Upgradation of InRow Cooling System in Data Centre to add Gas based Cooling System at Indian Oil Corporation Ltd., Marketing Division Head Office, Mumbai
2020_MKTHO_127242_1
HOSYS/ST-01/2020-21
Single
IT - Works related
Works
84 days
IOCL HO, Mumbai
Please refer Tender documents.
3 documents required · 3 mandatory
₹74,000
Yes
28 Nov 2020
18 Nov 2020
28 Nov 2020
18 Nov 2020
27 Nov 2020
18 Nov 2020
180 days
Amount
Capacity : 35 kw (with heater and humidifier) ( 25 M vertical distance + 15M horizontal distance)
Low Side Works for Inrow Units : Supply & Installation of Hard drawn Cu piping 16 gauge with suitable 13 mm thk insulation thickness of elastomeric nitrile rubber insulation from indoor to outdoor units.
Hot gas line : 1 1/8 " dia
Liquid line: 7/8 " dia
Refrigerant R-407C/R410a gas charge
Supply & Installation of MS Stands for indoor & outdoor units with rubber pads & the frame should be painted with two coats Black Colour synthetic enamel paint For outdoor units
Supply, installation, testing & commissioning of GI class ‘B’ pipe with nitrile rubber class "O" of 13 mm thk insulation for drain piping cut to required lengths and installed with all screwed joints, and providing and fixing in position with the necessary elbows, tees and reducers as per specifications. 25 mm dia
Supply, installation, testing & commissioning of GI class ‘B’ pipe for humidifier piping cut to required lengths and installed with all screwed joints, and providing and fixing in position with the necessary elbows, tees and reducers as per specifications. 20 mm dia
Supply, installation, testing & commissioning of Brass body Ball valve 20 mm dia
Supply, installation of extended piping kit (Solenoid Valve & Non return Valve) if overall copper pipe distance goes beyond 30 RMT per circuit.
Supply & installation of 1100 V grade, stranded(above 10Sq.mm) copper/aluminum conductor, XLPE insulated , PVC Inner sheathed, armored, PVC Outer sheath cables as per IS1554.. The cables shall be laid in tray/built up trench etc. 4 C x 2.5 sq.mm (Cu.)
Supply & installation of End Termination for above cable size 4C x 2.5 sq.mm
Supply & fixing of Earthing 8 SWG GI wire
Supply, installation of perforated type cable tray with cover and necessary supports (ms angles, threaded rod, flat & angle) as per site requirement to run the refrigerant pipes. 300 mm width
Electrical works for proposed inrow cooling units including works of tapping from existing panels, split panels, breakers, cables, cable trays with support and other accessories to complete the system. (20 mtrs distance from panel to inrow unit)
Civil works includes floor/wall cut out and finsing with same material to run the refrigerant pipes, power cables & cable trays etc., floor tail alignment, cutting, cleaning etc. and any other civil works requried to mount the out door units.
Project Management and Governance
stage.html
html • 0.01 MB
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .