8 Jul 2023, 6:00 pmClosed
GE(U) Meerut Cantt
Roorkee Road Meerut Cantt
REPAIR TO LED STREET LIGHTS ALONG WITH REPLACEMENT OF LT DAMAGE CABLE INCLUDING ALLIED ITEMS AND UPGRADATION OF STREET LIGHT SYSTEM IN NORTH AREA UNDER GE (UTILITY) MEERUT CANTT
2023_MES_602528_1
8514/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Meerut
Please prefer tender documents
11 documents required · 11 mandatory
₹500
GE(U) E/M Meerut
₹76,000
Yes
17 Jul 2023
10 Jun 2023
10 Jul 2023
10 Jun 2023
8 Jul 2023
24 Jun 2023
Amount
Taking out Eixsting Street / security lights any type and size and Supply and fixing LED street light fitting 90 Watt 230 V , 50Hz AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket , with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection , Surge protection @4Kv internal 8kv external to driver with superier finish with top maintanable driver compartmen complete all as specified and directed Engr -in -Charge
Taking out Eixsting Street / security lights any type and size and Supply and fixing LED street light fitting 70 Watt 230 V , 50Hz AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket , with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection , Surge protection @4Kv internal 8kv external to driver with superier finish with top maintanable driver compartment complete all as Specified and directed Engr -in -Charge
Taking out Eixsting Street / security lights any type and size and Supply and fixing LED street light fitting 50 Watt 230 V , 50Hz AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket , with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection , Surge protection @4Kv internal 4 kv external to driver with superier finish with top maintanable driver compartment cmplete complete all as Specified and directed Engr -in -Charge
Taking out Eixsting Street / security lights any type and size and Supply and fixing of mounting bracket made of 40 mm bore (or higher size to suit the opening of fitting) light grade GI pipe of approx 1.5 mtr length bent to shape and fixed to pole with FI 40mm x 6mm clamps, 2 nos and suitable size necessary nuts & bolts ,including Bracket complete set painting of two coat red oxide and aluminium painted fittings for Street lights with swaged tubular/ PCC pole connected all as specified and as directed Engr in charge.
Taking out old unsv existing cable any type and Supply, laying, jointing, testing and commissioning LT underground cables, 1100 volts grade, XLPE insulated and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-7098 (marked, laid in trenches / ducts / fixed on poles / walls / laid under roads / paths / drain / culverts or encased in GI pipe complete all as specified and directed. Cables of the following sizes:-(Note;- Rate quotted includes terminal Lugs / road cutting/ wall cutting/ floor cutting/ Inter locking floor and making good damged portion matching with existing surface with all existing finishes.) complete all as specified and directed Engr in Charge
(a) 16 Sqmm 4 core
(b) 25Sqmm 4core
(c) 35 Sqmm 3.5 core
Excavation in trenches not exceeding 1.5 m wide and exceeding 1.5 m in depth and getting out in Soft/Loose soil including trimming sides and bottom of trenches complete all as specified and directed.
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in Soft/Loose soil including trimming sides and bottom of trenches complete all as specified and directed.
Returning, filling-in, including spreading, watering and well ramming in layers not exceeding 25 cm thick each, in soft /loose soil complete all as specified and directed.
Removing excavated surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed.
Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables complete all as specified and directed.
M & L Bricks for protection cover to under ground cable (with standard size fly ash bricks) with width equal to length of brick laid dry and flat abutting each other with gaps between adjacent brick not exceeding 10mm as directed complete all as specified and directed.
Supply galvanised steel water tubing 40mm bore , light grade, IS-1239 marked with all fittings (IS marked) and laid in trenches / under roads / in drains / fixed to poles/walls incl taking out the existing same pipe ( with required size flat iron clamp bolts, nuts and washers ) complete all as specified and directed.
Supply galvanised steel water tubing 50 mm bore , light grade, IS-1239 marked with all fittings (IS marked) and laid in trenches / under roads / in drains / fixed to poles/walls incl taking out the existing same pipe ( with required size flat iron clamp bolts, nuts and washers ) complete all as specified and directed.
M&L for auguring of hole suitable for passing 40mm to 100mm bore pipe in true horizontal position under road, PCC paths etc., by means of mechanical ring/ auger after doing ultrasound to prevent any damage to existing cables pipe line specified and directed coming in the route not exceeding 1.5 m in depth below existing surface level of road and not excd 30M in length complete all as specified.complete all as specified and directed Engr in Charge Note: Pipe shall be measured and paid separately under appropriate items and any dahage to existing cables of anytype shall be made good by the Bidder without any extra cost to department complete all as specified and directed.
Supplying, transporting to site, erecting, and fixing in position, steel tubular swaged and welded poles of Overall height 9 metres, type 410 SP-31, IS-2713 marked, with mild steel base plate (fillet welded to poles), pole cap / finial taper plug, bolts, nuts, washers etc, including painting on the outside with two coats of aluminium paint over a coat of red oxide primer on exposed surfaces and black bituminous paint on steel surface embeded in concrete and painting 05 nos band /strips with fluorescent , Black/ Red/ White/ Green and Black synthetic enamel paint ( 30 cm wide each) at a distance of 30 cm from plinth block and numbering of poles, complete incl removing the existing unserviceable any type and size poles and all as specified and directed by Engr-in-Charge.(Note:- Poles shall be swaged and welded at manufacturer’s factory and not at site. The inner surface shall be factory painted)
M&L for PCC (1:4:8)type D2 with 40 mm graded stone aggregate infoundation(below pole ) complete all as specified and directed.
M&L for cement concrete (1:3:6) type C-2 using 40mm graded stone aggregate for foundation of stay assembly/struts/pole etc. (around the poles in pit) complete all as specified and directed.
M&L for PCC (1:3:6) type C-1 using 20mm graded stone aggregate for coping / pedestal of poles including necessary form work, fair finishing to exposed surfaces using extra cement complete all as specified and directed.
Taking out existing unsv juntion box any type and size and S&F pole mounting type junction box factory made of size 350x250x150mm of FRP sheet duly powder coated with front openable hinged door , locking arrangements, with 4 Nos aluminium bus bars 40 Amps rating mounted on porcelain insulator, cable glands and lugs consisting DIN type rails for fixing MCB SP 6/10 Amps, 10 kA suitable for domestic loading , -01 no. including mild steel flat iron clamp made out of 40x4mm FI, nuts, bolts and washers duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed Engr in Charge.
Taking out existing unsv conduit any type and size and Supply & fixing Unplasticised PVC pipes of prssure rating 10Kgf/cmSq 25 mm bore and 3mm thick complete fixed on pole using suitable clamps nuts & bolts (not less than 03 Nos) complete all as specified and as directed
Taking out existing unsv connection wire any type and size and S&F for one runs of three core 2.5 Sqmm x 3 core (nominal area) PVC insulated and PVC sheathed multi stranded unarmed copper conductor cable LT 1100 volt grade Confirming to IS : 7098 drawn through GI pipe for connecting to street light and pole JBs and one run of PVC insulated and all complete as specified and as directed.
M&L for preparation of old painted surfaces steel tubular swaged poles / Rails/Girder poles of LT over head line ( Except embedded portion) , 9 M long including all MS work mounted on pole , earth protection & water pipe ( if exists) including bracket(s), single or double of size 1.5m x 40/50 mm pipe ) and providing one coat of aluminium paint and providing 05 Nos bands/ straps with Two coats of retro refelective paint ( Black, Red , white, Green and Black and 25 cm wide each) from top of plinth block and numbering of poles with white refelective paint (50mm wide and 100mm high letters) including encircling the letters or figures complete all as specified and directed Engr in Charge
M & L for cleaning of all surfaces of concrete electric pole and painting complete including bracket(s), single or double of size 1.5m x 40/50 mm pipe ), with two coat of cement base and providing 04Nos bands/ straps with Two coats of retro refelective paint ( Black, Red , white, Green and Black and 25 cm wide each) from top of plinth block and numbering of poles with white refelective paint (50mm wide and 100mm high letters) including encircling the letters or figures complete all as specified and directed Engr in Charge
Trimming/ lopping branches of tree touching to LT/HT OH lines not exceeding 30 cm girth , shrub, vegetation, bushwwod and saplings at least upto 3 M from outer edge of ACSR including removing of braches of trees etc. to a distance exceeding 100 m and not exceeding 150 M complete all as specified and directed. Note :- (i) Shutdown wherever required shall be taken in writting from Engr-in-Charge.
Taking down LED street lights fittings from pole/ walls, opening of street light fittings of any type, wattage and make, making the light fittings operational to give the rated illumination by repairing/ renewal/ replacement pf components viz driver, LED bulbs, electronic circuit and other minor defective parts and refixing the street light in its original position and reconnecting with renewed cable of three core 2.5 sqmm stranded copper conductor ,PVC insulated and PVC sheathed cable of required length complete all as specified and directed. Note:- Driver only if renewed shall be measured separately at supplied only rates under relevant item (ii) Reparing to street light fittings shall be carried out at MES store yard of AGE E/M ES at Meerut.
Taking out existing unsv driver and Supply only Driver suitable for 25 watt LED light fittings, 140V to 270V universal driver with built in surge protection>5KV, 50 Hz +/- 3%, P.f.>0.95, Thd<10% with system efficiency >85 lumens (minium) per watt and power efficiency >= 90% and protection IP 65 or better .complying LM-79/IS:16106. complete all as specified and directed by Engr in Charge (Make:- Crompton, HPL, Philips, C&S, Polycab, and Surya roshni ltd)
Taking out existing unsv driver and Supply only Driver suitable for 45/48 /50watt LED light fittings, 140V to 270V universal driver with built in surge protection>5KV, 50 Hz +/- 3%, P.f.>0.95, Thd<10% with system efficiency >85 lumens (minium) per watt and power efficiency >= 90% and protection IP 65 or better .complying LM-79/IS:16106. complete all as specified and directed by Engr in Charge (Make:- Crompton, HPL, Philips, C&S, Polycab, and Surya roshni ltd)
Taking out existing unsv driver and Supply only Driver suitable for 60/70/72watt LED light fittings, 140V to 270V universal driver with built in surge protection>5KV, 50 Hz +/- 3%, P.f.>0.95, Thd<10% with system efficiency >85 lumens (minium) per watt and power efficiency >= 90% and protection IP 65 or better .complying LM-79/IS:16106.complete all as specified and directed by Engr in Charge. (Make:- Crompton, HPL, Philips, C&S, Polycab, and Surya roshni ltd) complete all as specified and directed.
Taking out existing unsv driver and Supply only Driver suitable for 90 watt LED light fittings, 140V to 270V universal driver with built in surge protection>5KV, 50 Hz +/- 3%, P.f.>0.95, Thd<10% with system efficiency >85 lumens (minium) per watt and power efficiency >= 90% and protection IP 65 or better .complying LM-79/IS:16106. complete all as specified and directed by Engr in Charge. (Make:- Crompton, HPL, Philips, C&S, Polycab, and Surya Roshni Ltd)
Taking out existing unsv driver and Supply only Driver suitable for 100 to 250 watt LED Flood light fittings, 140V to 270V universal driver with built in surge protection>5KV, 50 Hz +/- 3%, P.f.>0.95, Thd<10% with system efficiency >85 lumens (minium) per watt and power efficiency >= 90% and protection IP 65 or better .complying LM-79/IS:16106. complete all as specified and directed by Engr in Charge (Make:- Crompton, HPL, Philips, C&S, Polycab, and and Surya Roshni Ltd)
Taking down of existing unserviceable MCB and S & F Miniature circuit breakers TPN, 32/40 Amps, 415 Volts , 10 KA, 'C' curve rating and to be housed in existing sheet metal enclosures ( distribution boxes) complete all as specified and directed :- (Note :- Proper and suitable size cable lugs to be fixed with Miniature circuit breakers are included in unit rate of each Miniature circuit breakers of any rating). (Make : Legrand / L&T / ABB and Equivalent) complete all as specified and directed by Engr in Charge
Taking down of existing unserviceable MCB and S & F Miniature circuit breakers TPN, 63 Amps, 415 Volts , 10 KA, 'C' curve rating and to be housed in existing sheet metal enclosures ( distribution boxes) complete all as specified and directed :- (Note :- Proper and suitable size cable lugs to be fixed with Miniature circuit breakers are included in unit rate of each Miniature circuit breakers of any rating).(Make : Legrand / L&T / ABB and Equivalent) complete all as specified and directed by Engr in Charge
Repair/maintenance of timer switch assembly of any TYPE and MAKE after dismantling the same from pole, detecting fault, rectifying the same, testing and refixing in the same position after repair/replacement of defective part all as specified. complete all as specified and directed by Engr in Charge
Taking out unsv contactor any type and Supply only street light lexic power timer contactor,3 pole,32 Amps complete all as specified and directed by Engr in Charge
Taking down unsv burned timer panel any type and size and Supplying and fixing in repair automatic operation street light timing switch having lighting control (ON-OFF) through Astronomical Calculation of Sun rise/ sun set by setting date, time and degree of longitude and latitude without separate light sensors and prewired with suitable size of copper conductor single core PVC insulated and sheathed cable and all mechanism fitted into panel, outdoor type , pole mounted with FI 25x4mm clamps , nuts, bolts and washers dully painted, connecting and testing factory made , epoxy powder coated, Single Phase street light panel, digital 24 hrs, suitable for 6KW (max) complete with 32 Amps TP Contactor, and 40 Amps TPN MCBs and fixed on pole/ wall/ feeder pillar complete all as specified and directed by Engr in Charge
Taking down unsv burnet timer panel any type and sixe andSupplying and fixing in repair automatic operation street light timing switch having lighting control (ON-OFF) through Astronomical Calculation of Sun rise/ sun set by setting date, time and degree of longitude and latitude without separate light sensors and prewired with suitable size of copper conductor single core PVC insulated and sheathed caable and all mechanism fitted into panel, outdoor type , pole mounted with FI 25x4mm clamps , nuts, bolts and washers dully painted, connecting and testing factory made , epoxy powder coated, three Phase street light panel, digital 24 hrs, suitable for12 KW (max) complete with 63 Amps TP Contactor, and 63 Amps TPN MCBs and fixed on pole/ wall/ feeder pillar comcomplete all as specified and directed by Engr in Charge
Taking out unsv DBs any type and Supply and fix in repair SPN DBs for MCB complete with SPN MCB 63 Amp, 10 KA, suitable for domestic loading, 240 Volt as as specified.
Taking out unsv timer any type and Supply and fixing Anolog type timer swich 16 Amps range, AC 220/240 volt, 60 Hz , with IEC 60730-1/ IEC 60730-2-7 complete all as specified and directed by Engr in Charge
Taking out unsv timer any type and Supply and fixing Astronomical type timer swich 16 Amps range AC 220/240 volt, 60 Hz , with IEC 60730-1/ IEC 60730-2-7 complete all as specified and directed by Engr in Charge
NITHYA INFRATECH
D S Enterprises
M/S Ex Soldiers Mechanical Works
BHAGWAN DAS & Co
automation and switchgear control
Shikha Enterprises
Ramesh Traders Govt Contractors & General OrderSuppliers
Narender Construction
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .