Tender Value
₹2.2 Cr
EMD Value
₹2.6 L
Closing Date
25 Feb 2026, 4:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Revenue
ELECT.G
17 conditions · 5 needing a document upload
Financial Eligibility Criteria: (Ref: RB letter No. 2022/CE-I/CT/GCC- 2022/POLICY : Advance Correction Slip No.-1 dt 14.07.2022) The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-I, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
The intending tenderers should possess a valid electrical contractor license at the time of opening of tender, issued by any state government & same should be submitted along with tender documents by all bidders including working contractors of this unit otherwise offer shall be summarily rejected....... IT SHOULD BE NOTED BY THE TENDERER THAT ELECTRICAL LICENSE UNDER RENEWAL AT THE TIME OF TENDER OPENING WILL NOT BE CONSIDERED AND OFFER WILL BE SUMMARILY REJECTED. IT IS THE RESPONSIBILITY OF TENDERER TO UPLOAD VALID ELECTRICAL CONTRACTOR LICENSE ON THE DATE OF TENDER OPENING.
All requisite documents mentioned in clause 3.7 of tender document attached pertaining to constitution of firm/concern. (As applicable).
32 conditions · 4 needing a document upload
The rate to be quoted by tenderer shall be inclusive of all state/central taxes including GST. THE TENDERER SHOULD UPLOAD VALID GST REGISTRATION CERTIFICATE ALONG WITH THE OFFER.
The tender shall comply with General Condition of contract (GCC),2022 of Indian Railways (file attached). and its latest amendment, if any. The tenderer shall submit the offer after duly satisfying himself/herself with the GCC,2022 in general.
Tenderers are required to upload the Bank details as per Annexure-XII (Real Time Gross Saving (RTGS)/National Electronic Fund Transfer (NEFT) Model Mandate Form)of tender document.
Tenderers are required to upload requisite details as per Annexure-VIIB (DETAILS OF CONTRACTUAL PAYMENT RECEIVED IN LAST THREE FINANCIAL YEARS AND CURRENT FINANCIAL YEAR) without which the offer is liable to be rejected.
Tenderers are compulsorily required to upload Affidavit as per Annexure-XXIV along with tender document, without which the offer will be considered incomplete and will be rejected summarily.
All requisite documents/credentials mentioned in clause 3.5 of tender document attached pertaining to his/their technical and financial eligibility. (As applicable).
All requisite documents mentioned in clause 3.7 of tender document attached pertaining to constitution of firm/concern. (As applicable).
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
The site of work is under jurisdiction of DEE/G-II/NDLS ((PS/SMQL), (PS/HNZM, Coach Care Depot), (PS/TKD, Diesel Loco Shed, Wagon Care Depot, Running Room), (PS/SSB, OE&P/SSB, Diesel Loco Shed, Coach Care Depot, Running Room), (PS/DLI & AC-SP/DLI), (PS/PHG, PS/NRCH), (PS/DEE, Coach Care Depot, Running Room), (AC-SP/NDLS), (PS/DKZ), (L&E), (PS/PNP, Coach Care Depot, Running Room), (PS/KKDE, Running Room)) over Delhi Division. However, site can be changed anywhere in Delhi Division, if required.
After opening of tender, any document/credential pertaining to technical, financial eligibility and available Bid Capacity constitution of firm etc. shall neither be asked nor be entertained/ considered under any circumstances and no claim or representation whatsoever from the tenderer in this regard shall be entertained. Scanned copy of the documents, uploaded by the tenderer shall be clear & readable. However Railway reserves the right to ask for any clarification on the documents/credentials already submitted by the tenderer along with the offer. ii)Tenderer may have to produce the original Documents in physical form at short notice whenever asked by Railway at any stage of tender evaluation process or even after finalization of tender. iii)In E-tender, all submissions of documents are to be uploaded on web-site. There may be last minute hic-cups and delay in uploading the Documents and payment of Earnest Money etc. Tenderer's/Prospective bidders are advised to upload their offer well in time. Railway will not be responsible for any delay/non submission of offer due to any reason whatsoever
No post tender correspondence for submission of additional documents shall be entertained after opening of the Technical & Commercial offers. Even suo-moto post tender letters of the tenderer/s shall be treated as Null & Void.
Payment clause as per special conditions 100% payment will be done after successful supply, installation, testing and commissioning of actual work done by the tenderer and on certification by the Railway representative. No part payment shall be made for supply of material.
This tender complies with Public Procurement Policy (Make in India) Order 2017, dated 15/06/2017, issued by Department of Industrial Promotion and Policy, Ministry of Commerce, circulated vide Railway Board letter no. 2015/RS(G)/779/5 dated 03/08/2017 and 27/12/2017.
IF ANY DISCREPANCY IS FOUND IN THE TENDER DOCUMENT, NAMELY SOR ITEM DESCRIPTION, SPECIAL TENDER CONDITION ETC., CLARIFICATION CAN BE SOUGHT FROM THE OFFICE OF SRDEE/G/DLI, DRM OFFICE, STATE ENTRY ROAD, NEW DELHI.
This tender complies with Railway Board instructions for Startups (recognized by Department of Industrial Policy and Promotion, Ministry of Commerce and Industry) for exemption from payment of Bid Security as detailed in GCC 2022 as amended from time to time. Such Startup firms may note that no other exemption is applicable to them in this particular tender.
On account payment, contractor shall submitted indemnity bond with validity up to the completion/extended period in the prescribed format (please refer Annexure-XXVIII) at the contractor's cost, vesting the ownership of such material with the railways.
Electrical work in connection with Repair and maintenance of electrical assets installed in zone of DEE/G-II/DLI (Service Building and Railway quarters).
55-SRDEE-G-DLI-2025-26~NR
55-SRDEE-G-DLI-2025-26
Open
Works - General
15 Months
Delhi, Delhi
₹0
₹2.6 L
25 Feb 2026
3 Feb 2026
11 Feb 2026
251 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 2,23,78,495 | ||
| — | 2000.00 | — | — | ||
| Supply and recessing/fixing of PVC conduit pipe of 25mm size conforming to IS:9537 Part-III:1987 (or Latest version) with accessories junction box, bends etc. including making chase, plastering/clamping etc. as per site requirement conforming to IS 9537 (Part 3): 1983 or latest & as per Explanatory Note . | — | — | — | 62,000 | |
| — | 10000.00 | — | — | ||
| Supply, Fixing, testing & commissioning of following sizes FRLSH PVC insulated multi stranded copper (annealed) conductor single core cable conforming to IS 694 (or Latest Version) , and drawing in Laid (recessed /surface) PVC conduit pipe for wiring of point wiring / circuit wiring / sub main / main as required including connections, testing and commissioning. Size = 1x1.5 sq.mm. & as per Explanatory Note . | — | — | — | 2,40,000 | |
| — | 10000.00 | — | — | ||
| Supply, Fixing, testing & commissioning of following sizes FRLSH PVC insulated multi stranded copper (annealed) conductor single core cable conforming to IS 694 (or Latest Version) , and drawing in Laid (recessed /surface) PVC conduit pipe for wiring of point wiring / circuit wiring / sub main / main including connections, testing and commissioning. Size = 1x2.5 sq.mm . & as per Explanatory Note . | — | — | — | 4,00,000 | |
| — | 7000.00 | — | — | ||
| Supply, Fixing, testing & commissioning of following sizes FRLSH PVC insulated multi stranded copper (annealed) conductor single core cable conforming to IS 694 (or Latest Version) , and drawing in Laid (recessed /surface) PVC conduit pipe for wiring of point wiring / circuit wiring / sub main / main including connections, testing and commissioning. Size = 1x4.0 sq.mm. & as per Explanatory Note . | — | — | — | 3,71,000 | |
| — | 1000.00 | — | — | ||
| Supply, Fixing, testing & commissioning of following sizes FRLSH PVC insulated multi stranded copper (annealed) conductor single core cable conforming to IS 694 (or Latest Version) , and drawing in Laid (recessed /surface) PVC conduit pipe for wiring of point wiring / circuit wiring / sub main / main including connections, testing and commissioning. Size = 1x6.0 sq.mm. & as per Explanatory Note . | — | — | — | 88,000 | |
| — | 1000.00 | — | — | ||
| Supply, Fixing, testing & commissioning of following sizes FRLSH PVC insulated multi stranded copper (annealed) conductor single core cable conforming to IS 694 (or Latest Version) , and drawing in Laid (recessed /surface) PVC conduit pipe for wiring of point wiring / circuit wiring / sub main / main including connections, testing and commissioning. Size = 1x10.0 sq.mm. & as per Explanatory Note . | — | — | — | 1,35,000 | |
| — | 100.00 | — | — | ||
| Supply, Fixing, testing & commissioning of Batten/Angle Holder conforming to IS : 1258-2005 (or Latest Version) & installation on the junction box of laid conduit including connections, testing & commissioning as per site requirement and as per Tech. Specification & as per Explanatory Note . | — | — | — | 12,100 | |
| — | 500.00 | — | — | ||
| Supply, Fixing, testing & commissioning of ceiling rose, 3 plate conforming to IS : 371- 1999 (or Latest Version) & installation on the junction box of laid conduit including connections, testing & commissioning as per site requirement and as per Tech. Specification & as per Explanatory Note. | — | — | — | 35,000 | |
| — | 50.00 | — | — | ||
| Supply, fixing, testing and commissioning of following modules, GI box alongwith modular base and cover plate for modular switches/ sockets in recess etc as required as per IS, IE rules and site requirement complete and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 conforming to latest relevant IS & as per Explanatory Note. Size = 3 Module | — | — | — | 3,250 | |
| — | 100.00 | — | — | ||
| Supply, fixing, testing and commissioning of following modules, GI box alongwith modular base and cover plate for modular switches/ sockets in recess etc as required as per IS, IE rules and site requirement complete and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 conforming to latest relevant IS & as per Explanatory Note. Size= 4 Module | — | — | — | 9,100 | |
| — | 100.00 | — | — | ||
| Supply, fixing, testing and commissioning of following modules, GI box alongwith modular base and cover plate for modular switches/ sockets in recess etc as required as per IS, IE rules and site requirement complete and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 conforming to latest relevant IS & as per Explanatory Note. Size= 6 Module | — | — | — | 10,100 | |
| — | 100.00 | — | — | ||
| Supply, fixing, testing and commissioning of following modules, GI box alongwith modular base and cover plate for modular switches/ sockets in recess etc as required as per IS, IE rules and site requirement complete and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 conforming to latest relevant IS & as per Explanatory Note. Size= 8 Module | — | — | — | 12,400 | |
| — | 100.00 | — | — | ||
| Supply, fixing, testing and commissioning of following modules, GI box alongwith modular base and cover plate for modular switches/ sockets in recess etc as required as per IS, IE rules and site requirement complete and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 conforming to latest relevant IS & as per Explanatory Note. Size= 12 Module | — | — | — | 19,000 | |
| — | 2000.00 | — | — | ||
| Supplying and fixing following modular switch /socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required as per IS, IE rules and site requirement complete and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 conforming to latest relevant IS & as per Explanatory Note. 5/6 Amp Switch | — | — | — | 1,06,000 | |
| — | 500.00 | — | — | ||
| Supplying and fixing following modular switch /socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required as per IS, IE rules and site requirement complete and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 conforming to latest relevant IS & as per Explanatory Note. 16 Amp Switch | — | — | — | 43,000 | |
| — | 1000.00 | — | — | ||
| Supplying and fixing following modular switch /socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required as per IS, IE rules and site requirement complete and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 conforming to latest relevant IS & as per Explanatory Note. 3 pin 5/6 A socket outlet | — | — | — | 1,00,000 | |
| — | 500.00 | — | — | ||
| Supplying and fixing following modular switch /socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required as per IS, IE rules and site requirement complete and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 conforming to latest relevant IS & as per Explanatory Note. 6 pin 15/16 A socket outlet | — | — | — | 70,500 | |
| — | 100.00 | — | — | ||
| Supplying and fixing following modular switch /socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required as per IS, IE rules and site requirement complete and conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 & CPWD DSR(E&M) 2025 & confirming to latest relevant IS & as per Explanatory Note. Blanker Plate | — | — | — | 4,700 | |
| — | 50.00 | — | — | ||
| Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required and conforming to IS 3854:2023/ IEC 60669-1, IS 14772:2020 & CPWD General Specifications for Electrical Works Part-I Internal - 2023 & as per Explanatory Note. | — | — | — | 22,200 | |
| — | 50.00 | — | — | ||
| Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required and conforming to IS 3854:2023, IS 14772:2020 or latest & CPWD General Specifications for Electrical Works Part-I Internal - 2023 & as per Explanatory Note . | — | — | — | 27,850 | |
| — | 500.00 | — | — | ||
| Supply, fixing, testing and commissioning of LED light luminaire, having system wattage 1x18 watt. LED tube and inbuilt LED driver, CRCA body powder coated, complete with all mounting arrangement, accessories. The LED based 4 ft. tube light (lamp) shall be conforming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note. | — | — | — | 3,21,500 | |
| — | 500.00 | — | — | ||
| Supply, fixing, testing and commissioning of LED light luminaire, having system wattage 2x18 watt. LED tube and inbuilt LED driver, CRCA body powder coated, complete with all mounting arrangement, accessories. The LED based 4 ft. tube light (lamp) shall be confirming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note. | — | — | — | 5,44,000 | |
| — | 30.00 | — | — | ||
| Supply, fixing, testing and commissioning of LED based focus light having wattage less than or equal to 10W (approx.) complete with driver as per IS, IE rules, site requirement and prior approval of sample confirming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note. | — | — | — | 18,150 | |
| — | 30.00 | — | — | ||
| Supply, fixing, testing and commissioning of LED based picture light having wattage less than or equal to 10W (approx.) complete with driver as per IS, IE rules, site requirement and prior approval of sample confirming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note. | — | — | — | 19,500 | |
| — | 50.00 | — | — | ||
| Supply, fixing, testing and commissioning of LED Post Top 25W complete as per IS & IE rules and site requirement prior approval of sample confirming to CEE/NR's spec. No. CEE/NR/121- Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121- Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note. | — | — | — | 2,55,450 | |
| — | 50.00 | — | — | ||
| Supply, fixing, testing and commissioning of 15 W LED bollard light complete as per IS & IE rules and site requirement prior approval of sample confirming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note. | — | — | — | 2,77,500 | |
| — | 50.00 | — | — | ||
| Supply, fixing, testing and commissioning of LED down lighter, housing aluminum die cast, white powder coated and PMMA diffuser having system wattage less than or equal to 15 Watt complete with all mounting arrangement, accessories complete confirming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note. | — | — | — | 37,200 | |
| — | 50.00 | — | — | ||
| Supply, fixing, testing and commissioning of LED down lighter, housing aluminum die cast, white powder coated and PMMA diffuser having system wattage less than or equal to 15-18 Watt complete with all mounting arrangement, accessories complete confirming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note. | — | — | — | 39,850 | |
| — | 50.00 | — | — | ||
| Supply, fixing, testing and commissioning of LED deep recessed down lighter, housing aluminum die cast, white powder coated and PMMA diffuser having system wattage less than or equal to 15 Watt complete with all mounting arrangement, accessories complete confirming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note | — | — | — | 57,400 | |
| — | 100.00 | — | — | ||
| Supply, fixing, testing and commissioning of LED light luminaries 595x595 mm size, recessed mounting fitting (Tile type), as per IS : 10322 having system wattage less than or equal to 48 Watt, CRCA body powder coated, high efficiency milky white PMMA diffuser with no bright spot visible, complete with all mounting arrangement with suitable frame to avoid droping down of fitting of make Phillips, Bajaj, Havells or similar confirming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note. | — | — | — | 3,30,400 | |
| — | 250.00 | — | — | ||
| Supply, fixing, testing and commissioning of 4-feet long surface mounting 36-Watt, 5700K,CRI>80, LED Luminaire as per CEE/NR's spec. No. CEE/NR/121 Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121 Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest, IS, IE rules and site requirement. Fitting shall be environmentally friendly, long life, corrosion resistant, impact proof IP 66 with PC housing & opal finish cover suitable for wet location similar to Make - Havells Model No. MAGNUM NEO or equivalent. Fitting shall be suitable for operation on single phase 240Volt, 50 Hz AC supply & as per Explanatory Note. | — | — | — | 7,75,000 | |
| — | 50.00 | — | — | ||
| Supply, fixing, testing and commissioning of 05 meter LED strip of wattage less than or equal to 48 watt complete with driver and as per latest IS conforming to CEE/NR's spec. No. CEE/NR/121-lect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121 Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note. | — | — | — | 82,000 | |
| — | 50.00 | — | — | ||
| Supply, fixing, testing and commissioning of 05 meter LED strip of wattage less than or equal to 24 Watt complete with driver and as per latest IS & IE rules conforming to CEE/NR's spec. No. CEE/NR/121-lect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121 Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note. | — | — | — | 66,150 | |
| — | 50.00 | — | — | ||
| Supply, fixing, testing and commissioning of 48V, 50 Hz LED based bulk head/catwalk light/pathway light luminary with IP-66 protection, impact resistance IK10 having system wattage less than or equal to 22 watt complete with anti theft mounting arrangement made out of 2 mm thick CRCA sheet with anti corrosion treatment and suitable mounting arrangement as per site requirement conforming to CEE/NR's spec. No. CEE/NR/121-lect/PS/2018 (Rev- '3')or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121 Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note | — | — | — | 1,95,500 | |
| — | 100.00 | — | — | ||
| Supply, Fixing, testing & commissioning of 12 Watt, 4000/6500K LED COB swivel downlight with crisp light throw and high CRI complete conforming to CEE/NR's spec. No. CEE/NR's spec. No. CEE/NR/121 Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121 Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest and IS, IE rules and site requirement | — | — | — | 1,51,900 | |
| — | 100.00 | — | — | ||
| Supply, fixing, testing and commissioning of LED based highbay luminary with IP 66 having system wattage less than or equal to 150 Watt complete confirming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev-'3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note. | — | — | — | 9,29,000 | |
| — | 100.00 | — | — | ||
| Supply, fixing, testing and commissioning of 150 watt LED based flood light luminary with cool white light, pressure die cast aluminum housing, IP 66 or better having system wattage complete confirming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note. | — | — | — | 7,05,000 | |
| — | 10.00 | — | — | ||
| Supply, fixing, testing and commissioning of 200W LED based flood light luminary with cool white light, pressure die cast aluminum housing, IP 66 or latest complete confirming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note. | — | — | — | 95,000 | |
| — | 125.00 | — | — | ||
| Supply, fixing, testing and commissioning of 45 watt LED based street light luminary with cool white light, pressure die cast aluminum housing, IP 66 or better having system complete confirming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note. | — | — | — | 3,70,625 | |
| — | 125.00 | — | — | ||
| Supply, fixing, testing and commissioning of 90W LED based street light luminary with cool white light, pressure die cast aluminum housing, IP 66 or latest complete confirming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note. | — | — | — | 7,87,375 | |
| — | 20.00 | — | — | ||
| Design, manufacturing, supply, fixing, testing and commissioning of rolling examination LED based lights complete with 03 Nos. 30 watt LED flood light, IP-66 with cover and suitable locking arrangement as per drawing approved by competent authority and as per actual site requirement complete & as per Explanatory Note. (The mounting structure should be G.I angle iron size 50x50x3 mm, Iron Zali 32 mm x32 mm) | — | — | — | 5,08,160 | |
| — | 10.00 | — | — | ||
| Supply, Laying, fixing and commissioning of LT straight through joints along with loop of cable of following sizes as per IS/IE rules and site requirement and satisfaction to the Railway representative. Size = 50-95 sq.mm conforming to IS:7093 or latest & as per Explanatory Note. | — | — | — | 38,150 | |
| — | 10.00 | — | — | ||
| Supply, Laying, fixing and commissioning of LT straight through joints along with loop of cable of following sizes as per IS/IE rules and site requirement and satisfaction to the Railway representative. Size = 120-185sq. mm conforming to IS:7093 or latest & as per Explanatory Note. | — | — | — | 42,990 | |
| — | 10.00 | — | — | ||
| Supply, Laying, fixing and commissioning of LT straight through joints along with loop of cable of following sizes as per IS/IE rules and site requirement and satisfaction to the Railway representative. Size = 240-400Sq. mm conforming to IS:7093 or latest & as per Explanatory Note. | — | — | — | 45,300 | |
| — | 50.00 | — | — | ||
| Supply, erection, testing and commissioning of End termination of 2.0 C / 4.0 C X 70 to 240 sq. mm. LT XLPE cable as per specification. (One set means lugs in R-Y-B-N) conforming to IS:13573-1(2011) or latest & as per Explanatory Note. | — | — | — | 20,600 | |
| — | 1500.00 | — | — | ||
| Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation((upto 75-100 cm depth and not less than 35 cm wide ), sand cushioning, protective covering and refilling the trench etc. as required as per detail drawing approved by competent authority and conforming to IS 1255 (Reviewed in 2016) or latest & as per Explanatory Note. Upto 35 sq. mm | — | — | — | 5,28,000 | |
| — | 500.00 | — | — | ||
| Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation((upto 75-100 cm depth and not less than 35 cm wide ), sand cushioning, protective covering and refilling the trench etc. as required as per detail drawing approved by competent authority and conforming to IS 1255 (Reviewed in 2016) or latest & as per Explanatory Note. Above 35 sq. mm and upto 95 sq. mm | — | — | — | 2,10,500 | |
| — | 500.00 | — | — | ||
| Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation((upto 75-100 cm depth and not less than 35 cm wide ), sand cushioning, protective covering and refilling the trench etc. as required as per detail drawing approved by competent authority and conforming to IS 1255 (Reviewed in 2016) or latest & as per Explanatory Note. Above 95 sq. mm and upto 185 sq. mm | — | — | — | 2,33,500 | |
| — | 500.00 | — | — | ||
| Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation((upto 75-100 cm depth and not less than 35 cm wide ), sand cushioning, protective covering and refilling the trench etc. as required as per detail drawing approved by competent authority and conforming to IS 1255 (Reviewed in 2016) or latest & as per Explanatory Note. Above 185 sq. mm and upto 400 sq. mm | — | — | — | 2,53,500 | |
| — | 600.00 | — | — | ||
| Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation(upto 75-100 cm depth and not less than 55 cm wide & maintaining gap not less than 20 cm between the cables), sand cushioning, protective covering and refilling the trench etc as required as per detail drawing approved by competent authority and conforming to IS 1255 (Reviewed in 2016) or latest and explanatory note. Upto 35 sq. mm | — | — | — | 1,75,800 | |
| — | 200.00 | — | — | ||
| Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation(upto 75-100 cm depth and not less than 55 cm wide & maintaining gap not less than 20 cm between the cables), sand cushioning, protective covering and refilling the trench etc as required as per detail drawing approved by competent authority and conforming to IS 1255 (Reviewed in 2016) or latest and explanatory note. Above 35 sq. mm and upto 95 sq. mm | — | — | — | 62,200 | |
| — | 200.00 | — | — | ||
| Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation(upto 75-100 cm depth and not less than 55 cm wide & maintaining gap not less than 20 cm between the cables), sand cushioning, protective covering and refilling the trench etc as required as per detail drawing approved by competent authority and conforming to IS 1255 (Reviewed in 2016) or latest and explanatory note. Above 95 sq. mm and upto 185 sq. mm | — | — | — | 65,000 | |
| — | 200.00 | — | — | ||
| Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation(upto 75-100 cm depth and not less than 55 cm wide & maintaining gap not less than 20 cm between the cables), sand cushioning, protective covering and refilling the trench etc as required as per detail drawing approved by competent authority and conforming to IS 1255 (Reviewed in 2016) or latest and explanatory note. Above 185 sq. mm and upto 400 sq. mm | — | — | — | 76,200 | |
| — | 600.00 | — | — | ||
| Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative conforming to IS 1255 (Reviewed in 2016) or latest & as per Explanatory Note. Upto 35 sq. mm (clamped with 1mm thick saddle) | — | — | — | 35,400 | |
| — | 200.00 | — | — | ||
| Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative conforming to IS 1255 (Reviewed in 2016) or latest & as per Explanatory Note. Above 35 sq. mm and upto 95 sq.mm (clamped with 25x3mm MS flat clamp) | — | — | — | 28,200 | |
| — | 200.00 | — | — | ||
| Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative conforming to IS 1255 (Reviewed in 2016) or latest & as per Explanatory Note. Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) | — | — | — | 32,800 | |
| — | 200.00 | — | — | ||
| Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative conforming to IS 1255 (Reviewed in 2016) or latest & as per Explanatory Note. Above 185 sq.mm and upto 400 sq. mm (clamped with 25/40x3mm MS flat clamp) | — | — | — | 48,400 | |
| — | 100.00 | — | — | ||
| Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required conforming to conforming to IS/IEC 61537:2006 & as per Explanatory Note. 150 mm width X 50 mm depth X 1.6 mm thickness | — | — | — | 74,200 | |
| — | 100.00 | — | — | ||
| Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required conforming to conforming to IS/IEC 61537:2006 & as per Explanatory Note. 300 mm width X 50 mm depth X 1.6 mm thickness | — | — | — | 85,100 | |
| — | 100.00 | — | — | ||
| Earthing with 40 mm dia GI pipe class 'B' 4.5 meter long earth electrode as per IS:3043 (latest version)to achieve earth resistance less than 5 ohms including construction of masonry enclosures with hinged cover plate of cast iron with locking arrangement (approx. size 400 mmx 400 mm) on top, provision of earth plate, connections from earth electrode to switch gear/pole as per drawing & as per Explanatory Note. | — | — | — | 5,75,100 | |
| — | 500.00 | — | — | ||
| Supplying and laying 25 mm X 5 mm G.I strip confirming to relevant IS as per IS:3043 (Latest version), fixing on surface or as per site condition, clamping or fixing with suitable arrangement as per site requirement, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50 mm) & as per Explanatory Note. | — | — | — | 77,000 | |
| — | 2000.00 | — | — | ||
| Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required as per IS:3043 (Latest version) and as per Explanatory Note | — | — | — | 1,08,000 | |
| — | 10.00 | — | — | ||
| Earthing with 600x600x3mm thick copper plate earth electrode as per IS 3043(Latest version), to achieve earth resistance less than one ohm, including construction of masonry enclosure with hinged cover plate of cast iron with locking arrangement (Approx. size 600x600 mm) on top, watering pipe, connections from earth plate to top with 40x6mm copper stip in 50 mm dia pipe class 'B' provision of earth plate as per drawing and as per Explanatory Note. | — | — | — | 1,09,170 | |
| — | 200.00 | — | — | ||
| Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode confirming to relevant IS as per IS:3043 (Latest version), including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) conforming to CPWD DSR(E&M) 2025 & as per Explanatory Note. | — | — | — | 2,04,800 | |
| — | 100.00 | — | — | ||
| "Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal(Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 or latest fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. 1400mm, service value >= 6.0 CM/Min/Watt, air delivery 245 CM/Min (Minimum) conforming to CPWD DSR(E&M) 2025 item no. 9.2.4 & as per Explanatory Note. | — | — | — | 2,73,700 | |
| — | 100.00 | — | — | ||
| Supply, fixing, testing and commissioning of 1200 mm sweep AC ceiling fan, 230 Volt Single phase 50 Hz, complete with capacitor, double ball bearing , shackle, canopy ,without regulator as per site condition and technical scope of work. (Make:- Havells, Bajaj, CGL, Usha). " It shall also include the scope of supply and installation of safety cord of SS as per IS:302 Part 2 Sec- 80. Dia & length of such cord shall be as per recommendation of OEM of fan and same shall be approved by railway & as per Explanatory Note. | — | — | — | 2,64,800 | |
| — | 20.00 | — | — | ||
| Supply, fixing, testing and commissioning of 400 mm sweep BLDC wall mounted fan complete conforming to relevant IS/IEC standards & as per Explanatory Note. | — | — | — | 49,560 | |
| — | 50.00 | — | — | ||
| Supply, fixing, testing and commissioning of 250mm sweep fresh air fan complete conforming to IS 2312 & IS 302 or latest and other relevant IS/IEC standards and as per explanatory note | — | — | — | 61,400 | |
| — | 10.00 | — | — | ||
| Supply, installation, testing and commissioning of single phase propeller type exhaust fans sweep size 300 mm etc. including grounting of MS nuts, bolts and connection complete as per conforming to IS 2312 & IS 302 and other relevant IS/IEC standards & site requirement and as per explanatory note. Make Bajaj, Usha, Havells, Orient or equivalent | — | — | — | 25,260 | |
| — | 10.00 | — | — | ||
| Supply, fixing, testing and commissioning of 380mm sweep, 1400 rpm (approx) propeller type exhaust fan complete in all respect as specification and as per site requirement, including grouting of nut, bolts, washer and with the suitable fasteners conforming to IS 2312 & IS 302 or latest and other relevant IS/IEC standards . Make Bajaj, Usha, Havells, Orient or equivalent and as per explanatory note | — | — | — | 31,490 | |
| — | 20.00 | — | — | ||
| Supply fixing testing and commissioning of Heavy duty wall mounted air circulator fan 600 mm (24 inch), 1440 RPM ,180 watt, Air delivery 270 cubic meter per minute, No of blade 3, single speed, suitable to work on 230 Volts 50 HZ, single phase IS 2312 & IS 302 or latest and other relevant IS/IEC standards & as per explanatory note. | — | — | — | 1,22,260 | |
| — | 100.00 | — | — | ||
| Cutting/removing of existing rail pole/ tubular pole/octagonal pole including over head conductor, bracket, insulators, earth wire, guard wire etc. as per site requirement and instruction of site In charge and after removal of material, it shall be handed over to site incharge and stacked at suitable location. All materials are to be transported from site to Railway Store as decided by Railway administration. Note: Measurement shall be done in items of number of poles dismantled & as per Explanatory Note. | — | — | — | 1,10,900 | |
| — | 10.00 | — | — | ||
| Supply & erection of hot dip galvanized octagonal pole 5 Mtrs. long Single Arms, confirming to IS 2629/BSEN ISO 1461 latest version with top 70 mm and bottom 130 mm around face made of 3 mm thick, steel base plate size 200 x200x12 mm complete with appropriate sleeve at the top of the pole for mounting arm bracket 300 mm long (or as per site requirement) suitable for LED street light fittings including casting, muffing with cement concrete foundation (1:2:4) painting, earthing and foundation GI nut, bolts with washer and smart pack junction box with 1A single pole MCB and terminals. Pole junction box shall be sealed with water proof tape and display of danger sticker. Note- Wiring in between pole junction box to fitting shall be done through 3 cores 1.5 sq. mm double insulated weather proof cables confirming to IS 456 & other relevant IS/IEC standards & as per Explanatory Note. | — | — | — | 81,840 | |
| — | 10.00 | — | — | ||
| Supply & erection of hot dip galvanized octagonal pole 5 Mtrs. long Double Arms, confirming to IS 2629/BSEN ISO 1461 latest version with top 70 mm and bottom 130 mm around face made of 3 mm thick, steel base plate size 200 x200x12 mm complete with appropriate sleeve at the top of the pole for mounting arm bracket 300 mm long (or as per site requirement) suitable for LED street light fittings including casting, muffing with cement concrete foundation (1:2:4) painting, earthing and foundation GI nut, bolts with washer and smart pack junction box with 1A single pole MCB and terminals. Pole junction box shall be sealed with water proof tape and display of danger sticker. Note- Wiring in between pole junction box to fitting shall be done through 3 cores 1.5 sq. mm double insulated weather proof cables conforming to IS 456 & other relevant IS/IEC standards & as per Explanatory Note | — | — | — | 90,180 | |
| — | 10.00 | — | — | ||
| Supply & erection of hot dip galvanized octagonal pole 7 Mtrs. long Single Arms, confirming to IS 2629/BSEN ISO 1461 latest version with top 70 mm and bottom 130 mm around face made of 3 mm thick, steel base plate size 200x200x12 mm complete with appropriate sleeve at the top of the pole for mounting arm bracket 300 mm long (or as per site requirement) suitable for LED street light fittings including casting, muffing with cement concrete foundation (1:2:4) painting, earthing and foundation GI nut, bolts with washer and smart pack junction box with 1A single pole MCB and terminals. Pole junction box shall be sealed with water proof tape and display of danger sticker. Note- Wiring in between pole junction box to fitting shall be done through 3 cores 1.5 sq. mm double insulated weather proof cables conforming to IS 456 & other relevant IS/IEC standards & as per Explanatory Note. | — | — | — | 1,50,230 | |
| — | 100.00 | — | — | ||
| Erection, testing and commissioning of 5 meter high hot dip Galvanized octagonal pole with longitudinal seam weld throughout the length with bottom 130 mm across face, top 70 mm across face made of 3 mm thick high tensile plate and 200 mm X 200 mmX 12 mm base plate complete with two arm of 300 mm (or as per site requirement) for fitting installation and 04 No. M20 (EN 8 Gr) X 700 MM long J type foundation bolt set complete with washer and smart pack junction box with suitable single pole MCB & terminal conforming to IS 456 & other relevant IS/IEC standards & as per Explanatory Note. (Note: Only 5 meter high hot dip Galvanized octagonal pole is provided by Railway) | — | — | — | 3,34,900 | |
| — | 10.00 | — | — | ||
| Supply, installation, testing and commissioning of all in one solar street lighting system with 05 mtrs high octagonal GI pole as per IS 2629/BSEN ISO 1461, 30 - watt solar street light should be tested as per IS 10322 part- 5 Sec- 3 or IEC 60598-2-3, 120- watt solar panel, lithium- ion storage battery 12.8 V /30 Ah complete with ingress protection IP67 complete & as per Explanatory Note. | — | — | — | 2,80,110 | |
| — | 5.00 | — | — | ||
| Supply, erection, fixing, testing and commissioning of 4 way surface/recessed LT distribution board double door type made up of CRCA steel sheet, IP 54 phosphatised powder painted complete with neutral link, earth point, Din rail and prewired confirming to IS:13032, IEC 60947 & IS/IEC 60898-1:2002 or latest of make ABB, Havells, Siemens, L&T, Schneider, Legrand, C&S or equivalent with following items of matching make to be fixed in distribution board, confirming to & IS/IEC 60898-1:2002 or latest, IE rules and site requirement. It should be rodent entry proof. It should also include well dressing and coding of circuit. Along with 1x125 Amp 3 pole MCCB 35KA, 12 Nos. 6-32 Amp single pole MCB 10 KA as per requirement complete in all respect & as per Explanatory Note. | — | — | — | 76,790 | |
| — | 100.00 | — | — | ||
| Supply, erection testing and commissioning of out door type distribution box having IP 65 complete with 4 nos Aluminium bus bars 250A capacity fabricated with 14 SWG MS sheet steel, dust and vermin proof with anti corrosion treatment IS:13032, IEC 60947, IS/IEC: 61439 or latest & as per Explanatory Note. | — | — | — | 5,36,400 | |
| — | 5.00 | — | — | ||
| Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections etc.as required conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 and CPWD DSR(E&M) 2025 & as per Explanatory Note 125A, 36 KA, 4 pole MCCB | — | — | — | 43,220 | |
| — | 5.00 | — | — | ||
| Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections etc.as required conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 and CPWD DSR(E&M) 2025 & as per Explanatory Note 200A, 36 KA, 4 pole MCCB | — | — | — | 79,780 | |
| — | 5.00 | — | — | ||
| Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections etc.as required conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 and CPWD DSR(E&M) 2025 & as per Explanatory Note 250 A, 36 KA, 4 pole MCCB | — | — | — | 91,860 | |
| — | 5.00 | — | — | ||
| Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections etc.as required conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 and CPWD DSR(E&M) 2025 & as per Explanatory Note 400A, 50 KA, 4 pole MCCB | — | — | — | 2,23,315 | |
| — | 10.00 | — | — | ||
| Supply, fixing, testing and commissioning of LT distribution board surface mounting double door out door type made up of CRCA sheet sheet with anti corrosion treatment and suitable, IP 43 phosphatised powder painted complete with neutral link, earth point, Din rail and prewired confirming to IS:13032 & IEC 60947 & IS/IEC:61439 or latest of make ABB, Havells, Siemens, L&T, Schneider, Legrand, C&S or equivalent with following items of matching make to be fixed in distribution board, confirming to & IS/IEC:60898-1 :2002 or latest, IE rules and site requirement. It should be rodent entry proof. It should also include well dressing and coding of circuit & as per Explanatory Note 63A 4P RCBO 100 mA= 01 No. (Incoming) 6-32A MCB SP ""C"" Series =18 Nos. (Outgoing)" It should be rodent entry proof. It should also include well dressing and coding of circuit IP2X terminal , reversible door with 180 degree opening, cement spill protection, detachable gland at top and bottom and short link for MCBs. | — | — | — | 1,08,630 | |
| — | 10.00 | — | — | ||
| Supply, Fixing, testing & commissioning of LT distribution board recessed mounting double door type made up of CRCA sheet sheet with anti corrosion treatment and suitable, IP 43 phosphatised powder painted complete with neutral link, earth point, Din rail and prewired confirming to IS:13032, IEC 60947 & IS/IEC:61439 or latest of make ABB, Havells, Siemens, L&T, Schneider, Legrand, C&S or equivalent with following items of matching make to be fixed in distribution board, confirming to IS/IEC:60898-1 :2002 or latest, IE rules and site requirement. It should be rodent entry proof. It should also include well dressing and coding of circuit & as per Explanatory Note 63A 4P RCBO 100 mA= 01 No. (Incoming) 6-32A MCB SP "C" Series =18 Nos. (Outgoing) It should be rodent entry proof. It should also include well dressing and coding of circuit IP2X terminal , reversible door with 180 degree opening, cement spill protection, detachable gland at top and bottom and short link for MCBs. | — | — | — | 1,08,630 | |
| — | 4.00 | — | — | ||
| Design, Supply, fixing, testing and commissioning of front operated double door type weather proof feeder pillar body made of CRCA sheet sheet with anti corrosion treatment and suitable having IP 65 protection (MCCB - Incoming & MCCB - Outgoing) comprising with the following MCCB's fixed in it of make: Havells, Siemens, L&T, Schneider, Legrand or equivalent conforming to IEC 60947 & IS/IEC:61439 or latest with digital measuring instrument & bus-bar arrangement and as per latest IS, IE rules and site requirement. It should be dust and vermin proof and powder coating as per IS 13871-2021 (or latest version & as per Explanatory Note. 4P MCCB 250Amps 36 kA with adjustable thermal & fixed magnetic release = 01 No. (Incoming) 4P MCCB 125Amps 36 kA with adjustable thermal & fixed magnetic release = 02 No. (outgoing) 4P MCCB 63Amps 36 kA with adjustable thermal & fixed magnetic release = 04 No. (outgoing) | — | — | — | 4,31,636 | |
| — | 2.00 | — | — | ||
| Design, Supply, fixing, testing and commissioning of front operated double door type weather proof feeder pillar made of CRCA steel sheet having IP 65 protection (MCCB - Incoming & MCCB - Outgoing) comprising with the following MCCB's fixed in it of make: Havells, Siemens, L&T, Schneider, Legrand or equivalent conforming to IEC 60947 & IS/IEC:61439 or latest with digital measuring instrument & bus-bar arrangement and as per latest IS, IE rules and site requirement. It should be dust and vermin proof and powder coating as per IS 13871-2021 (or latest version) & as per Explanatory Note. a) 4P MCCB 400Amps 36 kA with adjustable thermal & fixed magnetic release =01 Nos. (Incoming). b) 4P 400 Amps on load change over switch (COS)=01 No. c) 4P MCCB 250Amps 36 kA with adjustable thermal & fixed magnetic release =04 Nos. (Outgoing). d) 4P MCCB 125Amps 36 kA with adjustable thermal & fixed magnetic release =04Nos. (Outgoing). | — | — | — | 8,35,282 | |
| — | 200.00 | — | — | ||
| Design, manufacture, display of wall / hanging / floor mounting type LED illuminated sign / direction boards in half elliptical shape. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2 mm thickness. The text / graphics matter visibility shall not be less than 160 deg. The approved colour text and graphics shall be printed /router cut on monomeric calendered vinyl of 70 mm thickness and shall be firmly pasted on display sheets. The mounting arrangement shall be hanging, wall mounting, ceiling mounting, pole mounting or floor mounting and as per site requirement. The signage shall have the integral mounting arrangements with sturdy structural frame and ACP cladding on the back side of the signage to avoid rusting and entry of dust. The LED board shall have uniform illumination with 4-8 W / sq. ft. and with brightness more than ambient light. Suitable size endcap of 1.5 mm thick SS304 should be provided as per Railway Board letter no. 2023/SD-II/22/07/02 dated 15.05.2023 & as per Explanatory Note. | — | — | — | 4,85,600 | |
| — | 200.00 | — | — | ||
| Erection and installation of wall / hanging / floor mounting type LED illuminated sign /direction boards in half elliptical shape. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2 mm thickness. The text / graphics matter visibility shall not be less than 160 deg. The approved colour text and graphics shall be printed /router cut on monomeric calendered vinyl of 70 mm thickness and shall be firmly pasted on display sheets. The mounting arrangement shall be hanging, wall mounting, ceiling mounting, pole mounting or floor mounting and as per site requirement. The signage shall have the integral mounting arrangements with sturdy structural frame and ACP cladding on the back side of the signage to avoid rusting and entry of dust. The LED board shall have uniform illumination with 4-8 W / sq. ft and with brightness more than ambient light & as per Explanatory Note | — | — | — | 48,600 | |
| — | 15.00 | — | — | ||
| Supply, fixing, testing and commissioning of 2 KVA online UPS complete with battery 72Volt,42AH should have input, output protection, Complete with trolly. Preferred Make :- Microtek/Uniline/Sukam/Luminious or similar conforming to IS 16242 & as per Explanatory Note. | — | — | — | 4,18,380 | |
| — | 2.00 | — | — | ||
| Supply, erection, testing and commissioning of 1400 VA inverter confirming to latest relevant IS, A.C. input voltage 160V-280V, DC input voltage 24V, output voltage same as supply voltage, when inverter is working 220V +(-) 10%, output frequency 50 +(-) 0.5%, output wave form: square wave, backup full load: upto 3 hours 25% load upto 7 hours, wiring with 6 nos. light and fan point, Protection: over load battery over charge battery deep discharge, Battery charge: constant current thyristor controlled for extra wide range. Supply and erection of 150 Amp Hour LMLA tubular battery confirming to latest relevant IS complete in all respect as per above specification & as per Explanatory Note. | — | — | — | 61,044 | |
| — | 25.00 | — | — | ||
| Supply, fixing, testing and commissioning of 63 A, 30 mA DP RCCB AC type confirming to IS/IEC 60947 with 10KA short circuit with stand capacity complete with enclosure for water cooler. conforming to CPWD General Specifications for Electrical Works Part-I Internal - 2023 and CPWD DSR (E&M) 2025 & as per Explanatory Note. | — | — | — | 68,050 | |
| — | 10.00 | — | — | ||
| Supply, erection, connection, testing and commissioning of digital Multifunctional Meter (V,A,PF & KWH meter) on existing LT / HT panel / feeder, of approved make, including disconnection & stripping of existing defective indication lamps if any as per technical scope of work and specifications confirming to latest relevant IS as per Explanatory Note. | — | — | — | 45,000 | |
| — | 100.00 | — | — | ||
| Supply, provision, connection, Testing & commissioning of LED type indication lamp, dia. 22.5/ 30.5 mm, of suitable voltage as per site requirement for LT / HT Electric Panels (in Red, Yellow & Blue colour) of approved make, including disconnection & stripping of existing defective indication lamps if any, as per technical scope of work and specifications & as per Explanatory Note. | — | — | — | 6,500 | |
| — | 10.00 | — | — | ||
| Supply, provision, connection, Testing & commissioning of Digital type Ampere meter, Accuracy Class-1, CT Ratio -400 or 200/5 Amps., size 144mmX144mm of approved make, on Electric Panels, including disconnection & stripping of existing meters if any as per technical scope of work and specifications confirming to IS:13875 & as per Explanatory Note. | — | — | — | 12,000 | |
| — | 10.00 | — | — | ||
| Supply, provision, connection, Testing & commissioning of Digital type Voltmeter, Accuracy Class-1, PT Ratio 11000/110 Volts, size 144mmX144mm of approved make, on Electric Panels, including disconnection & stripping of existing meters if any As per technical scope of work and specifications confirming to latest relevant IS & as per Explanatory Note. | — | — | — | 12,500 | |
| — | 4.00 | — | — | ||
| Supply, fixing (retro-fitting), testing and commissioning of 630 A/800 A 4 pole 50KA Breaking capacity ACB microprocessor MDO type in existing LT panel as per site requirement conforming to IEC 60947 & as per Explanatory Note. | — | — | — | 7,20,000 | |
| — | 2.00 | — | — | ||
| Supply, fixing(retro-fitting), testing and commissioning of 1600 A 4 pole 50KA Breaking capacity ACB microprocessor MDO type based in existing LT panel as per site requirement conforming to IEC 60947 & as per Explanatory Note | — | — | — | 4,60,000 | |
| — | 200.00 | — | — | ||
| supply, fabrication (including powder coating painting) and installation of LT panel/feeder pillar cover made of 2mm thick CRCA sheet with suitable hinges and locking arrangements for existing LT/feeder pillar as per site requirement confirming to latest relevant IS & as per Explanatory Note. | — | — | — | 45,000 | |
| — | 50.00 | — | — | ||
| Supply and fixing of IP 67 cable gland suitable for following sizes of cables in existing LT panel/feeder pillar.(double compression brass cable glands with nickel plated weather proof type) confirming to latest relevant IS & as per Explanatory Note. 4Cx16 sq.mm. size | — | — | — | 21,000 | |
| — | 50.00 | — | — | ||
| Supply and fixing of IP 67 cable gland suitable for following sizes of cables in existing LT panel/feeder pillar.(double compression brass cable glands with nickel plated weather proof type) confirming to latest relevant IS & as per Explanatory Note. 4Cx35 sq.mm. size | — | — | — | 27,500 | |
| — | 50.00 | — | — | ||
| Supply and fixing of IP 67 cable gland suitable for following sizes of cables in existing LT panel/feeder pillar.(double compression brass cable glands with nickel plated weather proof type) confirming to latest relevant IS & as per Explanatory Note. 4Cx70 sq.mm. size | — | — | — | 55,000 | |
| — | 50.00 | — | — | ||
| Supply and fixing of IP 67 cable gland suitable for following sizes of cables in existing LT panel/feeder pillar.(double compression brass cable glands with nickel plated weather proof type) confirming to latest relevant IS & as per Explanatory Note. 4Cx120 sq.mm. size | — | — | — | 75,000 | |
| — | 20.00 | — | — | ||
| Supply and fixing of IP 67 cable gland suitable for following sizes of cables in existing LT panel/feeder pillar.(double compression brass cable glands with nickel plated weather proof type) confirming to latest relevant IS & as per Explanatory Note. 4Cx185 sq.mm. size | — | — | — | 44,400 | |
| — | 20.00 | — | — | ||
| Supply and fixing of IP 67 cable gland suitable for following sizes of cables in existing LT panel/feeder pillar.(double compression brass cable glands with nickel plated weather proof type) confirming to latest relevant IS & as per Explanatory Note. 4Cx240 sq.mm. size | — | — | — | 58,800 | |
| — | 100.00 | — | — | ||
| Supply and erection of 1A MCB in existing octagonal pole conforming to IEC 60947 & other latest relevant IS/IEC standards & as per Explanatory Note. | — | — | — | 19,500 | |
| — | 100.00 | — | — | ||
| Supply and installation of safety wire of SS as per IS:302 Part 2 Sec-80. Dia & length of such wire shall be approved by railway & as per Explanatory Note . For existing ceiling fan | — | — | — | 2,500 | |
| — | 500.00 | — | — | ||
| Supply and erection of materials of gaurding arrangement for HT/LT overhead line - Hard drawn GI, 8 SWG Main wire, Guarding loop conforming to latest relevant IS/IEC rules & as per Explanatory Note. | — | — | — | 8,500 | |
| — | 20.00 | — | — | ||
| Supply, Fixing, testing & commissioning of 300 mm Single Arm of Octagonal pole made out of 48 mm dia pipe with canopy of 300 mm conforming to latest relevant IS/IEC rules & as per Explanatory Note. | — | — | — | 27,000 | |
| — | 20.00 | — | — | ||
| Supply, Fixing, testing & commissioning of 450 mm Single Arm of Octagonal pole made out of 48 mm dia pipe with canopy of 300 mm conforming to latest relevant IS/IEC rules & as per Explanatory Note. | — | — | — | 30,000 | |
| — | 20.00 | — | — | ||
| Supply, Fixing, testing & commissioning of 300 mm Double Arm of Octagonal pole made out of 48 mm dia pipe with canopy of 300 mm conforming to latest relevant IS/IEC rules & as per Explanatory Note . | — | — | — | 35,000 | |
| — | 100.00 | — | — | ||
| Supply of pole cover for existing 5 mtr/ 7 mtr octagonal pole conforming to latest relevant IS/IEC rules & as per Explanatory Note. | — | — | — | 80,000 | |
| — | 700.00 | — | — | ||
| Suplying and fixing of FRP Fencing rust proof, shock proof, anti-corrosive, self extinguishing, ultraviolet stabilized, FVO-UL94, weather proof, flame retardant, environment friendly, installed at electrical installations with necessary concreting for grouting vertical post, hardware, accessories, fitting etc. of 2000 mm height above the ground and minimum 300 mm grouting in ground i.e. total height will be 2.3 meter along with 1 number of FRP almirah type double door gates with necessary hardware accessories like stainless steel heavy duty L-Drop, hinges, screws, nut and bolt, lock fittings etc. with double door openable-lockable provision for top ceiling arrangement with appropriate cut for high mast pole/CSS/FTU along with pad lock, hinges for the same of suitable length, width & height with vertical post of size 50x50x3mm, sub-frame of 50x25x3mm, pickets of size 38x15mm, hollow section size of not more than 5x5 inch and also providing 1 number danger plate of size 250x200x2mm, 1 number name plate of property of N. Railways and sponsors name as per site requirement & as per Explanatory Note. | — | — | — | 8,70,800 | |
| — | 100.00 | — | — | ||
| Spray painting of Complete LT / HT Main Panel/ DG set/Feeder pillar with synthetic enamel paint, as per technical scope of work and specifications & as per Explanatory Note. | — | — | — | 28,800 | |
| — | 100.00 | — | — | ||
| Supply, fixing, testing and commissioning of LED bed side lights, system wattage 6W, CRI>80, 4000K/6000K, Housing made of aluminum/CRCA sheet with powder coated, mild steel neck, cool white with compatible inbuilt LED driver complete with prior approval of sample and shall be conforming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest and as per site requirement & as per Explanatory Note. | — | — | — | 59,900 | |
| — | 10.00 | — | — | ||
| Repair and service, of up to 30 m high mast tower at HNZM station, Delhi Main work details is as follows: A) Lowering and dismantling of luminaries and depositing in concern depot store for safe custody. B) Dismantling and lowering of high mast tower from foundation for repair, without damaging the tower. The charges of hiring the hydraulic Crane will be paid up by contractor C) Replacement of stainless steel wire rope of same size 06 MM load bearing capacity 2350 kg 7/19 AISI 316 of suitable breaking load High Mast tower. D) Supply and fixing off electric supply cable 5 core 4 mmsq copper, flexible EPR insulated PCP, sheathed complete length required. E) Servicing of double drum, winch gear and electric motor cap. F) Servicing, greasing, gear oil, balancing and testing of complete installation. Erection, commissioning and testing of dismantled high mast tower on existing/ new foundation with fixing of luminaries, including charges of hiring the Hydraulic Crane. Complete job should be satisfactory of railway site incharge without damaging sight and tower & as per Explanatory Note. | — | — | — | 7,00,000 | |
| — | 10.00 | — | — | ||
| Shifting of High Mast system (16-30 m) from one location to another. This item includes the supply, installation, casting and commissioning of RCC foundation for 16-30 m high mast system, along with erection of foundation suitable bolt manufacture from special steel as per drawing/specification of OEM along with nuts, washer, anchor plate and templates, considering the safe soil bearing capacity at site as 10 T/sq.mtr Depth as per approved foundation structure design should be as per High mast OEM as per technical scope of work. This also include earthing and hiring of crane for the work & as per Explanatory Note. | — | — | — | 9,00,000 | |
| — | 30.00 | — | — | ||
| Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 meters lead as per direction of Engineer - in - charge for making trench for cable laying as per explanatory note. Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix) | — | — | — | 60,210 | |
| — | 30.00 | — | — | ||
| Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 meters lead as per direction of Engineer - in- charge for making trench for cable laying as per explanatory note. | — | — | — | 87,840 | |
| — | 30.00 | — | — | ||
| Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:2:4 (1 Cement : 2 coarse sand (zone- III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) & as per explanatory note | — | — | — | 2,20,950 | |
| — | 30.00 | — | — | ||
| Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) & as per Explanatory Note. | — | — | — | 2,38,350 | |
| — | 2.00 | — | — | ||
| Supply, Inspection & testing of 5 KV portable Digital insulation tester capable to measure at each stage volts of 250/500/1000/2500/5000 Volts along with capable to give PI and DAR reading values having short circuit current of 3mA or above, like of Sanwa MG 5000 or similar with 12 months warranty. Two days field training is mandatory by OEM representative person to railway staff for better application utilisation of product & as per Explanatory Note | — | — | — | 1,35,400 | |
| — | 4.00 | — | — | ||
| Shifting ,dismantling & commissioning charges of LT panels, Transformers etc as per site requirement & as per Explanatory Note. | — | — | — | 1,79,928 | |
| — | 100.00 | — | — | ||
| Fabrication of MS stand/cabinets or any other MS structure of approved drawing for precooling points/battery charger/ covering of electrical structure. The work includes cutting, welding , riveting, nut bolts of the MS structure including applying a primary coat of steel primer and one coat of paint of approved shade & as per Explanatory Note . | — | — | — | 11,700 | |
| — | 50.00 | — | — | ||
| Precast R.C.C. grating with frame 500x450 mm horizontal grating conforming to CPWD DSRS.no. 19.27.1 with item code 7380 in DAR) & as per Explanatory Note. | — | — | — | 1,37,800 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TECHSPEC-I.pdf
ATTACHMENT
GCC-2022-ACS10_merged.pdf
ATTACHMENT
TECHSPEC-II.pdf
ATTACHMENT
TenderDocument55_1.pdf
ATTACHMENT
ExplanatoryNote55.pdf
ATTACHMENT
SpecialCondition55_1.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .