Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | FIRST₹28.0 LAccepted-AOC | FIRST | Accepted-AOC BEING LOWEST | |
| 2 | SECOND₹29.2 LRejected-AOC NO 354 2ND CROSS VARADARAJNAGAR VIDYARANYAPURA POST BANGALORE 5600 097 | 5600097 | SECOND | Rejected-AOC BEING NOT LOWEST | |
| 3 | THIRD₹29.3 LRejected-AOC 39 SR LAYOUT MAIN ROAD NAL WING TUNNEL ROAD MURUGESH PALYA BANGALORE 560 017 | BENGALURU URBAN | KARNATAKA | 560017 | THIRD | Rejected-AOC BEING NOT LOWEST | |
| 4 | FORTH₹30.0 LRejected-AOC | FORTH | Rejected-AOC BEING NOT LOWEST | |
| 5 | FIFTH₹30.4 LRejected-AOC | FIFTH | Rejected-AOC BEING NOT LOWEST |
Tender Value
₹35.2 L
EMD Value
₹70,400
Closing Date
17 Sept 2021, 6:00 pmClosed
GE (AF) MARATHAHALLI
GE AF MARATHAHALLI WIND TUNNEL ROAD, KEMPAPURA, YEMALUR POST, BANGALORE. PIN- 560037
SPECIAL REPAIR REPLACEMENT OF LT PANEL BOARD FEEDER PILLAR BOX AT VAYU VIHAR AND PROVISION OF INTERNAL ELECTRICAL SERVICES AND CERTAIN MINOR WORKS AT IAM UNDER GE AF MARATHAHALLI
2021_MES_469675_1
8895/E8
Open Tender
Civil Works
Item Rate
180 days
GE (AF) MARATHAHALLI
AS PER ENIT
10 documents required · 10 mandatory
₹500
GE (AF) MARATHAHALLI
₹70,400
Yes
11 Mar 2022
21 Aug 2021
22 Sept 2021
21 Aug 2021
17 Sept 2021
4 Sept 2021
Amount
Supply, installation, testing and commissioning of outdoor type cubicle panel board suitable for 3 phase 4 wire 415 V, 50 Hz and tested at CPRI for 415 volts factory fabricated in an approved factory having modern fabrication process powder coating in approved shared having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS : 8623/93 comprising. The outer shell shall be made out of 3 mm thick CRCA sheet and MS angle section 40x40x6 mm base frame factory fabricated with front openable, double door system lockable/ open able. The bottom of the outer shell contains a detachable plate having size with glands. The outer shell shall be mounted on stand having zine coating not less than 80 microns. Provision of threaded earthing stud at bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. The degree of protection of outer shell shall be IP - 54. Inner shell shall be made out of 2.0 mm thick CRCA sheet duly compartmentalized for each control gear, TPN alluminum bus bar of rating not less than the 1.5 times the rated capacity of the incomer MCCB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleave. All control wires shall be with 2.5 sqmm multi strand copper conductor and shall be propely bunched, tied, ferruled for proper identification and crimped with adequate size of lugs all as specified and directed by Engr in charge. INCOMING : (a) Air circuit breaker 630 Amp fixed type 4 pole (b) Intelligent AC digital display three phase LCD ammeter 0 to 630A and voltmeter 0 to 500V with CT (c) Indication lamp RYB/RRR-set of 03 -01 No OUTGOING (a) MCCB 4 pole 200 Amps 35 KA 415 Volt -4 No (b) MCCB 4 pole 32 Amps 16 KA 415 Volt - 2 Nos (c) MCCB 4 pole 160 Amps 35 KA 415 Volt - 1 No
Supply, installation, testing and commissioning of outdoor type cubicle panel board suitable for 3 phase 4 wire 415 V, 50 Hz and tested at CPRI for 415 volts factory fabricated in an approved factory having modern fabrication process powder coating in approved shared having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS : 8623/93 comprising. The outer shell shall be made out of 3 mm thick CRCA sheet and MS angle section 40x40x6 mm base frame factory fabricated with front openable, double door system lockable/ open able. The bottom of the outer shell contains a detachable plate having size with glands. The outer shell shall be mounted on stand having zine coating not less than 80 microns. Provision of threaded earthing stud at bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. The degree of protection of outer shell shall be IP - 54. Inner shell shall be made out of 2.0 mm thick CRCA sheet duly compartmentalized for each control gear, TPN alluminum bus bar of rating not less than the 1.5 times the rated capacity of the incomer MCCB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleave. All control wires shall be with 2.5 sqmm multi strand copper conductor and shall be propely bunched, tied, ferruled for proper identification and crimped with adequate size of lugs all as specified and directed by Engr in charge. INCOMING : (a) Air circuit breaker 630 Amp fixed type (b) Intelligent AC digital display three phase LCD ammeter 0 to 630A and voltmeter 0 to 500V with CT (c) Indication lamp RYB/RRR-set of 03 -01 No OUTGOING ((a) MCCB 4 pole 400 Amps 35 KA 415 Volt -1 No (b) MCCB 4 pole 200 Amps 10 KA 415 Volt - 2 Nos (c) MCCB 4 pole 160 Amps 25 KA 415 Volt - 1 No
Supply, installation, testing and commissioning of outdoor type cubicle panel board suitable for 3 phase 4 wire 415 V, 50 Hz and tested at CPRI for 415 volts factory fabricated in an approved factory having modern fabrication process powder coating in approved shared having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS : 8623/93 comprising. The outer shell shall be made out of 3 mm thick CRCA sheet and MS angle section 40x40x6 mm base frame factory fabricated with front openable, double door system lockable/ open able. The bottom of the outer shell contains a detachable plate having size with glands. The outer shell shall be mounted on stand having zine coating not less than 80 microns. Provision of threaded earthing stud at bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. The degree of protection of outer shell shall be IP - 54. Inner shell shall be made out of 2.0 mm thick CRCA sheet duly compartmentalized for each control gear, TPN alluminum bus bar of rating not less than the 1.5 times the rated capacity of the incomer MCCB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleave. All control wires shall be with 2.5 sqmm multi strand copper conductor and shall be propely bunched, tied, ferruled for proper identification and crimped with adequate size of lugs all as specified and directed by Engr in charge. INCOMING : (a) MCCB 4 pole 200 A 25 KA 415 Volts - 1 No (b) Intelligent AC digital display three phase LCD ammeter 0 to 200A and voltmeter 0 to 500V with CT (c) Indication lamp RYB/RRR-set of 03 -01 No OUTGOING (a) MCCB 4 pole 160 Amps 25 KA 415 Volt -1 No (b) MCCB 4 pole 63 Amps 10 KA 415 Volt -1 Nos (c) MCCB 4 pole 40 Amps 10 KA 415 Volt -7 No
Supply, installation, testing and commissioning of outdoor type cubicle panel board suitable for 3 phase 4 wire 415 V, 50 Hz and tested at CPRI for 415 volts factory fabricated in an approved factory having modern fabrication process powder coating in approved shared having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS : 8623/93 comprising. The outer shell shall be made out of 3 mm thick CRCA sheet and MS angle section 40x40x6 mm base frame factory fabricated with front openable, double door system lockable/ open able. The bottom of the outer shell contains a detachable plate having size with glands. The outer shell shall be mounted on stand having zine coating not less than 80 microns. Provision of threaded earthing stud at bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. The degree of protection of outer shell shall be IP - 54. Inner shell shall be made out of 2.0 mm thick CRCA sheet duly compartmentalized for each control gear, TPN alluminum bus bar of rating not less than the 1.5 times the rated capacity of the incomer MCCB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleave. All control wires shall be with 2.5 sqmm multi strand copper conductor and shall be propely bunched, tied, ferruled for proper identification and crimped with adequate size of lugs all as specified and directed by Engr in charge. INCOMING : (a) MCCB 4 pole 160 A 25 KA 415 Volts - 1 No (b) Intelligent AC digital display three phase LCD ammeter 0 to 200A and voltmeter 0 to 500V with CT (c) Indication lamp RYB/RRR-set of 03 -01 No OUTGOING(a) MCCB 4 pole 63 Amps 10 KA 415 Volt -1 Nos (b) MCCB 4 pole 40 Amps 10 KA 415 Volt -4 Nos (c) MCCB 4 pole 32 Amps 10 KA 415 Volt -1 No
Supply, installation, testing and commissioning of outdoor type cubicle panel board suitable for 3 phase 4 wire 415 V, 50 Hz and tested at CPRI for 415 volts factory fabricated in an approved factory having modern fabrication process powder coating in approved shared having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS : 8623/93 comprising. The outer shell shall be made out of 3 mm thick CRCA sheet and MS angle section 40x40x6 mm base frame factory fabricated with front openable, double door system lockable/ open able. The bottom of the outer shell contains a detachable plate having size with glands. The outer shell shall be mounted on stand having zine coating not less than 80 microns. Provision of threaded earthing stud at bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. The degree of protection of outer shell shall be IP - 54. Inner shell shall be made out of 2.0 mm thick CRCA sheet duly compartmentalized for each control gear, TPN alluminum bus bar of rating not less than the 1.5 times the rated capacity of the incomer MCCB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleave. All control wires shall be with 2.5 sqmm multi strand copper conductor and shall be propely bunched, tied, ferruled for proper identification and crimped with adequate size of lugs all as specified and directed by Engr in charge. INCOMING : (a) MCCB 4 pole 160 A 25 KA 415 Volts - 1 No (b) Intelligent AC digital display three phase LCD ammeter 0 to 200A and voltmeter 0 to 500V with CT (c) Indication lamp RYB/RRR-set of 03 -01 No. OUTGOING (a) MCCB 4 pole 63 Amps 10 KA 415 Volt -4 Nos. (b) MCCB 4 pole 40 Amps 10 KA 415 Volt -1 Nos. (c) MCCB 4 pole 32 Amps 10 KA 415 Volt -1 No.
Excavation in trenches in soft/loose soil not exc 1.5 mtr wide and not exc 1.5 mtr in depth for laying of cables/errection of pole etc complete all as specified and as directed.
Returning, filling in trenches incl spreading leveling watering and well ramming in layers with hard/dense soil not exc 25 cm thick in each layer complete as specified and as directed
Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and as directed
M & L for sand cushioning with a layer of river sand 23 cm thick under and above the cable complete all as specified and as directed
S & L sub class burnt bricks for cable protection complete as specified as directed
Supply and laying cable XLPE insulated armoured,electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 Sqmm 3½ core connected with suitable legs including taking out the existing unserviceable cable complete all as specified and as directed.
Boring of holes under road ,pavement hard standing by trenchless technology using ultra sounding,technique including HDPE pipe 110 mm dia complete all as specified and as directed.
Supply and laying cable XLPE insulated armoured,electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size240 Sqmm 3½ core connected with suitable legs including taking out the existing unserviceable cable complete all as specified and as directed.
Supply and laying cable XLPE insulated armoured,electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 300 Sqmm 3½ core connected with suitable legs including taking out the existing unserviceable cable complete all as specified and as directed.
Supply and laying cable XLPE insulated armoured,electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 Sqmm 3½ core connected with suitable legs including taking out the existing unserviceable cable complete all as specified and as directed.
M & L for GI tubing light grade 80mm with all accessories for cable protection fixed on poles/bldgs of laid in trenches incl necessary MS clamps, bolts and nuts etccomplete all as specified and as directed.
M & L for GI tubing light grade 50mm with all accessories for cable protection fixed on poles/bldgs of laid in trenches incl necessary MS clamps, bolts and nuts etc complete all as specified and as directed.
M & L for PCC 1:3:6 type C2 with 40mm graded stone aggregate filling road cutting incl necessary form work complete all as specified and as directed.
M&L for point wiring complete with 1.5 Sqmm single core FRLS PVC insulated unsheathed cable 1100 volts grade multi stranded with copper conductor conforming to IS 694 drawn through and incl non-metalic rigid PVC conduit incl accessories run surface on walls/ ceiling incl MS terminal boxes fabricated with 1.6 mm thick MS sheet concealed where feasable on walls with moduler cover plate with frame for housing the moduler switches ,soccket,regulator incl provision of 1.5 Sqmm FRLS PVC insulated single core multi stranded copper conductor cable as earth continuity conductor and connecting to common earth dolly, all as specified and as directed. (a) One fan/Exhaust fan point controlled by one switch.
All as per item no 19 above, but, One 5A 2pin/3pin switch socket out let multipurpose on independent Board complete all as specified and as directed.
All as per item No.19 above, but , wiring complete with 2.5 Sqmm for 5 pin 5/15A socket on independent board with 2.5 sqmm copper conductor for earth continuity complete all as specified and as directed.
S&F for Modular Socket,6 Amps- 2/3 pin combined 2 Module complete all as specified and as directed.
S&F for Modular Switch 1 way 16 Amps 1 Module complete all as specified and as directed.
S&F for Modular Socket,6 A/16A,2 Module complete all as specified and as directed.
S&F for Modular Switch 1 way 6 Amps 1 Module complete all as specified and as directed.
Material and labour for PVC ceiling rose two to three terminal surface complete all as specified and as directed.
Fixing only in repair Modular type Fan step regulator, 2 module /1 module complete all as specified and as directed.
Supply and fixing ceiling fans complete with blades ,down rods,electronic regulator and accessories ,230 V ,1200 mm sweep.Min air delivery 210CFM with service value 6 BEE.Five star rated with brusless direct current motor (BLDC) complete all as specified and as directed.
Supply and fix exhaust fan made of sturdy Engineering plastic complete with louvers shutter ,voltage 230 V ,50 Hz,rpm 1200 , copper winding of sweep 300 mm complete all as specified and as directed.
Making suitable size Core cutting on stone/Bricks wall for fixing of exhaust fan 250 mm sweep and making good to the distrubed surface complete all as specified and as directed.
Supply and fix exhaust fan made of sturdy Engineering plastic complete with louvers shutter ,voltage 230 V ,50 Hz,rpm 1200 , copper winding of sweep 250 mm complete all as specified and as directed.
Material and labour for maintenance free single earth pit consisting of copper coated steel rod of size 17.2mm dia 3 mtr long 250 microns molecularly bonded joind with connecting clamp filled with maintenance free earth enhancing compound curec + 6 Kgs & curecon - 10 Kgs , compound strictly be a eco friendly and must comply to IEEE 80- 2000 clause 14.5 (d) ,(b) and this compound should be electrically & thermally conductive ,must be tested for long term in CPRI for atleast 2 years to display its stability and compound must be ISO certified, connected with 25 x 3mm strip fixed with spacer and saddles and all connected accessories including up to 7.5 mtrs up to equipement room and termination the wire with 25mm x6mm x300mm long copper bus bar fixed on wall with insulator support providing one test point Note :- (i) The soil resistivity must be checked before designing the quantity of earth pits based on the user requirement accordingly design should be submitted. (ii) Rate deemed to be inclusive of one PCC inspectin pit of 30cmx30cmx 30cm depth and RCC cover placed on pit. (iii) Earth pit required to be idetified by specific marker, colour codes (a) Maint free earthing pits Red colour and write proper earthing details all as specified and directed
Material anf Labour for 50 sqmm single core multistranded PVC insulated copper wire complete all as specified and as directed.
Supply and fix single pole and neutral sheet metal enclosure with a two pin and earth plug and socket complete with one 20 Amps SPN MCB complete all as specified and as directed.
Sub main wiring with Two runs of single core pvc insulated cable FRLS with copper conductor multistranded 1100 volts grade 4.0 sqmm through and including with suitable size of PVC conduit and its accessories , surface/ ceiling along with fixing arrangement etc including one run of 4.0 sqmm pvc insulated multistranded copper earth contuinuity conductor and connected to common earth dolly complete all as specified and as directed.
M & L point wiring with 1.5 sqmm nominal cross sectional area, single core, 1100 Volts grade, stranded, PVC insulated, unsheathed copper conductor cable in and including PVC cassing capping 20 mm dia or higher, medium grade complete with and including accessories/fittings, brass screws, washers etc, Sunk Zinc coated pressed steel terminal boxes for mounting modular switches including all cutting/chases etc in walls, making good to walls, ceiling etc including two coats of white/colour washing/ distempering etc to the disturbed surfaces to match and including continuous earth wire of size 1.5 Sqmm nominal cross sectional area, single core, PVC insulated copper conductor cable, unsheathed and connected to common earth and earth dolly complete all as specified and directed by Engr -in -charge for One light point controlled by one, one way switch.
All asper Item No.36 above, but , One fan point controlled by one, one way switch complete all as specified and as directed.
All asper Item No.36 above, but , for One 3 pin, 05 /06 Amps socket outlet point on same board controlled by one , one way 05/06 Amps switch complete all as specified and as directed.
All asper Item No.36 above, but ,for One 3 pin, 05 /06 Amps socket outlet point on independent board controlled by one , one way 05/06 Amps switch complete all as specified and as directed.
M & L point wiring with 2.5 sqmm nominal cross sectional area, single core, 1100 Volts grade, stranded, PVC insulated, unsheathed copper conductor cable in and including PVC cassing capping 20mm mm dia or higher, medium grade complete with and including all accessories/fittings, brass screws, washers etc, Sunk Zinc coated pressed steel terminal boxes for mounting modular switches ,including all cutting/chases etc in walls, making good to walls, ceiling etc including two coats of white/colour washing/ distempering etc to the disturbed surfaces to match and including continuous earth wire of size 1.5 Sqmm nominal cross sectional area, single core, PVC insulated copper conductor cable, unsheathed and connected to common earth and earth dolly complete all as specified and directed by Engr -in -charge for one 15 /16 Amps socket outlet point on independent
S & F MCB DB TPN 4Way, Double Door flush to wall including all cutting etc on wall including making good the disturbed surfaces to match the existing complete all as specified and directed.
S & F MCB SPN 40 Amps, 'C' series, 240 V complete incl making conections all as specified and directed.
S & F MCB SP 6-32 Amps, 'C' series, 240 V complete incl making conections all as specified and directed.
S & F MCB TPN 63 Amps incl making connections all as specified and directed.
Supply and fixing 36W LED Fitting, 2 x 2 recess / Surface LED flat panel with high brightness LED for glare free homogenous illumination including LED driver complete all as specified including taking down old unserviceable fittings complete all as specified and as directed.
Supply and fix DLP UPVC adaptable trunking of size 195 x 50mm complete with trunking accessories viz cover joints, clips, internal/external angles, partition/flat junctions and branches complete for camouflaging existing LT UG cable/ copper wires refixing the same after removing the existing copper/aluminium wiring from wall/roof and making proper connection to the existing panel/board complete all as specified and as directed.
Dismantling and taking out care fully the existing KWH meter single phase kept in side and refixing and connecting the same after completiion of E/M work complete all as specified and as directed.
S&F ceiling fan down rod suitable size up 1 Mtr long including clamp complete all as specified and as directed.
S S BUILDERS
GKR and CO
m/s raghavendra kulkarni
Pacific Enterprises
Varsha Enterprises
G K CONSTRUCTIONS
RRK PROJECTS
B5BUILDING SOLUTIONS
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .