Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹25.4 LAdmitted-Finance | -18.12% | ₹25.4 L | L1 | Admitted-Finance |
| 2 | L2₹30.5 LAdmitted-Finance | -1.60% | ₹30.5 L | L2 | Admitted-Finance |
Updated dates
Tender Value
₹33 L
EMD Value
₹66,000
Closing Date
3 Feb 2026, 11:00 amClosed
SE Civil, HATHI BHATA POWER HOUSE, AJMER
O/O SE (CIVIL), HATHI BHATA POWER HOUSE , AVVNL , AJMER
Supply and Installation of smoke detector and fire fighting system at IT Building Madar Ajmer
2026_AVVNL_526203_1
AVV2526GLOB00493
Open Tender
Civil Works
180 days
SE Civil, HATHI BHATA POWER HOUSE
PLEASE REFER TENDER DOCUMENTS
3 documents required · 3 mandatory
₹590
AO O and M AVVNL AJMER and MD RISL JAIPUR
₹66,000
Yes
4 Feb 2026
8 Jan 2026
4 Feb 2026
8 Jan 2026
3 Feb 2026
8 Jan 2026
Supplying, Installation, Testing & Commissioning of Electrical Driven fire fighting duty pump as per TAC and IS 12469-1988., Factory assembled in Pump make OEM for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given as A, B, C, D, E, F, G and H. (A) End Suction / Horizontal Axially split casing volute type Single / Multi stage Centrifugal pump complete for delivery of below mentioned discharge and Head (B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze, Shaft - SS 410, Packing - Mechanical Seal (C)Pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head (D) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed 2900 / 1500 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect . ( E) Common bed plate fabricated from mild steel channel for installation of pump and Motor including anti vibration pads. (F) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Physical presence of Department’s representatives. G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM (H)Suitable size Reinforced cement concrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying, Installation, Testing & Commissioning of Electrical Driven fire fighting duty Jockey pump as per TAC and IS 12469-1988., Factory assembled in Pump make OEM suitable for automatic operation and consisting of following details given as A, B, C, D, E,F and G A) Horizontal End suction Single / Multi Stage Centrifugal Back pull type pump complete for delivery of below mentioned discharge and Head (B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze, Shaft - SS 410, Packing - Mechanical Seal (C) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed not Exceeding 2900 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect . D) Common bed plate fabricated from mild steel channel for installation of pump and Motor including anti vibration pads. (E) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Virtual / Physical presence of Department’s representatives. (F) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM G)Suitable size Reinforced cement concrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ) All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 180 LPM suitable for 88 Mtr Multi Stage
SITC of pressure switches of pressure range 3 to 15 Bar for Main, Jockey, Terrace pump and Diesel pumps, Etc. as Required ( Control Cable from Pressure switch to Panel to be Paid Extra ). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Providing and fixing 20/25 mm dia. (PN - 1.6, Type-S1, Flanged, ISI marked) air release valve confirming to IS - 14845 : 2000 with Double Flange isolating valve (pressure rating PN 1.6) complete with 1 no. Matching Flanges (Minimum 10 mm thick), nuts, bolts, washers, gaskets etc as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS 'C ' class (Heavy) pipes conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applications including cutting, screwing, welding etc. & forged steel fittings like elbows, tees, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts including cutting hole and chase in brick or RCC walls/ slab and making good the same. complete with painting of one coats of Red Oxide and two or more coats of synthetic enamel paint of required shade complete as required. (Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs.). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 100 mm dia
Supplying and Fixing of PN 16 Cast Iron Dual Plate Wafer Type Check Valve / Non return valve with SS / Bronze flap complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 100 mm dia
Supplying and fixing Inlet Breeching Connection of CI body with Gun Metal male instantaneous inlet couplings with Inbuilt NRV, Drainage Connection with 50 mm Brass gate valve complete with PVC blank cap and chain as required for 150mm dia Outlet with 1 no. Matching Flange (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following Ways. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 2 Way
Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS 'C' class (Heavy) pipe conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applications in Existing trench with cement concrete block as supports including cutting, welding etc & forged steel fittings like elbows, tees, tapers, reducer with cleaning,wrapping and coating of the pipe with 4 mm thick tar based polymaric corrosion protection tape including applying uniform coat of cold pipekot primer as per IS; 10221 for protection against corrosion complete in all respect. ( Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs. & Excavation of Trench and refilling of trench to be paid extra). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 100 mm dia
Supplying and fixing cylindrical air vessel of continuous welded construction fixed at riser top made of 250 mm dia, fabricated out of 8 mm thick MS sheet, 1200 mm in height with flanged connection, Provision for 25 mm dia drain valve,air release valve,safety valve pressure gauge as required accessories and painting with two coats of Red Oxide and two coat of post office red enamel paint including The tank shall be installed on suitable vertical legs. The legs shall be provided with M.S. Angle of size 75 mm x 75 mm x 5 mm at the bottom. The legs shall be grouted in cement concrete foundation. as required. ( Air Release valve, Drain valve, PRV, Pressure Gauge shall be Paid Extra ). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying and Fixing of PN 16 Flanged Y strainer fabricated out of cast iron body, SS 304 strainer with perforated screen with 3 mm. dia holes in existing MS / GI pipe complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets etc as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying and Fixing of PN 1.6 Butterfly Valve (Wafer Type) with S.G Iron Disc and confirming to IS:13095 complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 100 mm dia
Supplying and Fixing of PN 16 Brass/GM Ball valves with screwed end, SS Ball including teflon tape etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 25 mm dia.
Supplying and fixing of flexible hose made with 100% polyester, black EPDM internal rubber lining with External coat of synthetic elastomer (IS:636, type-A) 63 mm dia, 15 mtr. Long RRL hose pipe with instanteneous type 63 mm dia SS-304 male and female couplings (IS:903) duly bound and riveted to hose pipes with copper rivets and SS wire etc. as required.Appropriate Test Certificate/ report with liable warranty of product/accessories from OEM shall be submitted.
Supplying & fixing SS-304 Short Branch Pipe conforming to IS: 903:93 fitted with 20mm (nominal internal diameter) bore nozzle, for projecting water in form of solid jet. The Branch shall have 63mm Male Instantaneous Inlet, suitable for use with 63 mm size Fire fighting hoses. H.P. tested to 21 kgf/cm² for 2.5 minutes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying and fixing first -Aid Fire hose reel Drum wall mounted swinging type with MS construction powder painted in post office Red, conforming to IS 884-1985 with upto date amendments, complete with the following as required. (A) Thermoplastic / Rubber Hose (B)20 mm dia UL, FM Bronze / SS nozzle with 5mm orifice (C)Drum and brackets for fixing the equipments on wall. (D) Connections from riser with 20/25 mm dia Brass/GM gate valves with screwed end and conforming to IS:778 Class-1 through Forged steel Screwed Union & M.S. pipe. Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . With 30 m x 20 mm Thermoplastic hose as per IS:12585 Type-2 and Bursting pressure 42 Kg/sqcm
Supplying and fixing of SS 304 Single / Double headed oblique pattern hydrant landing valve (internal/external) with 75 / 100 mm dia flanged inlet & 63 mm dia instantaneous type female outlet coupling with cast iron wheel complete with ABS cap and chain and all accessories as per IS:5290-93 (Type-A) in cluding matching flange (14 mm thick), nuts, bolts, washers, gaskets, etc as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . Double Headed with 100 mm Dia. Flanged Inlet
Providing and fixing of 100 mm Dia. Flanged Gun Metal Fire brigade Suction hose coupling (draw out connection) for female coupling as per IS:902-1974 complete with Matching Flange (Minimum 14 mm thick), nuts, bolts, washers, gaskets, etc as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supply and Fixing of Cast iron body one side Flanged and other side strainer ball type foot valve with Reinforced rubber Nitrile rubber coated Ball including Matching Flange (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following Sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying and fixing of 750 mm x 600 mm x 250 mm Outdoor application Fire Hose Cabinet made of 1.6 mm thick MS sheet Duly powder coated in red color externally and white internally with 6 mm thick glazed doors with Expanded Metal 2 mm thick Jali including necessary locking arrangement suitable to accommodate 2 Nos 15 Mtr. Long RRL Hose and 1 No. branch pipe on Existing Wall / Angle Iron Frame as required. (Cost of MS structure for mounting Frame is to be Paid Extra) All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying and fixing of 1000 mm x 600 mm x 500 mm Outdoor application Fire Hose Cabinet made of 1.6 mm thick MS sheet Duly powder coated in red color externally and white internally with 6 mm thick glazed doors with Expanded Metal 2 mm thick Jali including necessary locking arrangement suitable to accommodate External hydrant with butterfly valve, 2 Nos 15 Mtr. Long RRL Hose and 1 No. branch pipe on Existing Wall / Angle Iron Frame as required. (Cost of MS structure for mounting Frame is to be Paid Extra). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supply & Fixing of Fire Man's Axe with carbon steel head & rubber moulde handel usable upto 20 KV and confirming to IS :926 with length approx 0.4 M & weight 3.0 Kg. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Providing & fixing Stainless Steel pressure gauge with dial of 150 mm dia size and range 0 to 20 kg/sq.cm with 3 / 8 " BSP bottom entry , Ball valve , SS Syphon tube all fittings etc, duly calibrated before installation in MKS and FPS units, Accuracy Level +/- 1% including Making Drilling in Existing MS Pipe Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying and Fixing of Galvanized Mild Steel fire bucket Confirming to IS: 2546 : 1974 with one coat of primer and two coat of enamel paint of approved shade on Angle Iron ( 50 x 50 x 5 mm) Stand of Size 800 x 1240 x 400 mm with MS 22 SWG Galvanized Canopy, 4 Hooks for Buckets including associated civil works etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying and fixing orifice plate made of 6 mm thick stainless steel with orifice of required size in between flange & landing valve of external and internal hydrant to reduce pressure to working pressure of 3.5 kg/cm2 complete with rubber gasket, GI bolts, nuts, washers etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Providing and Fixing of PN16 Resilient rubber lined single arch vibration eliminators suitable for raw water up to 45 deg. C temperature, working pressure 8.5 Kg/cm2 and test pressure 14 Kg/cm2 to provide relief from stresses at pipe including Matching Flange (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following Sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 100 mm Dia. x 150 mm Oal
Providing and fixing of Fire / Electrical Shaft Door made from powder coated (50 Micron) aluminium partialy glazed with 6 mm thick glass and Partialy / Fully Louvered with Outer frame of Aluminium Section of Size 100 mm x 45 mm x 1.5 mm and Shutter's Top, Middle & side Section of Size 82 mm x 45 mm x 1.5 mm, Bottom Section of Size 110 mm x 45 mm x 1.5 mm Complete with Hinges, Tower bolt, Handle, Aldrop, Locking Arrangement including dash fasteners of required dia and size, necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. as per drawings and the directions of Engineer-in-charge. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 2 x 1.5 sq.mm
Providing and fixing of Aluminium housing body self contained Rechargeable LED Emergency Light with required content and Size Approx. 300 mm x 180 mm, confirming to IS:9583 :1981with Ni-Mh / Ni - Cd Battery, 3 Hrs Back Up, Constant Current Charger, Input Voltage 230 V , 50 Hz including fixing on wall, door, ceiling etc. with proper clamps, hangers, cleats, anchor fasteners etc. complete in all respects required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . Double sided signage
Supply & Fixing of Trolley mounted 22.5 Kg CO2 type Fire Extinguisher conforming to IS: 16018:2012, charged with CO2 gas (purity 99.7% conforming to IS 15222), Powder coated Internal & External Surface Manganese steel ISI marked as per IS 7285 cylinder body , Wheel type Forged brass release valve ISI Marked as per IS 3224 with Inbuilt safety release device ((Fusible plug and Rupture Disc Type), 1.5 Mtr. long Metal wire braided hose having minimum bursting pressure of 140 Kgf/cm2, Horn with metallic thread connection, QR code for Product Traceability, including Double mounted handle as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of UL 10th edition / EN54 / VDS certified Automatic Floating Sensitivity type Analog addressable Multi criteria (two optical/Smoke sensor to reduce false alarm) detector with mounting base & LED etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of UL 10th edition / EN54 / VDS certified Rate of Rise Heat Detectors (Thermal Detectors):GRADE-I Analouge Addressable type Heat Detectors with solid state design with sensing element combination of fixed type and rate of rise of temperature mounting base & LED etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of UL 10th edition / EN54 / VDS certified Addessable Manual Call point (MCP) with LED / FIRE Indication Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of UL 10th edition / EN54 / VDS certified Addressable sounder with strobe light, Loop Powered / Direct powered from FACP with sound level 90 dB and programmable from the panel etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of Response Indicator for indicating the activation of the Remotely located Detector for Addressable type Detectors Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of UL 10th edition / EN54 / VDS certified Microprocessor based inteligent, Analogue addressable,modular, expandable networkable loop Fire Alarm Control Panel with each loop capacity of min 125 detectors per loop with total of 125 detectors & devices with Loop length up to 1 KM as per NFPA 72 approval. The Panel shall be able to give pin point location of addressable units via the address code for each unit. The Panel shall also be able to automatically switch off all control switches when-ever any Alarm is triggered. . The panel shall have 230 + 5 % volts power supply, Automatic battery charger 24V, sealed lead acid maintanence free battries sufficient for 24 hours normal working and then be capable of operating the system for 30 minutes during emergency condtion. Loop interface cards, communication module, LCD/LED unit to indicate Fire / Fault Signal of individual unit, inbuilt networking port(both RS485&Ethernet),Serial port for printer,two supervisory inputs,two position key switch and USB port for programming.including the cost of all accessories Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of UL 10th edition / EN54 / VDS certified Microprocessor based inteligent, Analogue addressable,modular, expandable networkable loop Fire Alarm Control Panel with each loop capacity of min 125 detectors per loop with total of 125 detectors & devices with Loop length up to 1 KM as per NFPA 72 approval. The Panel shall be able to give pin point location of addressable units via the address code for each unit. The Panel shall also be able to automatically switch off all control switches when-ever any Alarm is triggered. . The panel shall have 230 + 5 % volts power supply, Automatic battery charger 24V, sealed lead acid maintanence free battries sufficient for 24 hours normal working and then be capable of operating the system for 30 minutes during emergency condtion. Loop interface cards, communication module, LCD/LED unit to indicate Fire / Fault Signal of individual unit, inbuilt networking port(both RS485&Ethernet),Serial port for printer,two supervisory inputs,two position key switch and USB port for programming.including the cost of all accessories Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . Add Extra for per Loop expansion beyond Two Loop
SITC 6 watt Speaker mounted in M S sheet box with perforated front mesh for PA and Emergency System. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 2 x 1.5 sq.mm
SITC of 2 way communication Fire Fighter's Telephone Handset to make a call to the Main FACP from Telephone Jack Location Complete as required . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
SITC of 2 way communication Fire Fighter's Telephone Jack.Complete as required . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Supplying and drawing Fire Resistant flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR 2 x 1.5 Sq.mm Armoured With Outer Sheath in Red Color.
SITC of IP-42 and general construction confirming to IEC 61439-1&2. type tested assembly (TTA) wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:- (a) Panel having short circuit withstand capacity of minimum of 50 kA for 1s (Icw rating) at 415 V, 50 HZ AC supply, Rated Impulse withstand voltage (Uimp) of 12kV for withstanding against transient Overvoltages, mechanical impact level of IK10 level and internal arc for 50kA for 0.3 second with aluminum busbar and fully type tested at an Independent Laboratory, Type test certifacte has to be submitted for all rating of LV Switchgear to be used in Panel. (b) All four Horizontal Busbars shall be in same compartment. Certified design of switchboards shall be proven design from OEM (Switchgear Manufacturer). OEM name should be mentioned on top of each column of switchboard. Also, OEM Partnership Certificate shall be furnished by Panel builder. Panel shall be fabricated with a double door arrangement. Front Door shall be fitted with transparent Glass to allow maintenance staff to visually access device status, meter readings, indicating lamp status without opening the door.© Panels and cubicles shall be fabricated with CRCA Sheet Steel of thickness, same as as per OEM Design. Sheet Steel having vibration free structure chemically treated with nine tank process before painting for surface treatment and powder coated, with suitable electrolytic grade high conductivity Aluminium busbar extensible type, busbar supports, ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra ) (d)Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. (e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. (f)Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra ) (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test and Heat run test(type test) shall also be carried out. (h) only outer surface area on all sides shall be measured & panel to be fabricated only from Switchgear OEM approved fabricators only. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia 200 mm dia per running inch length
Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it's ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR Short point (up to 3 mtr.)
Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it's ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR Medium point (up to 6 mtr.)
Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it's ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR Long point (up to 10 mtr.)
S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including cutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 25 mm
Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 10 A modular switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR On board
P/Laying ISI marked P.V.C. insulated submersible cable confirming to(IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, existing pipe / open trench / Cable tray / on surface including making connection etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 6.0 Sq.mm 3 core flat / Round
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.03 MB
TDSomkedetector.pdf
Tender Documents • 2.61 MB
BOQ_938875.xls
BOQ • 0.38 MB
Download all tender documents and submit your bid