Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.2 CrAccepted-AOC KHASRA NO 183 10 SHYAM VIHAR HISAR HISAR HARYANA 125001 | HISAR | HARYANA | 125001 | ₹6.2 Cr | L1 | Accepted-AOC accepted |
| 2 | L2₹6.5 Cr+₹28.2 L (4.55%)Rejected-AOC VISHAVKARMA CHOWK NARWANA VISHAVKARMA CHOWK NARWANA 126116 | NARWANA | JIND | HARYANA | 126116 | ₹6.5 Cr+₹28.2 L (4.55%) | L2 | Rejected-AOC rejected |
| 3 | Rejected-Technical SCF 15 HUDA COMPLEX 184 NEW IDC 124001 | ROHTAK | HARYANA | 124001 | - | - | Rejected-Technical rejected |
| 4 | Rejected-Technical 12 BHARTI AARTIST COLONY VIKAS MARG NEW DELHI 110092 | EAST | DELHI | 110092 | - | - | Rejected-Technical rejected |
Tender Value
₹5.7 Cr
EMD Value
₹11.3 L
Closing Date
12 Apr 2024, 5:00 pmClosed
VISHWNATH KHICHI
ED - Rohtak
Provision for 4 Nos. 1010 KVA DG Set, Cabling, earthing and 20000 Liters capacity MS Tank for storage of diesel and other related accessories have been taken in the estimate.
2024_HRY_368056_1
2024322197E5 C36D 4DB5 9A74 A3390028A258667BAR
Open Tender
Electrical Works
Works
150 days
HAIBATPUR
Technical documents as per approved DNIT conditions.
3 documents required · 3 mandatory
₹20,000
₹11.3 L
Yes
19 Feb 2025
13 Mar 2024
15 Apr 2024
13 Mar 2024
12 Apr 2024
13 Mar 2024
Amount
HSR Items
[13.32]Providing and fixing bolts including nuts and washers complete.
[23.26.1]SAFETY ITEMS 1. Supply and erection of Medium Voltage caution notice plate of size 200*150 mm in three languages.
[24.1.3]EARTHING AND LIGHTENING ARRESTOR 3. Earthing with G.I. earth plate 600 mmx 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) complete as required.
[24.1.5]EARTHING AND LIGHTENING ARRESTOR 5. Extra for charcoal or coke and salt for G.I. plate or copper plate earth electrode.
[24.1.6]EARTHING AND LIGHTENING ARRESTOR 6. Supplying and laying 25mm x 3mm G.I. strip at 0.5 metre below ground as strip earth electrode including soldering etc. as required.
[24.1.7]EARTHING AND LIGHTENING ARRESTOR 7. Supplying and laying 25mm x 3 mm G.I. strip in 40 mm dia,GI pipe as/from earth electrode including soldering etc. as required.
[4.12.1]Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead up to 50 m and lift up to 1.5 m, as directed by Engineer-in-charge. 1. All kinds of soil
[4.32]Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.
[6.1.6]Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work below plinth level and up to Floor IV level: 6. 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size)
[6.25.1]Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. 1. All works up to plinth level
[6.30.1]Centering and shuttering including strutting, propping etc. and removal of form for 1. Foundations, footings, bases of columns, etc. for mass concrete
[6.30.6]Centering and shuttering including strutting, propping etc. and removal of form for 6. Columns, Pillars, Piers, Abutments, Posts and Struts
[6.33.6]Steel reinforcement for R.C.C. work, where not included in the complete rate of RCC, including straightening, cutting, bending, placing in position, binding, wastage, overlaps, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire etc. complete in all respect below plinth level 6. Thermo-Mechanically Treated bars of grade Fe-500D or more.
NS Items
26 N.S. - 26 Supplying, Laying, terminating, testing, commissioning of folowing sizes of Copper Conductor XLPE insulated, PVC sheathed armoured cable 1100 V grade. On surface the cable run shall be fixed on G.I. clamps etc of suitable size or as directed by the E-I-C complete in all respects. Supply and providing cable identification markers. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. as per specifications complete as required. Make: Havells / KEI / Polycab a) 3 C x 6 sq.mm
N.S. - 26 Supplying, Laying, terminating, testing, commissioning of folowing sizes of Copper Conductor XLPE insulated, PVC sheathed armoured cable 1100 V grade. On surface the cable run shall be fixed on G.I. clamps etc of suitable size or as directed by the E-I-C complete in all respects. Supply and providing cable identification markers. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. as per specifications complete as required. Make: Havells / KEI / Polycab b) 3 C x 4 sq.mm
N.S. - 26 Supplying, Laying, terminating, testing, commissioning of folowing sizes of Copper Conductor XLPE insulated, PVC sheathed armoured cable 1100 V grade. On surface the cable run shall be fixed on G.I. clamps etc of suitable size or as directed by the E-I-C complete in all respects. Supply and providing cable identification markers. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. as per specifications complete as required. Make: Havells / KEI / Polycab c) 3 C x 2.5 sq.mm
N.S. - 27 Making end termination with brass double compression gland including crimping of copper solderless lugs/ferrules for armoured power copper conductor cables of 1.1 KV grade of following sizes. a) 3 C x 6 sq.mm (Copper)
N.S. - 27 Making end termination with brass double compression gland including crimping of copper solderless lugs/ferrules for armoured power copper conductor cables of 1.1 KV grade of following sizes. b) 3 C x 4 sq.mm (Copper)
N.S. - 27 Making end termination with brass double compression gland including crimping of copper solderless lugs/ferrules for armoured power copper conductor cables of 1.1 KV grade of following sizes. c) 3 C x 2.5 sq.mm (Copper)
N.S. - 29 Providing and fixing 50 mm x6mm copper strip in 40 mm dia G.I. pipe from earth electrode as required.
N.S - 31 SITC of electrical driven rotary gear-pumps suitable for pumping of HSD
N.S. - 33 SITC of 80 Nb Flexible Hose pipe with AL Adopter for filling of HSD in BOT
N.S. - 34 SITC of Pot-Strainer a) 80 mm dia
N.S. - 35 SITC of oil flow meter 80 nb with flanged end for HSD service.
N.S. - 37 SITC of cast steel non return valves a) 50 mm dia
N.S. - 38 SITC of CAST STEEL Y Strainer a) 50 mm dia
N.S. - 36 SITC of cast steel ball valves a) 80 mm dia
N.S. - 36 SITC of cast steel ball valves b) 50 mm dia
N.S. - 36 SITC of cast steel ball valves c) 25 mm dia
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of smoke exhaust piping (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with 80 kg/cum density resin bonded fiber glass or 144 Kg/ cu m density mineral wool (non Combustible) pipe section insulation covered with a layer of 120 gm/sqm polythene sheet (vapour barrier) and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip (as per IS:1322 as amended up to date ) at joints and repairing of damage to building etc. as per specifications and as required. a) 350 mm dia.(75 mm thick insulation)
Supply and fixing of SS Bellow of following diameter b) 350 mm dia
Supply and fabrication of D G exhaust pipe supports by M.S angle of size not less than 100 x 50 mm x 6/8 mm including Nuts/ Bolts etc. of various sizes complete in all respect as per the approved design of structure to support the Exhaust pipes . The entire MS support structure should be painted by 2 coats of anti corrosive paint over primer coat of approved shade and make. The design of support to be duly approved by the Structural Consultant / Architect before fabrication and installation including RCC Foundation.
SITC of HSD storage tanks 20 KL capacity (6mm thick flat end) as per IS : 10987-1992 and approved for construction, shop drawings duly approved by “CCOE” suitable for under ground installation including the following: a. Inlet and outlet connections b. Vent pipe. c. Dip pipe assembly with calibration chart d. 550 mm dia manhole with cover. e. Lifting lugs f. MS ladder g. Providing Anti corrosive Pypcoat (AW4) treatment complete in all respect including taking fire NOC from the fire department upto the entire satisfaction of engineer in charge
Providing, laying, testing and commissioning of `C` class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : a) 25 mm dia
Providing, laying, testing and commissioning of `C` class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : b) 50 mm dia
Providing, laying, testing and commissioning of `C` class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : c) 80 mm dia
cost for approval of design of foundation of MS structure to support the exhaust pipes
Sandwiched Bus ducts Supplying, Installing by suspension on ceiling, testing and commissioning of following capacity Sandwich Type Bus Duct for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with metal clad enclosure having IP-66 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos aluminium bus bars having current density of 150 A/ sq cm at nominal current rating, necessary joints, elbow joints and expansion joints and bends, fire barrier at each floor, provision of tapping at every metre, adopter box and copper flexible for joints, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required (Based on DSR 3.13) MAKE: SCHNEIDER, LEGRAND, ABB, LandT, CandS b) 1600 A 50 KA SC for 1 Sec
Earthing with copper earth plate 600 mm X 600 mm X 6 mm (21 KG) thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required
Supply, Testing and Commissioning of Silent Type Diesel Generating Set at 0.8 PF, 415 Volts, 50 Cycles Per Second, 1500 RPM, 3 phase, suitable for parallel operation, 0.85 load factor including circuit breaker for isolation, sound proof acoustic and weather proof enclosure, residential type silencer (as per CPCB Norms-2) fabricated out of CRCA Sheet of 14 / 16 SWG thickness with 9 Tank pretreated before powder coating with Ventilation System complete in all respects comprising of the following. Diesel Engine - Diesel Engine suitable for driving alternator of below rating, compression ignition, 4 stroke cycle, Radiator cooled, turbo charged, battery starting, 1500 RPM, suitable for below output of alternator at 40oC, 50% RH and at 210 M MSL and confirming to BS 5514, BS 649, IS 10000, capable of taking 10% overloading for one hour after 12 Hrs. of prime continuous loading, complete with all the accessories i.e. tachometer with hour meter, flexible coupling with guard, crank case of steel, crank shaft, connecting rods, electronic governing system, dynamically balanced flywheel, air intake manifold, Air cleaner, anti vibration pads, starter motor, including all other accessories required to complete the system. Make: Koel Green / Greaves Cotton / Kirloskar (Kirloskar Oil Engines Ltd. Koel) / Ruston Instrument Panel - Engine mounted Instrument Panel fitted with and having digital display for followings : Start stop switch with key Water temperature indication Lubrication oil pressure indication. Lubrication oil temperature indication. Battery charging indication RPM indication Over speed indication Low Lube oil trip indication Engine hours indication Alternator - Synchronous Alternator of below capacity at 0.8 PF, 3 phase, 415 volts, 50 cycles, 4 wire, 1500 RPM, suitable for operation at 40 deg C, 50% RH and at 210 meter above MSL, capable
of taking 10% overloading for one hour after 12 Hrs. of prime continuous loading, brushless, self excited, self regulated through AVR, continuous duty confirming to IS 4722, BS 2613 suitable for tropical conditions, class H insulation, including terminal box suitable for bus duct termination as required. Make: Crompton / Crompton Greaves / Kirloskar / NGEF / Stamford Note : - Alternator should have with all other accessories as per specified in Technical specifications. Base Frame - Both the engine and alternator shall be mounted on suitable base frame made of MS channel which shall be installed on a cement concrete foundation and vibration isolating arrangement as per recommendations of the manufacturer. Power Controller For DG synchronization, Microprocessor based Power command controller (P.C.- 3.3 Jakson or equivalent) suitable for auto / manual synchronization and auto load sharing. Daily service Fuel tank of 990 liters capacity fabricated out of 2 mm thick MS sheet complete with inlet and outlet connections, oil indication gauge, drain plug, air breather, provision for fuel transfer system, level indicators and all standard accessories etc. as required. Exhaust Silencer - Exhaust manifold with residential silencer. The DG Set should be supplied with required hardware for external PLC based auto synchronization, auto load sharing, auto load management system. Starting system - 24 Volt DC starting system comprising of starter motors : voltage regulator and arrangement for initial excitation complete with 12/24 Volts suitable nos. lead acid type batteries of suitable AH. Ventilation System - Arrangement for fresh air intake for cooling of the engine and alternator, extraction, discharging hot air into the atmosphere as per standard specifications. a) 1010 KVA
LOHAN ELECTRICAL WORKS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .