Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.8 LAccepted-AOC 319 A MEERAPUR PRAYAGRAJ | PRAYAGRAJ | UTTAR PRADESH | 211001 | L1 | Accepted-AOC First Lowest | |
| 2 | L2₹1.9 L+₹11,000 (6.28%)Rejected-AOC | L2 | Rejected-AOC Second Lowest |
Tender Value
₹1.9 L
EMD Value
₹2,000
Closing Date
28 Feb 2024, 5:00 pmClosed
Superintending Engineer
Superintending Engineer Electricity Transmission Circle I 57 George Town Prayagraj 211002
Rectification of SCADA installed at 132 KV Substation Kaurihar, Under Electy. Trans Division-I, Prayagraj
2024_UPTCL_884439_2
145-ETC-I(A)/ 2023-2024
Open Tender
Electrical Works
Item Rate
60 days
Kaurihar
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
SE,ETC,PRAYAGRAJ
₹2,000
23 Jul 2024
22 Feb 2024
29 Feb 2024
22 Feb 2024
28 Feb 2024
22 Feb 2024
Amount
Inspection and rectification of Siemens make substation Automation System installed at 132KV S/S KAURIHAR PRAYAGRAJ. The following works are Including for healthy SCADA communication. (a)Replacing the defective optical fibre cable and splicing it if Required anywhere in the ring. (b) Replacing the defective FO Multimode ST-ST port cords. (c) Checking & Rectifying the healthiness of LIUs and its communicating Ports. (d) Checking &rectifying the healthiness of IEC 61850-7 Ethemet switches. (e) Replacing the defective CAT-5/LAN cables and checking its healthiness. (f) Rectifying communication healthiness of MOD bus RTU for various MFM meters. (g) Rectification /checking healthiness of GPS system and its time synchronization with all relay’s. (h)Reinstallation of old backup to SCADA. (I) Checking the healthiness of all protection realy’s communication to SCADA. (j) Checking of all required events, alarms, numerical dates, status and signals to SCADA from various bays & feeders. (k) Checking the SLD of s/s to SCADA screen. (l) Checking the all required operation of equipment’s from SCADA. (m) Configuration of Ethernet switches/modems/ rut etc. If required. (n) Installation of new window and DS agile SIEMENS automation software in standby PC. And reinstalling the old backup in HMI-2making both HMI-1 & HMI-2 in all respect. At the time of rectification all required materials and computer parts will be arranged by department without extra charges, except the following given material will be provided by contractor. Scada license key, activation key, old SAS backup and software CD will be provided by department.
Windows 10/11 OS with 32/64 bit suitable for ADVANTEC PC.
Supply of fibre optical Multimode patch cards for ST-ST ports.
Supply of fibre optical Multimode patch cards for LC-ST ports.
M/S OM SHANTI ENTERPRISES
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .