: ONAN
[ix] Audible Sound Level: < 75 dB
[xi] Impedance: Upto 4 - 6 %
[xi] Maximum Losses:
(1) Maximum Total Loss @ 50% load, 75 °C: 1.441 kW
(2) Maximum Total Loss @ 100% load, 75 °C: 3.717 kW
[xii] Cable Box / Busduct Clearance (as per CBIP):
(1) HV Cable Box: 165 mm Phase to Phase; 75 mm Phase to Earth
(2) LV Busduct: 40 mm Phase to Phase; 25 mm Phase to Earth
[xiii] Terminal Markings:
(1) HV: 1U, 1V, 1W
(2) LV: 2u, 2v, 2w, 2n
[xiv] Off Circuit Tap Changer (OCTC): Off circuit tap-changing arrangement (+7.5% to -7.5% in steps of 2.5%) shall be either by means of links or by means of an externally-operated switch with mechanical locking device and a position indicator. Arrangement for pad-locking shall be provided.
[xv] The following standard fittings / accessories shall be provided along with the transformer:
(1) Non-detachable rating & terminal marking plates
(2) Monogram plate
(3) Lifting lugs for main tank & top cover & jacking lugs
(4) Top filter valve
(5) Drain cum bottom filter valve
(6) Oil sampling valve
(7) Earthing terminals with lugs: 2 Nos.
(8) Storage & instruction plate
(9) Skid type under base
(10) Bi-directional plain / flange rollers
(11) Detachable type radiators with top & bottom shut-off valve
(12) WTI & OTI with alarm & trip contact
(13) Marshalling box
(14) Magnetic Oil level gauge low oil level alarm contact
(15) Pressure Relief Valve
(16) Buchholz alarm and trip relay.
NOTES:
[a] The Contractor shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, typical GADs, etc. to the engineer-in-charge for approval of the MEP Consultant and thereafter A.O. / representative.
[b] The Contractor shall intimate the Engineer-in-Charge of the routine tests in accordance with IEC 62271-200 & IEC 62271-100 in the OEM factory in presence of a representative nominated by the accepting officer before dispatch. [c] The Contractor shall intimate the engineer-in-charge for the routine tests in accordance with IS: 2026 in the OEM factory in presence of a representative nominated by the accepting officer before dispatch.
Supply, installation, testing and commissioning of factory made, CPRI/ERDA type tested, fully compartmentalized bolted type Main LT Panel (MLTP) (design verified assembly - DVA) of suitable size conforming to IEC 61439-1 & 2 and IEC 61641 and having modular extensible design suitable for indoor mounting, internal arc compliance of minimum 70kA for 0.5 s, made out of 2.0 mm thick mild steel CRCA sheet, having both sides openable with hinged doors and locking arrangement, IP 54 & IK 10 protection, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B-1, with danger notice plate of 1.6 mm thick mild steel vitreous enameled (White) with letter, figures and conventional skull and bones in signal red colour suitable for 3 phase, 4 wire system, 500V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete all as specified and directed by the Engineer-in-Charge. The MLTP shall comprise of the following [A] BUSBAR CHAMBER (i) 01 Set (3L + N) of copper busbar of rated capacity 1250 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection.
[ii] Instrumentation & Measurement (a) CI 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interrupts- 01 Nos. (b) 1000/5A Cl. 1.0 C.T. with 15 VA burden- 02 Nos. (c) 6A, 10kA, 415V, 50 Hz 4P MCB- 01 Nos.
[iii] Indication & Annunciation (a) LED phase indicators (Red, Yellow, Blue)- 01 Set (b) LED status indicators (ON, OFF, TRIP)- 01 Set
[C] OUTGOING
[i] Circuit Breaker
(a) 400 A, 415 V, Ics = 100% Icu = Icw = 36 kA, 50 Hz 3 P MCCB (with LSIG protection), conforming to IEC 60947-2 : 2016, having microprocessor based trip unit, adjustable overload setting, adjustable short-circuit setting, adjustable neutral protection, electrical interlocking, front indication LEDs, etc. - 02 Nos.
(b) 315 A, 415 V, Ics = 100% Icu = Icw = 36 kA, 50 Hz 3 P MCCB (with LSIG protection), conforming to IEC 60947-2 : 2016, having microprocessor based trip unit, adjustable overload setting, adjustable short-circuit setting, adjustable neutral protection, electrical interlocking, front indication LEDs, etc. - 01 No.
(c) 250 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz 3 P MCCB (with LSIG protection), conforming to IEC 60947-2: 2016, having microprocessor based trip unit, adjustable overload setting, adjustable short-circuit setting, adjustable neutral protection, electrical interlocking, front indication LEDs, etc.- 02 Nos.
(d) Spare for to accommodate 01 MCCB.
[ii] Indication & Annunciation
NOTES:
[i] The busbars shall be of double deck arrangement for rating ≥ 2000A interleaved /non-interleaved design as per OEM. Separation of busbar shall be as per Form 4b.
[ii] ACBs shall have separately powered, individual fault trip indication LEDs (For overload, short circuit, earth fault and trip-unit failure) shall be available on the trip unit which shall function even in the absence of external power supply to the breaker.ACB shall be suitable for ZSI. Trip units shall have thermal memory as standard.
[iii] Necessary control and switching devices to execute the switching and control logic shall be deemed inclusive of the scope of supply irrespective of them being specified / not specified above or in the SLD.
[iv] The Panel / Switchboard shall be tested to withstand vibration caused by an earthquake in accordance with IEC 60068-3-3:2013 or IS 1893 Zone V.
[v] The Panel shall be purchased from the original equipment manufacturer (OEM) or OEM authorized franchises only.
[vii] All the necessary noble components (viz., structural, Door noble like hinge, Bush, Door alignment gauge and Bus bar noble - Bus bar support, Close profile structure - horizontal & vertical) of the Panel shall be supplied by the OEM.
[viii] The Contractor shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, typical GADs, etc. to the GE for approval of the MEP Consultant and thereafter A.O. / representative.
[ix] The Contractor shall intimate GE of the routine tests in the OEM factory in presence of a representative nominated by GE before dispatch.
Supply, installation, testing and commissioning of factory made, CPRI / ERDA type tested, fully compartmentalized bolted type Essential Load Panel (ELP) (design verified assembly- DVA) of suitable size conforming to IEC 61439-1 & 2 and IEC 61641 and having modular extensible design suitable for indoor mounting, internal arc compliance of minimum 70 kA for 0.5 s, made out of 2.0 mm thick mild steel CRCA sheet, having both sides openable with hinged doors and locking arrangement, IP 54 & IK 10 protection, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enameled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3-Phase, 4-Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete all as specified and directed. The ELP shall comprise of the following:-
Make: ABB, Legrand, L&T E&A, Schneider, Siemens, BCH
[A] BUSBAR CHAMBER 01 Set (3L + N) of copper busbar of rated capacity 1000 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection.
[B] INCOMING
[ii] Instrumentation & Measurement (a) CI 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interrupts- 01 No. (b) 800/5A Cl. 1.0 C.T. with 15 VA burden- 02 Nos. (c) 6A, 10kA, 415V, 50 Hz 4P MCB- 01 No.
[iii] Indication & Annunciation (a) LED phase indicators (Red, Yellow, Blue)- 01 Set (b) LED status indicators (ON, OFF, TRIP)- 01 Set
[C] OUTGOING
[ii] Indication & Annunciation (a) LED status indicators (ON, OFF, TRIP)- 06 Set (b) LED status indicators (SC, CSH, RTC)- 02 Set
NOTES:
[i] All the MCCBs up to 250 A shall be with thermal magnetic trip unit & above 250A shall be with microprocessor trip units. To ensure failsafe emergency tripping of the breakers (ACBs & MCCBs), it shall be supplied with continuous rated shunt trip coils.
[ii] The Panel shall be purchased from the original equipment manufacturer (OEM) or OEM authorized franchises only.
[iii] All the necessary noble components (viz., structural, Door noble like hinge, Bush, Door alignment gauge and Bus bar noble - Bus bar support, Close profile structure - horizontal & vertical) of the Panel shall be supplied by the OEM.
Supply, installation, testing and commissioning of free-standing indoor, modular, extendable, 200 kVAr APFC Panel having maintenance friendly semi compartmentalized bolted construction, made out of 1.6 mm thick CRCA sheet and built upon rigid framework, having MPP- HD box type capacitor with 7% aluminium wound reactor units type tested in accordance with fully type tested at an Independent laboratory and conforming to IEC 61439-1&2 and IEC 61921 or IS 16636: 2017 with contactor switching, IP 4X protection and including air system provided by axial flow fan or centrifugal fan, control wiring with FR-LSH copper wires complete as specified and directed. The APFC Panel (Capacitor Bank) shall comprise of the following:
[ii] High performance microprocessor based APFC relay with 3 CT sensing auto / manual switch option- 01 Nos.
[iii] MPP-HD box capacitor of 200 (1 X 100 + 1 X 50 + 1 X 25 + 2 X 10 + 1 X 5) kVAr
[iv] 10 kVAr, 525V - 02 STEPS [a] 20 A, 415, Ics = 100% Icu = 16 kA, 50 Hz TP MCCB with fixed magnetic settings and adjustable thermal settings- 02 Nos. [b] 3 P, 10 kVAr Power contactor (Capacitor duty), 415 V, 50 Hz 230 VAC Coil - 02 Nos. [c] 7% detuned reactor, 3- Ph, 10 kVAr, 440 V, 50 Hz- 02 Nos.
[v] 5 kVAr, 525V - 01 STEP [a] 10 A, 415, Ics = 100% Icu = 16 kA, 50 Hz TP MCCB with fixed magnetic settings and adjustable thermal settings- 01 No. [b] 3 P, 5 kVAr Power contactor (Capacitor duty), 415 V, 50 Hz 230 VAC Coil - 01 No. [c] 7% detuned reactor, 3- Ph, 5 kVAr, 440 V, 50 Hz- 01 No.
[vi] 25 kVAr, 525V - 01 STEP [a] 50 A, 415, Ics = 100% Icu = 36 kA, 50 Hz TP MCCB with fixed magnetic settings and adjustable thermal settings- 01 No. [b] 3P, 25 kVAr power contactor (capacitor duty), 415 V, 50 Hz 230 VAC coil- 01 No. [c] 7% detuned reactor, 3- Ph, 25 kVAr, 440 V, 50 Hz- 01 No.
[vii] 50 kVAr, 525V - 01 STEPS [a] 80 A, 415, Ics = 100% Icu = 36 kA, 50 Hz TP MCCB with fixed magnetic settings and adjustable thermal settings- 01 No. [b] 3P, 50 kVAr power contactor (capacitor duty), 415 V, 50 Hz 230 VAC coil- 01 No. [c] 7% detuned reactor, 3- Ph, 50 kVAr, 440 V, 50 Hz- 01 No.
[vi] 100 kVAr, 525V - 01 STEPS [a] 200 A, 415, Ics = 100% Icu = 36 kA, 50 Hz TP MCCB with fixed magnetic settings and adjustable thermal settings- 01 No. [b] 3P, 100 kVAr power contactor (capacitor duty), 415 V, 50 Hz 230 VAC coil- 01 No. [c] 7% detuned reactor, 3- Ph, 100 kVAr, 440 V, 50 Hz- 01 No.
NOTES:
[i] The APFC Panel shall be sourced directly from the OEM only.The APFC Panel described as above complete in all respect as per specification enclosed, up to the entire satisfaction of engineer-in-charge.
[ii] To ensure safety, reliability and accountability of component co ordination, all the major capacitor bank components such as capacitor units, de tuning reactors, PF controllers, circuit breakers, contactors and the enclosure system called for in this specification should preferably be from a single manufacturer.
[iii] The OEM shall manufacturer PFC components and switchgear. The OEM's specified cannot authorize any other partners / sub vendors to manufacture APFC Panels on their behalf. The APFC Panel manufactured by OEM's only will be accepted & factory acceptance test (FAT) will be carried out at OEM's plant only.
[iv] The APFC Panel shall have 10% extra space for future expansion.
Supply, installation, testing & commissioning of UL listed tube based Panel Fire Suppression System having 4 Kg automatic fire cylinder of CO2, linear pneumatic detection tube, CO2 discharge tubing with nozzles for protected panel space, master control unit having LED flasher, electronic hooter, LED indicator, silent switch, etc. with a provision for integration with the FACP along with all necessary accessories complete all as specified and directed.
S&F Perforated hot dipped galvanized iron cable tray having galvanization thickness not less than 50 microns and perforation not more than 17.5% including fittings viz. joints, bends, tees, etc. in convenient sections of length complete all as specified and directed. Make: Aravali Engineers, Elcon, Grent
300 mm X 50 mm X 1.6 mm
150 mm X 50 mm X 1.6 mm
100 mm X 50 mm X 1.6 mm
S&F LED bollard light fittings with LED light 8/9/10 Watt integral decorative with opal acrylic cone series IP 65 protection, and electronic LED driver, etc. with all accessories internal prewired & including connecting up with 2 core flexible copper conductor cable and foundation made of bricks with cement plaster of size 30 cm x 30 cm x 45 cm (height), including sintex box with heavy duty four pole connector 32 A - one no. and 6 A- MCB, sintex box of size 20 cm x 15 cm housed in the foundation with incoming/ outgoing PVC pipe of suitable size of cable all specified and directed.
M&L GI octagonal poles complete with single armed brackets as specified all for 6 m long with 70 mm top diameter and 130 mm bottom diameter, made of 3 mm thick tensile sheet along with base plate of size 225 X 225 X 12 mm thick, including 04 Nos. of M24 X 750 long 'J' type foundation bolts, MCB 6 A with 4-way heavy duty connector 32 A, single arm bracket and RCC foundation as per manufacturer's drawing(s) complete as specified and directed. Make: Jindal, Crompton, Bajaj
S&F 90 W LED street light having high efficiency long life LED module with SMD LED package mounted on MCPCB with high LED efficacy of > 100 lumen/W, integral SMPS based constant current electronic LED driver with THD < 10%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, IP 66 protection, high efficiency polycarbonate cover with integrated lens housed in pressure die-cast aluminium alloy heat sink for effective thermal management, sturdiness, excellent corrosion resistance, separate optical and control gear compartment & top opening for easy maintenance, suitable for side entry, pole mounting with bracket arm OD 35 mm to 42 mm including necessary electrical connection to the fixture with 3 core flexible copper conductor cable of appropriate size complete as per OEM specification/ dwg and as directed.
Supply, installation, testing and commissioning of intelligent street light control (ATSC) suitable for 6 kW maximum load, wall/pole mounted, having built-in networking support, built-in astronomical timer, 32 A TP contactor, 40 A TPN MCB housed in 3.15 mm thick powder CRCA sheet housing complete as all specified and directed. (for street light and bollard light) Make: Havells, HPL, Insu
FIRE SAFETY SYSTEM
Supply, installation, testing and commissioning of FM approved and UL listed microprocessor- based, true peer-to-peer networkable, 6 loop (extendable up to 10 loops) addressable Fire Alarm Control Panel (FCAP) with its own microcontroller memory, communication module, fire device loop interface cards for intelligent initiating and indicating devices and peer-to-peer networkable with other addressable fire alarm panels. conforming to UL 2572 mass notification systems & NFPA 72, with required accessories complete all as specified and directed. The FACP shall meet the following specifications / functional requirements:- Make: Bosch, Notifier NFS2-3030, Simplex
[a] The FACP shall have one to ten isolated intelligent Signaling Line Circuits (SLCs) capable of connecting up to 159 detectors and 159 modules per SLC or 318 devices per loop. [b] The FACP shall have a degrade mode and the loops shall work in degrade mode in case of the CPU failure. [c] The FACP shall have 640 character LCD backlit display/ Touch Screen display, full QWETRY program keypad, LED indicators viz. power; fire alarm; supervisory; system trouble; other event; signals silenced; point disabled; CPU failure; controls active; etc. membrane switch controls viz. acknowledge; signal silence; drill; system reset; lamp test; etc [d] The FACP shall have four access levels, flash EPROM, 240 VAC power supply, automatic battery charger, 24 V sealed lead acid batteries, sufficient for 24 hrs normal working and 30 min in alarm condition.
[e] The FACP shall have manual sensitivity adjustment up to nine levels, built-in alarm; trouble; security and supervisory relays, history file with 4000-event capacity in non-volatile memory plus separate 1000-event alarm-only file, keypad operation, LCD unit to indicate fire / fault signal of individual unit, in built printer to log all incoming data, etc. [f] The FACP shall have integrated 8 channel digital voice evacuation system controller capable of broadcasting evacuation messages on the same peer-to-peer network, fire fighter's telephone two-way communication system capable of supervising all the speaker circuits with adequate zone control and accessories etc.
NOTES: [i] The FACP shall be serviceable by any system integrator & shall not have dependency on specific system integrator. [ii] The FACP shall have feature to "ADD", "EDIT" & "DELETE" field devices like detectors & modules without dependency on PC / Software / Special tool / dongle.
Supply, installation, testing and commissioning of FM approved and UL listed Network Control Display (NCD/REPETER PANEL) capable of full supervision of all inputs and network integrity, having 10" high definition 1024 X 600 colour touch screen display, environmental adjustment controls to maximize LCD legibility, LED status indicators (for power supply and off normal condition), network connection, three USB connections, trouble relay, tamper and trouble inputs, etc. and features viz. network-wide acknowledge silence, reset, lamp test, fully programmable node-mapping subsystem, colour coded icon based event notification, event vectoring, etc. along with UL listed non-resettable 24 VDC power source complete all as specified and directed. Make: Bosch, Hochiki, Notifier, Simplex
Supply, installation, testing and commissioning of FM approved and UL listed intelligent plug-in photoelectric mult heat and smoke detector, conforming to UL 268 7th Edition, sealed against back pressure, with sensitivity range 0.5 % to 4.0 % per foot obscuration, two-wire SLC connection, fixed-temperature set point 135°F (57°C), built-in functional test switch activated by external magnet, built-in tamper resistant feature, remote test feature from the panel, dual LED design providing 360° viewing angle, visible bi-colour LEDs blink green every time the detector is addressed, and illuminate steady red on alarm, compatible with Flash Scan® and CLIP protocol systems, Rotary, decimal addressing, etc. and having the ability to combine temperature thermal sensing with optical sensing, complete with all accessories viz. base, base box, etc. to be installed below / above false ceiling, roof and concealed space, etc. complete all as specified and directed. Make: Bosch, Hochiki, Notifier, Simplex
Supply, installation, testing and commissioning of FM approved and UL listed intelligent plug-in intelligent thermal detector, two-wire SLC connection, fixed-temperature set point 135 °F (57 °C), rate of temperature rise 15 °F (8.3 °C) per minute, built-in functional test switch activated by external magnet, built-in tamper resistant feature, remote test feature from the panel, dual LED design providing 360° viewing angle, visible bi-colour LEDs blink green every time the detector is addressed, and illuminate steady red on alarm, compatible with Flash Scan® and CLIP protocol systems, rotary & decimal addressing, etc. complete with all accessories viz. base, base box, etc. to be installed below / above false ceiling, roof and concealed space, etc. complete all as specified and directed. Make: Bosch, Hochiki, Notifier, Simplex
S&F Flush / ceiling wall mounted remote response indicator to duplicate detector alarm latching LED(s), compatible for two wire detectors, having 12 VDC operating voltage, dual LEDs for 360⁰ visibility in case the detector is placed above the false ceiling / inside closed room complete all as specified and directed. Make: Bosch, Hochiki, Notifier, Simplex
Supply, installation, testing and commissioning of FM approved and UL listed fault isolator module powered by SLC loops directly to protect system against wire-to-wire short circuits on the SLC loops by limiting the number of modules or detectors that may be rendered inoperative by a short circuit fault on the SLC loop, having integral LED indicators, high noise immunity, SEMS screws with clamping plates for ease of wiring complete all as specified and directed. Make: Bosch, Hochiki, Notifier, Simplex
NOTES: [i] The Fault Isolator Module shall not require any address-setting, and its operations shall be totally automatic. [ii] It shall not be necessary to replace or reset an Fault Isolator Module after its normal operation.
Supply, installation, testing and commissioning of FM approved and UL Intelligent monitor module with built in type identification automatically identifying the device as a monitor module to the FCAP to supervise a circuit of dry contact input devices viz. flow switch of sprinkler line, powered directly by two wire SLC loop, high noise immunity, SEMS screws with clamping plate for ease of wiring, direct dial entry of addresses, LED indicators etc. complete all as specified and directed. Make: Bosch, Hochiki, Notifier, Simplex
Supply, installation, testing and commissioning of FM approved and UL listed addressable control module to provide FACP a circuit for notification appliances (viz. Horns, strobes, horn strobe etc.) having built in type identification, integral LED indicators, high noise immunity, SMES screws with clamping plates for wiring ease, direct-dial entry of address, etc. complete all as specified and directed. Make: Bosch, Hochiki, Notifier, Simplex
Supply, installation, testing and commissioning of FM approved and UL listed addressable relay module to provide FACP a dry-contact output for activating a variety of auxiliary devices, viz. fans, dampers, control equipment, etc. having built-in type identification, integral LED indicators, high noise immunity, SMES screws with clamping plates for wiring ease, direct-dial entry of address, etc. complete all as specified and directed. Make: Bosch, Hochiki, Notifier, Simplex
Supply, installation, testing and commissioning of FM approved and UL listed surface / semi- flush mounted Dual Action Manual Pull Station "Push In & Pull Down" (MCP) including an addressable interface for the intelligent FACP having built-in bicolour LED which is visible, flashing in normal operation and latching steady red in alarm condition, captive screw terminals wire-ready for easy connection to SLC loop complete all as specified and directed by engineer-in-charge. Make: Bosch, Hochiki, Notifier, Simplex
Supply, installation, testing and commissioning of UL listed Horn Strobe wired as a primary notification appliance, flashing 75 cd at 1 Hz over the strobe's entire operating voltage range, xenon flash tube and associated lens / reflector system, built-in synchronization feature keeping strobes in sync for up to 30 minutes, horn producing audible annunciation of 75 dBA at 3 m distance complete all as specified and directed. Make: Bosch, Hochiki, Notifier, Simplex
Supply, installation, testing and commissioning of UL listed Fire fighter's addressable Telephone Jack mounted to a single-gang electrical back box with suitable interface module for two way communication with the Central Fire Fighter Telephone Console complete all as specified and directed. Make: Bosch, Hochiki, Notifier, Simplex
Supply, installation, testing and commissioning of UL listed Fire Fighter's Telephone Handset for two way communication with the Central Fire Fighter Telephone Console complete all as specified and directed. Make: Bosch, Hochiki, Notifier, Simplex
M&L Low smoke zero halogen (LSOH) flame retardant fire alarm cable, conforming to BS 7629-1, BS 6387 & BS EN 50200 and rated for 500 V, drawn through concealed with and including PVC conduit not less than 20 mm and having plain annealed stranded copper conductor with primary insulation of glass mica fire resistant tape and secondary insulation of high performance silicone rubber, earth/drain wire of annealed tinned copper, electrostatic screen of aluminium fire barrier and type LTS3 outer sheath conforming to BS 7655, suitable for operating temperature range -30 ˚C to +70 ˚C and minimum bending radius being 6 times the overall cable diameter, RED in colour, including laying, termination and ferruling complete all as specified and directed.
2 core, 1.5 mm²
2 core, 2.5 mm² (supply to hooter/strobe)
M& Transparent FR PVC insulated, twin core copper conductor flexible industrial Speaker cable having stranded annealed tinned copper conductor, PVC insulated cores twisted to form pairs, shielded for interference rejection, unarmoured PVC sheathed 1.1 kV grade in conductor size 2 X 1.0 mm2 including laying, with and including PVC conduit not less than 20 mm, termination and ferruling complete all as specified and directed.
Supply, installation, testing and commissioning of UL listed all purpose 2 W ceiling speaker having crush and rust resistant design and fully ABS plastic & ABS grille with tap-setting range between 1/4 W and 2 W, rated (RMS) voltage 70.7 V, sound pressure level at 1 W (1 m & 1 kHz) 80 ± 4 dB, frequency response 125 Hz- 16 kHz, (-10 dB with reference to 1 kHz), complete all as specified and directed. Make: Bosch, Hochiki, Notifier, Simplex
Supply, installation, testing and commissioning of UL listed Digital Audio Amplifier capable of accessing and processing one of up to eight audio channels on the DVC audio loop, amplifying the signal and distributing it via eight Class B (speaker line) outputs having two wire digital audio ports to connect to wire DAL (digital audio loop) segments, Firefighter telephone riser supporting 7 active firefighter telephones, 300 W total output at 70 V (RMS) complete all as specified and directed. Make: Bosch, Hochiki, Notifier, Simplex
Supply, installation, testing and commissioning of electric driven Main Fire Pump to deliver 2850 LPM flow rate at 135 mWC head and suitable for automatic operation and consisting of following, complete with accessories as specified and directed. The fire pump shall consist of the following:- Make: Kirloskar, SPP Pumps, Precision Engineering Works
[i] Horizontal type, single suction, multi-stage multi-outlet pump of cast iron body & stainless steel impeller with stainless steel shaft, mechanical seal, etc. conforming to IS 12469: 2019, suitable RPM to deliver 2850 LPM flow rate at 135 MWC head.
[ii] Suitable HP squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on 3- Ph, 415 V, 50 Hz AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class 'F' insulation, conforming to IS 12615: 2018 & IS 15301: 2003.
[iii] MS fabricated common base-plate, coupling, coupling guard, foundation bolts, etc. complete with accessories as required.
[iv] Suitable cement concrete foundation duly plastered with anti vibration pads.
Supply, installation, testing and commissioning of diesel engine driven main fire pump to deliver 2850 LPM flow rate at 135 mWC head and suitable for automatic operation and consisting of following, complete with accessories as specified and directed. The fire pump shall consist of the following:- Make: Kirloskar, SPP Pumps, Precision Engineering Works
[i] Horizontal type, single suction, multi-stage multi-outlet pump of cast iron body & stainless steel impeller with stainless steel shaft, mechanical seal, etc. conforming to IS 12469: 2019, suitable RPM to deliver 2850 LPM flow rate at 135 MWC head.
[ii] Suitable HP, suitable RPM, diesel engine, water cooled with radiator, confirming to IS- 10002 : 1981, complete with auto starting mechanism, 12 / 24 V electric starter equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specifications, stop solenoid for auto stop in the event of fault with audio indication, painted with post office red colour etc. as required.
[iii] MS fabricated common base-plate, coupling, coupling guard, foundation bolts, etc. complete with accessories as required.
[iv] Suitable cement concrete foundation duly plastered with anti vibration pads.
Supply, installation, testing and commissioning of electric driven Jockey Pump to deliver 180 LPM flow rate at 135 mWC head and suitable for automatic operation and consisting of following, complete with accessories as specified and directed. The Jockey pump shall consist of the following:- Make: Kirloskar, SPP Pumps, Precision Engineering Works
[i] Horizontal type, single suction, multi-stage multi-outlet pump of cast iron body & stainless steel impeller with stainless steel shaft, mechanical seal, etc. conforming to IS 12469: 2019, suitable to deliver 180 LPM flow rate at 135 MWC head.
[ii] Suitable HP squirrel cage induction motor, TEFC, synchronous suitable RPM and suitable for operation on 3- Ph, 415 V, 50 Hz AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class 'F' insulation, conforming to IS 12615: 2018.
[iii] MS fabricated common base-plate, coupling, coupling guard, foundation bolts, etc. complete with accessories as required.
[iv] Suitable cement concrete foundation duly plastered with anti vibration pads.
Supply, installation, testing and commissioning of factory made, CPRI / ERDA type tested, fully compartmentalized bolted type Fire Emergency Panel (design verified assembly- DVA) of suitable size conforming to IEC 61439-1 & 2 and IEC 61641 and having modular extensible design suitable for indoor mounting, internal arc compliance of minimum 70 kA for 0.3 s, made out of 2.0 mm thick mild steel CRCA sheet, having both sides openable with hinged doors and locking arrangement, IP 54 & IK 10 protection, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enameled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3-Phase, 4-Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete all as specified and directed by the engineer-in-charge. Note: Rate quoted shall be included for control wiring for smooth functioning of fire control panel in auto mode / manual mode. The FEP shall comprise of the following:- Make: ABB, Legrand, L&T E&A, Schneider, Siemens, BCH
[A] BUSBAR CHAMBER 01 Set (3L + N) of copper busbar of rated capacity 1000 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection
[C] OUTGOING [i] Circuit Breaker (a) 200 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz 3P MCCB (LSI protection), conforming to IEC 60947-2: 2016, having microprocessor based trip unit, adjustable overload setting, adjustable short-circuit setting, front indication LEDs, etc.- 03 Nos. (for EP 2W+1S)
[iii] Instrumentation & Measurement (a) 400/5A Cl 1.0 CT having 15VA burden- 03 Nos. (b) 100/5A Cl 1.0 CT having 10VA burden- 03 Nos. (c) 50/5A Cl 1.0 CT having 5VA burden- 03 Nos. (d) 0-400A ammeter- 03 Nos. (e) 0-80A ammeter- 03 Nos. (f) 0-63A ammeter- 03 Nos. [iv] Indication & Annunciation (a) LED status indicators (ON, OFF, TRIP)- 02 Set NOTES: [i] The busbars shall be of double deck arrangement for rating ≥ 2000A interleaved /non-interleaved design as per OEM. Separation of busbar shall be as per Form 4b. [ii] All the MCCBs up to 250 A shall be with thermal magnetic trip unit & above 250A shall be with microprocessor trip units. To ensure failsafe emergency tripping of the breakers (ACBs & MCCBs), it shall be supplied with continuous rated shunt trip coils. [iii] Necessary control and switching devices to execute the switching and control logic shall be deemed inclusive of the scope of supply irrespective of them being specified / not specified above or in the SLD. [iv] The Panel/Switchboard shall be tested to withstand vibration caused by an earthquake in accordance with IEC 60068-3-3:2013 or IS 1893 Zone V. [v] The Panel shall be purchased from the original equipment manufacturer (OEM) or OEM authorized franchises only.
[vi] All the necessary noble components (viz., structural, Door noble like hinge, Bush, Door alignment gauge and Bus bar noble - Bus bar support, Close profile structure - horizontal & vertical) of the Panel shall be supplied by the OEM. [vii] The Contractor shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, typical GADs, etc. to the engineer-in-charge for approval of the MEP Consultant and thereafter A.O. / representative. [viii] The Contractor shall intimate the Engineer-in-Charge of the routine tests in the OEM factory in presence of a representative nominated by the Engineer-in-Charge before dispatch.
M&L Low Smoke Zero Halogen (LS0H) fire survival control cable with circuit integrity, conforming to BS 7846 and rated for 600 V, having plain annealed stranded copper conductor with fire-resistant mica tapes covered by an extruded layer of cross-linked polyethylene, extruded layer of thermoplastic low smoke zero halogen (LS0H) compound, single layer of galvanized steel wires and thermoplastic LS0H compound sheath, suitable for operating temperature range -40 ˚C to +90 ˚C and minimum bending radius being 12 times the overall cable diameter, including laying, clamping, termination and ferruling complete as specified and directed for following size of cables:-.
2 core, 2.5 mm² (for instrumentation)
3 core, 2.5 mm² (for auto start/stop panel)
12 core, 2.5 mm² (for diesel engine pump)
M&L ISI marked, 1.1 kV grade copper conductor, XLPE insulated, armoured cables conforming to IS 7098 (Part 2): 1985, having stranded copper compact shaped conductor as per Cl. 2 of IS 8130: 1984, extruded PVC inner sheath and PVC Type ST-2 outer sheath, conforming to IS: 5831- 1984, single layer of galvanised steel round wire/ flat strip armouring including necessary clamping / dressing with cable ties and termination complete as specified and directed for following size of cables:-
3 core 70 mm² (For electric motor driven main fire pump)
3 core 16 mm² (for Jocky pump and other motors)
S&F 300 mm X 50 mm X 1.6 mm (LxDxT) size of perforated painted with powder coating MS cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with MS suspenders including bolts, etc. complete all as specified and directed. Make: Elcon, Aravali Engineers, Grent, OBO
M&L ASTM (UPVC) D 1785 / Sch 80 pipe, conforming to IS 4985: 2000, with all fittings fixed to walls and ceilings or laid in floors complete as specified and directed. Make: Astral, Precision, Finolex NOTES: [i] All hangers, clamps, brackets etc. shall be of galvanized iron. [ii] Welding of any kind on the galvanised support / hanger shall not be permitted.
M&L PN 1.6 rated 250 mm NB polypropylene vortex inhibitor suction lift, conforming to BS 4504 with stainless wire mesh, bolts, nuts and washers, etc. complete all as specified and directed. Make: Tyco, Associated Enterprise, HD
M&L PN 1.6 rated 250 mm NB CI 'Y' -type strainer with flange end for suction conforming to IS 907: 1984 having CI body, cover, drain plug, SS filter screen, C.N.A.F. gasket, CS bolts and flange drilling standard end connection conforming to IS 1538: 1993 along with necessary accessories complete all as specified and directed. Make: Kirloskar, Leader, Venus
S&F PN 1.6 rated CI sluice valve, 250 mm NB, conforming to IS 14846: 2000, having CI body, wedge, bonnet, stuffing box, gland, handwheel, thrust plate, GM body ring, wedge ring, wedge nut, CS bolts & nuts, SS stem, flange drilling standard end connection conforming to IS 1538: 1993, etc. along with necessary accessories complete all as specified and directed.
Supply, installation, testing and commissioning of PN 1.6 rated CI swing check type reflux (non return) valve, 250 mm nominal bore, conforming to IS 5312 (Part 1): 2004, having CI body & flap, H.T. brass locking pin / hinge pin, EPDM 'O' ring, G.M. locking plug, CS eye bolt, flange drilling standard end connection conforming to IS 1538: 1993 along with necessary accessories for following sizes complete as specified and directed.
Supply, installation, testing and commissioning of PN 1.6 rated lever operated, wafer type, CI butterfly valve, conforming to IS 13095: 1991, having CI body, SS disc, CS L-key, bolt & nut, EPDM moulded liner, 'O' ring & packing, hardened steel taper pin, PTFE bushing, flange drilling standard end connection conforming to IS: 1538- 1993 along with necessary accessories complete as specified and directed.
M&L FM approved and UL listed 25 mm NB compact 3 position ball valve with drain orifice (test and drain valve) to test and drain water flow through sprinkler systems having OFF-TEST-DRAIN position, integral sight glass, rated pressure 300 psi, orifice size 15 mm and K factor 5.6, conforming to NFPA 13, along with necessary accessories complete as specified and directed. Make: Tyco, HD, Viking
S&F Orifice plate made out of 6 mm thick SS 304 with orifice of required size to be fitted between flange and landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as specified and directed. Make: Newage, AAAG, Minimax
S&F Non-percolating rubber reinforced lined RRL hose type- A 30 m long fire hose of 63 mm NB size, conforming to IS 636: 1988, rated for bursting pressure of 35.7 kg/cm² complete with gunmetal male & female coupling conforming to IS: 903- 1993, bound and riveted to the hose pipe with copper rivets and 1.5 mm² copper wire complete as specified and directed.
Supply, installation, testing and commissioning of 2- way fire brigade draw- off connection with two 63 mm NB inbuilt gunmetal non-return valves instantaneous coupling type arranged on 100 mm NB pipe manifold and connected to wet riser main as well as to fire water tank including CI butterfly valve, CI non-return valve and MS cabinet with mounting supports, etc. all complete as specified and directed. Make : Newage, AAAG, Minimax
S&F 9 kg capacity water type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted in gunmetal union, high pressure , discharge hose, wall mounting bracket / floor trolley mounting accessories along with suitable signage, etc. complete all as specified and directed. Make: Safex, Ceasefire, Minimax, NewAge, Kanex
S&F 9 kg capacity dry chemical powder (ABC) type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted in gunmetal union, high pressure CO2 gas cartridge, discharge hose, wall mounting bracket / floor trolley mounting accessories along with suitable signage, etc. complete all as specified and directed. Make: Safex, Ceasefire, Minimax, NewAge, Kanex
S&F 3 kg light-weight squeeze grip CO2 type fire extinguisher, conforming to IS 15683: 2006, with CO2 gas filled in brand new seamless cylinder with powder coated finish, made out of Manganese steel with wheel type valve, discharge nozzle, bend & horn, wall mounting bracket / floor trolley mounting accessories along with suitable signage complete all as specified and directed. Make: Safex, Ceasefire, Minimax, NewAge, Kanex
S&F 9 litre mechanical foam type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted with gunmetal union, high pressure CO2 gas cartridge, hose and ABS type branch pipe and wall mounting bracket / floor trolley mounting accessories along with suitable signage complete all as specified and directed. Make: Safex, Ceasefire, Minimax, NewAge, Kanex
S&F Galvanized mild steel Fire bucket (FILLED WITH DRY SAND) conforming to IS 2546: 1974 round bottom type enamel painted, white inside & Red out side and Letter "FIRE" in black out side and handle with mounting bracket complete as specified and directed.
M&L Fireman Axe confirming to IS:926 - 1985, made of cast iron (IS: 210) with chrome plated finish, Handle made of vulcanised rubber capable of withstanding 20000 volts, all as specified and directed. Make: Safex, Ceasefire, Minimax, NewAge, Kanex
Supply, Installation, Testing & Commissioning of AXIAL FANS 18000 CFM, 40 mm SP as per specifications. Fan shall be direct driven VANE AXIAL FLOW FAN AMCA Certified (For Air and Sound Performance).Fan motor shall be suitable for 415 ± 10% volts, 50 cycles, 3 phase power supply of class 'F' insulation. The fan shall be equipped with mounting bracket for the installation of the fans and flexible connections as required. Fan static pressure shall be as indicated. All vane axial fans motors shall be of minimum IE2 efficiency. Fan total efficiency should not be less than 70 % & noise level should not be more than 85 dbA @ 3 m distance for fans when measured in hemispherical reverberant room conditions. Sound attenuators of appropriate length shall be included in the cost to achieve the desired result if required. All the fans shall be hot dipped/galvanized with minimum 220 GSM Zinc Coating, complete all as specified and directed. Axial fans shall comprise and shall have following specifications:- Make : Kruger, JC, Comefri, Nicotra, Humidin
[ii] GI duct suitable size for supply air duct with GI plate as per design approved including SA air grill/ diffuser of suitable size for entire building floors (G + 19) in fire lift shaft and fire lobby - 01 Job
S&F Signages of following type and sizes, made out of 3 mm thick opaque PVC foam board with computer cut, PVC non-reflective self adhesive vinyl painted foam board, complete with mirror fasteners as specified and directed of following details:-
Signage of size 250 mm X 300 mm reading 'IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED OTHERWISE' in 12.5 mm block letters in red and white background, properly spaced to provide good legibility located directly above the call-button and squarely attached to the wall or partition in a way that the top of the sign is not above 2 m from the finished floor level.
Signage of size 150 mm X 600 mm, posted and maintained within each stair enclosure on every floor, indicating the number of the floor in bold type and at 75 mm high numerals in red and white background, securely attached to the stair side of the door in a way that the bottom of the sign is not above 1.5 m from the finished floor level.
Signage of size 150 mm X 600 mm, posted and maintained at each lift landing and on the side of the stairway door from which egress is to be made on every floor, indicating the lift / lift bank / stairway by an alphabetical letter in bold type and at 75 mm high letters in red and white background, securely attached to the side of the stairway door from which egress is to be made in a way that the bottom of the sign is not above 1.5 m from the finished floor level.
M&L Construction of fly-ash brick masonry valve chamber of size 1000 mm X 1000 mm X 1000 mm (internal dimensions) with PCC foundation 1:4:8 type D2 using 40 mm graded stone aggregate, 150 mm thick & 150 mm wide offsets around over 100 mm thick hardcore , 200 mm thick fly-ash brick masonry walls built in CM 1:6, 100 mm thick PCC 1:2:4 Type B1 coping finished even and smooth, rendering 10 mm thick in cement mortar (1:6) finished even and smooth, with out using extra cement internally including top of floor including excavation earth work in hard/dense soil 6 mm thick MS sheet cover fixed on 40 mm X 40 mm X 6 mm thick angle iron frame with hold fasts embedded in PCC cooping with locking arrangement, mild steel handle and painting to steel surfaces with two coats of synthetic enamel paint over one coat of primer including disposal of surplus soil to a distance not exceeding 50 m etc. complete as specified and directed.
COMPOUND WALL, FENCING AND GATE
Providing & fixing Concertina coil fencing with punched tape concertina coil 450 mm dia up to 3.0 m ht of wall with existing angle iron 'Y' shaped placed 2.4 m or 3.0 m apart; stud tired with G.I barbed wire tied to angle made from High Tensile Spring Steel - High Carbon Wire conforming to IS 4454/ Part -1 /Grade –SM duly Hot dipped galvanized with diameter starting from 2.50 mm , UTS 1670 N/mm2, Heavy zinc coating with minimum 230 gms per sqm. all complete as directed. Note: Length shall be measure horizontal straight along wall where concertina coil is provided.
S&F Cast iron arrow, tee, bends and designs of various pattern as per requirement of site for gates, rails, braces, etc., complete, drilled for fixing of hooks and hinges or steel hanging door fittings also fastening, welding and fixing complete including dismantling/ taking down old existing complete all as specified & directed.
M&L Preparation of surfaces of walls of any description and applying two coats of 100% exterior grade acrylic paint (weather proof paint) over one coat of primer complete all as specified & directed.
MODULAR KITCHEN ITEMS
S&F Perforated cutlery basket of size 530 x 505 x 100 mm; fabricated purpose made with stainless steel of grade 304, not less than 6 to 8 Kg each rack, using square hollow tubes for frame work and solid round bars / 26 gauge thick sheet to make desired pattern, suitable for sliding under kitchen platform on a pair of channels, including fixing with steel screws, complete all as specified and directed. Note: Telescopic channels shall be measured and paid separately under respective item.
S&F SS Cup & saucer basket of size 530 x 505 x 100 mm; fabricated purpose made with stainless steel of grade 304, not less than 6 to 8 Kg each rack, using square hollow tubes for frame work and solid round bars / 26 gauge thick sheet to make desired pattern, suitable for sliding under kitchen platform on a pair of channels, including fixing with steel screws, complete all as specified and directed. Note: Telescopic channels shall be measured and paid separately under respective item.
S&F Perforated Thali of size 530 x 505 x 200 mm; fabricated purpose made with stainless steel of grade 304, not less than 6 to 8 Kg each rack, using square hollow tubes for frame work and solid round bars / 26 gauge thick sheet to make desired pattern, suitable for sliding under kitchen platform on a pair of channels, including fixing with steel screws, complete all as specified and directed. Note: Telescopic channels shall be measured and paid separately under respective item.
S&F Plain basket 710 x 505 x 200 mm size; fabricated purpose made with stainless steel of grade 304, not less than 6 to 8 Kg each rack, using square hollow tubes for frame work and solid round bars / 26 gauge thick sheet to make desired pattern, suitable for sliding under kitchen platform on a pair of channels, including fixing with steel screws, complete all as specified and directed. Note: Telescopic channels shall be measured and paid separately under respective item.
S&F Fixed pull out 3 shelf drawer; fabricated purpose made with stainless steel of grade 304, not less than 6 to 8 Kg each rack, using square hollow tubes for frame work and solid round bars / 26 gauge thick sheet to make desired pattern, suitable for sliding under kitchen platform on a pair of channels, including fixing with steel screws, complete all as specified and directed. Note: Telescopic channels shall be measured and paid separately under respective item.
S&F Fixed multipurpose double tier 456 x 170 x 450 mm tray; fabricated purpose made with stainless steel of grade 304, not less than 6 to 8 Kg each rack, using square hollow tubes for frame work and solid round bars / 26 gauge thick sheet to make desired pattern, suitable for sliding under kitchen platform on a pair of channels, including fixing with steel screws, fixed in repairs, complete all as specified and directed. Note: Telescopic channels shall be measured and paid separately under respective item.
Note for item No. 17.82 to 17.87: Model of reputed make (as per recommendation of modular kitchen manufacturer) shall be approved by GE.
S&F Telescopic channels soft closing, mild steel powder coated with ball bearings, suitable for sliding SS plate racks 60 cm long standard width, fixed over 2nd class HW rectangular fillet sectional area exc 3 & n exc 6 sqcm, clean swan secured with screws and the fillet fixed on cudappah stone with screws, all as specified and directed.
S&F Stainless steel hanging spice rack of size 500 mm length x 1500 mm height having three shelves spaces of length 500 mm complete all as specified and directed.
S&F Pull out detergent rack; fabricated purpose made with stainless steel of grade 340 of size 180 x 515 x 485 mm, using square hollow tubes for frame work and solid round bars / 26 gauge thick sheet to make desired pattern, suitable for sliding under kitchen platform on a pair of channels, including fixing with steel screws, complete all as specified and directed. Note: Telescopic channels shall be measured and paid separately under respective item.
S&F Stainless steel handle oval shape ISI marked, fabricated type, anodized 150 mm long of approved design, shape and make fixed in repairs with nut screws & washers complete all as specified and directed.
S&F Stainless steel finish soft closing hinges of approved design, shape and make, ISI marked, fixed with nut screws & washers complete all as specified and directed.
S&F 18 mm thick marine plywood as per IS 710 laminated of any colour with both side high glossy acrylic sheet of 3mm thick grade I of frame and shutter for kitchen cabinets complete all specified and directed .
S&F Hydraulic G lift regular gas spring 250 N with soft closing of approved design, shape, ISI marked, fixed with and including nuts, screw and washers etc. complete all specified and directed .
SCH 'A' PART- XV WORK (COMPREHENSIVE MAINTENANCE OF LIFTS AFTER SUCCESSFUL COMPLETION OF DEFECTS LIABILITY PERIOD)
Comprehensive maintenance and repair of Passenger lift (02 numbers) having capacity 08 passengers (544 Kgs) as installed vide BOQ item No. 15.24 complete all as specified and directed.
(i) First Year after expiry of defect liability period (i.e for 3rd year)
(ii) Second Year after expiry of defect liability period (i.e for 4th year)
(iii) Third Year after expiry of defect liability period (i.e for 5th year)
Comprehensive maintenance and repair of Stretcher cum Fire Lift suitable for 16 passengers/ 1088 Kg (01 Number) as installed vide BOQ item No. 15.30 complete all as specified and directed.
(i) First Year after expiry of defect liability period (i.e for 3rd year)
(ii) Second Year after expiry of defect liability period (i.e for 4th year)
(iii) Third Year after expiry of defect liability period (i.e for 5th year)
JAI CONSTRUCTION CO.
SHRE GURMUKHDAS CONTRACTOR PVT. LTD.
MAHINDER PAL CONSTRUCTIONS PVT LTD
Mukund Enterprises
SOOD ASSOCIATES PVT LTD
Ktech Engineer Builders Co. Pvt. Ltd
Hariom Projects Pvt Ltd