| Sl No | Description | Qty | Unit | lodhi switchgear enterprises L1 | M/S Shiv Shakti Enterprises L3 | JAI BHART ENGG WORKS L2 |
|---|---|---|---|---|---|---|
| 1.00Major overhauling of complete mechanism assembly of pneumatic type 145KV SF-6 CGL make (Mfg Year 1995) Circuit Breaker installed on LV Side Bays of 220/132KV, 160MVA TF-1, 2 & 3 Bays at 400 KV Sub-station Unnao. The work includes overhauling of complete control valve assembly by replacement of control valve seat, O-Ring P-50 and Roller C/D. Overhauling of holding latch, anti-pumping pin, opening & cleaning of pneumatic system, cylinder shock absorber etc. cleaning & greasing of all these parts, opening and cleaning of reservoir with replacement of O-6mm and 12mm gas pipe assembly. Checking of electrical connection and tightening them. Rectification of air leakage problem through NRV safety valve replacement of consumable spares as roller D valve sheet, O-rings of suitable size and other damaged rings if necessary. Overhauling of NRV and air filter of switch cubical along with replacement of all defective gaskets. Rectification of gas leakage by replacement of O-ring and brazing of gas pipe assembly of the mechanism, Checking and adjustment of air pressure switches and gas pressure switches and their replacement if required. Measurement of tripping/closing time of CB measurement of Contact Resistance of CB with digital meter and sunmission of report with all cost of required required O-rings, gaskets, misc. consumable items, skilled technician and T&P for satisfactory completion of work. | ||||||
| 1.01 | 145KV SF-6 CB (CGL Make) of 220/132KV, 160MVA TF-1 | 1 | Job | 78,500 ₹78,500 Lowest | 81,000 ₹81,000 | 80,000 ₹80,000 |
| 1.02 | 145KV SF-6 CB (CGL Make) of 220/132KV, 160MVA TF-2 | 1 | Job | 78,500 ₹78,500 Lowest | 81,000 ₹81,000 | 80,000 ₹80,000 |
| 1.03 | 145KV SF-6 CB (CGL Make) of 220/132KV, 160MVA TF-3 | 1 | Job | 78,500 ₹78,500 Lowest | 81,000 ₹81,000 | 80,000 ₹80,000 |
| 1.04 | Complete dismantling of INGERSOL RAND make compressor installed in 145KV SF-6 circuit breakers of above 220/132KV, 160MVA T/F bays at 400 KV S/S Unnao and their thorough overhauling by way of cleaning and replacing all gaskets (Form manufacturer tune kit), draining of old lubricating oil, cleaning of reservoir, filling of new lubricating oil of suitable grade, assembling the compressor after complete overhauling and commissioning the same including replacement of worn out motor drive belt and filling up of lubricating oil in compressor reservoir with SAE-40 grade lubricating oil and testing, including all cost of materials, T&P, and labour. The work also includes oiling and greasing of mechanism & motors. | 3 | Job | 24,500 ₹73,500 Lowest | 27,000 ₹81,000 | 25,000 ₹75,000 |
Tender Value
₹3.8 L
EMD Value
₹3,800
Closing Date
23 Mar 2025, 5:00 pmClosed
SE
ETC-II, UPPTCL, PAARESHAN BHAWAN, VIBHUTI KHAND, GOMTI NAGAR, LUCKNOW-226010
Work
2025_UPTCL_1017198_1
E-Tender No. ETC-II/L/61/2024-25
Open Tender
Electrical Works
Item Rate
60 days
Electy. 400 KV S/S
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
SE, ETC-II, UPPTCL, LUCKNOW
₹3,800
3 Dec 2025
12 Mar 2025
24 Mar 2025
12 Mar 2025
23 Mar 2025
12 Mar 2025
Amount
Major overhauling of complete mechanism assembly of pneumatic type 145KV SF-6 CGL make (Mfg Year 1995) Circuit Breaker installed on LV Side Bays of 220/132KV, 160MVA TF-1, 2 & 3 Bays at 400 KV Sub-station Unnao. The work includes overhauling of complete control valve assembly by replacement of control valve seat, O-Ring P-50 and Roller C/D. Overhauling of holding latch, anti-pumping pin, opening & cleaning of pneumatic system, cylinder shock absorber etc. cleaning & greasing of all these parts, opening and cleaning of reservoir with replacement of O-6mm and 12mm gas pipe assembly. Checking of electrical connection and tightening them. Rectification of air leakage problem through NRV safety valve replacement of consumable spares as roller D valve sheet, O-rings of suitable size and other damaged rings if necessary. Overhauling of NRV and air filter of switch cubical along with replacement of all defective gaskets. Rectification of gas leakage by replacement of O-ring and brazing of gas pipe assembly of the mechanism, Checking and adjustment of air pressure switches and gas pressure switches and their replacement if required. Measurement of tripping/closing time of CB measurement of Contact Resistance of CB with digital meter and sunmission of report with all cost of required required O-rings, gaskets, misc. consumable items, skilled technician and T&P for satisfactory completion of work.
145KV SF-6 CB (CGL Make) of 220/132KV, 160MVA TF-1
145KV SF-6 CB (CGL Make) of 220/132KV, 160MVA TF-2
145KV SF-6 CB (CGL Make) of 220/132KV, 160MVA TF-3
Complete dismantling of INGERSOL RAND make compressor installed in 145KV SF-6 circuit breakers of above 220/132KV, 160MVA T/F bays at 400 KV S/S Unnao and their thorough overhauling by way of cleaning and replacing all gaskets (Form manufacturer tune kit), draining of old lubricating oil, cleaning of reservoir, filling of new lubricating oil of suitable grade, assembling the compressor after complete overhauling and commissioning the same including replacement of worn out motor drive belt and filling up of lubricating oil in compressor reservoir with SAE-40 grade lubricating oil and testing, including all cost of materials, T&P, and labour. The work also includes oiling and greasing of mechanism & motors.
JAI BHART ENGG WORKS (BID ID -5069734)
M/S Shiv Shakti Enterprises (BID ID -5070283)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .