| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.8 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹32.6 L+₹1.2 L (3.78%)Rejected-Finance 307 SADAR BAZAR LUCKNOW UP 226002 | LUCKNOW | UTTAR PRADESH | 226002 | L2 | Rejected-Finance Being L2 | |
| 3 | L3₹33.4 L+₹2.0 L (6.37%)Rejected-Finance | L3 | Rejected-Finance Being L3 | |
| 4 | L4₹35.3 L+₹3.9 L (12.4%)Rejected-Finance | L4 | Rejected-Finance Being L4 | |
| 5 | L5₹38.8 L+₹7.4 L (23.5%)Rejected-Finance | L5 | Rejected-Finance Being L5 |
Tender Value
₹41 L
EMD Value
₹82,000
Closing Date
22 Jul 2023, 6:00 pmClosed
GE E/M Lucknow
Garrison Engineer E/M, 36 LBS Marg, Lucknow Cantt, Lucknow (U.P.) PIN 226002
REPAIR/MAINT OF LT PANEL INCL LT SWITCH GEAR, EARTHING, TIMER PANEL, LT POLES, POLE BOX, STREET LIGHTS, FLOOD LIGHTS, AREA LIGHTS, LT DISTR NETWORK AND CONNECTED ITEMS AT HQ CC, HQ MUPSA, KB ROAD, THIMMAYA MARG, HM MARG UNDER GE E/M LUCKNOW
2023_MES_591242_2
GE/EM/LKO/EXT(ELECT)/T-06 OF 2023-2024
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Lucknow
As per NIT
8 documents required · 8 mandatory
₹500
GE E/M Lucknow
₹82,000
Yes
18 Aug 2023
3 Jul 2023
24 Jul 2023
3 Jul 2023
22 Jul 2023
10 Jul 2023
Amount
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft/loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom suface to required level complete all as specified and directed.
Returning filling in including spreading, levelling, Watering and well ramming soil in layers not exceeding 25 cm thick complete all as specified and directed.
Removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point complete all as specified and directed.
Sand cushioning for protection of cable complete all as specified and directed. (Note :- Local approved tibba dry sand after removal of vegetations; grass and other deleterious substances shall be used for sand cushioning).
M&L laying well burnt brick work with fly ash bricks as per IS 12894 -2002, straight or curved on plan , laid flat with width equal to length of brick , laid dry over electric cable for protection complete all as specified and directed.
All as per item No 5 above but using old bricks obtained under srl item No 1 here in before.
M&L for demolition /cutting of road/ path/hardstading/ concrete in floor, etc for laying of cable complete all as specified and directed.
Material and labour for PCC 1:2:4 type B-2 using 40 mm graded stone aggregates for filling of cutting of roads/path/hardstanding etc complete all as specified and directed.
Boring of hole under road/pavement/hard standing or any other situation by manual means and suitable for passing of GI pipe 40 to 100 mm bore and making good both ends complete all as specified and directed.
S&F in replacement GI Pipe (light grade) with necessary accessories/ fittings for cable protections/pole for crossing of culverts/nallah of 80 mm bore, complete all as specified and directed.
All as per item No 10 above but 50mm bore
All as per item No 10 above but 40 mm bore
Material & Laying, jointing and testing in replacement of LT under ground electric power cable crossed linked polyethylene ( XLPE) insulated, galvanised steel strip or wire armoured, ISI-7098 Marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of size 10 sqmm cross sectional area, 2 core ,complete all as specified laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts , bolts, washers complete all as specified and directed. Note :- Excavation, earth work, sand cushioning, protection bricks/ tiles/ block and pipe shall be measured and paid separately under appropriate items.
All as per item No 13 above but of size 16 Sqmm 2 core
All as per item No 13 above but of size 16 Sqmm 4 core
All as per item No 13 above but of size 25 Sqmm 4 core
All as per item No 13 above but of size 35 Sqmm 3.5 core
All as per item No 13 above but of size 50 Sqmm 3.5 core
All as per item No 13 above but of size 70 Sqmm 3.5 core
All as per item No 13 above but of size 95 Sqmm 3.5 core
All as per item No 13 above but of size 120 Sqmm 3.5 core
All as per item No 13 above but of size 185 Sqmm 3.5 core
All as per item No 13 above but of size 240 Sqmm 3.5 core
M&L Earthing in replacement complete with galvanised steel earth plate electrode 60cmx60cmx6.0mm thick, burried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using GI strip 32 x 6 mm as earth strip electrode bolted or rivetted to earth plate at one end and connected to equipments at another end, GI earth strip encased in and including 40 mm dia GI 'light grade' pipe from upper end of earth plate upto equipments,20 dia bore GI pipe 'light grade' as water pipe from earth chamber to upper edge of earth plate, Test point , GI funnel with wire mesh fixed on water pipe and PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1, duly reinforced with MS TMT bars 8mm dia @ 100 c/c both ways with 10mm dia MS round bar as in lifting handles, excavation, earth work including laying the GI pipe concealed in floor/wall all as described in electric plate of SSR Part I complete all as specified and directed and testing on completion. Note :- If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department.
Earthing in replacement complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by mean of GI wire 4 mm dia by means of bolts, nuts check nuts and washers of GI or steel and connecting to earthing test point, main switch board, testing on completion including PCC cover and frame, PCC (1:3:6) type C-2 as in earthing pit, MS funnel with wire mesh GI pipe 20 mm dia light grade for watering and GI pipe 15 mm dia light grade for the protection of GI wire from earth pit to earth point complete including necessary excavation and earth work in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance n.exc 50 m all as specified as shown in electrical plate No 5 SSR Part-I. PCC chamber shall be constructed at least one metre away from the earth pit and GI pipe fittings for watering shall be provided up to chamber and cost of the same is deemed to be included in the rate of earthing, complete all as specified and directed. Note :- If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department.
Disconnecting the existing cable from Panel / Pole, preparing the end for jointing including all earth work, Supply and fixing Cable end termination heat shrinkable joint including sleeves suitable for LT XLPE cable of size 3.5/4 core 10 to 16 Sqmm, complete all as specified and directed.
All as per item No 26 above but size 25 to 50 Sqmm
All as per item No 26 above but size 70 to 120 Sqmm
All as per item No 26 above but size 150 to 185 Sqmm
All as per item No 26 above but size 240 to 300 sqmm
Disconnecting the existing cable from Panel / Pole, preparing the end for jointing including all earth work, Supply and fixing straight through heat shrinkable joint suitable for LT XLPE cable of size 3.5/4 core 10 to 16 sq mm, complete all as specified and directed.
All as per item No 31 above but size 25 to 50 Sqmm
All as per item No 31 above but size 70 to 120 Sqmm
All as per item No 31 above but size 150 to 185 Sqmm
All as per item No 31 above but size 240 to 300 sqmm
Supply & Fixing in replacement twin core, 6 sqmm nominal cross sectional area multistranded aluminium conductor cable, over all PVC sheathed, 1100 Volts grade heavy duty cable PVC insulated and PVC sheathed complete all as specified and directed.
Supply & Fixing in replacement twin core, 10 sqmm nominal cross sectional area multistranded aluminium conductor cable, over all PVC sheathed, 1100 Volts grade heavy duty cable PVC insulated and PVC sheathed complete all as specified and directed.
Supply, fixing, connecting and testing in replacement MCCB 63 Amp 4 pole 25 KA 415 volts 50 Hz thermal magnetic release with spreader after taking down old existing unserviceable MCCB complete all as specified and directed.
Supply, fixing, connecting and testing in replacement MCCB 100 Amp 4 pole 25 KA 415 volts 50 Hz thermal magnetic release with spreader thermal magnetic release after taking down old existing unserviceable MCCB complete all as specified and directed.
Supply, fixing, connecting and testing in replacement MCCB 125 Amp 4 pole 25 KA 415 volts 50 Hz thermal magnetic release with spreader after taking down old existing unserviceable MCCB complete all as specified and directed.
Supply, fixing, connecting and testing in replacement MCCB 160 Amp 4 pole 25 KA 415 volts 50 Hz thermal magnetic release with spreader after taking down old existing unserviceable MCCB complete all as specified and directed.
Supply, fixing, connecting and testing in replacement MCCB 200 Amp 4 pole 36 KA 415 volts 50 Hz thermal magnetic release with spreader after taking down old existing unserviceable MCCB complete all as specified and directed.
Supply, fixing, connecting and testing in replacement MCCB 250 Amp 4 pole 36 KA 415 volts 50 Hz thermal magnetic release with spreader after taking down old existing unserviceable MCCB complete all as specified and directed.
Supply, fixing, connecting and testing in replacement MCCB 400 Amp 4 pole 36 KA 415 volts 50 Hz thermal magnetic release with spreader after taking down old existing unserviceable MCCB complete all as specified and directed.
Supply, fixing, connecting and testing in replacement MCCB 630 Amp 4 pole 50KA 415 volts 50 Hz thermal magnetic release with spreader after taking down old existing unserviceable MCCB complete all as specified and directed.
S&F in replacement on load change over switch open execution of capacity 400 Amps , 4 pole , 415 volt , 50 Hz fixed in any type of existing LT panel/Feeder piller including taking out old existing unserviceable change over from panels etc complete all as specified and directed.
S&F in replacement on load change over switch open execution of capacity 250 Amps , 4 pole , 415 volt , 50 Hz fixed in any type of existing LT panel/Feeder piller including taking out old existing unserviceable change over from panels etc complete all as specified and directed.
Supply and fixing in replacement MCCB FP 125 Amps, 25 kA, 415 Volt AC, 50 Hz, complete with sheet metal enclosure of 1.6 mm thick MS sheet factory made with powder coat paint including connecting with existing system with existing cablling network including making good disturbed surfaces complete all as specified and directed. Note : The cost of suitable size fastner/Nut bolts required at site for fixing of cubical is deemed to be included in the quoted rate by the contractor.
Supply and fixing in replacement double pole sheet metal enclosure made of 1.6 mm thick MS sheet factory made with powder coat painting including 01x MCB 20 Amps 10 kA complete all as specified and directed. Note : The cost of suitable size clamp/Nut bolts required at site for fixing of enclosure on garden light post/wall is deemed to be included in the quoted rate by the contractor.
Supply drawing, connecting and testing in replacement 3 core, 1.5 Sqmm PVC insulated and PVC round sheathed` copper conductor (flexible ) industurial cable, 1100 Volts conforming to IS 694 in steel tubular poles from Junction box to street light fitting including providing suitable copper lugs complete all as specified and directed.
S&F in replacement wheather proof pole mounting PVC junction box, base and door of junction box made out of SMC having outside dimention 333x233x120mm, inside dimention 300x200x105mm , single door front openable provided with hinged cover and locking arrangements with 4 Nos aluminium bas bar 63 Amps, mounted on porcelin insulator including M&L for MCB SP 10 Amp -1No, fixed on box in Din rail complete with electrical connection fixed to pole with suitable size FI clamp nut bolts and washer including embossing/painting of danger notice of size not less than 10cm x 7.5cm with letters, figures and conventional skull and bones in signal red colour on front face of junction box body complete all as specified and directed.
Supply & fixing in replacement GI brackets made of 40 mm nominal bore GI pipe medium grade of required length not less than 1.5 M long, mounting brackets made out of Mild steel FI 40x6 mm of required shape ( two Nos) duly fitted with Mild steel nuts, bolts and washers and painting with two coats of synthetic enamelled paint over one coat of red oxide Zn chrome primer and fixed to pole / walls etc complete all as specified and directed.
Supply and fixing in replacement CRCA MS sheet for LT panel having thickness 3.15 mm powder coated finish over one coat of red oxide on out side surface and painted in side with two coats of red oxide primer including all fixing acessories i.e. suitable size of hinge, nuts, bolts, washers, cutting and welding works etc complete all as specified and directed.
Supply and fixing in replacement Digital VAF+PF meter with RS 485 CL1 in LT panel including taking out old existing unserviceable meter from panels etc complete all as specified and directed.
Supply and fixing in replacement of LED indication lamp including taking down old unserviceable LED indication lamp from LT panel complete all as specified and directed.
Preparation of old painted surfaces and painting of LT steel tubular pole 9 mtrs long from bottom to top with aluminium paint and painting to bottam up to 1.5 mtr height from top of PCC coping with synthetic enamel paint 2 coats in black and Yellow/white alternate strip including numbering in 8 cm height of number with white paint both paint aluminium /synthetic duly approved by Engineer-in-Charge and complete all as specified and directed.
Cleaning the existing painted surface of LT panel by scrapping, making good distrubed surfaces by applying putties on uneven surface to make it even and M&L for spray painting to LT panel of any size with two coat of synthetic enamel paint with desired colour over one coat of red oxide primer complete all as specified and directed.
Material and labour disconnecting faulty /burnt end or portion of cable from LT panel/LT pole /main switch/changeover etc by removing the cable from loop including necessary excavation & earth work , cleaning the surface area not less than 1 mtr surrounding the panel/pole , provision of suitable size of thimble, LT tap , relaying and reconnecting the cable by removing faulty/burnt portion of cable and preparing fresh terminals for 16 Sqmm 3.5/4 core to 240 Sqmm 3.5 core of LT cable to LT Panel/pole/main switch/changeover complete all as specified and directed.
Supply and fix in replacement 15 Watt LED Post Top lanterns housing made of Die-cast aluminum spigot for mounting LED driver and spun aluminum canopy , epoxy powder coated matt black finish after phosphochromate treatment , high quality polycarbonate cover is used over LED moudule to enhance the lumen output & clear acrylic diffuser is used to provide overall glare free light , Powered by electronic integral , isolated poted electronic LED driver in ABS housing with APFC (SMPS based constanct current supply) with lower THD , output short/open circuit protection , Surge Voltage protection & other safety test as per IS 15885 Part-2/Sec-13 , IP 65 , Lumen efficiency not less than 98 lumen per watt system efficency ,power factor >0.95, THD<10% at Full load CRI> 70%, complete all as specified and directed.
All as per item No 59 above but 25 Watt LED Post Top lanterns but Lumen efficiency not less than 100 lumen per watt system efficency
Supplying and fixing in replacement 8 Watt Bamboo LED bollard fitting of 1 meter height new generation , energy saving , enviornmental friendly , long life aesthetically designed aluminium landscape IP 65 luminaire for diffused lighting with high power LED as light souce housing made up of aluminium pipe UV protected pure polyester powder coated black after phosphochromate treatment it consists of aluminum heat sink for effective thermal management , sturdiness & excellent corrosion resistant mounting flange of MS sand casting is used at bottom PC diffuser in opal finish is used for glare free uniform light distribution powered by built in , isolated , potted electronic LED driver in ABS housing with APFC (SMPS based constant current supply) with lower THD , output short/open circuit protection , over voltage protection , Surge voltage protection Lumen efficiency not less than 110 lumen per watt system efficency ,power factor >0.95, THD<10% at Full load CRI> 70%, complete all as specified and directed.
Supply, installing, testing and commissioning in replacement factory made , tested , CPRI approved powder coated LT Panel board(Dimention of Cubical/enclosure not less than 1200mmx900mmx500mm) ,cubical compartmentalized , out door type double door , plate form mounted, suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with insulated aluminium bus bars four pole installed on porcelain/SMC insulator. The panel shall be dust and vermin proof IP-54 class protection and outer shell made of of 3.15 mm CRCA MS sheet, inner shell made of 2.0 mm thick CRCA MS sheet , 50x50x6mm thick MS angle iron frame work, the cubical have bottom channel of size 75x40mm duly coated with zink metal coating,front and rear opening type, with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid, copper conductor FRLS cable, IS-694 marked, 1100 volts grade of appropriate size ( but not less than 2.5 Sqmm) and comprising of the following :- (a) Incoming :- (i) MCCB 4 pole , 400 Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release - 01 Nos (ii) On load change over switch open execution type , 400 Amps , 4 pole , 415 volt , 50 Hz-01 No (iii) Digital VAF+PF meter with RS 485 CL1 -01No (iv) CTs ratio 400/5 A ,class 1, ISI marked -01 sets of three (v) Indicating lamp- 01 set of three (vi) Four Pole , Aluminium bus bar 800 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing (i) MCCB 4 pole ,250 Amps,50 Hz,415 Volts, 36 KA thermal magnetic release - 02 Nos (ii) MCCB 4 pole ,160 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release - 02 Nos (iii) MCCB 4 pole ,125 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release - 02 Nos (iv) MCCB 4 pole ,100 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release - 03 Nos (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. Note :- (i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer
All as per item No 62 above but comprising with following:- (a) Incoming :- (i) MCCB 4 pole , 250 Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release - 01 Nos (ii) On load change over switch open execution type , 250 Amps , 4 pole , 415 volt , 50 Hz-01 No (iii) Digital VAF+PF meter with RS 485 CL1 -01No (iv) CTs ratio 250/5 A ,class 1, ISI marked -01 sets of three (v) Indicating lamp- 01 set of three (vi) Four Pole , Aluminium bus bar 500 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing (i) MCCB 4 pole , 160 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release - 01 Nos (ii) MCCB 4 pole , 125 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release - 02 Nos
All as per item No 62 above but comprising with following:- (a) Incoming :- (i) MCCB 4 pole , 250 Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release - 01 Nos (ii) On load change over switch open execution type , 250 Amps , 4 pole , 415 volt , 50 Hz-01 No (iii) Digital VAF+PF meter with RS 485 CL1 -01No (iv) CTs ratio 250/5 A ,class 1, ISI marked -01 sets of three (v) Indicating lamp- 01 set of three (vi) Four Pole , Aluminium bus bar 500 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing (i) MCCB 4 pole , 125 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release - 02 Nos (ii) MCCB 4 pole , 63 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release - 05 Nos
All as per item No 62 above but comprising with following:- (a) Incoming :- (i) MCCB 4 pole , 400 Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release - 01 Nos (ii) Digital VAF+PF meter with RS 485 CL1 -01No (iii) CTs ratio 250/5 A ,class 1, ISI marked -01 sets of three (iv) Indicating lamp- 01 set of three (v) Four Pole , Aluminium bus bar 800 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing (i) MCCB 4 pole , 200 Amps,50 Hz,415 Volts, 36 KA thermal magnetic release - 01 Nos (ii) MCCB 4 pole , 160 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release - 01 Nos (iii) MCCB 4 pole ,125 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release - 01 Nos (iv) MCCB 4 pole ,100 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release - 04 Nos
Supply and errection in replacement 07 mtr continuously tapered hot dip galvanised Octagonal cross sectional pole with single dipping method having bottom 130 mm A/F and top 70 mm A/F 3 mm thick confirming to ASTM A 572 Gr with yield 450 mpa cut and folded to form an octagonal section and welded in accordance with AWS for wind loading as per IS 875 part 3 1987.Poles shall be provided with base plate of size 225x225x12 mm which shall be free from any lamination or incursion with no cutting or welding on the pole after hot dip galvanising with single arm 1000 mm long bracket tilted to 150 degree from horizontal toward vertices suitable for mounting on the octagonal pole, of company recommendation and one no TPN Connecton 3 phase 4 wire 100 Amps, and one number MCB SP 6 Amps. A triangular flat MS plat of 6mm thick duly coated with GI shall be welded between cap of the octagonal pole and bracket. Welding work shall be done 250mm on bracket and 150 mm on pole's cap including all RCC work type (1:2:4) type B-1 including 04 Nos foundation nut bolt and plate as per pole manufacturer's drawing and earth work all as per requirement complete all as specified and directed. Note Cost of construction of RCC foundation including construction material, necessary earth work and excavaton as per manufacturer design for above pole complete all as required at site and as directed by Engr-in-charge are deemed to be included in the quoted rate.
Supply & fixing in replacement automatic street light timer panel 12 KW /40 Amp switch using Infrared Sensor based for automatic switching of street lights based on LUX level of natural light. Required illuminance for switching ON is < 30 Lux and for switching OFF > 10 Lux level. The sensor (nature switch) alongwith suitable power contactors, Input (supply) MCB and output (load) MCB(s), support terminals should be enclosed in pole/ wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR graded SMC junction box conforming to IP-54 degree of ingress three phase 8 KW lightening load capacity including mounting bracket, cable glands, openable doors with lock complete all as specified and directed.
Disconnecting faulty 1.1 KV LT cables of any size and any length from both ends Hiring of cable fault detector machine to detect exact position of fault , removal of Fault, Re-connections and testing of cables after removal of fault including excavation, returung filling, Removal, relaying of cable protection cover etc complete all as specified and directed. Note : (a) 1.1 KV LT cable & joints shall be measured and paid for seperately under respective items of schedule. (b) Contractor or his rep shall come to the site of breakdown within one hour of notification of breakdown alongwith fault locating machine and manpower. In case the rep or contractor shall not come to the site of breakdown and not to start attending breakdown within 1.00 hour a penalty of Rs 1000 per fault per hour will be imposed over contractor and will be deduct from his dues.
Taking out faulty underground 1100 Volt LT cable of different sizes by excavation and removing bricks of any size and relaying in the same trenches or re routing after rectification of fault or replacing faulty portion of cable with new cable and removing of surplus soil and using new bricks as required. Note: (a) 1100 Volt LT cable & joints shall be measured and paid for seperately under respective items of schedule. (b) Retrieved old serviceable bricks will be laid in trenches for cable protection. If extra bricks and sand required at site shall be measured and paid separately under respective items of BOQs. (c) Excavation and earth work will be measured and paid for seperately under respective items of schedule.
Supply and fixing in replacement 60 W LED street light fitting with mandatory driver set having pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embaded PC cover /IP lens, street light should have IP 66 protection, impact resistance of IK 07 , Lumen efficiency of LED not less than 110 lumen per watt system efficency ,power factor >0.95, THD<10% at Full load CRI> 70% ,street light should have built in potted electronic LED driver with , lower THD, open circuit protection , over voltage protection , surge voltage protection , and provided with company LOGO ingraved on housing of the street light complete including taking down of old UNSV fittings complete all as specified and directed. Note :-The contractor should take approval of techincal specification of luminaries and driver from department before procurement .
All as per item No 70 above but 90 Watt
Supply and fixing in replacement of 200 W LED flood fitting having epoxy powder coated die cast aluminium housing ADC12 in grey finish with elegantly designed heat sink for efficient thermal management , sturdiness & excellent corrosion resistant. PG9 gland is used for cable entry and provision for loopin -loopout , PC lens/IP lens with narrow /wide beam distribution and toughened glass fixed to housing with screws , flood light should have IP 66 protection and impact resistance of IK 07 , Lumen efficiency of LED not less than 120 lumen per watt system efficency ,power factor >0.95, THD<10% at Full load CRI> 70% ,flood light should have built in potted electronic LED driver with , lower THD, open circuit protection , over voltage protection , surge voltage protection , and provided with company LOGO ingraved on housing of the flood light complete including taking down of old UNSV fittings complete all as specified and directed. Note :-The contractor should take approval of techincal specification of luminaries and driver from department before procurement .
All as per item No 72 above but 120 Watt & Lumen efficiency of LED not less than 110 lumen per watt system efficiency
All as per item No 72 above but 100 Watt & Lumen efficiency of LED not less than 110 lumen per watt system efficiency
All as per item No 72 above but 50 Watt & Lumen efficiency of LED not less than 100 lumen per watt system efficiency
M/s Vatsh Raj and co
MTR GROUP & COMPANY
Ajanta Associates
Ajanta Motor Store
Unnati Engineers
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .