Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹36.0 LAccepted-AOC | 1 | Accepted-AOC Being lowest and reasonable | |
| 2 | 2₹38.8 L+₹1.0 L (2.75%)Rejected-Finance | 2 | Rejected-Finance Not being the lowest bidder | |
| 3 | 3₹41.9 L+₹4.2 L (11.0%)Rejected-Finance | 3 | Rejected-Finance Not being the lowest bidder | |
| 4 | 4₹46.6 L+₹8.9 L (23.6%)Rejected-Finance | 4 | Rejected-Finance Not being the lowest bidder | |
| 5 | 5₹49.1 L+₹11.4 L (30.2%)Rejected-Finance | 5 | Rejected-Finance Not being the lowest bidder |
Tender Value
₹47 L
EMD Value
₹94,000
Closing Date
11 Jan 2022, 6:00 pmClosed
GE(I) R AND D RCI, HYDERABAD
GE(I) RND RCI, MILITARY ENGINEER SERVICES, VIGNYANAKANCHA, RCI, HYDERABAD
REPAIRS MAINTENANCE OF LT DISTRIBUTION UNDER GROUND CABLE, LT PANEL BOARD AND CONNECTED ITEMS UNDER GE I RND RCI HYDERABAD
2021_MES_494579_1
8660
Open Tender
Electrical and Maintenance Works
Item Rate
300 days
GE(I) R AND D RCI
MES enlisted Class D category b i Un enlisted Meeting enlistment criteria of D class in MES and having no recovery pending. For further details ref NIT
8 documents required · 8 mandatory
₹500
Yes
GE(I) R AND D RCI, HYDERABAD
₹94,000
Yes
4 Mar 2022
14 Dec 2021
18 Jan 2022
14 Dec 2021
11 Jan 2022
28 Dec 2021
Amount
Excavation in trenches not exceeding 1.50m wide and not exceeding 1.50m depth for foundation, for laying of pipes/cables/poles etc., and getting out in any type of soil complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each layer as in soil complete all as specified and as directed.
Removing excavated material/soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed.
Supply and spreading natural river sand of approved quality for cushioning of cable laid in trenches including compacting and leveling complete all as specified and as directed. Note: Punned thickness will only be measured and paid.
Supply and laying un reinforced precast concrete cable cover, Class LV Type 1, size 250mm x 150mm x 40mm, laid flat adjacent to each other, perpendicular to cable in trenches for protection of cable complete all as directed.
Supplying, laying, jointing, testing and commissioning 1100 volts grade, LT XLPE insulated, PVC sheathed as per IS-7098 (Part-I), 1988 with latest amendments, galvanized steel strip or wire armoured, heavy duty, electric cables, with multistranded aluminium conductor laid in trenches/ passing through pipe/duct/road crossing or fixed on poles, walls with suitable size clamps made out of mild steel flat iron including jointing material such as crimping type lugs, brass cable glands, heavy duty double compression type etc., including disconnecting and taking down unserviceable cable complete all as specified and directed for the following sizes:- Note: Earthwork Excavation, sand cushioning, GI pipe and cable protection will be measured and paid separately.
3.5core 25Sqmm
3.5core 35Sqmm
3.5core 50Sqmm
3.5core 70Sqmm
3.5core 95Sqmm
3.5core 120Sqmm
3.5core 150Sqmm
3.5core 185Sqmm
3.5core 240Sqmm
3.5core 300Sqmm
3.5core 400Sqmm
S&F in repairs aluminium lugs suitable for aluminium conductor electric cables complete all as specified and directed for the following sizes:-
25Sqmm cable
35Sqmm cable
50Sqmm cable
75Sqmm cable
95Sqmm cable
120Sqmm cable
150Sqmm cable
185Sqmm cable
240Sqmm cable
400Sqmm cable
Taking out burnt out/unserviceable existing cable/jointing kit from trenches, cutting the same, supply and jointing new straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE insulated armoured aluminium conductor cable of size 25sqmm to 50sqmm for 1.1KV (Earthed) grade including testing complete all as specified and directed. Note: Quoted rate shall be deemed to include cost of earthwork excavation, RFR in any type of soil. Extra length of cable if any required will be measured and paid separately
All as per item No 8 above but for 3.5core 70 to 120Sqmm cable
All as per item No 8 above but for 3.5core 150 to 185Sqmm cable
All as per item No 8 above but for 3.5core 240 to 300Sqmm cable
All as per item No 8 above but for 3.5core 400Sqmm cable
S&F, 100mm dia GI pipe light grade fixed to walls/poles or laid in trenches, road crossing etc., for protection of underground cable/earth strip including sealing ends with hessian cloth impregnated with bituminous compound in ground and with teak wood bushes for ends fixed on walls/poles complete all as specified and directed.
All as per item No 13 above but 80 mm dia
All as per item No 13 above but 50 mm dia
All as per item No 13 above but 40 mm dia
Cutting of existing bituminous/PCC road or flooring/plinth protection, for laying of GI pipe in road intersection for passing of LT XLPE cable including excavation in any type of soil, returning and filling in and making good top 30cm of the trench by providing PCC 1:2:4 type B1 using 20mm graded stone aggregate to flush with existing road surface complete all as directed.
S&F, 3 pole MCCB 400Amp current carrying capacity with adjustable thermal and magnetic settings, 50KA, 415 volt, conforming to IEC -60947-II/ IS-13947-II with suitable extended ROM & extended link including dismantling of unserviceable MCCBs from the enclosures complete all as specified and directed. Make: L&T CAT No SB95053OOOO with Extension link CAT No ST30658OOOO and Extended ROM CAT No CM99898OOOO or equivalent in Legrand/Schneider/ Siemens/ C&S as approved by GE as approved by GE
S&F, 3 pole MCCB 630Amp current carrying capacity with adjustable thermal and magnetic settings, 50KA, 415 volt, conforming to IEC -60947-II/ IS-13947-II with suitable extended ROM & extended link including dismantling of unserviceable MCCBs from the enclosures complete all as specified and directed. Make: L&T CAT No SB95054OOOO with Extension link CAT No ST30658OOOO and Extended ROM CAT No CM99898OOOO or equivalent in Legrand/Schneider/ Siemens/ C&S as approved by GE as approved by GE
S&F in repairs, CRCA sheet metal enclosure with metal clad plug and socket three phase with a five pin and earth plug & socket suitable for surface/flush mounting, 415V, 63Amp capacity controlled by and including one No 63Amp MCB TPN 10KA complete all as specified and directed.
Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board indoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 2mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 2000Amps rating for phase and neutral 4 strips with colour coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar
tapings for ACBs/MCCBs, copper control wiring using suitable size of PVC insulated, multi stranded copper conductors with all connected accessories, duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate accessories including dismantling the unserviceable LT panel board from the existing position after disconnection of all electrical connections complete all as specified and directed with and including the following accessories :-
ACB 4pole, 1250Amps with adjustable thermal and magnetic settings (over load, short circuit, earth fault protection and metering relay), 50KA rupturing capacity at 415volt, mechanical draw out type with manual spring charge mechanism with self contained CTs - 01 No (Incoming)
MCCB 4pole, 200Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 06 No (Outgoing)
MCCB 4pole, 125Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 14 No (Outgoing)
Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
Note: Necessary arrangement shall be made for connecting and proper alignment of the panel board with the existing panel boards.
Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board indoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 2mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 2000Amps rating for phase and neutral 4 strips with colour coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar
tapings for ACBs/MCCBs, copper control wiring using suitable size of PVC insulated, multi stranded copper conductors with all connected accessories, duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate accessories including dismantling the unserviceable LT panel board from the existing position after disconnection of all electrical connections complete all as specified and directed with and including the following accessories :-
ACB 4pole, 1250Amps with adjustable thermal and magnetic settings (over load, short circuit, earth fault protection and metering relay), 50KA rupturing capacity at 415volt, mechanical draw out type with manual spring charge mechanism with self contained CTs - 01 No (Incoming)
MCCB 4pole, 200Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 06 No (Outgoing)
MCCB 4pole, 125Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 09 No (Outgoing)
Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
Note: Necessary arrangement shall be made for connecting and proper alignment of the panel board with the existing panel boards.
Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board indoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 2mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 2000Amps rating for phase and neutral 4 strips with colour coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar
tapings for ACBs/MCCBs, copper control wiring using suitable size of PVC insulated, multi stranded copper conductors with all connected accessories, duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate accessories including dismantling the unserviceable LT panel board from the existing position after disconnection of all electrical connections complete all as specified and directed with and including the following accessories :-
ACB 4pole, 1250Amps with adjustable thermal and magnetic settings (over load, short circuit, earth fault protection and metering relay), 50KA rupturing capacity at 415volt, mechanical draw out type with manual spring charge mechanism with self contained CTs - 01 No (Incoming)
MCCB 4pole, 200Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 09 No (Outgoing)
MCCB 4pole, 125Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 03 No (Outgoing)
Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
Note: Necessary arrangement shall be made for connecting and proper alignment of the panel board with the existing panel boards.
Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board indoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 2mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 1000Amps rating for phase and neutral 4 strips with colour coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar
tapings for MCCBs, copper control wiring using suitable size of PVC insulated, multi stranded copper conductors with all connected accessories, duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate accessories including dismantling the unserviceable LT panel board from the existing position after disconnection of all electrical connections complete all as specified and directed with and including the following accessories :-
MCCB 4pole, 630Amps, with adjustable thermal and magnetic settings, 50KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
MCCB 4pole, 200Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 04 No (Outgoing)
MCCB 4pole, 125Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 04 No (Outgoing)
Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
Note: Necessary arrangement shall be made for connecting and proper alignment of the panel board with the existing panel boards.
Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board indoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 2mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 800Amps rating for phase and neutral 4 strips with colour coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar
tapings for MCCBs, copper control wiring using suitable size of PVC insulated, multi stranded copper conductors with all connected accessories, duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate accessories including dismantling the unserviceable LT panel board from the existing position after disconnection of all electrical connections complete all as specified and directed with and including the following accessories :-
MCCB 4pole, 400Amps, with adjustable thermal and magnetic settings, 50KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
MCCB 4pole, 200Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing)
MCCB 4pole, 125Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 06 No (Outgoing)
Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
Note: Necessary arrangement shall be made for connecting and proper alignment of the panel board with the existing panel boards.
Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board indoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 2mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 800Amps rating for phase and neutral 4 strips with colour coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar
tapings for MCCBs, copper control wiring using suitable size of PVC insulated, multi stranded copper conductors with all connected accessories, duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate accessories including dismantling the unserviceable LT panel board from the existing position after disconnection of all electrical connections complete all as specified and directed with and including the following accessories :-
MCCB 4pole, 400Amps, with adjustable thermal and magnetic settings, 50KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
MCCB 4pole, 63Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 09 No (Outgoing)
Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
Note: Necessary arrangement shall be made for connecting and proper alignment of the panel board with the existing panel boards.
Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board indoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 2mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 1000Amps rating for phase and neutral 4 strips with colour coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar
tapings for MCCBs, copper control wiring using suitable size of PVC insulated, multi stranded copper conductors with all connected accessories, duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate accessories including dismantling the unserviceable LT panel board from the existing position after disconnection of all electrical connections complete all as specified and directed with and including the following accessories :-
MCCB 4pole, 630Amps, with adjustable thermal and magnetic settings, 50KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
MCCB 4pole, 100Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 10 No (Outgoing)
Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
Note: Necessary arrangement shall be made for connecting and proper alignment of the panel board with the existing panel boards.
M/s ANUSHA ENTERPRISES
S.S.ENGINEERING CORPORATION
SHANTI MARKETING AND SERVICES
SHRI GANESH ENTERPRISES
SUN LIGHT HOUSE
Universal refrigeration and Engineering Company
SHAH ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .