Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.8 LAccepted-Finance | L1 | Accepted-Finance Lowest | |
| 2 | L2₹21.9 L+₹4.1 L (23.0%)Accepted-Finance | L2 | Accepted-Finance Other than lowest | |
| 3 | L3₹22.3 L+₹4.5 L (25.2%)Accepted-Finance | L3 | Accepted-Finance Other than lowest | |
| 4 | L4₹24.5 L+₹6.7 L (37.5%)Accepted-Finance | L4 | Accepted-Finance Other than lowest |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
9 Dec 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Major Auronee Das GE (U) Chandimandir
GE (U) Chandimandir
GE(U)/CHM-40/2021-22 PROVN OF REPAIRS / MAINTENANCE CUM PREVENTIVE MAINTENANCE OF LT SUPPLY SYSTEM AND CONNECTED ITEMS OF WORK AT CERTAIN LOCATIONS AT CHANDIMANDIR CANTT
2021_MES_487728_1
GE (U)/CHM-40/2021-22
Open Tender
Miscellaneous Works
Item Rate
180 days
Chandimandir Cantt
Please refer tender documents
7 documents required · 7 mandatory
₹500
GE (U) Chandimandir
₹50,000
Yes
17 Dec 2021
11 Nov 2021
16 Dec 2021
11 Nov 2021
9 Dec 2021
25 Nov 2021
60 days
Amount
Excavation in trenches for foundations, laying / taking out of cables, erecting of poles etc, in any type of soil, not exceeding 1.5 mtr in depth and not exceeding 1.5 mtr in width and getting out, complete all as specified and as directed.
Returning, filling in soils, in trenches including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and as directed
Removing excavated soils to a distance exceeding 50 metres and not exceeding 100 metre and depositing where directed at a level not exceeding 1.50 metre above the starting point.
Taking out old unserviceable LT cable from trences/ ducts including protection (brick/ cable cover) or taking down from pole/ wall and removing cable from site of work complete all as directed by Engineer in Charge of size:-
400 Sqmm 3.5 Core
300 Sqmm 3.5 Core
240 Sqmm 3.5 Core
185 Sqmm 3.5 Core
150 Sqmm 3.5 Core
120 Sqmm 3.5 Core
95 Sqmm 3.5 Core
70 Sqmm 3.5 Core
50 Sqmm 3.5/4 Core
25 Sqmm 3.5/4 Core
16 Sqmm 3.5/4 Core
Supply, laying , jointing testing and commissioning LT underground electric cable XLPE insulated, PVC sheathed armoured heavy duty 1100 volts grade heavy duty multystranded aluminium conductor laid in trenches / ducts or passing through pipe/duct under road or fixing on wall or along pole complete all as specifed and as directed of following size :--
400 Sqmm 3.5 Core
300 Sqmm 3.5 Core
240 Sqmm 3.5 Core
185 Sqmm 3.5 Core
150 Sqmm 3.5 Core
120 Sqmm 3.5 Core
95 Sqmm 3.5 Core
70 Sqmm 3.5 Core
Laying and jointing only, LT cable PVC insulated armoured, heavy duty 1100 volts grade with aluminium conductor cable laid in trenches or thorugh ducts/ pipes or fixed to poles or walls through pipes under road, jointing to OH conductor, LT panle, main swithces with new aluminum lugs of appropriate size as per size of cable complete as specified and as directed of size:-
400 Sqmm 3.5 Core
300 Sqmm 3.5 Core
240 Sqmm 3.5 Core
185 Sqmm 3.5 Core
150 Sqmm 3.5 Core
120 Sqmm 3.5 Core
95 Sqmm 3.5 Core
70 Sqmm 3.5 Core
50 Sqmm 3.5/4 Core
25 Sqmm 3.5/4 Core
16 Sqmm 3.5/4 Core
NOTES: For Serial No 6.01 to 6.11:- (i) Cables shall be issued under Schedule 'B' "free for fixing/ laying only". (ii) Excavation and earth work as required, pipe as required as protection to cable shall be measured and paid for sepratialy under respective items. (iii) Cutting chasis if any required for fixing cable on wall including fixing clamps are deemed included in the unit rate.
Double wall corrugated HDPE duct pipe of 100mm outer dia conforming to IS:14930 Pt-II with antirodant and non flame propergating properties of make and colour as approved by Engineer-in-Charge with fittings as protection to cable, laid in trenches or fixed to poles/walls complete all as specified and as directed.
MCCB, 415 volts 50 Hz with phase separators, adjustable thermal and magnetic release Ics = 100% of Icu, supplied and fitted/ fixed in position in replacement (including taking down old MCCB) complete all as specified and directed of capacity:-
630 Amp 35 KA , Triple pole
400 Amp 35 KA, Triple pole
200 Amp 25 KA, Triple pole
160 Amp 25 KA, Triple pole
125 Amp 25 KA, Triple pole
100 Amp 25 KA, Triple pole
63 Amp 16 KA, Triple pole
630 Amp 35 KA , Four pole
Change over switch ON LOAD type, 415 volt, 50 Hz, AC 3 pole 1-0-11 position door interlocking feature in sheet steel / metal enclosure, capacity 630 Amps rated current manually operated conforming to IS : 13947 or latest edition with high thermal and dynamic strength to withstand short circuit current level of 80 KA rms, fitted/ fixed in position, in replacement, (including taking down old switch) complete all as specified and as directed.
200 Amp 4 pole, busbar chamber 415 volts 50 Hz alongwith thick CRCA steel sheet enclosure of size not less than 80 cm x 12 cm x 10 cm and size of bus bar not less than 15 mm x 5mm and length of bus bar not less 75 cm supplied fitted/ fixed in position, in replacement (including taking down old chamber) complete all as specified and directed.
Straight through joint heat shrinkable for XLPE/PVC insulated and sheathed aluminum conductor under ground cable 1100 volts 3.5/4 core 95 to 120 sqmm, supply & jointing at any position/ location including testing complete all as specified and directed.
Main switch with rewireable fuses in sheet steel enclosure capacity 200 amps TPN 415 volts with and including porcelain fuses complete fitted/ fixed in position, in replacement (including taking down old switch) with and including making all incoming/ outgoing cable connection all as directed by Engr in Charge and as specified.
All as per the discription of ser No 12 above but of capacity 400 amps.
Supply and laying in position high voltage electrical insulation rubber mat as per IS - 15652 of size 5 m x 1 m, 3 mm thick complete all as specified and directed by Engr in Charge.
Material and labour for cutting of Road/ hard standing not less than 30 cm in depth and 30 cm in width for passing the cable/pipe and making good with PCC 1:2:4 type B-1 to make the road surface fair and level complete all as specified and directed by Engr-in Charge.
80mm bore (internal dia) steel water tubing, galvanized light grade, laid in trenches /fixed to wall/ along pole or as protection to cable, with all fittings and fixtures like mild steel flat iron clamps of appropriate size and shape, nuts, bolts and washers as approved by Engineer-in-Charge complete all as specified and as directed, with and including taking up/down old damaged steel pipe and removing from site of work complete all as directed.
Supply only PVC electrical insulation tape ISI marked 0.125 mm thickness x 1.80 cm width x 25 m length complete all as specified and directed by Engr in Charge.
Supply only cable lugs (Thimble) for LT cable, made out of aluminum of appropriate size and shape complete all as specified and directed for cable of size:-
Supply only LT cable inline connector (Ferrule) , made out of aluminum of appropriate size and shape complete all as specified and directed for cable of size:-
Cleaning of HT/LT electric cable ducts by removing cable duct cover, removing all the material / things from ducts of size 1.5 mtr depth (Avg) and width 1.00 mtr (Avg) and placing cable duct cover in position complete all as dircted and to the satisfaction of the Engr -in-Charge.
Schematic line diagram chart of size 2 mtr x 1 mtr made of 220 GSM white colour flex sheet computerized printed with different colour coding as required as per site alongwith suitable size of iron/steel frame and nut bolts, name of E/M installation and electric circuit diagram of size of text thickness and colour of line diagram as per sample kept in AGE E/M-I office and as approved by Engr-in-Charge fixed/ fitted in position in replacement (including taking down old chart / board) all as directed.
Supply, installation testing and commissioning new LT ACB of 630 Amp four pole mannual draw out microprocessor based 415 Volts, 50 Hz, suitable for existing location alongwith and including replacement of burnt aluminum bus bar with connected not bolts, lugs complete all as specified and directed including taking down old ACB all as directed.
Supply and fix in replacement of high power LED street light fitting energy saving luminaire with lens, capacity 60 W with system efficacy (lm/w) not less than 90 W lumens per watt, total system lumen not less than 5400 lumens, PF not less than 0.95, CRI not less than 70, colour temp 5000K to 6500K, surge protection not less than 5KV, high pressure die cast alumimum alloy LM6 housing IP - 65/66 class 1 protection, toughened glass cover, driver efficency >85% with constant output of current and voltage against input voltage variation 120 to 270 volt at 50 Hz (+5%), THD<10% complete all as specified and directed by Engr-in-Charge.
M/S RAGBIR ENGINEERING SERVICES
Vasudeva Trading Co.
M/S BALWINDER SINGH
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .