GE (N) Bikaner
GE (N) Bikaner Mil Stn Bikaner
Repair/Maintennance of certain external electric works and LT UG cables at West camp and South Camp, Repair/replacement of existing sewage line, septic tank soakage well and repair to toilet in North camp , East camp, South camp, West Camp and DB
2019_MES_310671_1
GE (N) BKN-Token/56/2019-20
Open Tender
Civil Works
Item Rate
330 days
MFFR
Class E and category a (i) , b (i)
8 documents required · 8 mandatory
₹500
GE (N) Bikaner
₹50,000
Yes
13 Sept 2021
31 Dec 2019
23 Jan 2020
31 Dec 2019
21 Jan 2020
14 Jan 2020
Amount
Excavation in trenches, not exceeding 1.5 meter wide and not exceeding 1.5 meter in depth for foundation etc, route of cable or for shafts, wells, cesspits, manholes, pier holes etc not exceeding 10 Sqm area on plan and not exceeding 1.5 meter in depth and getting out in soft/loose soil complete all as specified.
All as per Srl item No. 01 here in before but exc 1.5m and not exceeding 3.0 in depth complete all as specified and as directed by the Engineer-in-Charge.
Returning, filling in soft/loose soil including spreading, levelling, watering and well ramming, in layers not exc 25 cm complete all as specified and as directed by the Engineer-in-Charge.
Removing of surplus soil to a distance not exc. 50 metre and depositing where directed at a level not exc.1.5 metre above the starting point complete all as specified and as directed by the Engineer-in-Charge.
M & L Local tibba dry sand cushioning and cover (8 cm thick layer of sand before laying of cable and 15 cm thick layer of sand after laying of cable) for protection of cable, material and labour complete all as specified and as directed by the Engineer-in-Charge.
M & L Protection to cable with one layer of bricks laid flat butting to each other in such a way that the length of the bricks is at right angle to the central axis of the cable using old size sub-class ‘B’ burnt-clay bricks having compressing strength not less than 75 kg/Square cm complete all as specified and as directed by the Engineer-in-Charge.
M & L Plain cement concrete 1:4:8 type D-2 using 40mm graded stone aggregate in foundations of poles above ground level including finishing to exposed concrete surfaces even and fair and provision of form work for rough finished surface complete all as specified and as directed by Engineer-in-charge.
M & L Plain cement concrete 1:3:6 type C-2 using 40mm graded stone aggregate in foundations for stays and coping complete all as specified and as directed by Engineer-in-charge.
Dismantling and taking down old damaged/broken pre-stressed concrete/steel LT electric poles of any type inclding breaking down existing pcc foundation and removing from site complete all as specified and as directed by the Engineer-in-Charge.
Taking out old US/faulty PVC armoured/un-armoured LT under ground cable of size 10 Sqmm to 120 sqmm 2/3 1/2 4 core complete all as specified and as directed by the Engineer-in-Charge.
M & L Cross linked poly-ethylene (XLPE) insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables ( heavy duty) with aluminium conductor, 1100 volts LT grade of cross-sectional area 06 Sqmm 2 core laid in trenches/through pipe in road crossings/paths/drains/ducts/floors/along poles/walls/ceilings/equipments etc supplied and fixed including commissioning and testing complete all as specified and as directed by the Engineer-in-Charge.( Note : (i) Necessary excavation and earth work, brick protection, sand cushioning and cover and GI pipe shall be measured and paid for separately. (ii) Road/boring roads manualy cutting/floor cutting/cutting holes etc in wall required for laying fising of cable etc shall be made good as per existing site condition. Nothing extra shall be admissible on this account and quoted rate for this item shall be deemed to include for the same.)
Ditto All as per srl item No. 11 here in above but of size 10 Sqmm 2 core
Ditto All as per srl item No. 11 here in above but of size 16 Sqmm 2 core
Ditto All as per srl item No. 11 here in above but of size 25 Sqmm 4 core
Ditto All as per srl item No. 11 here in above but of size 35 Sqmm 3.5 core
Ditto All as per srl item No. 11 here in above but of size 50 Sqmm 3.5 core
Ditto All as per srl item No. 11 here in above but of size 70 Sqmm 3.5 core
Ditto All as per srl item No. 11 here in above but of size 95 Sqmm 3.5 core
Ditto All as per srl item No. 11 here in above but of size 120 Sqmm 3.5 core
Ditto All as per Srl item No 11 here in above but of size 185 Sqmm 3.5 core
Boring of holes under road, pavement, hard standing by manually without damaging of road, material & labour including pipe 80/100 mm dia suitable complete all as specified and as directed by the Engineer-in-Charge. ( Note; length of pipe to be measured and paid seperately under relavant item)
Supply and fixing in replacement of LED based street lights, housing made of pressure die cast aluminium alloy with effective thermal management sturdiness. The fixture should have a minimum system efficacy of more than 80 lumen/Watt and a minimum system lumen output of not less than 4500 lumens and maximum system wattage 45 watts. The fuxture shall have a color temperature of minimum 5000k at a CRI of minimum 70. The fixture shall be designed for a system life of 50,000 hours @ 70% lumen maintenance, lngress protection of IP66 (lamps and gear compartment and Mechanical Impact) Resistance Rating of IK>= 05. The fixture should comply with the parameters as per IEC 60598 and IS 10322, and LED drive should apply to IEC 61000-3-2 ed 3.2. per haronics IEC 61347-2-13, 2006 in confirmation with IEC 61347-1 ed, 2.0, 2007 for electrical safety, LM 79 and LM 80 test report needs to be sumitted above parameters. The fixture driver should have an operating voltage range of 140-300V, frequency 50-60 Hz, surge protection not less than 4KV, PF>0.95 and THD<15%. The driver should have double phase protection. LED lights fitting should be suitable for ambient temperature from (-) 10 digree C to (+) 50 digree C, including street light GI bracket 40mm dia bent to shape 1200 and down 15mm Bore GI pipe with GI clamps with junction box for fixing LED light required, with suitable size clamp, nut bolts and washers as per site requirement complete all as specified as directed by Engineer-in-charge. (Note-The manufacture of LED fitting shall give Guarantee for 5 years from the date of installation and complete fixed with suitable bracket & Accessories) Make- Havells Cat part No ENDURAPEARLNEOSL45WLED757PASYTOPC or equivalents in Phillips, CG, Bajaj, Wipro, C&S and surya.
Supply and fixing in replacement for two core PVC insulated weather proof cable with aluminum conductor size 6 sqmm (nominal area), & drawing into hollow street light pole from fitting to juntion box or fitting to over head line complete all as specified and as directed by the Engineer-in-Charge.
S & F Pre-stressed concrete poles 9 meter long, 102mm x 172 mm at top and 102 mm x 279 mm at bottom, class 10, complying with requirements of IS-1678, including painting with two coats of synthetic enamel paint (in alternate black & white/yellow strips of 30 cm height) upto 1.5 meter height from top of PCC coping and also including numbering to poles with synthetic enamel paint on black base of size 15 cm x 10 cm and numbering in 8 cm height of number with white paint incl required iron channels/clamps/GI pipe for the protection of flexible cable connecter box with bus bars, bolts & nuts complete all as specified and as directed by the Engineer-in-Charge.
S&F juction box IP 66 made out of thermoplastic material of size 200mmx160mmx98mm with provn of three phase cable connector incomming and outgoing with MCB SP 'C' curve 6 Amps ansd single phase connection for street light fitting IP 65 protection totally enclosed weather and dust proof internally embedded gasket with cable entry gland along GI clamp nut bolt and washer foxed on poles including 3 phase busbar with netural in juction box complete all as specified and as directed by the Engineer-in-Charge.
S&F in replacement GI pipe light grade 100 mm bore (ISI marked) laid in trenches/ road crossings/ fixed to poles/Ceiling/along walls/path/drain/floors with and including all necessary clamps, nuts, bolts washers etc all fittings as required complete all as specified and as directed by the Engineer-in-Charge. (Note: - excavation, earth work will be measured and paid for separately.)
Ditto All as per srl item No 26 here in above but dia of pipe 50 mm.
Ditto All as per srl item No 26 here in above but dia of pipe 40 mm.
Ditto All as per srl item No 26 here in above but dia of pipe 20 mm.
Earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metre depth below normal ground level) with top edge of plate at a depth not less than 1.5 mtr below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to galvanized earth wire 04 mm dia with and including bolts, nuts, check nuts and washers of galvanised iron or steel and riveted to earth plate and one end and connecting to main switch board or metallic bodies of HT/LT equipments etc at the other end, GI wire encased in and including 15 mm bore GI light grade pipe with all fittings, from top of electrode to body of equipment fixed with and including flatiron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI light grade and including funnel, wire mesh, copper lugs etc from bottom of earth pit to top of electrode complete with earth pit in PCC 1:3:6 type C-2 using 40 mm graded crushed stone aggregate and CI cover complete all specified and shown in electrical plate No 03 of SSR Pt-I connecting earth electrode to test point with and including earthing lead including neessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance n.exc 50m, material and labour complete all as specified and as directed by Engineer-in-Charge. (Notes 1. The rate quoted shall be deemed to include for all the above provisions. 2. PCC chamber shall be constructed at least 1.5 m away from the earth electrode and pipe for watering shall be provided in slanting maner) .
Cable jointing kit for LT 1100 V cable for straight through end termination (Epoxy), hot shrinkable type joint kit complete with jointing material and accessories suitable for 25 Sqmm to 50 Sqmm 3.5/4 core XLPE armoured aluminium conductor cable including testing after jointing, fixing in replacement complete all as specified as directed by Engineer-in-charge.make: m seal/dension.
Ditto all as per srl item No. 31 here in above but 70 to 95 Sqmm
Ditto all as per srl item No. 31 here in above but 120 to 150 Sqmm
S & F MCB DB 2 way 240 Volts with MCB SPN 32 Amps 10 KA repturing capacity with mounting clamps nuts/bolts/washers for street light control complete all as directed by Engr-in-charge.
Cable indoor / outdoor end terminals jointing kit forLV/ LT 1100 V cable for heat shrinkable type joint kit complete with jointing material and accessories, thimbles etc suitable for 16 Sqmm to 50 Sqmm 3.5 core XLPE armoured aluminium conductor cable including testing after jointing, fixing in replacement complete all as specified as directed by Engineer-in-charge.make: m seal/dension.
Ditto all as per srl item No. 35 here in above but 70 to 95 Sqmm
Ditto all as per srl item No. 35 here in above but 120 to 150 Sqmm
Disconnection electric incoming cable connection and taking down old unserviceable change over switch of any size and description including complete all as directed by Engr-in-charge.
S&F inreplcement of change over switch 200 Amps, four pole, 415 Volt, cubical type and including making fixing arrangement in existing LT control panel and with proper connection of as per existing system all as directed by the Engineer-in-Charge Make-C&S, Cat part-CSSDF200B4CO or equivalent cat part in make Crompton Greaves/L&T/Siemens/Alstom.
S&F in replacement of US Feeder pillar box outdoor cubical type factory made vermin protected dust proof with canopy, water proof made out of MS sheet 1.6 mm thick and 50 cm x50 cm x1.6mm thick angle iron base frame having insulated bus bar aluminum 200amps cap 3 phase with neutral bus bar including fixing in PCC bed block complete all as reqd at site of all four camps and DBS as directed by Engineer in Charge.
Aluminium conductor, steel reinforced (ACSR) of any size/make including stringing for overhead line on HT poles including aluminum binding wire 14 SWG, jumpers, line tapes, conducting jelly etc including taking down old conductor complete all as specified and as directed by Engineer-in-Charge. (Notes : (i) The ACSR conductors shall be conforming to IS-398 and as specified in SSR Part-I. (ii) The unit rate quoted shall also be deemed to include for supply & fixing of aluminium binding wire, aluminium tapes etc which shall not be included in the weight of conductors.(iii) Weight of conductors shall be determined by measuring true horizontal distance between centers of two adjacent poles and compounding the weight of conductors of that size and length and 3% extra added for sag, jointing, jumpers etc.(iv) Weight of the conductors shall be calculated from the nominal weights given in tables in the relevant IS.)
Re-stringing of existing over head line ACSR conductor/GI wire of any size/type including repair of conductor broken due to wind storm/expansion, contraction etc, on existing HT steel and/or PCC pole including replacement of aluminium binding wire of suitable size carefully without damaging of insulator etc complete all as specified and directed by Engineer-in-Charge.
M & L for repairing of broken ACSR vessal/ squarel /ferrot/ mink conductor after proper shutdown of electric supply and jumpring / cut points changing the damaged/burned conductor, cable endes, change over MCCBs condutor broken due to wind/storm and binding with the aluminium wire etc and changing the damaged pin/disc insulators and replace the broken conductor, repairing the faults in the 11/0.44 KV outdoor/ indoor electric panels at sub stations complete all as specified and directed by engineer-in-charge.( Note :- cost of fues wire minor spares, aluminium binding wire shall be deemed included in the above quoted item.,(ii) Cost of items that is pin insulator,disc insulator etc. shall be measured and paid seprately under respective items.(iii)contrator take complaints from complaints cell(JE E/M)and rectify the same day and duely signed by the users and depositedthe same.one down breakdown/coplaint by attended shall be the each job.
Repair the following work to existing bus bar chamber(pillar box) outdoor cubical type factory made vermin protected dust proof, water proof made out of MS sheet 1.6 mm thick and 50 cm x50 cm x6mm thick angle iron base frame having insulated bus bar aluminum 200amps cap 3 phase with neutral bus bar including fixing in PCC bed block complete all as reqd at site and as directed by Engineer in Charge with following: - (a) welding of brocken/cracked joints of the feeder pillar box
(b) Replacing to locking arrangement of the feeder pillar box as per sample existing.
(c ) Painting with one coat of synthatic enamel paint after applying one coat of red oxide as a primer complete all as specified
(d) Replacing of aluminium bus bar (RYB with neutral 200 amps suitabale capacity as per existing complete all as specified
Supply and fixing in replacement of MCCB 3 pole 63 Amp, fixed type 25 KA, 415 Volt including making arrangement in existing LT panel and with proper connection of as per existing system complete all as specified as directed by Engineer-in-charge.
Supply and fixing in replacement of MCCB 3 pole 100 Amp, fixed type 25 KA, 415 Volt including making arrangement in existing LT panel and with proper connection of as per existing system complete all as specified as directed by Engineer-in-charge.
Demolition of brick work built in cement mortar including all quoins, arches pillars etc complete all as specified.
Demolition and breaking up drain pipes (SGSW, AC or PVC) of internal dia 150mm, set in cement mortar complete all as specified.
Demolition of reinforced cement concrete of any description and in any position complete all as specified.
Demolition of cement concrete (unreinforced) in ground floors and paving not exceeding 15cm thickness (below or above ground level) complete.
Cutting into existing manholes for removing existing branch drain, 150mm dia, making good to walling and rendering, cutting out branch channel and making good benching as required complete all as specified and directed by Engineer-in-Charge.
M & L Brickwork with subclass ‘B’ bricks, straight or curved on plan exc 6m mean radius built in CM 1:4 complete all as spd complete all as specified .
All as per srl item 47 above but except bricks complete all as specified .
M & L Rendering 15 mm thick in cement mortar 1:4 on fair faces of brick work or concrete surfaces, finished even and smooth without using extra cement mixed with water proofing compound as per manufacturer’s instructions complete all as specified.(WPC shall be measured and paid for separately as supply only).
M & L Concrete bed to drain pipes in PCC (1:4:8) types D-2 using 40mm graded stone aggregate including packing under and haunching against the sides of pipes after they are laid and tested as directed complete all as specified.
M & L Salt-glazed stoneware drain pipes 150mm dia graid 'A' laid in trenches and jointed as complete all as specified.
M & L PCC (1:4:8) type D-2 using 40mm graded stone aggregate in foundation/filling, mass concrete and base/sub floor complete all as specified.
Supply only integral water proofing compound complete all as specified.
M & L Cement concrete (1:2:4) type B1 (using 20 mm graded aggregate) as in copings, kerb etc complete all as specified.
M & L 50mm thick PCC 1:2:4 type B-1 using 20mm graded stone aggregate as in roof padding finished even and smooth without using extra cement complete all as specified.
M & L Providing precast reinforced cement concrete 1:2:4 type B-1 using 20mm graded stone aggregate in cover slabs (for manholes etc), shelves and similar articles with plain faces including necessary moulds and setting in cement mortar 1:4 including demolition of existing RCC cover slabs complete all as specified.(reinforcement to be measured separately)
M & L 5mm dia & over upto 10mm dia TMT bars cut to length bent to shape as required including binding with mild steel annealed wire not less than 0.90mm dia complete all as specified.
S&F in repair PVC (SWR) pipes, 110mm dia, single socketed, in any length with rubber ring joints, laid in trenches or in floors complete all as specified.
All as per ser item no 63 above but fixed on wall
S & F in repair 75 mm bore PVC (SWR) pipes single socketed in any length with rubber ring joints fixed to walls of suitable size complete all as specified.
S&F in repair PVC (SWR) bends any radius 110mm dia complete all as specified.
S&F in repair PVC (SWR) bends any radius 75mm dia complete all as specified.
S&F in repair PVC (SWR) branch piece 110mm bore, single (single Y) equal or unequal complete all as specified.
S&F in repair PVC (SWR) reducers 'T' 110mm X 75mm bore complete all as specified.
S&F in repair PVC (SWR) vent cowl 75mm bore complete all as specified.
S&F in repair PVC (SWR) vent cowl 110mm bore complete all as specified.
M & L Vitreous china wash basin, white, flat back, size 550 x 400mm, including brackets and cutting for and pinning in ends of brackets, fixed in repairs including 32mm bore brass chromium plated waste fitting and 32mm bore PVC waste pipe of sufficient length complete.
M & L Symphonic action PVC low level flushing cistern of 10 ltr capacity including internal fittings, brackets,32mm flush pipe for EWC etc as required on site fixed in repairs complete.
M & L Vitreous China wash down water closet pan, pedestal pattern, coloured, fixed in repairs including PVC seat cover black/white, closed pattern with flat bottom, and cover and mild steel chromium plated or aluminized hinging device and fixing bolts and making connections to flushing cistern complete
M & L Vitreous China Water closet Orissa pattern size 580 x 440mm, white with integral foot rests fixed in repairs including cast iron ‘P’ or ‘S’ trap, lime concrete in sunken floor making connection with flush pipe using new GI flush bend (Floor portion) and making good to floors, matching to existing surfaces complete.
S & F PVC connection 450 mm long for 15mm dia pipe having CP brass nuts with washers on both ends, fixed in repairs complete.
S&F in repair Plastic water closet seat cover, black/white, closed pattern with flat bottom, and cover and mild steel chromium plated or aluminized hinging device all as specified
M & L Vitreous China Urinal, Half stall type, white (excluding flushing cistern, flush pipe and waste pipe) Vitreous China urinals, Half stall type (back to corner wall type), complete including providing and fixing plus, bedding urinal against wall in cement mortar 1:2 securing urinal to plus with and including 60mm long brass screws, pointing around urinal back in cement; fixing automatic flushing cistern with brackets, flush pipe, grating and Union for discharge pipe. fixed in repair complete.
M&L 100 mm sand stone slabs and not less than 30cm wide and 1.50m long, set and jointed over joists, etc, complete in CM 1:3 complete all as specified.
De-sluding by removing of solid/semi solid sludge from existing septic tanks of any depth and capacity in foul conditions including taking and placing in position the cover slabs of any description including cement sand mortar 1:4 if required . Removal of sludge/solid contents will be removed to any place out side defence land or depositing where directed by Engr-in-Charge all as specified and directed. (Note : The sludge shall have to be disposed off in trenches duly excavated and covered after sprinkling of chemicals and cover with excavated soil and removal of extra soil without any extra cost to govt)
Cleaning of PVC tank of capacity 500 Litre kept in any position by draining of water complete, scraping the bottom, & sides of tank as required and taking out all waste particles , cleaning of outlets pipe, complete all as directed by Engineer-in-Charge
Cleaning of PVC tank of capacity 1000 Litre kept in any position by draining of water complete, scraping the bottom, & sides of tank as required and taking out all waste particles , cleaning of outlets pipe, complete all as directed by Engineer-in-Charge
Gill Construction Co
M/S BIKANER CHEMICAL LABORATORIES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .