Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹83.3 LAccepted-AOC 46 S P MUKHERJEE ROAD KOLKATA 700026 | KOLKATA | KOLKATA | WEST BENGAL | 700026 | ₹83.3 L | L1 | Accepted-AOC AOC_Issued |
| 2 | L2₹85.5 LRejected-Finance | ₹85.5 L | L2 | Rejected-Finance that the bid is not L1 |
| 3 | L3₹86.9 LRejected-Finance | ₹86.9 L | L3 | Rejected-Finance that the bid is not L1 |
| 4 | L4₹94.0 LRejected-Finance | ₹94.0 L | L4 | Rejected-Finance that the bid is not L1 |
| Sl No | Description | Qty | Unit | M/S N. C. HORE L3 | M/S. A.D.ELECTRICAL ENTERPRISE L4 | C. CHOWDHURY AND CO L1 | THE INDIAN OVERSEAS TRADING COMPANY L2 |
|---|---|---|---|---|---|---|---|
| 1.00Supply , delivery at site on foundation , commissioning of 750 KVA, 415V, 50Hz, 3Ø silent new DG Set, comprising of Engine, alternator, separate AMF panel, Base frame, Fuel tank, Battery, CPCB-II approved Engine & Acoustic Enclosure having following specifications :- | |||||||
| 1.10ENGINE Make : CUMMINS/Caterpillar /Parkins/MTU/Volvo Penta Engine Type : 4 Stroke Diesel Engine RPM : 1500 Rated Output : 891 BHP or Higher Duty : PRIME Cooling : Liquid Cooled Cylinder : 12 Aspiration : Turbo Charged Type of Governor : Electronic Fuel Tank Capacity : As per manufacturer Design. | |||||||
| 1.20Fuel Consumption at 75% rated Load with Radiator or Fan : 130.42 Ltr./ Hr. or Less Fuel Consumption at 100% rated Load with Radiator or Fan : 165 Ltr./ Hr. or Less Overload Capacity : 10% overload for one hour for every 12 hours continuous running at full load or better Engine instrument Panel : Consisting of starting switch with Key, Lube Oil Indicator, water temperature Indicator, RPM indicator and hour meter. Safety Controls : Emergency Stop, Low Lube Oil Pressure warning/ Shutdown, High Engine Water Temp. warning/ Shutdown, Sensor failure Indicator, Engine over speed indicator, Battery charging and low battery indicator | |||||||
| 1.30Exhaust Silencer : Residential Type Starting system : 12V./ 24 V. starting system complete with starter motor, charging alternator with rectifier and Cutout as per manufacturer standard. Battery : Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak Battery warning ALTERNATOR Make : Stamford/ Leroy Somer Rating : 415 V., 3Ph. 50 Hz., 750 KVA, 1500 rpm Type : Brushless, self excited and self regulated Insulation : Class H | |||||||
| 1.40Protection : screen-protected drip proof with Min.IP-23 degree of protection RPM : 1500 Voltage Regulation (max) : ±1% Winding connection : Star with Neutral Total Distortion factor : Less than 3% Total Harmonic distortion in output waveform : < 5% AMF PANEL Cubical type floor mounted AMF panel made from 14 SWG Sheet Steel, duly pretreated, powder coated painted and aesthetically finished, suitable for controlling of 750 KVA DG set having following specification/features. | |||||||
| 1.50i) 415V, 1200 A , 50KA, EDO type ACB with O/L, S/C, E/F protection and microprocessor based protection release , U/V release etc. [make: Legrand DMX3/ Siemens ‘WL’ series / Schneider Electric (Master pact )NW/ L&T (‘U power’ Series) /ABB Emax] - 2Sets ii) In Built By-Pass switch for rated capacity iii) On -delay timer for load change over iv) On-delay timer for engine shut off v) Engine On-Off switch (Push button type) | |||||||
| 1.60vi) Battery charger complete with voltage regulator, booster selector switch, on-off switch, voltmeter and ammeter for charging the battery from mains. This will be in addition to the battery charging alternator fitted on the engine vii) Minimum five number indicating lamps to indicate 'mains ON', 'load on mains', Set running', 'load on set' and 'battery charger on'. viii) Audio visual alarm for 'Low lubricating oil pressure', 'High water temperature, Start failure', and DG over load'. ix) Mode selector for setting the panel on Auto/ Man/ Test Mode x) Microprocessor based relay with composite meter for digital display of following. Generator voltage/AC Mains voltage | |||||||
| 1.70Generator Current in all phases Frequency Power Factor Energy Indication for alternator supply Running time indications number of hours of operation and service intervals, service due indications The AMF panel must be designed to ensure trouble free performance and ensure switching over Electrical Load to DG within 15 (fifteen) second from the instant of mains failure. | |||||||
| 1.80 | ACOUSTIC ENCLOSURE
The DG set should have integrated acoustic enclosure at the manufacturing state itself. High quality acoustic enclosure must be certified as per CPCB-II norms.
Base Frame
Common iron channel fabricated base frame containing the engine and alternator, mounted on AVM pads and having provision for lifting Hook. | 1 | Item | 70,14,000 ₹70.1 L | 79,76,935 ₹79.8 L | 68,95,000 ₹69.0 L | 71,91,156 ₹71.9 L |
| 2.00 | INSTALLATION WORK OF DG:
Providing cement concrete foundation for the DG set with 1:2:4 (1 cement : 2 course sand : 4 graded stone aggregate 20 mm nominal size)[M20 grade ] including excavation, providing base concrete with 1:5:10 cement concrete, required centering/ shuttering, finishing the exposed portion etc. as reqd. ( Item will be paid based on measurements for 1:2:4 CC, but excluding the 1 : 5: 10 leveling course of base concrete) as per direction of E-in-Charge and manufacturer recommendation for 750 KVA DG Set. | 1 | Item | 1,80,000 ₹1.8 L | 2,45,308.5 ₹2.5 L | 3,00,000 ₹3 L | 2,38,906 ₹2.4 L |
Tender Value
Refer Docs
EMD Value
₹1.3 L
Closing Date
30 May 2022, 1:00 pmClosed
EE II KNHED PW Dte
KIT Building Annex, 4thFloor,P-16, India Exch. Place Extn., Kolkata -700073
Construction of Proposed seven storied building with two tire basement for Regional Cancer Centre within compound of Medical College Hospital Kolkata SITC of 415V 3 Ph 750 KVA DG Set
2022_PWDE_380227_1
WBPWD/EE-II/KNHED/NIQ-13/22-23
Open Tender
ELECTRICAL WORKS ORG
90 days
Kolkata
Please refer Tender documents.
5 documents required · 5 mandatory
₹1.3 L
8 May 2026
12 May 2022
1 Jun 2022
14 May 2022
30 May 2022
14 May 2022
Amount
Supply , delivery at site on foundation , commissioning of 750 KVA, 415V, 50Hz, 3Ø silent new DG Set, comprising of Engine, alternator, separate AMF panel, Base frame, Fuel tank, Battery, CPCB-II approved Engine & Acoustic Enclosure having following specifications :-
ENGINE Make : CUMMINS/Caterpillar /Parkins/MTU/Volvo Penta Engine Type : 4 Stroke Diesel Engine RPM : 1500 Rated Output : 891 BHP or Higher Duty : PRIME Cooling : Liquid Cooled Cylinder : 12 Aspiration : Turbo Charged Type of Governor : Electronic Fuel Tank Capacity : As per manufacturer Design.
Fuel Consumption at 75% rated Load with Radiator or Fan : 130.42 Ltr./ Hr. or Less Fuel Consumption at 100% rated Load with Radiator or Fan : 165 Ltr./ Hr. or Less Overload Capacity : 10% overload for one hour for every 12 hours continuous running at full load or better Engine instrument Panel : Consisting of starting switch with Key, Lube Oil Indicator, water temperature Indicator, RPM indicator and hour meter. Safety Controls : Emergency Stop, Low Lube Oil Pressure warning/ Shutdown, High Engine Water Temp. warning/ Shutdown, Sensor failure Indicator, Engine over speed indicator, Battery charging and low battery indicator
Exhaust Silencer : Residential Type Starting system : 12V./ 24 V. starting system complete with starter motor, charging alternator with rectifier and Cutout as per manufacturer standard. Battery : Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak Battery warning ALTERNATOR Make : Stamford/ Leroy Somer Rating : 415 V., 3Ph. 50 Hz., 750 KVA, 1500 rpm Type : Brushless, self excited and self regulated Insulation : Class H
Protection : screen-protected drip proof with Min.IP-23 degree of protection RPM : 1500 Voltage Regulation (max) : ±1% Winding connection : Star with Neutral Total Distortion factor : Less than 3% Total Harmonic distortion in output waveform : < 5% AMF PANEL Cubical type floor mounted AMF panel made from 14 SWG Sheet Steel, duly pretreated, powder coated painted and aesthetically finished, suitable for controlling of 750 KVA DG set having following specification/features.
i) 415V, 1200 A , 50KA, EDO type ACB with O/L, S/C, E/F protection and microprocessor based protection release , U/V release etc. [make: Legrand DMX3/ Siemens ‘WL’ series / Schneider Electric (Master pact )NW/ L&T (‘U power’ Series) /ABB Emax] - 2Sets ii) In Built By-Pass switch for rated capacity iii) On -delay timer for load change over iv) On-delay timer for engine shut off v) Engine On-Off switch (Push button type)
Generator Current in all phases Frequency Power Factor Energy Indication for alternator supply Running time indications number of hours of operation and service intervals, service due indications The AMF panel must be designed to ensure trouble free performance and ensure switching over Electrical Load to DG within 15 (fifteen) second from the instant of mains failure.
ACOUSTIC ENCLOSURE The DG set should have integrated acoustic enclosure at the manufacturing state itself. High quality acoustic enclosure must be certified as per CPCB-II norms. Base Frame Common iron channel fabricated base frame containing the engine and alternator, mounted on AVM pads and having provision for lifting Hook.
INSTALLATION WORK OF DG: Providing cement concrete foundation for the DG set with 1:2:4 (1 cement : 2 course sand : 4 graded stone aggregate 20 mm nominal size)[M20 grade ] including excavation, providing base concrete with 1:5:10 cement concrete, required centering/ shuttering, finishing the exposed portion etc. as reqd. ( Item will be paid based on measurements for 1:2:4 CC, but excluding the 1 : 5: 10 leveling course of base concrete) as per direction of E-in-Charge and manufacturer recommendation for 750 KVA DG Set.
SITC of Self Suppurting Special Type MS Structure Made from 50 mm dia Hollow Pipe, 50 X 50 X 8 mm & 40 X 40 X6 mm MS Angle incld. S & F Annodised GI Sheet to cover up the DG Set as per direction of Engineer-in-Charge [ Drawing and design to be approve by Rngineer in Charge befote execution of Work ]
Supply and Installation of exhaust pipe line connection with MS black pipe 300mm (12”) dia ISI approved, necessary bend, tee etc. and nuts, bolts, washer, gasket incl. electrical welding where necessary.
S&F special type lattice (box) MS angle iron structure made of (65x65x8)mm (4 nos) for main structure with 50mm x 50mm x 6mm MS angle bracing(inclined cross member) properly welded with main structure to support 300mm dia MS pipe, incl CC foundation 1mtr x 1mtr x 2 mtr & painting as per direction of the EIC.
Wrapping the Exhaust pipe line (300mm dia) with Al. sheet high quality with necessary wire mesh & 50mm thick glass wool.as per direction of EIC.
S&F rain protection canopy for 300mm Exhaust pipe.
Hire charges for scaffolding by bamboo required rope of square type arrangement for smooth working & carriage of MS black pipe by vertical run & dismantling at the end of work.
Excavation of soil for installation of Earth Electrode and filling & ramming. For Soft Soil
Earthing with Copper plate (610x610x3mm size) having weight of 9.84 Kg and 1 No. 25x5mm Copper strip (3.20 mt long) & 1 no. 6 sqmm PVC insulated stranded Copper wire (4 Mt long) incl. S & F 15 mm dia GI pipe (ISI-Medium) protection (4 mt. long) to be fillied with bitumen, partly under the ground level & partly above ground level to an average depth of 3.65 Mts. below the ground level and restoring the surface duly rammed incl. providing 3.0 mt long, 25 mm dia GI pipe (ISI-Medium) for periodic treatment,incl. providing masonery enclosure on the top of the earth electrode of overall size 86.36x86.36x46cm deep (below Ground level) complete with cemented brick work (1:6) of 25 cm width, duly plastered with cement morter (inside) CI hinged inspection cover of size36.56x35.56cm with locking arrangement, GI reducer and treatment of soil by using salt & charcoal or coke for plate electrode.
Earthing with 80 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 No. 65 mm x 8 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 80 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe
Extra for treatment of soil by using salt and charcoal for earth electrod .
Supplying & fixing of galvanized (Hot Dip) MS flat 65 mm x 8 mm in excess of 4mt for each earthing and S & F 80 mm dia GI pipe (ISI-Medium) protection to be filled with bitumen.
Supply & Laying of 12core 1.5 Sqmm Copper Aurmoured control cable, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as 100mm and mending good the damages to original finish incl. removing the rubbish
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : 12core 1.5 Sqmm Copper Aurmoured cable
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. 1.5Sqmm
Supply and Laying 150mm dia spiral nylon pipe inside the DG foundation.
Supply, Delivery including transportation of HSD Oil
Supply, Delivery including transportation of Mobil Oil
Supply and delivery Diesel Hand fuel transfer pump . ( manual operation ) as per direction of EIC .
S &D of 200 Ltr Capacity Heavy Guage MS Shrrt Barrel
TERMS & CONDITION (i) Rate should be quoted inclusive of all applicable taxes and Duty etc. (ii) All materials, equipments & accessories must conform to relevant IS specifications. The DG Set to be supplied must be from the authorized OEM of the respective Engine Manufacturer. (iii) Necessary manufacturer's test certificate for Diesel Engine, Alternator etc. Will have to submit in triplicate copy during delivery of the equipment. (iv) Copy of "Type Approval Certificate" and Certificate of "COP" must be produced at the time of delivery issued from competent Authority (As per CPCB-II).
(v) Circuit Diagram for AMF Panel must be submitted from the Manufacturer/OEM. (vi) The entire set must be warranted at least 15 months from the date of Delivery/12 months/ 5000 Hrs from the date of Commissioning whichever is earlier. However Engine & Alternator should be warranted of 2 years/5000 Hrs, whichever is earlier.
Special Terms and Conditions 1. It is stated that the above work place is existing COVID Hospital, In case of any mishap or accidental to any staff that deputed by the agency the whole responsibility is to be borne by the concern agency. 2. The Agency shall be responsible for provisioning of all COVID safety measures including regular sanitiziation of work places, vaccination of employees and compliance of stated directive and COVID appropriate norms. 3. All the issues related to the safety of the staffs should be taken care by the agency itself. (Defect Libilities period for 01 year from the date of completion of work)(Rate should be quotated including all taxes and duties)
THE INDIAN OVERSEAS TRADING COMPANY
M/S N. C. HORE
M/S. A.D.ELECTRICAL ENTERPRISE
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.49 MB
BOQ_742430.xls
BOQ • 0.35 MB
2911.pdf
Tender Documents • 1.86 MB
suspension.pdf
Additional Documents • 2.91 MB
Download all tender documents and submit your bid