Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.4 LAccepted-AOC | L1 | Accepted-AOC 1st lowest | |
| 2 | L2₹3.4 L+₹920 (0.27%)Rejected-Finance | L2 | Rejected-Finance 2nd lowest | |
| 3 | L3₹3.4 L+₹1,834 (0.54%)Rejected-Finance | L3 | Rejected-Finance 3rd lowest |
Tender Value
Refer Docs
EMD Value
₹6,853
Closing Date
23 Feb 2023, 12:30 pmClosed
Executive Engineer,Bankura Electrical Division,PWD
PWD Compound, Kenduadihi, Near Bhairabsthan,Bankura-722102
UPS system for Refrigerated Centrifuge Machine (for uninterrupted Power Supply) at upcoming Blood Component Separation Unit, Bishnupur District Hospital, Bishnupur Health District.
2023_WBPWD_475532_1
WBPWDTE/EE/BED/NIQ_140/Q of 2022-23
Open Tender
ELECTRICAL WORKS ORG
Item Wise
14 days
Bankura Electrical Division
Please refer Tender documents.
3 documents required · 3 mandatory
₹6,853
24 Feb 2025
16 Feb 2023
27 Feb 2023
16 Feb 2023
23 Feb 2023
16 Feb 2023
Amount
Cutting Channel of required size on masonry wall by Electric operated cutting machine incl. supplying & fixing of heavy gauge Polythene pipe of following diameter as per GS. 25mm dia 3 mm thick
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire of the following sizes in the prelaid polythene pipe as per GS. 2x(4 sqmm)+1x (2.5 sqmm)
4x84/0.3 (6 sqmm) + 2x56/0.3 (4 sqmm) as ECC
Supply, installation & Testing and Commissioning of 10 KVA, 3 phase INPUT and 1 phase OUTPUT UPS with SMF Battery bank for 30 Mins. backup, Having following Specification : IGBT based double convesion True Online UPS with built-in Isolation Transformer on the Inverter output, input and output EMI Filter, Voltage Range Input -- 300V-480V AC, Frequency-46 to 54 Hz, Output--230V AC Phase to Nutral (+/- 1%) on 100% load, Frequency-50 Hz +/- 0.5%, Output Power Factor: 0.8 or better, Efficiency >=92% on rated full load, DC Voltage-192V DC. Minimum VAH for 30Mins. back up required 8064 VAH; Battery make - Exide/Quanta , Including Battery Rack, Inter Connection of above Batteries with Suitable copper interlinks, Lugs etc. as required UPS should comply General & Safety Standards: CEI EN 62040-1 ; EN 62040 - 2 : 2006; IEC 62040 - 3 Quality Certification of the OEM: ISO 9001:2015; ISO 14001:2015; ISO 50001:2018: & ISO 45001: 2018 Warranty: 1 year for UPS from date of commissioning & 2 years for batteries from date of supply Approved Make: Vertiv / Schneider / Power One /ABB / Riello.
Supplying & Fixing Industrial Plug & Socket board with 240 V, 20A, SPN & Earth Metal Industrial Plug socket & 20A Industrial top incl. S&F 20 A SP MCB breaking capcity 10kA (C- Curve) in SS enclosure fixed on wall and necessary connection.
Supply of 240V 32A single phase industrial Top ( Make - Legrand) (Cat no-555234)
Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. 2+4 way, Enclosure (607710) , Make-Legrand
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS [ Make -Legrand ] 6-32 SP
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection as perGS [Make-Legrand ]. 32 A DP
MANDAL TRADERS
ASSOCIATE
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .