Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.4 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹8.9 L+₹1.5 L (20.0%)Rejected-Finance 403 GH MANSADEVI COMPLEX PANCHKULA 134109 HARYANA | PANCHKULA | HARYANA | 134109 | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹10.0 L+₹2.5 L (34.2%)Rejected-Finance HOUSE NO 102 LANE NO 4 C ANAND NAGAR BOHRI JAMMU 180002 J K | JAMMU | JAMMU AND KASHMIR | 180002 | L3 | Rejected-Finance Other than L1 |
Tender Value
₹9.7 L
EMD Value
₹19,400
Closing Date
10 Mar 2022, 6:00 pmClosed
Col S S Babu
Headquarters 138 Works Engineers Pin-914138 C/o 56 APO
Special Repair/Replacement and upgradation of VCBs at 153 GH Power Houses under GE 865 EWS at Leh
2022_MES_507144_1
138WE/L-87/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE 865 EWS
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE 865 EWS
₹19,400
Yes
27 Apr 2022
10 Feb 2022
17 Mar 2022
10 Feb 2022
10 Mar 2022
24 Feb 2022
Amount
Supply installing, Commissioning & testing HT 11 KV, 3 Phase 50 Hz, rupturing capacity 350 MVA indoor type, totally metal clad withdrawable type vacuum Circuit Breaker Outgoing panels with Copper bus bar of suitable rating horizontal isolation type VCB of capacity minimum 800 Amps rated current, as per IEC 62271-100-200. The switchgear panel shall be of sheet steel construction with ALUZINC not less than 2.5 mm thickness for load bearing section and not less than 2 mm thickness for non- load bearing and shall be totally dust and vermin proof. The offered panels shall be tested for IAC level of 25KA, No of operation of Vacuum Interrupter Bottles for better performance :- (a) Mechanical life 30,000, (b) Rated electrical operations – 10,000/ (c) Rated Short Circuit Current – 100A. All the main components like VCB/Relays/ Meters shall be of same make. Panel and VCB parameters are as below:- (i) Rated Voltage level/ PF withstand voltage/impulse level – 12 KV/28KV/75KVp. (ii) Continuous current rating minimum 800A. (iii) Short circuit withstand current minimum 25 KA for 3 sec (iv) One of minimum 800Amps Horizontal draw out type vacuum circuit breaker in 12KV metal clad floor mounting panel complete with following:- (aa) Manually & Motor operated (230V,AC, 50HZ) Spring charged type, manually electrically open (electrical- 220VDC) operation type, incorporating mechanical as well as electrical ON/OFF indication ‘OFF” push button, test/service position limit switches with minimum 6NO+6NC breaker auxiliary contacts in C5 service position. (ab) Epoxy cast wound current transformer (CT), 11 KV, 400-200/5-5A, Core 1: Class 1, 15VA for 3 phase Core 2 : 5P10, 15VA burden with metering and protection core including necessary control wiring. (ac) Manual Charging of breaker should be done without operating the front door. (ad) Cast resin potential transformer 11 KV/V3/110V/V3/110V/3, 50VA, Cl 1.0, Cl 3P and HT fuse at the primary end and pole MCB at the secondary end of the PT (Conforming to IS specification).
Supply and laying XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty with alluminium conductor, 11000 Volts (Earthed), grade cross sectional area 95 Sqmm 3 Core complete all as specified and directed by Engr-in-charge.
Material & Labour jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm complete all as specified and directed by Engr-in-charge.
EESSI
SUMEET TRADING CORPORATION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .