Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.0 LAccepted-AOC HYDERABAD TELANGANA 500076 INDIA UDYAM TS 02 0009467 | MEDCHAL MALKAJGIRI | TELANGANA | 500076 | L1 | Accepted-AOC Quoted L1 | |
| 2 | L2₹21.0 L+₹4.4 L (26.7%)Rejected-AOC | L2 | Rejected-AOC Quoted L2 |
Tender Value
₹16.9 L
EMD Value
₹33,800
Closing Date
25 Jan 2022, 6:00 pmClosed
GE (AF) Chandigarh
GE (AF) Chandigarh PIN-160003
REPAIR TO WATER SUPPLY LINE, ELECTRIC CABLE, AC, DG SET ETC AND COOLING APLLIANCES AT AIR FORCE STATION MULLANPUR
2021_MES_491207_2
GE(AF)/CHD/T-38/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Mullanpur
All as per NIT and Tender documents
9 documents required · 9 mandatory
₹500
GE (AF) Chandigarh
₹33,800
2 May 2022
4 Jan 2022
27 Jan 2022
4 Jan 2022
25 Jan 2022
11 Jan 2022
4 Jan 2022 - 10 Jan 2022
Amount
External Electrification
Excavation in trenches in soft/loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for laying/taking out of cables and foundation of poles etc. and getting out, complete all as specified and directed.
Returning, filling in trenches (soil), including spreading, leveling and well ramming in layers not exceeding 25 cm thick, complete all as specified and directed.
Removal of surplus excavated soil to a distance not exceeding 50metre and depositing where directed at a level not exceeding 1.5metre above the starting point, complete all as specified and directed.
Material and labour, sand cushioning with a layer of dry river sand, 80mm thick before laying of cable and 150mm thick (punned down to 100mm thick) after laying of cables, in trenches/ducts, complete all as specified and directed. Note : Punned down thickness (overall 18cm), shall be considered for measurement and payment.
Material and labour, locally available, sub class `B’ bricks (old size), laid flat and dry perpendicular to the direction of cable adjacent to each other, in trenches over the cable for protection, complete all as specified and directed.
Taking out / down old existing LT 1100volt grade cables, size 2x10Sqmm, aluminium conductor 2core, XLPE/ PLCA/ PVC, armoured, laid in trenches, including bricks for protection, sand cushioning and stacking, removal to store for re-use or for credit, complete all as specified and directed Note : Excavation shall be measured and paid for separately
All as per Serial Item No.1.06 here-in-before but 16Sqmm 2Core size
All as per Serial Item No. 1.06 here-in-before but 16Sqmm 4Core size
All as per Serial Item No. 1.06 here-in-before but 35Sqmm 3.5Core size
All as per Serial Item No.1.06 here-in-before but 50Sqmm 3.5Core size
All as per Serial Item No. 1.06 here-in-before but 95Sqmm 3.5Core size
All as per Serial Item No .1.06 here-in-before but HT cable 95Sqmm 3Core size
Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated and armoured, heavy duty, electric power cable, cross sectional area 10Sqmm 2 core aluminum conductor 1100volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: Returning filling & removal of earth, sand cushioning and bricks for protection of cable shall be measured and paid separately.
All as per Serial Item No. 1.13 here-in-before but 16Sqmm 2Core size
All as per Serial Item No. 1.13 here-in-before but 16Sqmm 4Core size
All as per Serial Item No. 1.13 here-in-before but 35Sqmm 3.5Core size
All as per Serial Item No. 1.13 here-in-before but 50Sqmm 3.5Core size
All as per Serial Item No. 1.13 here-in-before but 95Sqmm 3.5Core size
Supply, laying, jointing, testing and commissioning of High Tension (HT) XLPE insulated , screened, PVC bedded, galvanized steel strip or wire armoured, armoured, heavy duty, electric power cable, cross sectional area 95Sqmm 3core aluminum conductor 11000volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: Returning filling earth work, sand cushioning and bricks for protection of cable shall be measured and paid separately.
Supply, jointing & testing, indoor end termination joint kit (Heat shrinkable) complete with jointing material and accessories suitable for 3wire, 11KV (Earthed) grade, HT, underground XLPE insulated armoured aluminium conductor cable, 3core, 95Sqmm size cable, complete including taking dwon old jointing kit all as specified and directed
Supply, jointing & testing, outdoor end termination joint kit (Heat shrinkable) complete with jointing material and accessories suitable for 3wire, 11KV (Earthed) grade, HT, underground XLPE insulated armored aluminium conductor cable, 3core, 95Sqmm size cable, complete including taking dwon old jointing kit all as specified and directed
Supply, jointing & testing, straight through joint kit (Heat shrinkable) complete with jointing material and accessories suitable for 3wire, 11KV (Earthed) grade, HT, underground XLPE insulated armoured aluminium conductor, 3core, 95Sqmm size cable,including taking down old jointing kit complete all as specified and directed
Supply and laying / fixing , GI pipe light grade 100mm dia bore for cable protection fixed to pole/wall or laid under floor/roadv /pavement, including flat iron clamp, nut, bolt, wahser etc of required size and taking out old & removal, complete all as specified and directed. Note: Boring of holes under road etc. shall be measured and paid separately.
All as per item No 1.23 here - in before but GI pipe 80mm complete all as specified and directed.
All as per item No 1.23 here - in before but GI pipe 50mm complete all as specified and directed.
Material and labour for switch air break, gang operated triple pole ,mechanically operated, mounted on 12 insulators including drop out insulators including 3 nos barrel type drop out fuses and steel frame with operating mechanism worked from ground level with 25mm light grade GI tubing for current rating upto 400 amps,11000 volt including taking down old and removal complete all as specified and directed.
Material and labour for lightening arrestor high tension ,expulsion type complete with all fittings, transmission class ,discharge capacity 65 kilo amp ,suitable for 11000 volt grade system fixed in position including disconnecting and taking down old and removal complete all as specified and direced
Supply and fixing in replacement the under mentioned spare/parts of transformer capacity from 50 KVA to 250KVA, complete all as specified and directed.
Air breather assembly with silica gel
HT side procelain bush 11KV (Set of 03) with brass studs, nuts & washers, rubber gasket etc
LT side procelain bush 415V upto 100KVA transformer (Set of 04) with brass studs, nuts & washers, rubber gasket etc
LT side procelain bush 415V upto 200KVA - 250KVA transformer (Set of 04) with brass studs, nuts & washers, rubber gasket etc
Dismantling/Strip opening of the HT VCB 11KV 400 Amps for calibration, repairing, preventative maintenance, servicing including replacement of worn out parts to make it fully functional, reassembling the same after repair, installation to its original position, connection input/output supply, testing to its full load capacity and all other relevant tests as per IE/IS rules, complete all as specified and directed. Note: Spare parts required for repair/replacement shall be maeasured and paid separately.
Supply and fixing in replacement under mentioned spare/parts 11KV, 400 Amps HT VCB, any model/type of make :- Kirloskar/Crompton complete all as specified and directed.
Supply only, Potenional Transformer (PT) of 11KV/110V , totally enclosed, sealed and stamped, epxoy filled, heavy duty, suitable for 11 KV 400 Amps HT VCB, complete including taking dwon old PT all as specified and directed.
Supply only, Micro process based relay heavy duty, suitable for 11 KV 400 Amps HT VCB, complete inlcuding taking down old relay all as specified and directed.
Supply only, vaccum interruptor for VCB, complete all as specified and directed.including taking down old interruptor
Supply only, trolly insulator for mounting vaccum interruptor for VCB, complete all as specified and directed.
Supply only, epoxy fibre base plate for interruptor, complete all as specified and directed.
Supply only, epoxy insulator for bus bar supports, complete all as specified and directed.
Supply and fix, finger moving contact (Made up of six, each male and female, fingers), spring loaded, heavy duty, suitable for 11KV, 400Amp, HT VCB, complete all as specified and directed.
Supply and fix, Current Transformer (CTs) of CTR 50-25 / 5Amps, totally enclosed, sealed and stamped, epxoy filled, heavy duty, suitable for 11 KV 400 Amps HT VCB, complete all as specified and directed.
Supply and fix in replacement of spout type insulator suintable for HT VCB including cleaning the bus bar all as specified and directed by Engineer in Charge
Supply and fix, in replacement MCCB, four pole, 250Amps, 415 volts, 35 KA, 50Hz , with adjustable thermal and magnetic release, complete with extension links and making connection in panel board, complete all as specified and directed.
Supply and fix, in replacement MCCB, four pole, 200Amps, 415 volts, 35 KA, 50Hz , with adjustable thermal and magnetic release, complete with extension links and making connection in panel board, complete all as specified and directed.
Supply and fix, in replacement MCCB, four pole, 160Amps, 415 volts, 25 KA, 50Hz , with adjustable thermal and magnetic release, complete with extension links and making connection in panel board, complete all as specified and directed.
Supply and fix, in replacement MCCB, three pole, 250Amps, 415 volts, 35 KA, 50Hz , with adjustable thermal and magnetic release, complete with extension links and making connection in panel board, complete all as specified and directed.
Supply and fix, in replacement MCCB, three pole, 200Amps, 415 volts, 25 KA, 50Hz , with adjustable thermal and magnetic release, complete with extension links and making connection in panel board, complete all as specified and directed.
Supply and fix, in replacement MCCB, three pole, 160Amps, 415 volts, 25 KA, 50Hz , with adjustable thermal and magnetic release, complete with extension links and making connection in panel board, complete all as specified and directed.
Supply and fix, in replacement MCCB, three pole, 125Amps, 415 volts, 25 KA, 50Hz , with adjustable thermal and magnetic release, complete with extension links and making connection in panel board, complete all as specified and directed.
Supply and fix, in replacement MCCB, three pole, 63Amps, 415 volts, 16 KA, 50Hz , with adjustable thermal and magnetic release, complete with extension links and making connection in panel board, complete all as specified and directed.
Material and labour, Cross arms, bracing, supports, clamps and back plates, fabricated from structural steel section Fe-290 grade E-165 quality including nuts, bolts, washers, and welding, bending cold or hot, drilling holes for bolts, in any shape or size as directed including two coats of alminium paint over a coat of red oxide primer, complete all as specified and directed.
Material and labour, painting two coats of aluminium paint to steel tubular poles of any description (external surface only) including MS cross arms etc making of 5 strips of width 300mm each (03 Nos Sky blue and 2 No. white) writing pole No. with black paint with letters/figures in girth 3 inch, including preparation of old painted surface, complete all as specified and directed.
Material and labour, painting two coats of aluminium paint to MS cross arms only fitted with PCC poles of any description and making of 5 strips of width 300mm each (03 Nos Sky blue and 2 No. white) writing pole No. with black paint with letters/figures in girth 3 inch, including preparation of old painted surface, complete all as specified and directed.
M & L preparation of old steel suface over 10cm width or grith not otherwise described and applying a coat of synthetic enamal paint to LT feeder pillar box all as specified and directed by Engineer in charge
M & L cable jointing kit for 1100 Volts (Earthed) grade cable for straight through joint complete with jointing materials and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25 Sqmm to 50 Sqmm complete all as specified.
M & L cable jointing kit for 1100 Volts (Earthed) grade cable for straight through joint complete with jointing materials and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 Sqmm to 95 Sqmm complete all as specified.
M & L cable jointing kit for 1100 Volts (Earthed) grade cable for straight through joint complete with jointing materials and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 150 Sqmm complete all as specified.
M & L cable jointing kit for 1100 Volts (Earthed) grade cable for straight through joint complete with jointing materials and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 185 Sqmm to 300 Sqmm complete all as specified.
Supply and fixing , LED box type batten fitting 1x20W,including LED tube rod retrofit type 20W, prewired upto connection block and connecting with three core PVC copper flexible cable of size 1. Sq. mm from ceiling roseto connector block, including taking down old unserviceable surface mounted fitting of any wattage and type, complete all as specified and directed by Engineer-in-Charge.
Finding/locate fault in HT 11 KV grade cable of any size and depth with in 1 KM length or more with the help of cable fault locator insutrument of latest design ,cable in trenches,floor or pipe and rectrifecation the same complete all as specified and directed
All as per item no 1.61 here in before but in LT 1100 Volts grade cable ,complete all as specified and directed by Engineer Note for seril item no 1.61 & 1.62 (i) The fault shall be rectified within 6 hrs from receiving complaint telephoniclly/SMS by JE or AGE E/M, if the fault is not rectified within 6 hrs,the penalty for Rs 5000 per Hour shall be recovered from contractor (ii) The number of fault occured within 1 KM length in same location shall be treated as on fault
Water Supply and Sewage Installations
Taking out defective submersible pump & motor set 6 to 8 stage, 700-900 LPM at 112mtr head of any dia upto 150mm from bore well with the help of chain pulley after disconnecting electrical connections from motor starter, disconnecting the column pipe from supply pipe line, opening each column pipe by unscrewing nut bolt, rubber packing of each column pipe, submersible cable and keeping a side for reuse the number of column pipe to be taken out upto 24-28 Nos. alongwith submersible cable, for repair / replacement of parts to make it fully functional, reassembling the same after repair, lowering/ installation to its original position, electric connection of input/ output electric supply, connecting the column pipe to supply pipe line testing to its full load capacity at least for 4 hours and all other relevant tests including any minor repair, replacement of rubber gasket for column pipe etc. transportation to workshop and vice-versa, complete all as specified and directed by the Engineer-in-Charge.
Dismantling of submersible motor 35 to 38 HP 415 volts 50 Hz 3 phase AC electric supply, taking out the burnt winding of stator, removal of burnt insulation material from the slots, cleaning the stator slots and preparation for rewinding the same and material and labour for winding the stator of motor with PVC insulated copper wire of standard size and superior quality copper winding wire as per the existing gauge including the F class insulation materials, turning, balancing & alignment of rotor etc. to get the proper RPM and torque & tested to its full load capacity complete all as specified and directed Note :- Spare parts required to be replaced shall be measured and paid separately as 'Supply only'.
Opening of pump set 6 to 8 stage, 700-900LPM at 112mtr head for repair and replacement of unserviceable parts, reassembling the same after repair, machining work of impeller housing, remetaling of pump shaft, grinding, scraping, cleaning and balancing the same to make it fully functional at the full load capacity including turning, balancing & alignment of shaft etc. reassembling of complete Pump & Motor set and testing on completion for the entire satisfaction of Engineer – in - Charge all as directed. Note:- Spare parts required to be replaced shall be measured and paid separately as 'Supply only'.
Supply only of motor housing rotor bush for 35 to 38 HP submersible motor complete all as specified and directed.
Supply only of water seal for 35 to 38 HP submersible motor complete all as specified and directed.
Supply only of thrust bearing set for 35 to 38 HP submersible pump complete all as specified and directed.
Supply only bush Gun metal for 700-900LPM submersible motor complete all as specified and directed.
Supply only impeller Gun metal for 700-900LPM submersible pump complete all as specified and directed.
Supply only impeller neckring for 700-900LPM submersible pump complete all as specified and directed.
Supply only impeller bush for 700-900LPM submersible pump complete all as specified and directed.
Supply only impeller locknut for 700-900LPM submersible pump complete all as specified and directed.
Supply only stainless steel shaft for 700-900LPM submersible pump complete all as specified and directed.
Supply only of Coupling set including key and MS nut bolt suitable for submersible pump sets, complete all as specified and directed.
Supply and fixing/laying in replacement cable submersible PVC insulated water proof with copper conductor cable 3x16sqmm ,1100 volt grade after taking out old unserviceable cable confirming to IS complete all as specified and directed by Engineer-in-charge.
Supply only sodium Hypo chlorite( NaOCL) chemical solution conforming to IS-1673/86 having chloride content 10 % by weight (bleach liquid solution) complete all as specified and directed by Engineer-in Charge. Note : Chemical solution shall be supplied by the contractor as on requirement basis through out the currency of the contract .Therefore the contractor shall procure the chemical solution in piecemeal as per requirement .. Contractor shall also arrange independent testing of chemical from Govt authorized laboratory at his own expense. The cost of testing shall be deemed to be included in the quoted rate. Payment of supply of Sodium chlorite solution shall only be made on production of test report.
Supply and fix in repair electronic metering dozing pump with following technical specification, complete all as specified :- Item : Dosing Pump Capacity (lph) : 0 – 6 Back Pressure (kg/cm2) : not less than 5.5 Drive : Solenoid Capacity adjustment :- 1. Adjustable stroke frequency between 0 to 100 strokes/min 2. Adjustable stroke length between 0 to 100% MOC of wetted parts : PP MOC of diaphragm : PTFE coated EPDM Power (W) : 30 Power supply : Single phase 230V, 50 Hz Accessories : Foot Valve, Injection Fitting and 3 mtrs Hose pipe Make : Toshcon Jesco /Unichlor or equivalent in Appx `B'
Taking out/down old GI pipe 15mm dia bore with fittings, laid in trenches, under floors or on roof, along walls etc, stacking serviceable and removal of unserviceable pipe, complete all as specified and directed. Note : Excavation & earthwork shall be measured and paid separately.
All as per item No 2.17 but GI pipe 20mm bore complete all as specified and directed by Engineer-in-charge.
All as per item No 2.17 but GI pipe 25mm bore complete all as specified and directed by Engineer-in-charge.
All as per item No 2.17 but GI pipe 40mm bore complete all as specified and directed by Engineer-in-charge.
All as per item No 2.17 but GI pipe 50mm bore complete all as specified and directed by Engineer-in-charge.
Supply and laying GI pipe medium grade 15mm dia with all fittings laid in trenches/fixed along with walls or laid under floors, complete all as specified and directed. Note :- Excavation & earthwork shall be measured and paid separately.
All as per item No 2.22 but GI pipe 20mm bore, complete all as specified and directed .
All as per item No. 2.22 but GI pipe 25mm bore, complete all as specified and directed .
All as per item No 2.22 but GI pipe 40mm bore, complete all as specified and directed .
All as per item No 2.22 but GI pipe 50mm bore, complete all as specified and directed .
Supply and fix, Gun Metal gate valve with iron wheel head, screwed both ends for 15mm dia bore pipe, including taking down old and removal, complete all as specified and directed.
All as per item No 2.27 but Gun metal gate valve 20mm bore complete all as specified and directed .
All as per item No 2.27 but Gun metal gate valve 25mm bore complete all as specified and directed .
All as per item No 2.27 but Gun metal gate valve 40mm bore complete all as specified and directed .
All as per item No 2.27 but Gun metal gate valve 50mm bore complete all as specified and directed .
Supply and fix, cast iron sluice valve for 150mm dia bore pipe, with flanged and drilled ends, any pattern, heavy duty, class PN 1.6, ISI marked & of specified make, Cast iron wheel, including joints and jointing materials as rubber washers/gaskets, bolts and nuts, etc, also taking down old and removal, complete all as specified and directed.
Supply and fix, cast iron sluice valve for 200mm dia bore pipe, with flanged and drilled ends, any pattern, heavy duty, class PN 1.6, ISI marked & of specified make, Cast iron wheel, including joints and jointing materials as rubber washers/gaskets, bolts and nuts, etc, also taking down old and removal, complete all as specified and directed.
Material and labour, run lead joint for 80mm dia bore CI pipe and fittings, complete all as specified and directed.
Material and labour, run lead joint for 100mm dia bore CI pipe and fittings, complete all as specified and directed.
Material and labour, run lead joint for 150mm dia bore CI pipe and fittings, complete all as specified and directed.
Material and labour, run lead joint for 200mm dia bore CI pipe and fittings, complete all as specified and directed.
Material and labour for construction of brick masonry valve pit in CM 1:4 of size 120cmx120cmx120cm (internal dimension), PCC 1:5:10 as in foundation 50mm thick, 15mm thick cement plaster in CM 1:4 internally including exposed surfaces externally and pointing flush in cement mortar 1:2 as the work proceeds externally, angle iron frame of size 40mm x 40mm x 6mm embedded in 50mm thick coping as in PCC 1:2:4, MS sheet cover 3mm thick and locking arrangements with MS handle made out of 12mm dia bar, duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, including dismantling of old valve pit and removal of retrieved material outside MoD land, complete all as specified and directed.
All as per item No 2.38 but of size 105x105x105mm complete all as specified and directed.
Draining out water completely from RCC over head Reservoir of capacity 50000 gallons in two parts at 60 feet staging and material and labour for desludging of RCC over head reservoir manually ,cleaning the inner portion of RCC tank by brooming with fine brush ,removing complete silt,sludge,vegetations unwanted foreign materials etc manually under artificial pressure from the tank, filling of cracks with pidilite /Dr fixit non shrink compound suitable to potable water to make tank leak proof. Plastering in CM 1:4, 15mm thick to the internal & external surfaces of the damaged portions of the reservoir and staging and applying two coats of cement base paint to the external surface of the reservoir and staging. Painting with black synthetic enamel paint to the all CI pipe line and other MS work etc fitted with the RCC OH reservoir and staging including making a block in Synthetic enamel paint 1mtr in height black base and writing in 50mmx50mm size letters with white synthetic enamel paint, DATE OF TANK CLEANING complete all as specified and as directed.
Excavation & earth work in any type soil for locating the leakage in existing cast iron water mains any type/size 80mm bore (including all fittings) and rectifying the leakage complete all as specified and directed. Note: Any CI fittings/specials, joint & jointing material etc required for the rectification of leakage shall be measured & paid for separately.
All as per Serial Item No. 2.41 here-in-before but CI pipe of 100mm bore complete all as specified and directed.
All as per Serial Item No 2.41 here-in-before but CI pipe of 150/200mm bore complete all as specified and directed.
All as per Serial Item No 2.41 here-in-before but GI pipe up to 25mm bore complete all as specified and directed. Note - Cost of all GI fittings/special required deemed to be included in the rate quoted and nothing extra shall be admissible on this account.
All as per Serial Item No 2.41 here-in-before but GI pipe up to 40/50mm bore complete all as specified and directed.
All as per Serial Item No 2.41 here-in-before but GI pipe up to 80/100mm bore complete all as specified and directed.
Collection of the water sample from the borewell duly sealed by the Engineer- in - Charge, carrying to the PHE UT Chandigarh/ Govt lab for testing, depositing it and collecting the test report from the lab & deposited with the department complete all as specified and directed.
Supply and fix fully automatic star - Delta Starter suitable for 40 HP Submersible motor 415 volts 50 HZ AC including over load relay, range and power contactor, single phase preventer with volt meter and ammeter and MCB TP etc complete all accessories pre-wired /connected with suitable size copper conductor. complete all as specified and directed.
DG Set Repairs
Maintenance of DG set of any make, type, model as per set norms of the original manufacturer set and by the authorised rep of the company after unscrewing nut, bolts, screws etc. for servicing, maintenance, tigthtening, adjustment & cleaning of all moving and stationary parts of DG set, complete and segregating the parts for repair/ refixing/ replacing of capacity 15KVA , complete all as specified and directed. Make of DG sets :- kirloskar/Crompton Greaves/Ruston/Ashok Leyland Note: The quoted rate includes the following: (a) Taking down of unserviceable parts. (b) Any minor repair, replacement of minor parts such as screws, gasket, nuts, bolts, washers, cleaning & greasing etc. of DG set parts. (c) Defective parts/ engine oil to be replaced will be measured & paid separately under supply only item as apended below.
All as per Serial Item No. 3.01 here-in-before but capacity 30 KVA
All as per Serial Item No.3.01here-in-before but capacity 40 KVA
All as per Serial Item No. 3.01 here-in-before but capacity 63 KVA
Supply only under mentioned spare/parts suitable for the DG set complete all as specified and directed:-
Primary fuel filter element for DG set capacity 15KVA
Primary fuel filter element for DG set capacity 30KVA
Primary fuel filter element for DG set capacity 40KVA
Primary fuel filter element for DG set capacity 63KVA
Secondry fuel filter element for DG set capacity 15KVA
Secondry fuel filter element for DG set capacity 30KVA
Secondry fuel filter element for DG set capacity 40KVA
Secondry fuel filter element for DG set capacity 63KVA
Air filter element for DG set capacity 15KVA
Air filter element for DG set capacity 30KVA
Air filter element for DG set capacity 40KVA
Air filter element for DG set capacity 63KVA
Oil filter element for DG set capacity 15KVA
Oil filter element for DG set capacity 30KVA
Oil filter element for DG set capacity 40KVA
Oil filter element for DG set capacity 63KVA
Fuel line complete for DG set capacity 15KVA
Fuel line complete for DG set capacity 30KVA
Fuel line complete for DG set capacity 40KVA
Fuel line complete for DG set capacity 63KVA
Material and labour for taking out radiator and repairing/brazing to make it leakage free, cleaning and re-fixing the radiator including testing for DG set capacity 15KVA to 40KVA, complete all as specified and directed.
All as per item No. 136 here-in-before but DG set capacity 63KVA complete all as specified and directed.
Supply only lubricant oil (Engine oil) SAE30 (Make as recommended by the manufacturer of DG set and as approved)
Supply, install, connecting and testing in replacement maintenance free batteries, 12 Volts, 180AH, complete all as specified and directed.
Supply, install, connecting and testing in replacement maintenance free batteries, 12 Volts, 92AH, complete all as specified and directed.
Supply and fix, battery lead not less than 1.5mtr long, made out of 50Sqmm copper cable with terminal of brass with marking (+)/(-) and fixing in position and testing, including taking down and removal, complete all as specified and directed.
Supply and filling, engine coolant in radiators of DG sets as per DG set manufacturer's recommendations at different locations, brought at site in sealed packets, complete all as specified and directed.
Maintenance, repair, servicing and calibration of automatic mains failure panel, DC & 415/440 volt AC supply operated system by locating faults and replacement of unserviceable parts and components for DG set 10KVA to 400KVA and testing on completion , complete all as specified and directed. Make of DG sets:- Kirloskar/Crompton Greaves/Ruston/Ashok Leyland Note: The quoted rate includes the following: (a) Taking down of unserviceable parts. (b) Any minor repair, replacement of minor parts such as screws, gasket, nuts, bolts, washers, cleaning & greasing etc. of DG set parts. (c) Defective parts/ engine oil to be replaced will be measured & paid separately under supply only
Repair of faulty worn out control wiring DC/AC for engine starting and off, with adequate and suitable size copper conductor wire, connected with proper copper lugs & terminals through protection pipe/casing, complete all as specified and directed.
Repair of worn out/faulty internal wiring of controls and timers, indicating/measuring instruments through various control fuses and relays with suitable and adequate size of copper conductor wire, connected with suitable copper lugs and terminals, complete all as specified and directed.
Replacement of worn out small control fuses, indicating lamps, various type of copper lugs, thimbles terminals all as deemed necessary or directed including minor spare parts and components in order to make system serviceable and perfectly in working order , complete all as specified and directed.
M & L for repairing battery charging dynoma including replacing worn out/unserviciable spares up to the capacity of 63 KVA all as specified and directed by Engineer in charge
M & L for repairing self starfer including replacing worn out/unserviciable spares up to the capacity of 63 KVA all as specified and directed by Engineer in charge
M & L for replacing the unserviciable AVR of DG sets up to the capacity of 63KVA and testing complete all as specified and directed by Engineer in charge
M & L repairs to unserviceable street/security lights fittings of LED, of any wattage and size by taking down from poles/buildings after disconnecting the electric connection, replace the unserviceable drive ,PVC connector etc, cleaninng, refixing the light fittings at its original position after rectifying the defects and connecting to street light feeder including testing complete all as specified and directed. Note :- (i) Replacement of parts like drive , will be measured and paid seperatily as supply only (ii) The cost of labour ,tools and minor spares required for replacement of parts shall deem to include in the unit rate quoted by the contractor.
Taking down the existing light fittings multi mounting brackets from High Mast Pole/Structure (12 mtrs High) for repairs/replacing the defective parts and refixing the same in original position after carrying out necessary repair/replacement of parts i.e. unserviciable ignitor, ballast, capacitor from control gear box , complete all as specified and directed.
PVC insulated stranded aluminium conductor, 1100 volts grade heavy duty cable of size 2.5Sqmm 2 core (from junction box to street light fitting mounted on steel tubular/PCC pole) including taking down existing unserviceable cable, complete all as specified and directed.
Supply and fixing electronic drive suitable for LED street light /Flood light of capcity up to 90W all as specified and and directed by Engineer in charge
Supply and fix in replacement of LED street light fitting 60W AC 230V 50 Hz powder coated pressure die cast alluminum housing power LED with heat resistant toughned glass IP 66 complete all as specified and diredted by Engineer in charge
Supply and fixing LED flood light luminare 150Watts comprising of single piece pressure die cast aluminium alloy housing powder coated with clear acrylic bowl, complete prewired fixed to pole/wall bracket and connected with flexible copper conductor cable
Supply and fixing LED post to latern 15Watts comprising of single piece pressure die cast aluminium alloy housing powder coated cone round milkey post top ,complete prewired fixed to pole/wall bracket and connected with flexible copper conductor cable of size 1Sqmm three core suitable length, including taking down old fitting, complete all as specified and directed.
S & F in replacement of 200x160x98mm PVC junction box having IP 65 protection with metric knockouts for 16/25 sqmm cable entry with terminalals /bus bar 4 pole including provn of one MCB 6 Amps complete all as specified incl Make Sintex/Hensel
Air Conditioning
Material and labour for servicing to Split type AC operated on 240 volts single phase AC electric supply of any make/type capacity 1.5/2.0 Ton, both internal / external units of AC, dry cleaning with blower / vacuum cleaner, washing with soap solution and cleaning with water pressure through jet, making it fully serviceable , complete all as specified and as directed by Engineer-in-Charge.
All as per item no 4.01 here in before but for window type AC unit of any make/model and capacity complete all as specified and directed by Engineer in charge
Supply & fixing sealed Compressor operated on "R-22 refrigerant" Company replaced only, suitable for split / window type AC 1.5 Ton capacity of existing make and model duly filled of gas, compressor oil including taking out old US compressor complete all as specified and as directed by Engineer-in-Charge.
Supply & fixing the following spares/parts for split /window type AC unit including taking out old /US spares/parts complete all as specified and as directed:-
Copper tube 1/2 inch bore including necessary insulation.
Copper tube 1/4 inch bore including necessary insulation.
Copper tube 5/8 inch bore including necessary insulation.
Copper tube 3/8 inch bore including necessary insulation.
Blade only for blower outdoor motor split unit any type.
Starting Capacitor 80-100MFD any capacity Make:Epcos/Usha/Tesla
Starting Capacitor 100-120MFD any capacity Make:Epcos/Usha/Tesla
Running Capacitor 36MFD any capacity Make:Epcos/Usha/Tesla
Running Capacitor 45MFD any capacity Make:Epcos/Usha/Tesla
Running Capacitor 50MFD any capacity Make:Epcos/Usha/Tesla
Blower motor for outdoor unit. Make:AUE/Cool Home/Universal
Blower motor for indoor unit. Make:AUE/Cool Home/Universal
Remote Control system complete including PC Cards /Circuits.
Capacitor 4MFD 230Volts. Make:Epcos/Usha/Tesla
PCB Cards of indoor unit
Material and labour for Internal wiring for split unit of any capacity with single core copper conductor FRLS cable as per existing size only complete all as specified and as directed by Engineer-in-Charge.
M&L for repairing the leaking area and recharging refrigerant gas R-22 in Split type AC’s/Window AC/water cooler /deep freezer/refrigerator all as directed by Engineer-in-Charge.
Supply and fixing in repair sealed Compressor suitable for Water Cooler 40/80Ltrs capacity of existing make and model duly filled of gas, compressor oil including taking out old/US compressor complete all as specified and as directed by Engineer-in-Charge
All as per item No 4.22 here in - before but for Water Cooler 150Ltrs capacity complete all as specified and as directed by Engineer-in-Charge.
All as per item No 4.22 here in - before but for Refrigerator 165 to 180Ltrs capacity complete all as specified and as directed by Engineer-in-Charge.
S&F in repairs the following items of existing make and model suitable for refrigerator 165/320 capacity including taking out old /US spares / parts complete all as specified and as directed by Engineer-in-Charge:-
Starting Relay Box 165 - 180Ltrs. capacity. Make:Renutral/Indfoss/Denfoss
Overload Protection Box 165 - 180Ltrs. capacity. Make:Renutral/Indfoss/Denfoss
Steel Shelves PVC coated 300-320Ltrs. capacity Make:Renutral/Indfoss/Denfoss
Starting Relay Box 300 - 320Ltrs. capacity.
Overload Protection Box 300 - 320Ltrs. capacity.
Running Capacitor 10MFD 230volts.
Thermostat switch any capacity.
S&F in repairs the following items of existing make and model suitable for water cooler of any capacity including taking out old /US spares / parts complete all as specified and as directed by Engineer-in-Charge:-
Condensor motor only
Push Cock CP 15mm.
Magnetic Rubber gasket for top cover any capacity.
PVC Drain pipe 32mm bore not less than 1mtr in length.
Internal wiring of refrigerator/deep freezer/water cooler etc of any capacity
Cleaning of water storage tank, detection of water leakage, brazing / welding to restore the leakage, scraping old paint, completely and painted with 2 coat of synthetic enamel paint over a coat of red oxide primer after filling the cavities of MS Sheet with filler to external surface complete all as specified and as directed by Engineer-in-Charge.
S&F in repairs the following items of existing make and model suitable for desert cooler of any capacity including taking out old /US spares / parts complete all as specified and as directed by Engineer-in-Charge:-
Fan motor 350Watts 230Volts 3Speed copper winding single phase complete. Make: KHAITAN/Crompton/Universal
Submersible type Tulu pump 230Volts single phase 1750LPH at 1.5 mtr head complete Make : KHAITAN/Crompton/Universal
Fan blade only
Front grill of M S /PVC complete with slides operation and indicator lamps.
Wood wool pad set of three of best quality including fixed wth bamboo stick any size.
PVC pipe heavy duty 15mm bore ISI Marked.
PVC Distribution Tee, Elbows and other minor items (heavy duty) 15mm bore ISI Marked.E101
Internal wiring of desert cooler of any capacity as per existing specifications
Taking down to desert cooler of any make/capacity carefully without damaging, scraping old paint, completely and painted with 2 coats of synthetic enamel paint over a coat of red oxide primer after filling the cavities of MS Sheet with filler to external surface and inner surface of bottom & sides painted with 2 - coat of black Japan paint completed all as specified and as directed by Engineer-in-Charge. Note : Taking down and re-fixing in the same position after painting work shall be deemed to include in the unit rate of this item.
Supply only PVC insulated, sheathed 3 core flexible cable of size 1.5Sqmm all as directed.
All as Srl item No.4.51 above but of size 4 Sqmm, complete all as specified and directed.
Supply,and fix in replacement of voltage stabilizers for automatic operation three phase naturally air cooled indoor type & designed for input variation between 140 to 250 V with output voltage stabilized at 230 Volts with accuracy +/- 2.05% and speed of correction 8 Volts per second and of capacity 5KVA. including taking down/ out old/ unserviceable voltage stabilizer complete all as specified and directed. Make : Carrier/Blue Bird/ V Guard
Taking up / down water heater (Geyser) of capacity 50/35/25 ltrs operating on 230 volts AC electric supply, in any position and of any make, after disconnecting all electric connection and hot and cold water connection, and including transportation to the contractor 's workshop/at site for repair and vice - versa, , general cleaning/overhauling, cleaning and discaling the tank and assembly with suitable detergent and making fully serviceable and fixing back in same location / position or new location all as directed. Note :- (a) Repairing of any parts except the work mentioned in item will be maasured and paid seperatelly. (b) Replacement of any un serviceable parts required for making the geyser serviceable will be measured and paid seperatelly under "supply only" No extra payment will be allowed for replacing these items, as the same is deemed to be included in relevant item
Supply only Stainless steel inner tank suitable for 25 ltrs Geyser of any make / shape /holes for fixing geyser assembly.
All as per item No 4.55 herein before but for 35 ltrs.
All as per item No 4.55 herein before but for 50 ltrs.
Supply only bottom base assembly of copper 9/8 holes type suitable for 35/25 ltrs capacity geyser all as directed.
All as per item No 4.58 here-in- before but for 50 ltrs capacity geyser .
Supply only heating element 1000/1500/2000 watts capacity of any shape /type with rubber gasket . Make :- Ditz, Dass pass
Supply only Thermostat suitable to adjust the temperature from 0º C to 80º C all as directed. Make :- Ditz, Dass Pass
Supply only Neon indicator lamp of any shape / size / colour all as directed.
Supply only PVC insulated, sheathed 3 core flexible cable of size 2.5Sqmm all as directed.
Supply only Safety plug any type.
Supply & fixing non return valve 15mm bore cast copper alloy suitablwe for geyser complete all as specified and as direceted
Supply only Rubber gasket of thickness 5 mm for geyser assembly of 08 holes / 09 holes all as specified.
Supply only Bottom inspection cover plate in two pieces with suitable openings for indicator lamps, power cable entry with rubber washer etc, gauge of plate not less than 18 SWG for 25/35/50 Ltrs capacity geysers of any make/ shape all as directed.
Supply anly 3 pin plug top 15 Amps, bakelite suitable for 230/240 volts AC supply all as directed.
Supply only Outer MS sheet complete including top and bottom suitable for 25 Ltrs capacity geyser of any make, shape & size as per existing but gauge of sheet not less than 22 SWG all as directed.
Supply only CP connection 15mm bore 450mm long in any position with both end brass nut with inner thereading and washer suitable for cold water connection complete all as directed .
M/L for spray painting of geyser outer body of any make / size by applying one coat of synthetic enamel white paint over the existing paint including cleaning and preparation of surfac complete all as specified
S & F Switch piano, flush type, single pole, one way, 15 Amp 230volts complete all as specified.
S & F Socket outlet multipurpose 3 pin 5 Amp & 15 Amp, flush type, complete all as specified.
Note:- Amount of credit of Rs 58497.00 for retrieved materials is mentioned in Schedule of Credit Page No 102 of tender documents in pdf form which will be deducted offline while acceptance of tender.
M/s Shiksha Enterprises
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .