Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.7 CrAccepted-AOC K 99 LGF KALKAJI NEW DELHI 110 019 | NEW DELHI | SOUTH EAST DELHI | DELHI | 110019 | ₹37.7 Cr | L1 | Accepted-AOC Being the Lowest and reasonable tender |
| 2 | L2₹40.5 CrRejected-Finance | ₹40.5 Cr | L2 | Rejected-Finance Not being the Lowest |
| 3 | L3₹41.4 CrRejected-Finance ONLOOKER BUILDING 3RD FLOOR 25 SHRI P M ROAD FORT MUMBAI 400 001 | MUMBAI | MAHARASHTRA | 400001 | ₹41.4 Cr | L3 | Rejected-Finance Not being the Lowest |
| 4 | L4₹43.7 CrRejected-Finance | ₹43.7 Cr | L4 | Rejected-Finance Not being the Lowest |
| 5 | L5₹48.5 CrRejected-Finance | ₹48.5 Cr | L5 | Rejected-Finance Not being the Lowest |
Tender Value
₹39.5 Cr
EMD Value
₹15 L
Closing Date
27 Jan 2024, 6:00 pmClosed
Chief Engineer (Navy) Mumbai
Headquarters, Chief Engineer (Navy) Mumbai 26, Assaye Building, Colaba Mumbai 400 005
COMPLETION OF INCOMPLETE WORK FOR PROVN OF DEFICIENT TRAINEE OFFRS SINGLE LIVING ACCN AND MESS AT INS HAMLA MUMBAI
2023_MES_620165_1
87927/E8
Open Tender
Civil Works
700 days
INS Hamla Mumbai
As per tender Documents
8 documents required · 8 mandatory
₹3,000
GE (P) Bhandup
₹15 L
Yes
1 Mar 2024
24 Oct 2023
29 Jan 2024
24 Oct 2023
27 Jan 2024
13 Jan 2024
25 Oct 2023 - 31 Oct 2023
Amount
SCHEDULE "A" Part - I (BUILDING WORKS) Total Amount B/F from Sch-'A' Part-I
SCHEDULE "A" PART-II (SITE CLEARANCE, AREA DEVELOPMENT, EXCAVATION & EARTHWORK) Total Amount B/F from Sch-'A' Part-II
SCHEDULE "A" PART-III (INTERNAL WATER SUPPLY) Total Amount B/F from Sch-'A' Part-III
SCHEDULE "A" PART-IV (INTERNAL ELECTRICFICATION) Total Amount B/F from Sch-'A' Part-IV
SCHEDULE "A" PART- V (ROAD/PATH/CULVERT) Total Amount B/F from Sch-'A' Part-V
SCHEDULE "A" PART-VI (SEWAGE DISPOSAL) Total Amount B/F from Sch-'A' Part-VI
SCHEDULE "A" PART-VII (AREA DRAINAGE) Total Amount B/F from Sch-'A' Part-VII
SCHEDULE "A" PART-VIII (RAIN WATER HARVESTING) Total Amount B/F from Sch-'A' Part-VIII
SCHEDULE "A" PART-IX (EXTERNAL ELECTRIFICATION) Total Amount B/F from Sch-'A' Part-IX
SCHEDULE "A" PART-X (EXTERNAL WATER SUPPLY) Total Amount B/F from Sch-'A' Part-X
SCHEDULE "A" PART-XI (FIRE FIGHTING SYSTEM) Total Amount B/F from Sch-'A' Part-XI
SCHEDULE "A" PART-XII ( LIGHTNING PROTECTION & AVIATION LIGHT) Total Amount B/F from Sch-'A' Part-XII
SCHEDULE "A" PART-XIII ( WATER COOLER & HOT WATER SYSTEM ) Total Amount B/F from Sch-'A' Part-XIII
SCHEDULE "A" PART-XIV ( SPECIAL ITEMS: ADD. POWER POINTS) Total Amount B/F from Sch-'A' Part-XIV
SCHEDULE "A" PART-XV (TV & TELEPHONE CONDUITS) Total Amount B/F from Sch-'A' Part-XV
SCHEDULE "A" PART -XVI (MISCELLANIOUS ITEMS)
INTERNAL WATER SUPPLY
S & F Two way bib cock with wall flange quarter turn (Low-flow) 16 mm dia complete all as specified and directed by Engineer-in-Charge. Make - Jaquar Model No KUP-35041PM or techno commercial equivalent in makes mentioned in Particular Specifications.
S & F Bib cock with wall flange quarter turn (Low-flow) 16 mm dia complete all as specified and directed by Engineer-in-Charge. Make - Jaquar Model No KUP-CHR-35037PM or techno commercial equivalent in makes mentioned in Particular Specifications.
S&F Pillar cock quarter turn (Low-flow) 16mm dia complete all as specified and directed by Engineer-in-Charge. Make - Jaquar Model No KUP-CHR-35001PM or techno commercial equivalent in makes mentioned in Particular Specifications.
S&F Sensor Mini Concealed Type Flushing Valve for Urinal Complete Set with Installation Box (Battery Operated) 16 mm dia complete all as specified and directed by Engineer-in-Charge. Make - Jaquar Model No SNR-STL-51083G or techno commercial equivalent in makes mentioned in Particular Specifications.
S & F Overhead Shower ø140mm Round Shape Single Flow with Air Effect (ABS Body & Face Plate Chrome Plated) with Rubit Cleaning System 16 mm dia complete all as specified and directed by Engineer-in-Charge. Make - Jaquar Model No OHS-1757GD or techno commercial equivalent in makes mentioned in Particular Specifications.
S & F Hand shower (Health faucet) with 1 meter long easy flex tube in chrome finish and wall hook with NRV (Back flow preventer) complete all as specified and directed by Engineer-in-Charge. Make - Jaquar Model No ALD-579 or techno commercial equivalent in makes mentioned in Particular Specifications.
S & F 50mm Bore Dia Brass Compact PRV complete all as specified and directed.
S & F 40mm Bore Dia Brass Compact PRV complete all as specified and directed..
S & F for 15mm bore dia Brass CP Mixture for mixing hot & cold water screwed down for iron pipe and fixed complete all as specified and directed. Make - Jaquar Model No KUP-CHR-35117PM or techno commercial equivalent in makes mentioned in Particular Specifications.
INTERNAL ELECTRIC SUPPLY
S & F 10 W surface/wall mounted LED batten having high efficiency long life LED chips with luminous efficacy of > 100 lumen/W, independent isolated SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in powder coated white extruded aluminium channel housing and white coloured ABS end caps having input voltage 220- 240 V, input frequency 50- 60 Hz, PF > 0.95, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed by the engineer-in-charge. Make: Havells Cat Part No. LHEXACP7IN1W010 or equivalent model in Philips, Wipro or makes mentioned in Particular Specifications.
S & F LED Bulb 9W including lamp holder Make for Bulb - HAVELLS or techno-commercial equivalent in Crompton /PHILLIPS
S & F 20 W surface/wall mounted LED batten having high efficiency long life LED chips with luminous efficacy of > 100 lumen/W, independent isolated SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in powder coated white extruded aluminium channel housing and white coloured ABS end caps having input voltage 220- 240 V, input frequency 50- 60 Hz, PF > 0.95, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed by engineer-in-charge. Make: Havells Cat Part No. LHEXAPP7UN1W020 or techno-commercial equivalent make mentioned in Particular Specifications.
S & F 12 W surface mounted round shape LED down light with minimum efficiency 85 lumen/W, high quality polycarbonate opal concave diffuser, high reflective polycarbonate conicle shape reflector, input voltage 240 V, input frequency 50 Hz including electric connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to fixture complate all as specified and directed by engineer-in-charge. Make: Havells Cat Part No. LHEAABP7IL1W012 or techno-commercial equivalent makes mentioned in Particular Specifications.
S & F of square shape fully diffused recessed mounted 2' X 2' LED luminaire with, metallic CRCA housing & powder coated body, initial luminous flux 3000 lm, luminous efficancy not less than 125 lm/W, initial CCT 6500 K, initial CRI greater than 80, initial chromaticity <5, L70B50 50000 hr, IP 20 and IK 02 protection, power factor not less than 0.90 and built-in driver conforming to IS 15885 (Part 2/Sec 13): 2012 complete with electrical connection through 3 core PVC insulated copper conductor unarmoured cable of suitable size from ceiling rose to the light fitting as specified and directed by engineer-in-charge. Make: Havells Cat Part No. LHEBAEP7IZ1W024 or techno-commercial equivalent makes mentioned in Particular Specifications.
S & F 8 W LED bollard fittings having high efficiency long life LED module with SMD LED package mounted mounted on MCPCB, luminous efficacy ≥ 100 lumen/W, integral SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, IP 65 protection, housed in powder coated aluminium pipe with aluminium heat sink for effective thermal management, sturdiness & excellent corrosion resistance and mounting flange of MS sand casting at the bottom, mounted by means of 3 Nos. M10 bolts, including electrical connection with 3 core flexible Cu conductor cable of appropriate size complete all as specified and directed. Make: Havells Cat Part No. MOUNTBL10WLED857PSYMTOPMMAM or techno-commercial equivalent makes mentioned in Particular Specifications.
S & F 35 W LED Security light having high efficiency long life LED module with SMD LED package mounted on MCPCB with high LED efficacy of ≥ 100 lumen/W, integral SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, IP 66 protection, high effiency polycarbonate cover with integrated lens housed in pressure die-cast aluminium alloy heat sink for effective thermal management, sturdiness, excellent corrosion resistance, separate optical and control gear compartment & top opening for easy maintenance, suitable for side entry, pole mounting with bracket arm OD 35 mm to 42 mm including necessary electrical connection to the fixture with 3 core flexible Cu conductor cable of appropriate size and 1.5 m long bracket, having 40 mm diameter light grade GI pipe, including GI clamps, nuts, bolts & washers with two coats of synthetic enemal paint over a coat of red oxide primer complete in all respect as specified and directed by engineer-in-charge. Make: Havells Cat Part No. ENDURACITYLITEPLATPLUSSL35WLED757SASYBOPC or techno-commercial equivalent makes mentioned in Particular Specifications.
S & F Energy efficient BLDC ceiling fan with 5 star rating and without remote(with 5-speed fixed regulator to measured seperately) having power consumption between 30 to 35 watts having 1200 mm blade sweep, air-flow not less than 200 CMM, operating voltage 220-240 V and frequency 50 Hz, including a downroad of suitable size complete with electrical connection through 3 core PVC insulated copper conductor unarmoured cable of suitable size as specified and directed by engineer-in-charge. Make: Crompton Cat-Part No. ENTRUST 50- 5 STAR or Havells Cat-Part No. ES - 50 Premium or BAJAJ Cat-Part No. Electra 50 or techno commercial equivalent in makes mentioned in Particular Specifications.
BLANK
S & F energy efficient non-metalic fresh air fan having blade sweep 250 mm, air delivery not less than 860 CMH, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fresh-air fan complete all as specified and directed by engineer-in-charge. Make: Crompton Cat-Part No. VENTILUS 10" or Havells Cat-Part No. Ventil Air - DX White or BAJAJ Cat-Part No. Maxima DX or techno commercial equivalent in makes mentioned in Particular Specifications.
S & F energy efficient metalic exhaust fan having blade sweep 300 mm, air delivery not less than 6000 CMH, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fresh-air fan complete all as specified and directed by engineer-in-charge. Make: Crompton Cat-Part No. EXHD300- 4-1 or Havells Cat-Part No. Ventil Air - DSP or BAJAJ Cat-Part No. Max Air or techno commercial equivalent in makes mentioned in Particular Specifications.
Supply, installation, testing and commissioning of sandwich type (3L+N+PE) busbar trunking system complete with two runs of 50 mm X 6 mm aluminium earthing strip and accessories all as specified and directed by engineer-in-charge. The BBT shall conform to the following technical specifications: [A] GENERAL [i] The busbar trunking system (BTS), both feeder and plug-in, shall be of sandwich construction. All components and fittings (straight length, elbow, tee, flanged end, cable tap-off box and circuit breaker etc.) shall conform to IEC 61439-6:2012 or UL 857 and shall be procured from the OEM of BTS. The BTS shall have IP 66 protection for outdoor application and IP 54 protection for indoor application in accordance with IEC 60529: 1989. [ii] The rated operation voltage of BTS shall not be less than 1 kV. The neutral conductor shall have the same cross-sectional area as the phase conductor and the earth busbar shall be provided on both sides of the housing. [B] CERTIFICATE [i] The busbar , of full range and each rating, shall pass full type tests specified in IEC 61439-6-2012. The certificate shall be issued by an international independent testing authority, e.g. ASTA. KEMA. UL and ERDA etc. [ii] A product safety mark, e.g. KEMA-KEUR, ASTA DIAMOND, UL and ERDA, etc. shall be on the product offering a visual assurance of full product safety testing, factory inspection and ongoing surveillance under independent authority. [iii] The BTS shall have UBC seismic zone 5 compliance tested with busduct and plug-in box assembly by an internationally recognized earthquake research body, e.g. Asian Pacific Network of Centres for Earthquake Engineering Research (ANCER) as per IEEE 693- 2018. The OEM shall also furnish a certificate to confirm that the BTS assembly is capable of withstanding the additional vibration in shaft owing to air movements.
[C] SHORT-CIRCUIT RATINGS & TESTS [i] The entire BTS (busduct and plug-in box assembly) shall be capable of withstanding the short-circuit of electrical installation without undergoing any electrical, mechanical or thermal stress under fault condition at a service voltage of 1 kV at 50 Hz frequency. The minimum rated insulation voltage shall be 1 kV. [ii] The minimum certified short-circuit withstand capacity for 400 A rating shall be 25 kA for 1 sec. [iii] The minimum certified short-circuit withstand capacity for 800 A rating shall be 50 kA for 1 sec. [iii] The minimum certified short-circuit withstand capacity for 1250 A rating shall be 65 kA for 1 sec. [iv] The minimum certified short-circuit withstand capacity for 2000 A rating shall be 80 kA for 1 sec. [D] HOUSING [i] The busbar trunking housing shall be constructed of 1.6 mm thick electro- galvanised steel and shall be provided with a suitable protective finish of epoxy paint. [ii] The busbar trunking housing shall be totally enclosed non-ventilated for protection against mechanical damage and dust accumulation and it shall be tested for its characteristics offering resistance against corrosion [iii] The totally enclosed housing shall be manufactured by the BTS OEM and modifications of busbar trunking to make it totally enclosed by housing other than the busbar trunking OEM shall be unacceptable without written consent of the OEM.
[E] BUSBARS [i] The busbars shall be of aluminium with tin / silver plating at joint. [ii] There shall be no bolts passing through the busbars of the BBT. [iii] Each busbar shall be insulated with Class- F (155 ˚C) insulation. Epoxy insulation shall be unacceptable. [iv] The temperature rise at any point of busbar trunking enclosure shall not exceed 55 ˚C above the ambient temperature of 40 ˚C when operated at the rated current. [F] JOINTS [i] The busbar trunking joint shall be of one-bolt type utilizing high strength steel bolt(s) and Belleville washers to maintain proper pressure over a large contact surface area. [ii] The bolt(s) shall be torque indicating and at earth potential. [iii] The bolt shall be of two-headed design to indicate proper torque has been applied and shall require only a standard long handle wrench to be properly activated. [iv] Access shall be required to only see one side of the busbar trunking to tighten joint bolts. [v] It shall be possible to remove any joint connection assembly to allow electrical isolation or physical removal of a busbar trunking length without disturbing adjacent busbar trunking lengths.
[G] PLUG-IN OPENING [i] The connecting jaw of a plug-in unit shall plug directly onto the busbar and have full contact with busbar itself. Welded tab at plug-in busbar is unacceptable. [ii] All contact on joint and plug-in opening shall be of copper strip in order to avoid external force damage on busbar while plugging in or plugging out operation. [iii] On plug-in busbar trunking there shall be three dead front, hinged cover type plug-in opening on each side. [iv] All openings shall be usable simultaneously. Busbar trunking shall be installed in such a manner that plugs are side mounted to permit practical use of all plug-in openings. [v] It shall be possible to inspect the plug-in opening and busbars prior to the installation of plug-in units. [H] SUPPORT STRUCTURE [i] Support structure shall be provided as per OEM's recommendation. [ii] Indoor feeder and plug-in busbar trunking shall be approved for hanger spacing of up to 3 m for horizontally mounted run and 4.88 m for vertically mounted runs. Outdoor feeder busbar trunking shall be approved for spacing up to 1.5 m for horizontally or vertically mounted runs.
[I] VOLTAGE DROP [i] The voltage drop (sending end voltage minus receiving end voltage) specified shall be based on the busway operating at full rated current and stabilized operating temperature in [ii] The 3- Phase line to line voltage drop shall not exceed 3.4 V per 100 feet length at 40% power factor concentrated load which may exist during motor starting. [iii] The line to line voltage drop shall not exceed 4.1 V per 100 feet at the load power factor which produces the maximum voltage drop in the busway. [J] INSPECTION / SUPPORT OF INSTALLATION [i] The installation of BBT shall be executed by skilled professionals with minimum experience of 4 yrs. having sufficient installation base and pre-commissioning experience. [ii] The entire installation shall be directly supervised by the OEM. [iii] The OEM shall also furnish a commissioning report underlining satisfactory installation after the commissioning of BBT system.
(a) 400 A Straight Run Feeder (IP 54 protection)
(b) Flange End with Equilizer / Shorting Plate
(c) Horizontal / Vertical Bend
(d) Plug-in Point
(e) Vertical Spring Hanger / Fix Hanger
(f)Tinned Copper Braided Flexibles with Hardware- Nuts & Bolts
(g) Adapter Box
STANDARD PLUG-IN BOX / TAP-OFF UNIT WITH FP MCCB
(h) PIB / TOU with 63 A, 415 V, 25 kA, 50 Hz, FP MCCB
(j) E.F.U. with 400 A, 415V, 36 kA, 50 Hz, FP MCCB
SUPPORTING STRUCTURE
(k) Horizontal Fixing Clips
M & L of structural steel for BBT support structure with painting as recommended by OEM. NOTES: [i] The bidder shall furnish dimensional drawings of the items offered, indicating all the fittings, dimensional tolerances, typical GADs, etc. with details of insulation at each point and core construction, etc. for approval of the Garrison Engineer.
S & F vertical triple pole & neutral, double door, 4-way metallic modular distribution board conforming to IEC 61439-3, suitable for flush / surface mounting with provision for MCCB up to 250 A as incomer and SP/TP MCBs as outgoing, reversible metal door, fully insulated 250 A copper busbar for each phase, two fully insulated & shrouded neutral bars, two earthbars, cable ties for cable management, prefitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified and directed by engineer-in-charge. NOTE: MCCB/MCBs shall be measured and paid separately.
S & F MCB for AC applications conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP 20 protected lower terminals and sliding shutters, etc. complete as specified and directed by engineer-in-charge.
a) 10 A, 230 V, 50 Hz SP MCB (c- curve)
b) 16 A, 230 V, 50 Hz SP MCB (c- curve)
c) 20 A, 230 V, 50 Hz SP MCB (c- curve)
d) 32 A, 230 V, 50 Hz SP MCB (c- curve)
e) 32 A, 230 V, 50 Hz TP MCB (c- curve)
f) 32 A, 230 V, 50 Hz FP MCB (c- curve)
g) 63 A, 230 V, 50 Hz FP MCB (c- curve)
M & L for 1.1 kV grade Copper conductor, XLPE insulated armoured cable conforming to IS 7098 (Part 1): 1988, having stranded aluminium compact shaped conductors as per Cl. 2 of IS 8130: 1984, PVC inner sheath, single armouring of galvanised steel strip/wire and PVC Type ST-2 outer sheath conforming to IS 5831: 1984, including necessary clamping / dressing with cable ties and termination complete all as specified and directed by engineer-in-charge.
a) 3.5 core, 35 mm² (for Tap- Box to floor DBs)
Supply, installation and commissioning of 50 Litres storage capacity electric geyser having temperature sensitive LED indicators, 5 star rated, shock safe plug, PUF insulation, incoloy glass coated heating element, anode rod, adjustable knob, multi-functional safety valve with IP 4X protection all complete as specified and directed. (for Kitchen) Make: Havells Cat-Part No. GHWAMGSWH050 or techno commercial equivalent in makes mentioned in Particular Specifications.
EXTERNAL ELECTRIFICATION
Supply,installation, testing and commissioning, Indoor type ,LT panel box ,cubicle type, factory fabricated,CPRI approved ( any company from list of make), panel board made with 2 mm thick CRCA Sheet , weather and vermin proof ,floor mounted ,Class 7 tank process ,powder coated in siemens gray colour inside and outside, 3 phase, 4 wire system copper bus bar mounted on hygroscopic insulator housed in separate bus bar chamber covered with R-Y-B and black PVC heat shrinkable sleeve, with 50mmx50mmx6mm angle iron frame with and including PCC 1:3:6 type C2 foundation and covering front and back opening hinged door along with suitable locking arrengement including necessry bus bar tappings, copper control wiring of required size, connecting cable with necessary cable glands, lugs etc, independent chamber to accomodate the MCCBs MCBs,measuring instruments,Bus bar and cable gallary chember ,proper arrangements for ventilation complete with provn for connecting earthing at both sides of panel board and comprises as following:- (MAIN PANEL)
INCOMER i) ACB 4 pole 630 A, EDO, incomer, 415V, 50Hz, 50 KA - 01 No. (Incomer) OUTGOING i) MCCB 4 Pole,250-320A, 415V, 36 KA - 4Nos. (BBT-02,AMF-01, Spare-01) ii) MCCB 4Pole, 160-200A, 415V, 35 KA - 1 No. (APFCP) iii) MCB TPN, 40 A, 415V, 35 KA - 1 No. (spare) iv) MCB SPN, 32 A, 415V, 35 KA - 1 No. ( Sub stn lighting) BUSBAR i)1000 A rated copper bus bar with colour coded heat shrinkable sleeve METERING & INDICATION i) Ammeter,Digital type, with suitable CTs - 06 set ii) Voltmeter, Digital type - 01 set iii) R-Y-B phase indicating lamp- 03 Nos iv) Multifunction meter -01
Supply, installation, testing and commissioning, Indoor type ,LT panel box ,cubicle type, factory fabricated, CPRI approved ( any company from list of make), panel board made with 2 mm thick CRCA Sheet , weather and vermin proof ,floor mounted , 7 tank process ,powder coated in Siemens grey colour inside and outside, 3 phase, 4 wire system copper bus bar mounted on hygroscopic insulator housed in separate bus bar chamber covered with R-Y-B and black PVC heat shrinkable sleeve, with 50mmx50mmx6mm angle iron frame with and including PCC 1:3:6 type C2 foundation and covering front and back opening hinged door along with suitable locking arrangement including necessary bus bar tappings, copper control wiring of required size, connecting cable with necessary cable glands, lugs etc., independent chamber to accommodate the MCCBs MCBs, measuring instruments, Bus bar and cable galley chamber ,proper arrangements for ventilation complete with proven for connecting earthing at both sides of panel board and comprises as following:- (UTILITY PANEL )
INCOMER i) MCCB 4 Pole, 250-320 A, 415V, 35 KA - 1 No. I/C OUTGOING i) MCCB 4P 32 A -03 Nos (lift panel ) ii) MCCB 4P 32 A - 1 No..(For WS pump) iii) MCCB 200-250 Amp 4 pole 415 v 35 KA-1No ( For FF pump panel ) iv) MCB TPN 20 A - 4 No ( stair case+ street lights). iv) MCB SPN 20 A - 1 No ( Pump house). BUSBAR 500 Amps copper bus bar with colour coded heat shrinkable sleeve METERING & INDICATION i) Ammeter, Digital type, with suitable CTs - 06 set ii) Voltmeter, Digital type - 01 set iii) R-Y-B phase indicating lamp- 03 Nos iv) Multi function meter with suitable CT's -01 No.
M&L GI Octagonal poles complete with single arm bracket as specified all for 6 metres long with 70 mm top dia nad 130 mm bottom dia, made of 3 mm thick tensile sheet along with base plate of size 225x225 x12 mm thick incl 04 nos. of M24 x750 long J type foundation bolts incl MCB 6 amps with 4 way heavy duty connector 32 Amps complete with its foundation all as specified by the pole manufacturer all as specified and directed by E-in-Charge ( rate quoted shall be inclusive all foundation RCC and form work complete)
S&F cable junction box of size 139mmx119mmx70mm, IP-65 with 6A MCB SP, class 'C' series-01 and 4way terminal block locking arrangement fixing arrangement with necessary MS clamps and washers of complete all as specified and directed
Supply and fix LED 60 Watts, IP-65. IK-10 street light fittings complete in street light poles/Buildings with and including drivers, pressure die cast aluminium housing, prewired complete. The fitting shall conform to cat No -ENDURAPEARLPLUSSL 60WLED 757SASY TOPC of Havells or techno commercial equivalent in makes mentioned in Particular Specifications.
M&L for 3 Core 1.5 Sq. mm size multistranded copper conductor PVC unsheathed 650 / 1100 Volt Grade drawn in through steel tubular poles, for interconnection of cable looping box to Street Light Fitting
M&L for Earthing complete with galvanised steel earth plate electrode 60cm×60cm× 6mm thick, buried directly in ground vertically (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to GI strip 32 x 6 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron and connected to main switch board including 20 mm bore medium grade GI pipe with MS funnel with wire mesh, watering arrangement and 50 mm bore light grade GI pipe for earth lead protection from earth plate to test point or panel connecting point, PCC Chamber,CI Cover with frame etc. including necessary excavation in any type of strata, returning, filliing, removal of soil outside MD landfilling of charcoal and salt complete all as shown in electrical plate No. 3 of MES Sch Part-I, connected to Earthing Test point all as specified and directed and testing on completion.
EXTERNAL WATER SUPPLY
M&L for cutting in position existing CI pipe line 150 mm bore for taping out branch connection including insertion of CI tee 150x150x80 mm & lead joints all necessary fittings as per site requirement including required excavation and earth work in any type of soil and disposal of surplus soil and disposal of surplus soil to a distance of n exec 50m etc. complete all as specified
M&L construction of brick masonry valve pit chamber 90 cm x 90 cm and 90cm deep (internal size )with 15cm thick foundation using PCC (1:4:8) type D-2 over 15 cm thick hard core ,23 cm thick ,brick wall built in cement and sand mortar1:4,15mm thick internal plaster including top of floor in cement and sand mortar 1:3,finished even and smooth, without using extra cement ,2mm thick MS sheet cover with 40mm X 40mm X 6mm MS angle frame fixed in PCC (1:2:4) type B-1,coping with 25mmX6mm flat iron hold fasts, hinges, handles, locking arrangements and applying one coat of red oxide primer and two coats of synthetic enamel paint to all steel surface including excavation and earth work in any type of soil and disposal of surplus soil to a distance of n exe 50 m complete all as specified.(2 for Ext Water Supply and 8 for FF)
Supply, installation, testing and commissioning, Pumping sets not less than 10 HP capacity , centrifugal, electric driven, complete with electric motor energy efficient , 3 ph, 415V 50 Hz, 2900 RPM,TEFC Induction type, with head 60 metres and discharge 375 lpm, with suitable cable copper for connection 6 runs from starter to Panel MCCB incl Suitable size GI pipe medium grade and NRV and Sluice valve on delivery side upto common header and suitable size GI suction pipe medium grade with suitable size foot valve make- Normex/kartar, with Nytrile rubber ball inside complete with PCC foundation as recommended by OEM.
Supply, installation, testing and commissioning, Indoor type ,LT panel box ,cubicle type, factory fabricated,CPRI approved ( any company from list of make), as per IS-8623, panel board made with 2 mm thick CRCA Sheet , weather and vermin proof ,floor mounted , 7 tank process ,powder coated in siemens gray colour inside and outside, 3 phase, 4 wire system copper bus bar mounted on hygroscopic insulator housed in separate bus bar chamber covered with R-Y-B and black PVC heat shrinkable sleeve, with 50x50x6mm angle iron frame with and including PCC 1:3:6 type C2 foundation and covering front and back opening hinged door along with suitable locking arrengement including necessry bus bar tappings, copper control wiring of required size, connecting cable with necessary cable glands, lugs etc, independent chamber to accomodate the MCCBs MCBs,measuring instruments,Bus bar and cable gallary chember ,proper arrangements for ventilation complete with provn for connecting earthing at both sides of panel board and comprises as following :-
FIRE DETECTION ALARM SYSTEM
Supply, installation, testing and commissioning of microprocessor based 2 loop addressable main fire alarm control panel, BS EN 54, Part -2 : 1997 + Appendix 2: 2006 control & indicating equipment and minimum 120 character alphanumeric liquid crystal display. The panel shall be able to store minimum 4000 log events in It's memory. The panel shall be able to give pin point location of all fire/fault, condltfons. Further, the panel musi be able to automatically switch off respective control switches when ever any alarm Is triggered. The panel shall have inbuilt rectifier, loop card, LCD unit to indicate Fire/-Fault signal with LED output, integral SMFLA batteries with sealed cell of 24 V capable of running for a minimum of 48 hours v/ith integral batteiy charger complete as required.
Supply, installation, testing and commissioning of FM approved and UL listed intelligent plug-in photoelectric smoke detector, conforming to UL 268 7th Edition, sealed against back pressure, with sensitivity range 0.5 % to 4.0 % per foot obscuration, two-wire SLC connection, fixed-temperature setpoint 135°F (57°C), built-in functional test switch activated by external magnet, built-in tamper resistant feature, remote test feature from the panel, dual LED design provideing 360° viewing angle, visible bi-color LEDs blink green every time the detector is addressed, and illuminate steady red on alarm, compatible with FlashScan® and CLIP protocol systems, Rotary, decimal addressing, etc. and having the ability to combine temperature thermal sensing with optical sensing, complete with all accessories viz. base, base box, etc. to be installed below / above false ceiling, roof and concealed space, etc. complete as specified and directed by engineer-in-charge.
Supply, installation, testing and commissioning of FM approved and UL listed intelligent plug-in intelligent thermal detector, two-wire SLC connection, fixed-temperature setpoint 135 °F (57 °C), rate of temperature rise 15 °F (8.3 °C) per minute, built-in functional test switch activated by external magnet, built-in tamper resistant feature, remote test feature from the panel, dual LED design provideing 360° viewing angle, visible bi-color LEDs blink green every time the detector is addressed, and illuminate steady red on alarm, compatible with FlashScan® and CLIP protocol systems, rotary & decimal addressing, etc. complete with all accessories viz. base, base box, etc. to be installed below / above false ceiling, roof and concealed space, etc. complete as specified and directed. (for kitchen)
Supply, installation, testing and commissioning of FM approved and UL listed dual- action, surface / semi- flush mounted break-glass type addressable manual call point (MCP) including an addressable interface for the intelligent FACP having built-in bicolour LED which is visible through the handle of the MCP, flashing in normal operation and latching steady red in alarm condition, captive screw terminals wire-ready for easy connection to SLC loop complete with accessories as specified and directed by engineer-in-charge.
Supply, installation, testing and commissioning of FM approved & UL listed of Horn Strobe, wired as a primary notification appliance, flashing 75 cd at 1 Hz over the strobe's entire operating voltage range, xenon flash tube and associated lens / reflector system, buil-in synchronization feature keeping strobes in sync for up to 30 minutes, horn producing audible annunciation of 75 dBA at 3 m distance complete with accessories as specified and directed by engineer-in-charge.
Supply, installation, testing and commissioning of FM approved and UL listed addressable control module to provide FACP a circuit for notification appliances (e.g. Horns, Strobes, Horn Strobes, etc.) having built-in type identification, integral LED indicators, high noise immunity, SMES screws with clamping plates for wiring ease, direct-dial entry of address, etc. complete with accessories as specified and directed by engineer-in-charge.
Supply, installation, testing and commissioning of FM approved and UL listed intelligent monitor module, with built-in type identification automatically identifying the device as a monitor module to the FCAP, to supervise a circuit of dry-contact input devices, viz. flow switch of sprinkler line, powered directly by two-wire SLC loop, high noise immunity, SEMS screws with clamping plates for ease of wiring, direct-dial entry of addresses, LED indicators, etc. complete with accessories as specified and directed by engineer-in-charge.(sprinkler flow switch)
Supply, installation, testing and commissioning of FM approved and UL listed (fire fighter's) addressable Telephone Jack mounted to a single-gang electrical back box with suitable interface module for two way communication with the Central Fire Fighter Telephone Console complete with accessories as specified and directed by engineer-in-charge.
Supply, installation, testing and commissioning of FM approved and UL listed Fire Fighter's Telephone Handset for two way communication with the Central Fire Fighter Telephone Console complete with accessories as specified and directed by engineer-in-charge.
M & L for low smoke zero halogen (LS0H) flame retardant fire alarm cable, conforming to BS 7629-1, BS 6387 & BS EN 50200 and rated for 500 V, having plain annealed stranded copper conductor with primary insulation of glass mica fire resistant tape and secondary insulation of high performance silicone rubber, earth/drain wire of annealed tinned copper, electrostatic screen of aluminium fire barrier and type LTS3 outer sheath conforming to BS 7655, suitable for operating temperature range -30 ˚C to +70 ˚C and minimum bending radius being 6 times the overall cable diameter, RED in colour, including laying, termination and ferruling complete all as specified and directed by engineer-in-charge. (drawn in PVC conduit concealed)
a) 2 core, 1.5 mm²
b) 2 core, 2.5 mm² (supply to hooter/strobe)
Supply, installation, testing and commissioning of electric driven Jockey Pump to deliver 180 LPM flowrate at 90 MWC head and suitable for automatic operation and consisting of following, complete with accessories as specified and directed by engineer-in-charge. [i] Horizontal type, centrifugal, split-casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal, etc. conforming to IS 12469: 2019, suitable to deliver 180 LPM flowrate at 90 MWC head. [ii] Suitable HP squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on 3- Ph, 415 V, 50 Hz AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class 'F' insulation, conforming to IS 12615: 2018. [iii] MS fabricated common base-plate, coupling, coupling guard, foundation bolts, etc. complete with accessories as required. [iv] Suitable cement concrete foundation duly plastered with anti vibration pads.
Supply, installation, testing and commissioning of factory made, CPRI type tested, indoor, cubical compartmental type "Motor Control Center" (MCC) of suitable size, conforming to IEC 61641, having both sides openable with hinged double doors & locking arrangement and IP 54 protection made out of 2.00 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete as specified and directed by the engineer-in-charge. The MCC shall comprise of the following:
M & L for 1.1 kV grade copper conductor, XLPE insulated armoured cable conforming to IS 7098 (Part 1): 1988, having stranded copper compact shaped conductors as per Cl. 2 of IS 8130: 1984, PVC inner sheath, single armouring of galvanised steel strip/wire and PVC Type ST-2 outer sheath conforming to IS 5831: 1984, including necessary clamping / dressing with cable ties and termination complete all as specified and directed by engineer-in-charge.
A) 3 core, 3.5 mm² (for Main Electric Pump)
B) 3 core, 4 mm² (for Jockey Pump)
M & L for low smoke zero halogen (LS0H) fire survival control cable with circuit integrity, conforming to BS 7846 and rated for 600 V, having plain annealed stranded copper conductor with fire-resistant mica tapes covered by an extruded layer of cross-linked polyethylene, extruded layer of thermoplastic low smoke zero halogen (LS0H) compound, single layer of galvanized steel wires and thermoplastic LS0H compound sheath, suitable for operating temperature range -40 ˚C to +90 ˚C and minimum bending radius being 12 times the overall cable diameter, including laying, clamping, termination and ferruling complete as specified and directed by the engineer-in-charge.
A) 2 core, 2.5 mm² (for instrumentation)
B) 3 core, 2.5 mm² (for auto start/stop panel)
C) 12 core, 2.5 mm² (for diesel engine pump)
M & L for ISI marked MS ERW pipes conforming to IS: 1239 (Part 1 & 2) with all accessories like all fittings including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer, including supporting/fixing the pipe on floor/wall/ceiling with clamps, hangers, angles, channels (using anchor fastners) with painting of one coat primer and 2 or more coats of synthetic enamel paint complete as specified and directed by the engineer-in-charge. NOTES: [i] Standard MS fittings with welded joint shall be used on the pipes. [ii] All hangers, clamps, brackets etc. shall be of galvenized iron. [iii] Welding of any kind on the galvenised support / hanger shall not be permitted. [iv] The pipe size 150 mm NB & below shall be MS 'C' class as per IS 1239 (Part- 1): 2004 & IS 1239 (Part- 2): 2011. [v] The pipe size above 150 mm NB shall be welded black steel pipe heavy class as per IS 3589: 2001. [v] Pipes of size more than 50 mm NB shall be butt welded with fittings of equal or higher thickness whereas pipes below 50 mm NB size shall be socket welded.
(a)125mm NB
Supply & Fix Automatic Air release valve 50mm Dia suitable for water supply with 50mm Gun Metal Stop Valve complete in all respect including all fixing accessories and all as specified and directed.
M & L for PN 1.6 rated 150 mm NB Cl 'Y' -type strainer for suction conforming to IS 907-19?4 with SS filter screen and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories for suction side of fire pumps complete as specified and directed by the engineer-in-charge.
S & F PN 1.6 rated CI sluice valve, conforming to IS: 14846- 2000, with SS spindle conforming to IS: 6603- 2001 and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories complete as specified and directed by the engineer-in-charge.
(a) 40 mm NB
(b) 125 mm NB
Supply, installation, testing and commissioning of 40mm NB, PN 1.6 rated CI swing check type reflux (non return) valve, conforming to IS: 5312 (Part 1)- 2004 with flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories complete as specified and directed by the engineer-in-charge.
S & F of CL 150 # rated 25 mm NB ball valve, designed & manufactured as per IS: 9890 (1981) and tested as per BS 6755 Part- I, having floating type three piece design, CS body, SS- 304 ball, PTFE seal/packing/gasket, CS fastners and lever and screwed/socket weld end connection, etc. with accessories complete as specified and directed by the engineer-in-charge.
M & L for ISI marked MS ERW pipes conforming to IS: 1239 (Part 1 & 2) with all accessories like all fittings including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer, including supporting/fixing the pipe on floor/wall/ceiling with clamps, hangers, angles, channels (using anchor fastners) with painting of one coat primer and 2 or more coats of synthetic enamel paint complete as specified and directed by the engineer-in-charge. NOTES: [i] Standard MS fittings with welded joint shall be used on the pipes. [ii] All hangers, clamps, brackets etc. shall be of galvenized iron. [iii] Welding of any kind on the galvenised support / hanger shall not be permitted. [iv] The pipe size 150 mm NB & below shall be MS 'C' class as per IS 1239 (Part- 1): 2004 & IS 1239 (Part- 2): 2011. [v] The pipe size above 150 mm NB shall be welded black steel pipe heavy class as per IS 3589: 2001. [v] Pipes of size more than 50 mm NB shall be butt welded with fittings of equal or higher thickness whereas pipes below 50 mm NB size shall be socket welded.
(a) 25 mm NB (for hose reel branch connection)
(b) 80 mm NB (for Hydrant / landing valve or connection)
(c) 100 mm NB
(d)150 mm NB
S & F of orifice plate made out of 6 mm thick SS 304 with orifice of required size to be fitted between flange and landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as specified and directed by the engineer-in-charge.
Supply, installation, testing and commissioning of 2- way fire brigade draw- off connection with two 63 mm NB inbuilt gunmetal non-return valves instanteneous coupling type arranged on 100 mm NB pipe manifold and connected to wet riser main as well as to fire water tank including CI butterfly valve, CI non-return valve and MS cabinet with mounting supports, etc. all complete as specified and directed by the engineer-in-charge.
S & F ABC powder type fire extinguisher of 4 Kgs. Capacity, with initial filling in brand new cylinder with powder coated finish, fitted with Gun metal union, high pressure CO2 gas cartridge, discharge hose, wall mounting bracket /floor trolley mounting accessories with suitable signage's etc. complete, confirming to IS:15683 complete as specified and directed by the engineer-in-charge.
S & F ABC powder type fire extinguisher of 9 Kgs. Capacity, with initial filling in brand new cylinder with powder coated finish, fitted with Gun metal union, high pressure CO2 gas cartridge, discharge hose, wall mounting bracket /floor trolley mounting accessories with suitable signage's etc. complete, confirming to IS:15683 complete as specified and directed by the engineer-in-charge.
S & F Carbon-di-oxide type fire extinguisher of 3 kgs. Capacity, CO2 gas filled in brand new seamless cylinder with powder coated finish, made out of Manganese steel, with wheel type valve, discharge Nozzle, bend & horn, wall mounting bracket /floor trolley mounting accessories with suitable signage's complete, confirming to IS: 2878 complete as specified and directed by the engineer-in-charge.
S & F Carbon-di-oxide type fire extinguisher of 4.5 kgs. Capacity, CO2 gas filled in brand new seamless cylinder with powder coated finish, made out of Manganese steel, with wheel type valve, discharge Nozzle, bend & horn, wall mounting bracket /floor trolley mounting accessories with suitable signage's complete, confirming to IS: 2878 complete as specified and directed by the engineer-in-charge.
S & F Mechanical Foam type fire extinguisher 9 Lts. Capacity, with initial filling in brand new cylinder with powder coated finish, fitted with Gun metal union, high pressure CO2 gas cartridge, hose and ABS type branch pipe and wall mounting bracket /floor trolley mounting accessories with suitable signage's complete. confirming to IS: 10204 complete as specified and directed by the engineer-in-charge.
S & F Fire buckets (FILLED WITH SAND) round bottom type enamel painted, white inside & Red out side and Letter "FIRE" in black out side and handle with mounting bracket complete as specified and directed by the engineer-in-charge.
Supplying and installing of in position the following type of sign boards made out of 3mm thick 'Opaque' PVC foam board with computer cut, PVC Non-reflective self adhesive vinyl painted foam board, complete with mirror fasteners.
a) Signage with printed "IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED OTHERWISE" of 1.5 cm height letters in red with white back ground, the size of the board shall be 25 cm x 30 cm and shall be fixed at the height of 2 mts. From finished floor near Manual call points.
b) Floor identification signage (i.e GROUND FLOOR… etc) at each stair enclosure on every floor, including the floor number in words, lettering size shall be 7.5 cm with contrasting color from ground. Size shall be 15 cm x 60 cm
Supplying and installing of in position the signages "FIRE ORDER " it should contain the following matter on 3 mm thick "Opaque" PVC foam board of computerized cut, PVC Non-reflective self adhesive vinly painted foam board of 3' x 4'. [a] Alert The Security At Security Room By Actuating Manual Call Point Located At Strategic Locations. [b] Evacuate The Occupants By Using Fire Exits And Emergency Exist Only And Assemble At Various Assembly Points. [c] If Possible Try To Extinguish The Fire By Using Nearest / Suitable Portable Extinguisher Or Water From Nearest Wet Riser. [d] Be Calm And Do Not Give Any Room From Panic, Walk, Do Not Run [e] If You Encounter Serious Difficulty In Evacuation, Flat And Try To Attract Attention Of Rescue Team.
Action By Security / Reception Upon Receipt Of Information Through Fire Alarm Or Fire Detectiors Or By Using Public Address System. [a] Alert The Occupants By Using Public Address System. [b] Inform Fire Control Through Any One Of The Following Phone Numbers: 101/ (Local Numbers) [c] Refer Evacuation Plan From Evacuating Standard People. [d] Guide The Fire Force, On Their Arrival To The Seat Of Fire. [e] In Case Of The Casualties, Call Ambulance By Dialing Number.
LIFTS
Design, Supply, install, testing & commissioning of 08 Passengers Lifts ( 544 kg ) suitable to serve G+12 upper floors with AC variable voltage & variable frequency (VVVF) drive complete with all standard accessories, simplex collective automatic & manual dual controlled operation with/without attendant, automatic centre/Telescopic opening doors with VVVF door drive (electric motor driven mechanism), sliding stainless steel doors, automatic rescue device (ARD) system, Over load device,3D infra red sensor in full height of door & built in announcing system without hand set (02 Nos, one each in car & near Ground floor landing door and one with hand set in Machine room) complete all as specified below :-
(a) Type of Lifts : 08 Passengers (b) Load capacity : 544 Kgs (c) Speed : 1.5 mtr/sec with variable speed motor (d) Power Supply : 415 volts, 3 phase AC, 50 Hz (e) Type of Drive : AC variable voltage & variable frequency drive along with converter unit. (f) Type of Machine : Low inertia gearless permanent magnet Synchronous motor, directly coupled Horizontal traction machine.
(g) Car size (Inside) : Not less than 1.43Sqm. (h) Car door & landing door at all floors : Automatic Centre / Telescopic opening with VVVF door drive, opening size not less than 800mmx2000mm, sliding type, fabricated by stainless steel sheet not less than 16 gauge having hair line finish (N - 304 ). (j) Car enclosure : (i) Manufactured with stainless steel frame stainless steel sheet not less than 16 gauge with hair line finish (N-304) having stainless steel false ceiling with hair line finish, internal lighting arrangement with Four Nos LED light fitting for commercial supply and one No LED for emergency light, internal ventilation system provided with concealed arial flow/cross flow fan with auto cut off system and stainless steel grill/wire mesh for protection. (ii) Provision of standard thickness stainless steel hand rail 40mm dia inside the car cabin .(01 Side) including standard size Mirror on one side (k) Terminal buffers : Metal special spring/oil buffers as per manufacturer specification. The buffing stroke should not be less than 200mm.
(l) Door opening (Inside) : Protected by centre / Telescopic opening stainless steel doors with hairline finish doors with clear opening size not less than 800 x 2000mm . (m) Car & counter weight Guide : Guide rails of `T' Section Mild steel as per OEM design. Counter weight shall be cast iron as recommended by OEM. (n) Flooring : Aluminium chequered plate 5mm thick complete. (o) Signals :- (i) Combined luminous hall buttons with LCD/VFD hall position indicators at all floor. (ii) LCD/VFD for car position indicator to be fitted in COP made of stainless steel. (iii) One No car operating panel with luminous buttons in car (stainless steel). (iv) Car direction indicator in car & Landing (v) Battery operated alarm bell & emergency light (rechargeable) along with suitable maintenance free battery. (This system should be separate from ARD batteries). (vi) Overload warning feature in car cabinet(Display & announcing both type). (vii) Fireman’s switch one No per lift to be installed at ground Floor near landing door.
(viii) All signal fixture & car operating panel on stainless steel face plate with hair line finish. (ix) Infra red door sensor safety edge of door for entire height. (x) Built in announcing system without hand set.02 Nos( One for lift car & ground floor landing door &one announcing system with hand set in machine room). (p) Stops & Opening : 13-13 Stop and one side opening ( Same side ) at all floors. (q) Safety Device : (i) Automatic rescue device (ARD)/Automatic landing device with maintenance free battery having suitable capacity. The batteries must have auto charging facilities. (ii) The ARD actuation should be after failure of power supply and when ARD is operative the car should stop at the nearest floor and then automatically open. (r) Operation: Simplex, full collective automatic operation with/without attendant. (s) Machine Room : Located above the hoist way, details as per building drawings (t) Hoist-Way Constn : Construction details as per building drawings
(u) Civil Work : Necessary Civil work such as making good disturbed surface, modification to landing space to suits to car size necessary foundation to machine. (v) Control system : shall be enclosed loop type. (w) Door shall have AC-VVVF controlled close loop operated. (x) Face plate shape shall be rectangular and stainless steel with hairline finish. (y) counter weight shall be of cast iron or as recommended by OEM. (z) One number wall mounted type telephone instrument of make Crompton Greaves / Beetel /OEM own make installed inside of car cabin along with fixing arrangement and telephone cable of suitable size from car cabin to machine room run along with trailing cable. The telephone instrument shall be connected in the telephone DB installed in the machine room. (aa) One number electrically operated siren, operating voltage 240 volts having audible range of 0.5 Km of Make : KHERAJ Model No SS050 /OEM own make alongwith One Number inverter unit of suitable capacity but not less than 0.5KVA comprising of maintenance free battery connected with charging system including a separate switch/push button inside of car panel and electric wiring circuit upto the machine room. The siren shall be installed over the building at appropriate place and to be operated from inside the car. (ab) Provision of suitable size of copper conductor XLPE insulated cable from Lift Panel installed at Ground floor to machine room will deemed to be included the rate quoted by the contractor.
Supply, install, testing & commissioning of 13 Passengers Lifts (884 kg ) suitable to serve G+12 upper floors with AC variable voltage & variable frequency (VVVF drive) drive complete with all standard accessories, simplex collective automatic & manual dual controlled operation with/without attendant, automatic centre opening doors with VVVF door drive (electric motor driven mechanism), sliding stainless steel doors, automatic rescue device (ARD) system, 3D infra red sensor in full height of door & built in announcing system without hand set (02 Nos, one each in car & near Ground floor landing door and one with hand set in machine room) complete all as specified and directed.
(a) Type of Lifts : 13 Passenger. (b) Load capacity : 884 Kgs. (c) Speed : 1.5 mtr/sec with single speed motor. (d) Power Supply : 415 volts, 3 phase AC, 50 Hz. (e) Type of Drive : AC variable voltage & variable frequency drive alongwith converter unit.
(f) Type of Machine : Low inertia gearless permanent magnet synchronous motor, directly coupled horizontal traction machine. (g) Car size (Inside) : Not less than 2.20 Sqmm. (h) Car door and landing door at all floor : Automatic centre / Telescopic opening with VVVF door drive, opening size not less than 900mm x 2000mm, sliding type, fabricated by stainless steel sheet not less than 16 gauge having hairline finish (N-304). (j) Car enclosure :- (i) Manufactured with stainless steel sheet not less than 16 gauge with hair line finish (N-304), having stainless steel false ceiling with hairline finish, internal lighting arrangement with 04 Nos LED light fitting for commercial supply and one No LED for emergency light each fitting complete, internal ventilation system provided with concealed arial flow/cross flow fan with auto cut off system and stainless steel grill/wire mesh for protection
(ii) Provision of standard thickness stainless steel hand rail 40mm dia inside the car cabin. (3 Sides) (k) Terminal buffers : Metal special spring/ Oil buffers as per manufacturer specification. The buffing stroke shall not be less than 200mm. (l) Door opening (Inside) : Protected by centre/ Tlescopic opening stainless steel doors with hairline finish doors with clear opening size not less than 900 x 2000mm. (m) Car & counter weight Guide : Guide rails of `T' Section Mild steel as per OEM design. Counter weight shall be cast iron as recommended by OEM. (n) Flooring : Aluminium chequered plate 5mm thick. (o) Signals :- (i) Combined luminous hall buttons with LCD/VFD hall position indicators at all floor. (ii) LCD/VFD for car position indicator to be fitted in COP made of stainless steel. (iii) One No car operating panel with luminous buttons in car (stainless steel). (iv) Car direction indicator in car & Landing (v) Battery operated alarm bell & emergency light (rechargeable) along with suitable maintenance free battery. (This system should be separate from ARD batteries).
(vi) Overload warning feature in car cabinet(Display & announcing both type). (vii) Fireman’s switch one No per lift to be installed at ground Floor near landing door. (viii) Built in announcing system without hand set.02 Nos( One for lift car & ground floor landing door & one announcing system with hand set in machine room). . (ix) The interior of the car should be provided with a device that audibly indicates the floor position of lift car has reached and indicates that car entrance/exit door is open or closed. (p) Stops & Opening : 13-13 stop and one side opening (same side) at all floors. (q) Safety Device : (i) Automatic rescue devise (ARD)/Automatic landing device with maintenance free battery having suitable capacity. The batteries must have auto charging facilities. (ii) The ARD actuation time should be less than one second after failure of power supply and when ARD is operative the car should stop at the nearest floor and then automatically open. (r) Operation : Simplex, full collective automatic operation with/without attendant. (s) Machine Room : Located above the hoist way, details as per building drawings
(t) Hoist-Way Constn :Construction details as per building drawings (u) Civil work : Necessary civil work such as making good disturbed surfaces, modification to landing space to suit to car size, necessary foundation to machine. (v) Control system shall be enclosed loop type. (w) Door shall have AC-VVVF controlled close loop operated. (x) Face plate shape shall be rectangular and stainless steel with hairline finish. (y) counter weight shall be of cast iron as recommended by OEM. (z) One number wall mounted type telephone instrument of make Crompton Greaves / Beetel/ OEM own make installed inside of car cabin along with fixing arrangement and telephone cable of suitable size from car cabin to machine room run along with trailing cable. The telephone instrument shall be connected in the telephone DB installed in the machine room. (aa) One number electrically operated siren, operating voltage 240 volts having audible range of 0.5 Km of make Kheraj, Model No SS050 alongwith one number inverter unit of suitable capacity of not less than 0.5KVA comprising of maintenance free battery connected with charging system including a separate switch/push button inside of car panel and electric wiring circuit upto the machine room. The siren shall be installed over the building at appropriate place and to be operated from inside the car. (ab) Provision of suitable size of copper conductor XLPE insulated cable from Lift Panel installed at Ground floor to machine room will deemed to be included the rate quoted by the contractor.
S & F Sheet metal enclosure 4 way Distribution Boards (DB’s), double door, Triple pole & neutral with 200 amps rated bus bar, IP-20 protection with MCCB as incomer, suitable for fixing MCCB'sMCB's/ RCBO's/lsolators complete all as specified and directed. INCOMER MCCB 63 Amp 4 pole 415 v 35 KA-01 No. OUTGOING RCBO 32 Amp 4 Pole, 300 Minliamps sensitivity-01 Nos
M & L for Earthing complete with Copper earth plate electrode 60 cm x 60cmx 3.00 mm thick, buried directly in ground vertically (earth pit not less than 2.25 m deep below ground level) with top edge of the earth plate not less than 1.5m below ground level, connected to Copper strip 20x3 mm as earthing lead by means bolts and nuts check nuts and washers of Brass and connected to main switch board including 20 mm bore midium grade GI Pipe with , MS funnel with wire mesh,.watering arrangement and 40 mm bore light grade GI pipe for earth lead protection from earth plate to test point or pannel connceting point , PCC chamber ,CI cover with frame etc including necessary excavation in any type of strata, returning, filling , removal of soil outside MD land ,filling of charcoal and salt complete all as shown in electrical plate No. 3 of MES SSR Part - I, connected to Earthing test point all as specified and directed and testing on completion.
AVIATION LIGHTS
S & F avation obstruction light LED type Red medium intensity with AllnGaP Led type, red flashing type with initial flashing effective intensity 3200cd, with 15 ckts Approx power consumption-65 watts with reverse diode protection Make- Binoy Opto electronics pvt ltd model - MIB-ST-1200 or equivalent all as per ICAO norms and techno commercial equivalent in makes mentioned in Particular Specifications.
Supply and fix cable PVC insulated 1100volts grade with stranded copper conductor of size 3 core 4 sqmm cable in and including PVC conduit fixed on wall/roof wall/roof with suitable saddles, spacer, screws etc complete all as specified and as directed.
WATER COOLER/ DEEP FREEZER HOT WATER SYSTEM
Supply & Fix Refrigerators Electric Driven (Single Phase), capacity not less than 310 litres bottom freezer refrigerator with invertor linear compressor BEE 4 star rated complete all as specified and directed.
TELEPHONE & TV CONDUITS
S & F modular type 1 module RJ 11 telephone socket with shutter complete all as specified and directed.
Supplying & erecting 50 pairs x 0.5 mm dia PVC insulated armoured telephone cable 0.5 sq.mm PVC Sheathed solid tinned copper conductor cable laid in provided trench/ cable tray complete all as specified and directed
Supplying & erecting 10 pairs x 0.5 mm dia PVC insulated armoured telephone cable 0.5 sq.mm PVC Sheathed solid tinned copper conductor cable laid in provided trench/ cable tray complete all as specified and directed.
S & F for 2 pair telephone cable having solid electrolytic annealed bare copper conductor of 0.5 mm nominal diameter with high density polyethylene insulation, paired, polyester taped, nylon rip cord and grey colour sheathed with FR PVC, conforming to ITD specification S/WS 113 C including termination complete all as specified and directed.
S&F 10 pair telephone distribution box with suitable S.S. frame for mounting tag module, Krone module and incorporated in 16 SWG MS box with proper lockable cover. The box should be fixed on wall with suitable fasteners including painting & earthing. This also includes fixing the cable, distribution chart sufficient space for the cables, wires etc. complete all as specified and directed.
S&F 50 pair telephone distribution box with suitable S.S. frame for mounting tag module, Krone module and incorporated in 16 SWG MS box with proper lockable cover. The box should be fixed on wall with suitable fasteners including painting & earthing. This also includes fixing the cable, distribution chart sufficient space for the cables, wires etc. complete all as specified and directed.
S&F modular type 1 module TV socket with suitable GI mounting complete all as specified and directed.
S & F RG 11 coaxial cable having solid electrolytic grade annealed plain copper central condutor of 1.63mm nominal diameter, gas injected physical polythylene foam insulated, wrapped with aluminium mylar tape aluminium alloy wire braided, jelly flooded and PVC jacketed including termination complete all as specified and directed.
S & FRG 6 coaxial cable having solid electrolytic grade annealed plain copper central condutor of 1.02mm nominal diameter, gas injected physical polythylene foam insulated, wrapped with aluminium mylar tape aluminium alloy wire braided, jelly flooded and PVC jacketed including termination complete all as specified and directed.
Supply & installation of 06 way splitter box for TV cable termination incl all necessary hardware accessories complete all as specified and directed.
DG SET
Supply installation, testing & commissioning of factory assembled stand by Diesel Engine driven generating set coupled with alternator AC to give continuous output of capacity not less than 160 KVA at a power factor of 0.8 lagging, 415 volts, AC, 3 phase, 4 wire, 50 HZ, 1500 RPM, diesel engine liquid cooled, mounted on common base frame complete with in built fuel tank of adequate capacity with fuel line & accessories, PCC foundation work as per manufacturer's instructions, vibration damper pads, micro processor based relay panel for automatic starting on mains failure, control panel showing all parameters of engine & alternator, sound proof canopy & other accessories etc. and confirming to the under mentioned technical specifications as per specified & directed.
(A) DIESEL ENGINE : Water cooled, turbo charged,1500 to 3000 RPM under NTP conditions conforming to IS -4722, BS-5000, IEC-34/1, ISO 8528, BS-5514, ISO-3046 with an overload capacity of 10% for 12 Hrs of continuous operation as per complete with the following accessories. (a) Radiator with blower fan with guard (b) Pipe coupling for cooling system (c) Corrosion inhibitor coolant (d) Filters for fuel/lube oil (e) Fly wheel housing and fly wheel suitable for alternator (f) Engine bearing mechanism in fly wheel housing (g) Shut off coil protection with safety for LLOP /HWT/ Over speed/high and low DC voltage.
(h) Dry type heavy duty replaceable paper element air cleaner with restriction indicator and vacuum indicators . (J) Residential silencers. (k) Stainless steel exhaust flexible bellows. (l) Motor driven priming pump. (m) Electric starter motor (n) Battery charging alternator. (o) Exhaust piping made out of "C" class MS Pipe inclusive of all accessories and hardware, necessary support as per manufacturer’s recommendations to sustain back pressure with rain cap. (p) Mineral wool insulation covered with aluminium sheets for the entire length of exhaust pipe as per manufacturer's recommendations. (q) First fill of oil, coolant and diesel during commissioning. (r) Interconnecting copper cabling of adequate capacity between batteries and controller. (s) Fuel pipe. C class (t) Self starter 12/24 volts DC. (u) Metering equipments for recording (i) Battery voltage and charging rate (ii) Coolant temperature (iii) Lubricating oil pressure (iv) Engine speed (RPM) (v) Engine hours run (vi) Balance of fuel.
(v) Safety as protection control (Trip and indication) (i) High water temperature (ii) Low Lube oil pressure (iii) Low and high speed trip (iv) High and low DC voltage (v) over speed Stop (w) Base frame : Sturdy fabricated welded construction, channel iron base frame (duly painted ) for mounting engine and alternator as per manufacturer’s design alongwith AVM pads (x) Battery: 12/24 Volt, 180 AH maintenance free with leads and terminals (y) Fuel Tank : Built in diesel storage capacity not less than 12 Hrs running of DG set or as per manufacturers recommendations
(B) ALTRERNATOR : 160 KVA at 0.8 PF lagging, 415 volts, 3 Phase, 4 wire, 50 Hz at 1500 RPM self excited and self regulated with AVR brushless excitation band of voltage ± 1% of rated voltage from no load to full load insulation class H, self ventilated and conforming to IS4722, BS5000, IEC 34/1, IS0 8528, BS5514, I503046, suitable for above mentioned diesel engine. (C) ACOUSTIC ENCLOSURE : Factory made acoustic enclosure (canopy) having size as per OEM (D) CONTORL PANEL : Control panel made out of 2mm thick CRCA sheets in suitable compartments front openable duly powder coated, weather proof and long lasting finishing including the followings :- (i) Set of 400 Amps electrolytic copper bus bar for phase and neutral mounted over the hygroscopic PVC insulator. (ii) MCCB ,100-250 A, 4 Pole microprocessor based adjustable magnetic and thermal release setting 70% to 100%, rupturing capacity 25 KA, 415 volt, 50 Hz with over load and short circuit protections as per approved make – 01 No. (iv) Voltmeter digital type 0 to 500 volts range : 01 No (v) Amp meter digital type 0 to 300 Amps range complete with suitable CT”s- 01 No. (vi) MF meter digital type incl recording total and running Hrs complete (vii) Instrument fuses (HRC type) (viii) Bottom gland plates for incoming and outing cable (ix) Circuit diagram plate
Removing excavated material (any type) and disposing it outside Ministry of Defence Land. Note: (i) Before quoting the tender, the bidders are advised to ascertain the distance outside MD and at which the excavated material/ debris are to be disposed off. No extra claim what-so-ever shall be entertained on this account. (ii) This item shall be considered as per the requirement at site.
Furniture
Manufacture & Supply only Bath MAT PVC , as per Drawing No. FD/E6/MAP/07, complete all as specified and directed
Manufacture & Supply only Bed hard with ply wood Top (MAP), as per Drawing No. FD/E6/MAP/08(R), complete all as specified and directed
Manufacture & Supply only Chair Easy, as per Drawing No. FD-229, complete all as specified and directed
Supply only Chair Writing, as per Drawing No. FD/E6/MAP/12, complete all as specified and directed
Manufacture & Supply only Peg Table, as per Drawing No. FD-236, complete all as specified and directed
Manufacture & Supply only Receptacle PVC 20 Ltrs, as per Drawing No. FD/E6/MAP/13, complete all as specified and directed
Manufacture & Supply only Table Bed side, as per Drawing No. FD/E6/MAP/15(R), complete all as specified and directed
Manufacture & Supply only Table Center, as per Drawing No. FD-274, complete all as specified and directed
Manufacture & Supply only Mirror Dressing (Gents), as per Drawing No. FD/E6/MAP/16, complete all as specified and directed
Manufacture & Supply only Almirah small Steel, as per Drawing No. FD-1032, complete all as specified and directed
Manufacture & Supply only Almirah Large Steel, as per Drawing No. FD/E6/MAP/18, complete all as specified and directed
Supply only Bar Stool 3' high, complete all as specified and directed. Make :- Geeken model No. GC-964 or Supereq model No-SSCC-20 or Bombay Eezy Model No 436 as approved by GE.
Manufacture & Supply only Book Case steel, as per Drawing No. FD-1028, complete all as specified and directed
Manufacture & Supply only Chair Dining with long back, as per Drawing No. FD/MAP- II/04, complete all as specified and directed
Manufacture & Supply only Chair Easy With pedded cushioned, as per Drawing No. FD-358, complete all as specified and directed
Manufacture & Supply only Chair Verandah, as per Drawing No. FD/MAP II/06, complete all as specified and directed
Manufacture & Supply only Hat Stand with Mirror (Large), as per Drawing No. FD-1110, complete all as specified and directed
Manufacture & Supply only Hot case large, as per Drawing No. FD-46(M), complete all as specified and directed
Manufacture & Supply only Rack Magazine, as per Drawing No. FD-365, complete all as specified and directed
Manufacture & Supply only Board Notice 900X600mm, as per Drawing No. FD-1042, complete all as specified and directed
Manufacture & Supply only Receptacle universal with bucket, as per Drawing No. FD-43(M), complete all as specified and directed
Manufacture & Supply only Plate Rack, as per Drawing No. FD-242, complete all as specified and directed
Manufacture & Supply only Side Board Large, as per Drawing No. FD-1112, complete all as specified and directed
Manufacture & Supply only Safe Meat and Milk, as per Drawing No. FD-47(M), complete all as specified and directed
Manufacture & Supply only Sofa set 5 seater with cushioned, as per Drawing No. FD-281, complete all as specified and directed
Manufacture & Supply only Table dressing incl stool, as per Drawing No. FD/MAP-II/07, complete all as specified and directed
Manufacture & Supply only Table dinning 8 person, as per Drawing No. FD/MAP-II/03, complete all as specified and directed
Manufacture & Supply only Table cook house, as per Drawing No. FD-377, complete all as specified and directed
Manufacture & Supply only Table Writing, as per Drawing No. FD-275, complete all as specified and directed
Manufacture & Supply only Table Pantry Medium, as per Drawing No. FD-1020, complete all as specified and directed
Manufacture & Supply only Table Officer Steel, as per Drawing No.FD-1003, complete all as specified and directed
Manufacture & Supply only Tea Poy, as per Drawing No.FD-382, complete all as specified and directed
Manufacture & Supply only Teapoy Verandah, as per Drawing No.FD/E6/MAP/17, complete all as specified and directed
Manufacture & Supply only Table card, as per Drawing No.FD-352, complete all as specified and directed
Manufacture & Supply only Chair dinning, as per Drawing No.FD-279, complete all as specified and directed
Comprehensive Maintenance of Lifts
Comprehensive maintenance and repairs of fully automatic electrically operated passenger lift -02 No. of any Make and installed capacity with a carrying capacity of 08 Passenger (G+12 Floors) with AC variable voltage & variable frequency (VVVF drive) drive complete with all standard accessories, simplex collective automatic & manual dual controlled operation with/without attendant, automatic center opening doors with VVVF door drive (electric motor driven mechanism), sliding stainless steel doors, automatic rescue device (ARD) system, 3D infra red sensor in full height of door & built in announcing system without hand set (04 Nos, one each in car, Machine room & near Ground floor landing door) comprising of all devices and accessories through 36 months for all days including holidays etc after expiry of defects liability period as shown below and all as specified and directed to Engr-in-Charge for 02 nos of lifts Note : Contractor shall carryout comprehensive maintenance (routine, daily, weekly, monthly, quarterly, half yearly, yearly) through OEM as per the MOU and maintain all the lifts in serviceable condition 24 hrs x 365 days with out any extra cost.
(a) 1 year after expiry of defects liability period
b) 1 year after completion of BOQ item No. 29.012 here-in-before
c) 1 year after completion of BOQ item No. 29.013 here-in-before
All as per item No. 29.010 to 29.011 above but 13 passenger lift 01 No.
(a) 1 year after expiry of defects liability period
b) 1 year after completion of BOQ item No. 29.021 here-in-before
c) 1 year after completion of BOQ item No. 29.022 here-in-before
Schedule-A' Part-XVII 'Schedule of Credit' Total of Schedule-'A' Part-XVII B/F
NOTE:- (i) Contractor shall quote the percentage addition over lumpsum price of credit for material inserted by MES and carry forward the corresponding amount. However the quoted percentage shall not be less than NIL percent (i.e. shall not be on minus side). In case contractor’s quoted percentage is less than 0% (zero percent) it shall be restricted to 0% (zero percent) & total amount accordingly be corrected. The contractor shall take this aspect in account and nothing extra whatsoever shall be admissible on this account. (ii) This schedule of credit amount will be deducted from the lumpsum to arrive quoted lumpsum.
M/S K N Rai
Idustrial products India
NITYA NAND AND SONS CONTRACTORS PVT LTD
S.N. Constructions
JAI CONSTRUCTION CO.
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid