Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹46.4 LAccepted-AOC 33 CHANDASI HOUSE LANE NO 11 S K PURAM ARYA SAMAJ MANDIR ROAD RPS MORE BAILEY ROAD DANAPUR PATNA BIHAR 801503 | PATNA | PATNA | BIHAR | 801503 | ₹46.4 L Quoted ₹46.5 L | L1 | Accepted-AOC ACCEPTED BEING LOWEST AS PER NIT |
| 2 | L2₹53 LRejected-Finance | ₹53 L | L2 | Rejected-Finance Rejected being L2 bidder |
| 3 | L3₹57.3 LRejected-Finance V P O SAROTARI TEHSIL BAROH DISTRICT KANGRA PIN 176037 HP | KANGRA | HIMACHAL PRADESH | 176037 | ₹57.3 L | L3 | Rejected-Finance Rejected being L3 bidder |
| 4 | Rejected-Technical | - | - | Rejected-Technical Due to Valid DD Bankers cheque against cost of tender documents neither uploaded nor submiited before bid submission end date in terms of Para 4 of NIT |
| Sl No | Description | Qty | Unit | Electromech Engineers L3 | Roy and Sons Infrastructures L1 | M/S Razdan Buildersand suppliers L2 |
|---|---|---|---|---|---|---|
| 1.00 | Dismantling of existing distribution Transformer fixed in 2 pole/4 pole / in plinth mounted from site with the help of crane and manpower after taking proper shut down and deposited in safe custody of MES complete all as specified and directed. | 5 | Each Job | 18,600 ₹93,000 | 15,000 ₹75,000 | 1,000 ₹5,000 Lowest |
| 2.00 | Supply, Installation, testing and commissioning copper wound step down transformer, Indoor type complete with standard fittings, HT, 11 KV, 3 Phase, LT, 433 Volts, 3 phase 4 wire with off load tapings on Primary side to vary secondary voltage + 7.5% with tapings at every 2.5% rating of capacity 500 KVA including bushing on HT side and LT side all as per IS 1180 complete including repairing of existing plinth as per direction by Engineer in charge complete all as specified and directed. | 1 | Each | 15,85,000 ₹15,85,000 | 12,30,000 ₹12,30,000 Lowest | 15,20,000 ₹15,20,000 |
| 3.00 | Supply, Installation, testing and commissioning copper wound step down transformer ,Outdoor type complete with standard fittings, HT, 11 KV, 3 Phase, LT , 433 Volts, 3 phase 4 wire with off load tapings on Primary side to vary secondary voltage + 7.5% with tapings at every 2.5% rating of capacity 400 KVA including bushing on HT side and LT side all as per IS 1180 complete all as specified and directed. | 1 | Each | 13,97,090 ₹13,97,090 | 10,70,000 ₹10,70,000 Lowest | 13,20,000 ₹13,20,000 |
| 4.00 | Supply, installation, testing and commissioning copper wound step down transformer ,Outdoor type complete with standard fittings, HT, 11 KV, 3 Phase, LT , 433 Volts, 3 phase 4 wire with off load tapings on Primary side to vary secondary voltage + 7.5% with tapings at every 2.5% rating of capacity 315 KVA including bushing on HT side and LT side all as per IS 1180 complete all as specified and directed. | 1 | Each | 10,92,000 ₹10,92,000 | 9,10,000 ₹9,10,000 Lowest | 11,35,000 ₹11,35,000 |
| 5.00 | Supply, installation, testing and commissioning copper wound step down transformer ,Outdoor type complete with standard fittings, HT, 11 KV, 3 Phase, LT , 433 Volts, 3 phase 4 wire with off load tapings on Primary side to vary secondary voltage + 7.5% with tapings at every 2.5% rating of capacity 100 KVA including bushing on HT side and LT side all as per IS 1180 complete all as specified and directed. | 1 | Each | 6,85,000 ₹6,85,000 | 5,00,000 ₹5,00,000 Lowest | 7,20,000 ₹7,20,000 |
| 6.00 | Supply, installation, testing and commissioning copper wound step down transformer ,Outdoor type complete with standard fittings, HT, 11 KV, 3 Phase, LT , 433 Volts, 3 phase 4 wire with off load tapings on Primary side to vary secondary voltage + 7.5% with tapings at every 2.5% rating of capacity 160 KVA including bushing on HT side and LT side all as per IS 1180 complete all as specified and directed.
Note for ser item No 2-6 :- The Transformer shall be IS : 1180 (Part-I) : 2014 with maximum total loses as per energy efficiency level 2 of IS : 1180 (Part-I) : 2014 and shall comprise of the following: -
(a) HT cable box on primary side(HV) including Three Nos of porcelain bushing with copper rods, complete all accessories as required.
(b) One cable box on LV side (Secondary side) consisting of four Nos
porcelain bushing with copper rods, complete with nuts and washers, with
cable glands suitable for XLPE insulated heavy duty armoured cables and jointing materials complete.
(c) Oil conservator with filter type drain valve and oil level gauge.
(d) De-hydrating breather with first fill dehydrating agent (silica gel).
(e) Explosive vent.
(f) Thermometer pocket on tank cover
(g) One No 100mm dia, dial type thermometer, vapour pressure type,
having range 0-120 degree Celsius with metal guard having maximum
perimeter reading temperature indicator with resisting device for
transformer. | 1 | Each | 8,09,100 ₹8,09,100 | 7,50,000 ₹7,50,000 | 5,20,000 ₹5,20,000 Lowest |
| 6.01(h) Two Nos earth terminals for body earthing and two No. earthing terminals for neutral earthing. (j) Rating plate and terminal marking plate. (k) Oil level gauge (l) Oil drain filter valve (m) Lifting lugs. (n) Initial filling to transformer oil with required capacity. (o) Pre-commissioning test shall be carried out by the SEI/IEM/Rep of Accepting Officer for which all arrangements shall be made by the contractor without any extra cost (p) Contractor will submit specification from approved manufacturer comprising of the above specification to Engr in Charge and take approval before placing order (q) By directional plane roller-04 Nos | ||||||
| 7.00 | M&L for earthing complete with galvanised iron earth plate electrode 600mmx600mm and 6mm thick buried directly in ground (earth pit not less than 2.25mtr deep below ground level) with top edge of earth plate not less than 1.5mtr below normal ground level, connected with 32x6mm size GI strip as earth lead, by means of bolts, nuts, check nuts and washers of galvanized iron or steel complete with 40mm dia GI light grade protection pipe, 20mm dia GI medium grade watering pipe with funnel including charcoal, dust, salt, PCC M-15, type B-1 in pit with precast RCC M-15(1:2:4), type B-1 (using 20mm graded crushed stone aggregates) in cover reinforced with XPM not less than 4.0 Kg per Sqm, test point etc. all as shown in electric plate No-3 of SSR Part-I (2009), complete with necessary earth work in any type of soil, removal to a distance not exceeding 50mtr, including testing on completion, complete all as specified and as directed by Engineer-in-Charge.
Note: Earth pit chamber and RCC pit cover shall be painted with two coats of synthetic enamel paint over one coat of red oxide primer including preparation of surfaces. | 16 | Each Set | 4,500 ₹72,000 Lowest | 7,000 ₹1,12,000 | 5,000 ₹80,000 |
Tender Value
₹52 L
EMD Value
₹1.0 L
Closing Date
20 May 2026, 6:00 pmClosed
CWE, HQ 133 WORKS ENGRS
HQ 133 WORKS ENGRS, C/O 56 APO, PIN- 914133
CWEK/TOKEN-154/864 EWS/2025-26 SPL REPAIRS/ RENEWAL OF VARIOUS CAPACITY DISTRIBUTION TRANSFORMERS AGAINST BER IN ZONE A ALONGWITH CONNNECTED ACCESSORIES IN THE AOR OF AGE E/M UNDER GE 864 EWS (JOB NO W/SPL REPAIRS (E/M)-07/BB CANTT/2025-26)
2026_MES_761495_1
CWEK/TOKEN-154/864 EWS/2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
GE 864 EWS
Class C and above and Category b (ii)
7 documents required · 7 mandatory
₹1,000
GE 864 EWS
₹1.0 L
HQ 133 WORKS ENGRS
23 Jun 2026
22 Apr 2026
28 May 2026
22 Apr 2026
20 May 2026
14 May 2026
22 Apr 2026 - 25 Apr 2026
28 Apr 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| - | Dismantling of existing distribution Transformer fixed in 2 pole/4 pole / in plinth mounted from site with the help of crane and manpower after taking proper shut down and deposited in safe custody of MES complete all as specified and directed. | - | Each Job | - | - |
| - | Supply, Installation, testing and commissioning copper wound step down transformer, Indoor type complete with standard fittings, HT, 11 KV, 3 Phase, LT, 433 Volts, 3 phase 4 wire with off load tapings on Primary side to vary secondary voltage + 7.5% with tapings at every 2.5% rating of capacity 500 KVA including bushing on HT side and LT side all as per IS 1180 complete including repairing of existing plinth as per direction by Engineer in charge complete all as specified and directed. | - | Each | - | - |
| - | Supply, Installation, testing and commissioning copper wound step down transformer ,Outdoor type complete with standard fittings, HT, 11 KV, 3 Phase, LT , 433 Volts, 3 phase 4 wire with off load tapings on Primary side to vary secondary voltage + 7.5% with tapings at every 2.5% rating of capacity 400 KVA including bushing on HT side and LT side all as per IS 1180 complete all as specified and directed. | - | Each | - | - |
| - | Supply, installation, testing and commissioning copper wound step down transformer ,Outdoor type complete with standard fittings, HT, 11 KV, 3 Phase, LT , 433 Volts, 3 phase 4 wire with off load tapings on Primary side to vary secondary voltage + 7.5% with tapings at every 2.5% rating of capacity 315 KVA including bushing on HT side and LT side all as per IS 1180 complete all as specified and directed. | - | Each | - | - |
| - | Supply, installation, testing and commissioning copper wound step down transformer ,Outdoor type complete with standard fittings, HT, 11 KV, 3 Phase, LT , 433 Volts, 3 phase 4 wire with off load tapings on Primary side to vary secondary voltage + 7.5% with tapings at every 2.5% rating of capacity 100 KVA including bushing on HT side and LT side all as per IS 1180 complete all as specified and directed. | - | Each | - | - |
| - | Supply, installation, testing and commissioning copper wound step down transformer ,Outdoor type complete with standard fittings, HT, 11 KV, 3 Phase, LT , 433 Volts, 3 phase 4 wire with off load tapings on Primary side to vary secondary voltage + 7.5% with tapings at every 2.5% rating of capacity 160 KVA including bushing on HT side and LT side all as per IS 1180 complete all as specified and directed.
Note for ser item No 1-6 :- The Transformer shall be IS : 1180 (Part-I) : 2014 with maximum total loses as per energy efficiency level 2 of IS : 1180 (Part-I) : 2014 and shall comprise of the following: -
(a) HT cable box on primary side(HV) including Three Nos of porcelain bushing with copper rods, complete all accessories as required.
(b) One cable box on LV side (Secondary side) consisting of four Nos
porcelain bushing with copper rods, complete with nuts and washers, with
cable glands suitable for XLPE insulated heavy duty armoured cables and jointing materials complete.
(c) Oil conservator with filter type drain valve and oil level gauge.
(d) De-hydrating breather with first fill dehydrating agent (silica gel).
(e) Explosive vent.
(f) Thermometer pocket on tank cover
(g) One No 100mm dia, dial type thermometer, vapour pressure type,
having range 0-120 degree Celsius with metal guard having maximum
perimeter reading temperature indicator with resisting device for
transformer. | - | Each | - | - |
| - | (h) Two Nos earth terminals for body earthing and two No. earthing
terminals for neutral earthing.
(j) Rating plate and terminal marking plate.
(k) Oil level gauge
(l) Oil drain filter valve
(m) Lifting lugs.
(n) Initial filling to transformer oil with required capacity.
(o) Pre-commissioning test shall be carried out by the SEI/IEM/Rep of Accepting Officer for which all arrangements shall be made by the contractor without any extra cost
(p) Contractor will submit specification from approved manufacturer comprising of the above specification to Engr in Charge and take approval before placing order
(q) By directional plane roller-04 Nos | - | - | - | - |
| - | M&L for earthing complete with galvanised iron earth plate electrode 600mmx600mm and 6mm thick buried directly in ground (earth pit not less than 2.25mtr deep below ground level) with top edge of earth plate not less than 1.5mtr below normal ground level, connected with 32x6mm size GI strip as earth lead, by means of bolts, nuts, check nuts and washers of galvanized iron or steel complete with 40mm dia GI light grade protection pipe, 20mm dia GI medium grade watering pipe with funnel including charcoal, dust, salt, PCC M-15, type B-1 in pit with precast RCC M-15(1:2:4), type B-1 (using 20mm graded crushed stone aggregates) in cover reinforced with XPM not less than 4.0 Kg per Sqm, test point etc. all as shown in electric plate No-3 of SSR Part-I (2009), complete with necessary earth work in any type of soil, removal to a distance not exceeding 50mtr, including testing on completion, complete all as specified and as directed by Engineer-in-Charge.
Note: Earth pit chamber and RCC pit cover shall be painted with two coats of synthetic enamel paint over one coat of red oxide primer including preparation of surfaces. | - | Each Set | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.41 MB
Tender154.pdf
Tender Documents • 1.25 MB
BOQ_852994.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].