Loading…
Loading…
| # | Company | Amount |
|---|---|---|
| 1 | ₹11.0 Cr C 30 SECTOR 3 CHIRANJEEV VIHAR GHAZIABAD U P 201002 | ₹11.0 Cr |
Tender Value
₹13.0 Cr
EMD Value
₹13.0 L
Closing Date
1 Nov 2022, 11:00 amClosed
Construction and development of Pre Engineered Manufacturing Unit at Industrial Plot No. B-208, at sector Phase-II, Noida-3rd Call
NBCC/RBG/Amrapali/PEB/Noida/2022/20
NBCC/RBG/Amrapali/PEB/Noida/2022/20
Open Tender-Domestic
Civil Works General
Gautam Buddha Nagar, Uttar Pradesh
₹11,800
₹13.0 L
22 Oct 2022
22 Oct 2022
1 Nov 2022
1 Nov 2022
9 Nov 2022
Bill of Quantity
S. NO DESRIPTION COST OF DSR ITEMS COST OF NON DSR ITEMS
2 FIRE FIGHTING WORKS 78,73,815.90 8,54,717.98
3 INTERNAL PLUMBING WORKS 7,89,113.00 2,60,766.00
4 EXTERNAL PLUMBING WORKS 35,72,206.00 2,51,103.00
6 ELECTRICAL WORKS 32,13,308.42 92,01,654.58
7 FIRE ALARM & PA SYSTEM WORKS 11,80,681.00 3,65,338.70
Add MF=1.0633 for GST (12% to 18%) 40,70,544.37 (included)
TOTAL COST OF DSR + NON DSR ITEMS 12,98,55,106
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
Name of Work- Construction and development of Pre Engineered Manufacturing Unit at Industrial Plot No. B-208, at sector Phase-II, Noida
S.No. DSR 2021 Description Unit TOTAL QTY. RATE DSR 2021 RATE NON DSR TOTAL DSR AMOUNT
2.6 Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over
areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including
getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed
by Engineer-incharge
2 2.25 Filling available excavated earth (excluding rock) in trenches, plinth,sides of foundations
etc. in layers not exceeding 20cm in depth,consolidating each deposited layer by ramming cum 1875.79 253.95 476357.70 0.00
and watering, lead up to 50 m and lift upto 1.5 m.
3 2.25 a Excavating, supplying and filling of local earth (including royalty) by mechanical transport
upto a lead of 5km also including ramming and watering of the earth in layers not cum 2500.00 368.65 921625.00 0.00
exceeding 20 cm in trenches, plinth, sides of foundation etc. complete.
2.26 Extra for every additional lift of 1.5 m or part thereof in excavation /banking excavated or
stacked materials.
2.28 Surface dressing of the ground including removing vegetation and inequalities not
exceeding 15 cm deep and disposal of rubbish, lead up to 50 m and lift up to 1.5 m.
4 CONCRETE WORK
6 4.1.8 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) cum 271.72 6326.05 1718933.91 0.00
7 4.10 Providing and laying damp-proof course 40 mm thick with cement concrete 1:2:4 (1
cement : 2 coarse sand : 4 graded stone aggregate 12.5 mm nominal size).
5.00 REINFORCED CEMENT CONCRETE
5.9 Centering and shuttering including strutting, propping etc. and removal of form for
9 5.9.1 Foundations, footings, bases and foundations for shed columns sqm 712.94 307.95 219548.95 0.00
10 5.9.2 Walls ( any thickness) including attached pilasters, buttresses, plinth and string courses
11 5.9.3 Suspended floors, roofs, landings, balconies and access platform. sqm 559.63 766.55 428982.23 0.00
12 5.9.5 Lintels, beams, plinth beams, girders, bressumers and cantilevers sqm 696.12 608.35 423481.56 0.00
13 5.9.6 Columns, piers, abutments, pillars, posts and struts. sqm 1632.74 804.25 1313129.94 0.00
14 5.9.7 Stairs, (excluding landings) except spiral-staircases sqm 20.59 657.75 13543.40 0.00
15 5.22 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in
position and binding all complete upto plinth level.
16 5.22.6 Thermo-Mechanically Treated bars of grade Fe-500D or more. kg 90518.57 89.65 8114989.57 0.00
17 Steel reinforcement for R.C.C. work including straightening, cutting,bending, placing in
position and binding all complete above plinth level.
18 5.22A.6 Thermo-Mechanically Treated bars of grade Fe-500D or more. kg 45184.95 89.65 4050830.66 0.00
19 5.30 Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections.
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No. DSR 2021 Description Unit TOTAL QTY. RATE DSR 2021 RATE NON DSR TOTAL DSR AMOUNT
5.33 Providing and laying in position ready mixed or site batched design mix cement concrete
for reinforced cement concrete work; using coarse aggregate and fine aggregate derived
from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement,
admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of
concrete, to improve durability and workability without impairing strength; including
pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost
of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-
charge; for the following grades of concrete.
Note: Extra cement up to 10% of the minimum specified cement content in design mix
shall be payable separately. In case the cement content in design mix is more than 110% of
the minimum specified cement content, the contractor shall have discretion to either re-
design the mix or bear the cost of extra cement.
5.33.1 All works upto plinth level :
20 5.33.1.1 Concrete of M25 grade with minimum cement content of 330 kg /cum cum 884.75 8683.80 7683031.52 0.00
5.33.2 All works above plinth level upto floor V level
21 5.33.2.1 Concrete of M25 grade with minimum cement content of 330 kg /cum cum 190.30 10306.20 1961318.94 0.00
6.0 MASONRY WORK
6.1 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in
foundation and plinth in:
22 6.1.2 Cement mortar 1:6 (1 cement : 6 coarse sand) cum 88.36 6658.25 588322.97 0.00
6.4 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in
superstructure above plinth level up to floor V level in all shapes and sizes in :
23 6.4.2 With F.P.S.(non modular) bricks cum 373.53 8288.35 3095937.81 0.00
6.13 Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class
designation 7.5 in superstructure above plinth level up to floor V level.
24 6.13.2 Cement mortar 1:4 (1 cement :4 coarse sand) sqm 45.12 1018.05 45934.42 0.00
6.15 Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars at every third course
of half brick masonry.
25 Providing and laying autoclaved aerated cement blocks masonry with 150mm/230mm/300
mm thick AAC blocks in super structure above plinth level up to floor V level with RCC band
6.47 at sill level and lintel level with approved block laying polymer modified adhesive mortar cum 142.52 6994.15 996802.76 0.00
all complete as per direction of Engineer-in-Charge. (The payment of RCC band and
reinforcement shall be made for seperately).
9 WOOD AND P. V. C. WORK
9.97 Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less
than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with
necessary screws etc. complete :
27 9.83 Providing and fixing aluminium die cast body tubular type universal hydraulic door closer
(having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 35 kg and
door width upto 700 mm), with necessary accessories and screws etc. complete.
9.101 Providing and fixing aluminium hanging floor door stopper, ISI marked,anodised (anodic
coating not less than grade AC 10 as per IS : 1868)transparent or dyed to required colour
and shade, with necessary screws etc. complete.
28 9.101.2 Twin rubber stopper each 22.00 62.25 1369.50 0.00
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No. DSR 2021 Description Unit TOTAL QTY. RATE DSR 2021 RATE NON DSR TOTAL DSR AMOUNT
29 9.128 Providing and fixing factory made Fiberglass Reinforced plastics (F.R.P.) chajja 4 mm thick
of required colour, size and design made by ResinTransfer Moulding (RTM) Machine
Technology, resulting in void free compact laminate in single piece, having smooth gradual
slope curvature for easy drainage of water and duly reinforced by 2 nos vertically and 1
nos horizontally 50x2 mm thick M.S. flat with 12 mm in built hole for grouting on the
existing wall along with the 50 mm flanges duly inserted and sealed in the wall complete in
one single piece casted monolithically, including all necessary fittings . The FRP Chajja
should be manufactured using unsaturated Polyester resin as per IS: 6746, duly reinforced
with fibre glass chopped strand mat (CSM) as per IS: 11551 complete with protective Gel
coat U/V coating on Top for complete resistance from the extreme of temperature,
weather & sunlight (Only plan area of chajjas shall be measured for making payment).
33 9.161 Providing and fixing fire resistant door frame of section 50 x 60 mm on horizontal side & 35
x 60 mm on vertical sides having built in rebate made out of 1.6 mm thick GI sheet ( Zinc
coating not less than 120gm/ m²) suitable for mounting 120 min Fire Rated Glazed Door
Shutters. The frame shall be filled with Mineral wool Insulation having density min
96Kg/m³ . The frame will have a provision of G.I. Anchor fastners 14 nos ( 5 each on vertical
style & 4 on horizontal style of size M10 x 80 ) suitable for fixing in the opening along with meter 10.80 1791.05 19343.34 0.00
Factory made Template for hinges is excluded). SS Ball Bearing Hinges of Size 100x89x3mm
for fixing of fire rated glazed shutter . The frame shall be finished with a approved fire
resistant primer or Powder coating of not less than 30 micron in desired shade as per the
directions of Engineer - in- charge . (Cost of SS ball bearing
30 9.162 Providing and fixing 60 mm thick glazed fire resistant door shutters of 120 min Fire Rating
confirming to IS:3614 (Part II) or EN1634-1:1999, tested and certified as per laboratory
approved by Engineer-in-charge,with suitable mounting on door frame, consisting of
vertical styles, top rail & side rail 60 mm x 60 mm wide and bottom rail of 110 mm x 60 mm
made out of 1.6mm thick G.I. sheet (zinc coating not less than 120gm/m²) duly filled
mineral wool insulation having density min 96 kg/ m³ and fixing with necessary stainless
steel ball bearing hinges of size 100x89x3mm of approved make, including applying a coat
of approved fire resistant primer or powder coating not less than 30 micron etc all
complete as per direction of Engineer-in-charge (panelling to be paid for seperately).
31 9.164 Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc.,
with G.I. beading made out of 1.6 mm thick G.I. sheet (zinc coating not less than 120
gm/m²) of size 20 x 33 mm screwed with M4 x 38 mm SS screws at distance 75 mm from
the edges and 150 mm c/c , including applying a coat of approved fire resistant primer/
powder coating of not less than 30 micron on G.I. beading, & special ceramic tape of 5 x 20
mm size etc complete in all respect as per NBC 2016, IS 16231 (Part 3):2016 and as per
direction of gineer-in-charge with glass of required thickness having 120 minutes of fire sqm 0.50 39995.80 19997.90 0.00
resistance both integrity & radiation control (EW120) and minimum 20 minutes of
insulation (EI20). The manufacturer have to give test report/certification of fire glass and
the glass should have the stamp showing the value of E, EW & EI. The glass shall be tested
in approved NABL accredited lab or by any other accreditation body hich operates in
accordance with ISO/IEC 17011 and accredits labs as per ISO/IEC 17025 for testing and
calibration scopes shall be eligible. The maximum glazing size shall not be more than
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No. DSR 2021 Description Unit TOTAL QTY. RATE DSR 2021 RATE NON DSR TOTAL DSR AMOUNT
32 9.139 Providing and fixing panic bar / latch (Double point) fitted with a single body, Trim Latch &
Lock on back side of the Panic Latch of reputed brand and manufacture to be approved by each 4.00 7145.90 28583.60 0.00
the Engineer- in- charge, all complete.
10.0 STEEL WORK 0.00
10.11 Providing and fixing factory made ISI marked steel glazed doors, windows
and ventilators, side /top /centre hung, with beading and all members
such as F7D,F4B, K11 B and K12 B etc. complete of standard rolled
steel sections, joints mitred and flash butt welded and sash bars tenoned
and riveted, including providing and fixing of hinges, pivots, including priming coat of
approved steel primer, but excluding the cost of other fittings, complete all as per
approved design, (sectional weight of only steel members shall be measured for payment).
33 10.11.1 Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block 15x10x10 cm of
C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)
10.5 Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and
3 mm M.S. gusset plates at the junctions and corners,all necessary fittings complete,
including applying a priming coat of approved steel primer.
34 10.5.2 Using flats 30X6m for diagonal braces and central cross piece. sqm 12.60 4615.15 58150.89 0.00
10.6 Supplying and fixing rolling shutters of approved make, made of required size M.S. laths,
interlocked together through their entire length and jointed together at the end by end
locks, mounted on specially designed pipe shaft with brackets, side guides and
arrangements for inside and outside locking with push and pull operation complete,
including the cost of providing and fixing necessary 27.5 cm long wire springs
manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 -
part 1 and M.S. top cover of required thickness for rolling shutters.
35 10.6.1 80x1.25mm M.S. laths with 1.25 mm thick top cover. sqm 44.00 3008.80 132387.20 0.00
10.8 Extra for providing mechanical device chain and crank operation for operating rolling
36 10.8.1 Exceeding 10.00 sqm and upto 16.80 sqm in the area sqm 44.00 1108.70 48782.80 0.00
37 10.19 Providing and fixing mild steel round holding down bolts with nuts and washer
plates complete (Hardware/Bolt Conferming Grade-8.8/4.4).
Providing, fabricating and erection of structural steel work in factory fabricated machine
welded and finished structural elements with plates, angles, channels, beams etc. of
specified grade of Fe 345 WA/WB as per IS 2062 to form structural members for all span
beams & columns as per GA drawings to meet all IS codal requirements based on the
design approved by structural Engineer. The rate shall include trasporation of materials
from steel manufacturer's yard to factory fabrication yard and then to site of work, making
NON DSR all necessary arrangement for safe handling and erection and hoisting i.e. like making
temporary sturdy structure to take erection loads and loads of the fabricated sections/
materials during execution, dismantling temporary structure after completion of structure
etc. Applying Primer (min. 50 micron thk) of approved make with min. 70 micron enamel
paint of approved make(colour to be approved by engineer in charge) and all work shall
be carried out true to line and levels as per approved drawings and specifications.
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No. DSR 2021 Description Unit TOTAL QTY. RATE DSR 2021 RATE NON DSR TOTAL DSR AMOUNT
The rate shall include cost of preparation of shop & GA drawings based on approved
structural design and drawing sincluding incorporating modification and preparation of
revised shop drawing as per direction of Engineer-in-Charge, materials and all operation
like cuttings, bevelling, tack welding, fine welding and re-welding, filling and smoothening
the edges to remove any blurrs and additional welds, making holes to receive nuts and
bots as required at site and in factroy fabrication yard to maintain line & level, providing
required machinery like hydra, cranes, jigs & fixtures, all necessary tools and plants to
handle structurral material, temporary jointing and disjointing, labour for carrying erection
and geometrical control survey, field and lab testing charges etc. all complete as per
approved architectural, structural and shop drawings and direction of Engineer-in-Charge.
38 NON DSR built up/ Hot rolled section kg 229873.00 121.57 0.00 27945835.46
41 Providing and fixing 0.47mm Bare galvalume roof sheet AZ -150, ,550MPA including ridge,
NON DSR flashing, over lapping, etc complete (plan area should be measured, nothing extra shall be sqm 5590.00 628.55 0.00 3513576.04
paid for lap, profile (valley, crest) etc.)
42 Providing and fixing Gutter in 0.5mm precoted galvalume 550MPA with supporting
43 NON DSR Providing and fixing 2mm thk ploycarbonete sheet for sky lights. sqm 144.00 1642.50 0.00 236519.79
44 Providing and fixing Metal deck sheet 250Mpa, 0.8mm thk (plan area should be measured,
nothing extra shall be paid for lap, profile etc.)
11.3 Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate)
finished with a floating coat of neat cement, including cement slurry, but excluding the
cost of nosing of steps etc. complete.
45 11.3.1 40 mm thick with 20 mm nominal size stone aggregate sqm 344.82 545.00 187926.79 0.00
46 11.37 Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness
to be specified by the manufacturer), of approved make, in all colours, shades
except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in
skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 sqm 247.18 935.60 231258.75 0.00
cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including
pointing in white cement mixed with pigment of matching shade complete.
11.41 Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the
manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of
approved make, in all colours and shades,laid on 20mm thick cement mortar 1:4 (1 cement
: 4 coarse sand),jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the
joints with white cement and matching pigments etc., complete.
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No. DSR 2021 Description Unit TOTAL QTY. RATE DSR 2021 RATE NON DSR TOTAL DSR AMOUNT
NDSR Providing & Laying "TRIMIX VACCUM DEWATERING SYSTEM" with M - 25 Grade mix
cement concrete (Min. cement content @ 330Kg/Cum) for spreading, screeding,
dewatering, floating & troweling with the help of power trowelling floater of concrete
floor as directed & specified using necessary steel form work with M.S. Channels including
providing & laying separation layer of 150 micron (LDPE) expanded polythin foam sheets.
Rate includes forming construction & Construction joints 4 mm to 6 mm wide by cutting
the floor upto 20 %(1/5th) depth of thickness of the concrete depth using mechanical saw
up to full depth of cutting including providing & fixing M.S. dowells bars with bitumen
painted of full length as shown in drawing as to form the bays not exceeding 6.0 m x 4.5 m,
including Isolation Joint-Wall/Colunm, Providing & proper fixing of 10mm thick armour
board for isolation joints between Floor and walls etc. complete as per direction & as per
Drawing & Design approved by the Engineer Incharge. (Steel Reinforcement paid
12.21 Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 stone
aggregate 10 mm and down gauge), including finishing with cement mortar 1:3 (1 cement :
3 fine sand) as per standard design :
49 12.22 Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4
(1 cement : 2 coarse sand : 4 graded stone micron, finished with 12 mm cement plaster 1:3
(1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and
finishing the outlet complete.
12.41 Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS :
13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap
for thermal expansion,(i) Single socketed pipes.
Note :- Rates for external plastic are for height upto 10m from ground level in less
otherwise stated.
51 13.1.2 P/L 12mm cement plaster of mix 1:6 ( 1 cement : 6 Fine sand ) . sqm 2156.18 282.00 608043.51 0.00
13.2 15 mm cement plaster on the rough side of single or half brick wall of mix :
53 13.21 Extra for providing and mixing water proofing material in cement plaster work in Per bags of 50kg
proportion recommended by the manufacturers. cement used in 91.52 60.55 5541.61 0.00
13.16 6 mm cement plaster of mix :
13.37 White washing with lime to give an even shade :
55 13.37.1 New work (three or more coats) sqm 1727.25 32.45 56049.31 0.00
13.46 Finishing walls with Acrylic Smooth exterior paint of required shade :
56 13.46.1 New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of ex sqm 1929.53 166.85 321942.21 0.00
13.61 Painting with synthetic enamel paint of approved brand and manufacture to give an even
57 13.61.1 Two or more coats on new work sqm 738.30 131.45 97049.27 0.00
15 DISMANTLING AND DEMOLISHING
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No. DSR 2021 Description Unit TOTAL QTY. RATE DSR 2021 RATE NON DSR TOTAL DSR AMOUNT
15.2 Demolishing cement concrete manually/ by mechanical means including disposal of
material within 50 metres lead as per direction of Engineer - in - charge.
58 15.2.2 Nominal concrete 1:4:8 or leaner mix (i/c equivalent design mix) cum 2.00 1239.60 2479.20 0.00
15.3 Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars
and disposal of unserviceable material within 50 metres lead as per direction of Engineer - cum 5.00 2928.10 14640.50 0.00
59 in- charge.
15.7 Demolishing brick work manually/ by mechanical means including stacking of serviceable
material and disposal of unserviceable material within 50 metres lead as per direction of
Engineer-in-charge.
16.59 Manufacturing, supplying and fixing retro reflective sign boards made up of 2 mm thick
aluminium sheet, face to be fully covered with high intensity encapsulated type heat
activated retro reflective sheeting conforming to type - IV of ASTM-D 4956-01 in blue and
silver white or other colour combination including subject matter, message
(bilingual),symbols and borders etc. as per IRC ; 67:2001, pasted on substrate by an
adhesive backing which shall be activated by applying heat and pressure conforming to
class -2 of ASTM-D-4956-01 and fixing the same with suitable sized aluminium alloy rivets
@ 20 cm c/c to back support frame of M.S. angle iron of size 25x25x3 mm along with theft
resistant measures, mounted and fixed with 2 Nos.M.S. angles of size 35x35x5 mm to a
vertical post made up to M.S.Tee section ISMT 50x50x6 mm welded with base plate of size
100x100x5 mm at the bottom end and including making holes in pipes, angles flats,
providing & fixing M.S. message plate of required size, steel work to be painted with two
or more coats of synthetic enamel paint of required shade and of approved brand &
manufacture over priming coat of zinc chromate yellow primer (vertical MS-Tee support to
62 Cautionary /warning sign boards of equilateral triangular shape having each side of 900
mm with support length of 3650 mm
16.69 Providing and laying at or near ground level factory made kerb stone of M-25 grade
cement concrete in position to the required line, level and curvature, jointed with cement
mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves
(thickness of joints except at sharp curve shall not to more than 5mm), including making cum 47.25 8613.55 406990.24 0.00
drainage opening wherever required complete etc. as per direction of Engineer-in-charge
(length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone
63 shall be approved by Engineer-in-charge).
16.78 Construction of granular sub-base by providing close graded Material conforming to
specifications, mixing in a mechanical mix plant at OMC, carriage of mixed material by
tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness
with motor grader on prepared surface and compacting with vibratory power roller to
achieve the desired density, complete as per specifications and directions of Engineerin-
64 16.78.2 With material conforming to Grade-II (size range 75 mm to 0.075 mm ) having CBR Value-
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No. DSR 2021 Description Unit TOTAL QTY. RATE DSR 2021 RATE NON DSR TOTAL DSR AMOUNT
65 16.79 Providing, laying, spreading and compacting graded stone aggregate (size range 53 mm to
0.075 mm ) to wet mix macadam (WMM) specification including premixing the material
with water at OMC in for all leads & lifts, laying in uniform layers with mechanical
paverfinisher in sub- base / base course on well prepared surface and compacting with cum 476.92 2803.65 1337106.15 0.00
vibratory roller of 8 to 10 tonne capacity to achievethe desired density, complete as per
specifications and directions of Engineer-in-Charge.
16.91 Providing and laying factory made chamfered edge Cement Concrete paver blocks in
footpath, parks, lawns, drive ways or light traffic parking etc, of required strength,
thickness & size/ shape, made by table vibratory method using PU mould, laid in required
colour & pattern over 50mm thick compacted bed of sand, compacting and proper
embedding/laying of inter locking paver blocks into the sand bedding layer through
vibratory compaction by using plate vibrator, filling the joints with sand and cutting of
paver blocks as per required size and per direction of Engineer-in-Charge.pattern, finishing
and sweeping extra sand. complete all as
66 16.91.1 60mm thick cement concrete paver block of M-35 grade with approved colour, design &
67 P/Grouting GP2 of Fosroc make in bases of columns etc., including cleaning, sealing the
edges with C.mortar for grouting all complete as per standard specifications and the kg 4250.00 23.48 0.00 99773.16
NDSR directions of the Engineer in charge.
68 NDSR Providing, laying and fixing in slope as per drawing or as directed by Engineer-In-charge,
300 wide prefabricated saucer drain along the road to connect and take storm water catch meter 350.00 724.70 0.00 253643.49
basin, with average thickness of 80 mm in concrete grade of M-30.
69 19.16 Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as
per IS : 10910, on 12 mm dia steel bar conforming to IS: 1786, having minimum cross
section as 23 mmx25 mm and over all minimum length 263 mm and width as 165 mm with
minimum 112 mm space between protruded legs having 2 mm tread on top surface by
ribbing or chequering besides necessary and adequate anchoring projections on tail length
on 138 mm as per standard drawing and suitable to with stand the bend test and chemical
resistance test as per specifications and having manufacture's permanent identification
mark to be visible even after fixing, including fixing in manholes with 30x20x15 cm cement
concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal
size) complete as per design.
19.19 Providing and fixing in position pre-cast R.C.C. manhole cover and frame of required shape
and approved quality
70 19.19.3.1 Circular shape 560 mm internal diameter each 12.00 1494.20 17930.40 0.00
21 ALUMINIUM WORK
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No. DSR 2021 Description Unit TOTAL QTY. RATE DSR 2021 RATE NON DSR TOTAL DSR AMOUNT
Providing and fixing aluminum work for doors, windows, ventilators and partitions
with extruded built up standard tubular sections/appropriate Z sections and other
sections of approved make conforming to IS:733 and IS: 1285, fixing with dash fastners of
required dia and size, including necessary filling up the gaps at junctions, i.e. at the
top, bottom and sides with required EPDM rubber/neoprene gasket etc. Aluminium
sections shall be smooth, rust free, straight, mitred and jointed mechanically
wherever required including cleat angle, Aluminium snap beading for
glazing/paneling, C.P brass/ stainless steel screws, all complete as per architectural
drawings and the directions of Engineer-in- charge.(Glazing paneling and dash fasteners
to be paid for separately) :
21.1.1 For fixed portion
71 21.1.1.2 Powder coated aluminium (minimum thickness of powder coating 50 micron) kg 892.44 466.30 416144.77 0.00
21.1.2 For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots
and making provision for fixing of fittings wherever required including the cost of EPDM
rubber / neoprene gasket required (Fittings shall be paid for separately)
72 21.1.2.2 Powder coated aluminium (minimum
thickness of powder coating 50 micron)
21.20 Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or
graded wood particle board conforming to IS:12823 Grade l Type ll, in panelling fixed in
aluminum doors, windowsshutters and partition frames with C.P. brass / stainless steel
screwsetc. complete as per architectural drawings and directions of Engineerin- charge.
73 21.2.1 Pre-laminated particle board with decorative laminationon one side and balancing
lamination on other side
21.8 Filling the gap in between aluminium frame & adjacent RCC / Brick / Stone work by
providing weather silicon sealant over backer rod of approved quality as per architectural
drawings and direction of Engineerin-Charge complete.
74 21.8.1 Upto 5 mm depth and 5 mm width meter 126.90 85.25 10818.23 0.00
21.3 Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions
etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings
and the directions of engineer-in-charge . (Cost of aluminium snap eading shall be paid in
75 21.3.1 With float glass panes of 4.0 mm thickness (weight not less than 10kg/sqm) sqm 74.25 1019.80 75720.15 0.00
21.4 Providing and fixing double action hydraulic floor spring of approved brand and
manufacture conforming to IS : 6315, having brand logo embossed on the body / plate
with double spring mechanism and door weight upto 125 kg, for doors, including cost of
cutting floors,embedding in floors as required and making good the same matching to the
existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer
box with slide plate etc. complete as per the direction of Engineer-in-charge.
76 21.4.1 With stainless steel cover plate minimum 1.25 mm thickness. each 2.00 2448.85 4897.70 0.00
77 21.13 Providing and fixing Brass 100mm mortice latch and lock with 6 levers without pair of
handles (best make of approved quality) for aluminium doors including necessary cutting each 7.00 449.55 3146.85 0.00
and making good etc.complete.
78 21.16 Providing and fixing aluminium round shape handle of outer dia 100 mm with SS screws
etc. complete as per direction of Engineer-incharge
79 21.16.2 Powder coated minimum thickness 50 micron aluminium each 44.00 89.60 3942.40 0.00
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No. DSR 2021 Description Unit TOTAL QTY. RATE DSR 2021 RATE NON DSR TOTAL DSR AMOUNT
22 WATER PROOFING
22.4 Providing and Placing in position suitable PVC water stops conforming to IS:12200 for
construction/ expansion joints between two RCC members and fixed to the reinforcement
with binding wire before pouring concrete etc. complete :
80 22.4.2 Dumb bell with central bulb (180 mm wide, 8 mm thick) meter 368.00 232.05 85394.40 0.00
22.3 Providing and laying water proofing treatment to vertical and horizontal surfaces of
depressed portions of W.C., kitchen and the like consisting of:
(i) Ist course of applying cement slurry @ 4.4 kg/sqm mixed with water proofing compound
conforming to IS 2645 in recommended proportions including rounding off junction of
vertical and horizontal surface.
(ii) IInd course of 20 mm cement plaster 1:3 (1 cement : 3 coarse sand) mixed with water
proofing compound in recommended proportion including rounding off junction of vertical
and orizontal surface.
(iii) IIIrd course of applying blown or residual bitumen applied hot at 1.7 kg. per sqm of area.
81 (iV) IVth course of 400 micron thick PVC sheet. (Overlaps at joints of PVC sheet should be 100
mm wide and pasted to each other with bitumen @ 1.7 kg/sqm).
22.5 Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc.,
by applying cement slurry mixed with water proofing cement compound consisting of
(a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement
compound @ 0.253 kg/ sqm. This layer will be allowed to air cure for 4 hours
(b) (b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement
compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with
water layer will be allowed to air cure for 4 hours followed with water curing for 48 hours.
82 The rate includes preparation of surface, treatment and sealing of all joints, corners,
junctions of pipes and masonry with polymer mixed slurry.
83 NDSR P/L cinder concrete in cement 1:15 (1 cement :15 cinder of 12.5 mm size) on terraced roof
laid to slope I/c consolidating the same.
23.0 RAIN WATER HARVESTING & TUBEWELLS
84 23.5 Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in
recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of cum 18.00 1302.30 23441.40 0.00
Engineer-in-charge.
85 23.6 Supplying, filling, spreading & leveling coarse sand of size range 5 mm to 10 mm in
recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per cum 10.33 1309.00 13524.59 0.00
direction of Engineer -incharge
86 23.7 Supplying, filling, spreading & leveling coarse sand of size range 1.5 mm to 2 mm in
recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per cum 4.61 1309.00 6031.87 0.00
direction of Engineer -incharge
NEW TECHNOLOGIES & MATERIALS
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No. DSR 2021 Description Unit TOTAL QTY. RATE DSR 2021 RATE NON DSR TOTAL DSR AMOUNT
26.22 Providing and fixing false ceiling at all heights with integral densified calcium silicate
reinforced with fibre and natural filler false ceiling tiles of Size 595x595mm of approved
texture, design and patterns as per CPWD Specification 2019, to be laid in true horizontal
level suspended on inter-locking metal T-Grid of hot dipped galvanised iron section of
0.33mmthick (galvanized @ 120 grams per sqm including both sides)comprising of main-T
runners of size 24x38mm of length 3000 mm,cross - T of size 24x32 mm of length
1200 mm and secondaryintermediate cross-T of size 24x32 mm of length 600mm to
formgrid module of size 600 x 600 mm,suspended from ceiling usinggalvanised mild steel
items (galvanizing @ 80 grams per sqm) i.e. 12x50 mm long dash fasteners, 6 mm dia fully
threaded hanger rod upto 1000 mm length and L-shape level adjuster of size 76x25x25x1.6
mm fixed with grid and Z cleat of size 25x37x25x1.6mm thick with precut hole on both
25mm flange to pierce into 12x50mm or even bigger size dash fastener if require, fixed
with Glavanised iron perimeter wall angle or size 24x24x0.40mm of length 3000 mm to be
fixed on periphey wall / partition with the help of plastic rawl plugs at 450mm center to
center and 40 mm long dry wall S.S screws. The workshall be carried out as per
pecifications, drawing and as per directionsof the Engineer-in-Charge.
87 26.22.1 With 15 mm thick Tegular edged light weight calcium sliciate false ceiling tiles sqm 90.00 1777.50 159975.00 0.00
HORTICULTURE & LANDSCAPING
88 2.10 Grassing with selection No. 1 grass including watering and maintenance of the lawn for 60
days or more till the grass forms a thick lawn, free from weeds and fit for mowing including
supplying good earth, if needed (the grass and earth shall be paid for separately). sqm 4500.00 17.70 79650.00 0.00
In rows 5 cm apart in both directions
89 7.5 Supply and stacking of Azadirachta indica ( Neem ) plant of height 120- 130cm in big
polybag of size 25 cm as per direction of the each 25.00 65.00 1625.00 0.00
officer-in-charge.
90 7.6 Supply and stacking of Bassia latifolia (Mahua) plant of height 90-105 cm. in big polybag of
size 25 cm as per direction of the officer-in-charge.
91 7.53 Supply and stacking of Mangifera indica (Mango-grafted ) plant of height
60-75 cm. in big poly bag of size 25 cm as per direction of the officer-incharge.
92 7.75 Supply and stacking of Polyalthia longifolia (Ashok) plant of height 180- 195 cm. in gunny
bag of size 30 cm as per direction of the officer-incharge.
93 7.83 Supply and stacking of Eugenia jambolana (Jamun) plant of height 150- 165 cm. in big poly
bags of size 25 cm as per direction of the officer-in-charge.
Total Amount 47521323.9 47537015.2
Total Amount 47521323.9 47537015.2
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
Name of Work- Construction and development of Pre Engineered Manufacturing Unit at Industrial Plot No. B-208, at sector Phase-II, Noida
FIRE FIGHTING SYSTEM
S.No DSR 2019/NON Description Unit Qty Rate DSR-2019 Rate NON Amount DSR Amount NON
Pump shall be capable of handling not less than 150% of rated
capacity at a head not less than 65 % of rated head. The shut off head
shall not exceed 120% of rated head. HP of motor should be 20%
more than the calculated HP.
1 1 Supplying, installation, testing and commissioning of Electric driven
Main Fire Pump suitable for automatic operation and consisting of
following, complete in all respects, as required :
(a) Horizontal type, multistage, centrifugal, split casing pump of cast
iron body & bronze impeller with stainless steel shaft, mechanical seal
conforming to IS 1520.
(b) Suitable HP Squirrel cage induction motor, TEFC, synchronous
speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50
Hz, AC supply with IP 55 protection for enclosure, horizontal foot
mounted type with Class-'F' insulation, conforming to IS-325.
(c) M.S. fabricated Common base plate, coupling, coupling guard,
foundation bolts etc. as required.
(d) Suitable cement concrete foundation duly plastered with anti
vibration pads.
1.5 2280 lpm at 70 m Head (For Main Electric Hydrant Pump) Set 1 367296.00 367296.00 0.00
1.5 2280 lpm at 70 m Head (For Main Electric Sprinkler Pump) Set 1 367296.00 367296.00 0.00
1.9 1620 lpm at 56 m Head (For Main Electric Water Curtain Pump) Set 1 282515.00 282515.00 0.00
Note: *The head of the pump is selected in a manner so as to give a
minimum 3.5kgf/cm2 pressure at the highest/farthest point.
Note: *The head of the pump is selected in a manner so as to give a
minimum 1.4kgf/cm2 pressure at the highest/farthest point for
Water Curtain Pump
2 2 Supplying, installation, testing and commissioning of diesel engine
driven main fire pump suitable for automatic operation and
consisting of following, complete in all respects, as required :
(Diesel Driven Pump)
Horizontal type, multistage, centrifugal pump of cast of iron body and
bronze impeller with stainless steel shaft, mechanical seal conforming
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No DSR 2019/NON Description Unit Qty Rate DSR-2019 Rate NON Amount DSR Amount NON
Suitable HP, 1500 RPM water cooled with radiator, diesel engine
conforming to relevant IS standard complete with auto starting
mechanism, 12 /24 volts electric starting equipment, diesel tank,
exhaust pipe extended upto 10 m outside pump house duly insulated
with 50 mm thick glass wool with 1.0 mm thick aluminium
sheet cladding, residential silencer, instruments and
protection as per standard specification, stop solenoid for auto
stop in the event of fault with audio indications, painted with post
office red colour etc. as required.
Suitable HP, 1500 RPM water cooled with radiator, diesel engine
conforming to relevant IS standard complete with auto starting
mechanism, 12 /24 volts electric starting equipment, diesel tank,
exhaust pipe extended upto 10 m outside pump house duly insulated
with 50 mm thick glass wool with 1.0 mm thick aluminium
sheet cladding, residential silencer, instruments and
protection as per standard specification, stop solenoid for auto
stop in the event of fault with audio indications, painted with post
office red colour etc. as required.
M.S fabricated, common base plate, coupling, coupling guard,
foundation bolts etc. as required.
Suitable cement concrete foundation duly plastered and with anti
vibration pads.
Note: *The head of the pump is selected in a manner so as to give a
minimum 3.5kgf/cm2 pressure at the highest/farthest point.
3 3 Supplying, installation, testing and commissioning of electric
driven pressurisation pump suitable for automatic operation
and consisting of following, complete in all respects, as required :
Horizontal type, multistage, centrifugal pump of cast iron body and
bronze impeller with stainless steel shaft, mechanical seal conforming
Suitable HP squirell cage induction motor TEFC type suitable for
operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class
of protection for enclosure, horizontal foot mounted type with
Class-'F' insulation,conforming to IS : 325.
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No DSR 2019/NON Description Unit Qty Rate DSR-2019 Rate NON Amount DSR Amount NON
M.S.fabricated Common base plate, coupling, coupling guard,
foundation bolts etc. as required.
Suitable cement concrete foundation duly plastered and with anti
vibration pads.
ELECTRICAL SYSTEM
4 DSR-2019 ITEM CONTROL PANELS
5.5 Fabrication, supply, Insallation testing & commissioning of Electrical Set 1 449335.00 449335.00 0.00
control panel of cubical construction, floor mounted type, fabricated
out of 2mm thick CRCA sheet, compartmentalised with hinged
lockable doors, dust and vermin proof, powder coated of
approved shade after 7 tank treatment process, cable alley, inter-
connection with suitable size copper conductor cable/solid
copper strip, having switchgears and accessories, mountings
and internal wiring, earth terminals, numbering etc. complete
in all respect, suitable for main fire pump, pressurisation pump
& diesel pump set complete as per CPWD specification with
following in coming and Outgoings, suitable for operation on
415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42
630A, 50kA 4 Pole MCCB, Ics=100% Icu Rating
Digital Voltmeter 0-500V with selector switch
Ammeter (0-630 A) with selector swtich & CTs etc.
LED type RYB phase indicating lamps, ON, OFF, trip indicating
Set of Copper Bus Bar 500Amps
( Note : All outgoing feeders for pumps should have digital
Ammeter with selector switches, and LED type ON, OFF, trip indicating
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No DSR 2019/NON Description Unit Qty Rate DSR-2019 Rate NON Amount DSR Amount NON
200 Amp, 50KA TPN MCCB, Ics=100% Icu, with fully automatic
Star/Delta starter suitable for 75 hp pump with overload
protection, current sensing type single phase preventor complete
with all acceessories and internal wiring required for
automatic operation, selector switch for local/remote,
auto/manual/OFF operation.- 3 sets
100 Amp, 50KA TPN MCCB, Ics=100% Icu, with Suitable HP
fully automatic Star/Delta starter with overload protection,
current sensing type single phase preventor complete with all
acceessories and internal wiring required for automatic operation,
selector switch for local/remote, auto/manual/OFF operation. - 2 sets
DIESEL ENGINE CONTROL
Control for diesel engine comprising -
Automatic/Manual selctor switch & 3 attempts starting device,
timers and relays as required, push buttons, start/stop in manual
Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp
and Engine on indication
Battery charger suitbale for 12V/24 V DC with boost and trickle
selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter
All standard relays and accessories for automatic operation of
System Controller
Designing, Supply, Installation, Testing and commissioning
of system controller to control operation of main electric fire
pump, diesel pump, Pressurization pump, Terrace pump in
sequence as per specification consisting of relays, timers.
Sensors, annunciation window for fault indication, complete as per
5 DSR-2019 ITEM Supplying and fixing of fire brigade connection of cast iron body
NO-19 with gun metal male instantaneous inlet couplings complete with
cap and chain as reqd. for suitable dia MS pipe connection
conforming to IS 904 as required :
5.01 19.1 2 way - 100 mm dia M.S. Pipe (FOR RINGMAIN) Each 1 6590.00 6590.00 0.00
5.02 19.2 4 way-150 mm dia M.S. Pipe (FOR FIRE WATER TANK) Each 1 13822.00 13822.00 0.00
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No DSR 2019/NON Description Unit Qty Rate DSR-2019 Rate NON Amount DSR Amount NON
6 NON DSR-1 Providing and fixing fire brigade suction hose coupling (draw out Each 1 6851.53 0.00 6851.53
connection) with nut for female coupling as per IS-902 complete with
100mm dia. Suction pipe and foot valve (to be connected to static
tank) complete as required and as per enclosed specification. (FOR
FIRE WATER TANK)
7 DSR-2019 ITEM Providing & fixing of pressure switch in M.S. pipe line including Each 5 1508.00 7540.00 0.00
NO-22 connection etc. as required.
8 DSR-2019 ITEM Supplying and fixing single headed internal hydrant valve with Each 12 5987.00 71844.00 0.00
NO-9 instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with
cast iron wheel ISI marked conforming to IS 5290 (Type -A)
with blank Gunmetal/Stainless Steel cap and chain as required :
8.01 9.2 Single headed Stainless steel
9 DSR-2019 ITEM Supplying and fixing Single headed external yard hydrant valve with 1 Each 8 5987.00 47896.00 0.00
NO-10 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling
and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with
blank Gunmetal/Stainless Steel cap and chain as required :
9.01 10.2 Single headed Stainless steel
10 DSR-2019 ITEM Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm Each 20 1648.00 32960.00 0.00
NO-18 nominal internal diameter size nozzle conforming to IS 903
suitable for instantaneous connection to interconnect hose pipe
coupling as required :
10.01 18.2 Stainless Steel (Grade 304)
11 DSR-2019 ITEM Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm Each 40 4434.00 177360.00 0.00
NO-16 dia male and female couplings duly bound with GI wire, rivets
etc. conforming to IS 636 (type-A) as required :
11.1 16.2 Stainless Steel (Grade 304)
12 DSR-2019 ITEM Supplying and fixing first-aid Hose Reel with MS construction
NO-17 spray painted in post office red, conforming to IS 884
complete with the following as required.
20 mm nominal internal dia water hose thermoplastic (Textile
reinforced) type -2 as per IS: 12585
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No DSR 2019/NON Description Unit Qty Rate DSR-2019 Rate NON Amount DSR Amount NON
20 mm nominal internal dia gun metal globe valve & nozzle.
Drum and brackets for fixing the equipmets on wall.
Connections from riser with 25 mm dia stop gun metal valve & M.S.
Pipe and socket.
13 DSR BASED Providing and fixing angle iron (40mmx40mmx5mm) door frame and Each 12 6956.11 0.00 83473.34
MS sheet (6mm thick) cum glass shutter of size 2.1mtrx0.9mtr(N.S.)
with 25mmx25mmx3mm angle frame all around and stiffened in
between i/c hinges, handle, locking arrangement, painting with
approved synthetic enamel paint i/c sign writing on glass at internal
hydrant including providing & fixing S.S. sheet 2mm thick on remaining
portion above door to close opening i/c painting etc. as required. Glass
shall be 6 mm thick.
14 DSR BASED Providing & fixing of MS fire Hose cabinet outdoor type of size 0.90 Each 8 6311.50 0.00 50492.03
Mx 0.60 Mx 0.50 M made of 6mm thick MS sheet with 6mm thick
glazed glass doors i/c necessary locking arrangement suitable to
accomodate 2nos 15m long hoses, one no branch pipe, etc. and
mounted on 400 mm height agle . The cabinet shall be painted with
red colour shade No. 536 of IS: 5 externally & white internally
complete in all respects for internal hydrant and as per enclosed
15 NON DSR-4 Providing and fixing stainless steel standard fireman's axe with heavy Each 12 1177.78 0.00 14133.38
insulated rubber handle tested to 20000 volts as per IS : 926 complete.
16 DSR-2019 ITEM Providing laying, testing & commissioning of 'C' class heavy duty MS
NO-6 Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges,
tapers, nuts bolts, gaskets etc. in ground including welding, excavation
& providing cement concrete blocks as supports, anticorrosive
treatment with coaltar/asphalt tape as per IS 10221, refilling the
trench etc. of following sizes complete as required.
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No DSR 2019/NON Description Unit Qty Rate DSR-2019 Rate NON Amount DSR Amount NON
17 DSR-2019 ITEM Providing, laying, testing & commissioning of 'C' class heavy duty MS
NO-7 pipe conforming to IS 3589/IS 1239 including Welding, fittings like
elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the
pipe on the wall/ceiling with suitable clamp/support frame and
painting with two or more coats of synthetic enamel paint
of required shade complete as required :
18 DSR-2019 ITEM Supplying, fixing, testing and commissioning of butterfly valve of PN
NO-11 1.6 rating with bronze/gunmetal seat duly ISI marked complete with
nuts, bolts, washers, gaskets conforming to IS 13095 of following
sizes as required :
19 DSR-2019 ITEM Supplying, fixing, testing & commissioning of double flanged sluice
NO-12 valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat,
ISI marked complete with nuts, bolts, washers, gaskets and conforming
to IS 780 of following sizes as required :
20 DSR-2019 ITEM Providing, installation, testing and commissioning of non-return
NO-14 valve of following sizes confirming to IS: 5312 complete with
rubber gasket, GI bolts, nuts, washers etc.as required :
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No DSR 2019/NON Description Unit Qty Rate DSR-2019 Rate NON Amount DSR Amount NON
21 DSR-2021-18.17 Providing and fixing gun metal gate valve with C.I. wheel of approved
quality (screwed end) :
22 DSR-2019 ITEM Providing, installation, testing and commissioning of stainless steel
NO-15 Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade
304, sheet with 3 mm dia holes with stainless steel flange.
23 NON DSR-5 Providing & fixing of 25mm dia. gunmetal air release valve with all Each 3 991.77 0.00 2975.31
fittings and forged ball valve on header complete as required and as
per enclosed specification.
24 NON DSR-6 Providing and fixing following size Pressure gauge (0-15 Kg/Cm2) Each 25 710.61 0.00 17765.30
complete with shut off valve duly calibrated before installation
complete as required & as per enclosed specification.
25 DSR-2019 ITEM Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS Set 6 18009.00 108054.00 0.00
NO-20 sheet, 1200 mm in height with air release valve on top and flanged
connection to riser, drain arrangement with 25 mm dia gun metal
wheel valve with required accessories, pressure gauge and
paintingwith synthetic enamel paint of approved shade as required.
26 NON DSR-7 Providing and fixing reinforced neoprene rubber vibration
eliminators/expansion joints (to provide relief from stresses at pipe
flanges) suitable for upto 20 kg/cm2 pressure, complete as per
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No DSR 2019/NON Description Unit Qty Rate DSR-2019 Rate NON Amount DSR Amount NON
27 NON DSR-8 Providing, fixing, testing & commissioning of Air Vessel fabricated Each 1 68827.36 0.00 68827.36
from 8 mm thick MS plate, 450 mm in diameter and 2 m in height with
dished ends fabricated from 8mm thick MS plate with Air release
valve with stop cock, flanged inlet connection and drain arrangement
with 25mm dia valve, pressure gauge with gun metal stop cock
complete with all accessories as required and conforming to IS 4736-
1968. (FOR FIRE PUMP ROOM)
Recommended dia. : 450 mm
Height of shell : 2000 mm
Working pressure : 7 Kg/Sq.cm
Test Pressure : 10 Kg/Sq.cm
28 DSR-2018 E&M- Supplying and drawing following sizes of FRLS PVC insulated copper
1.17 conductor, single core cable in the existing surface/ recessed steel/
PVC conduit as required.
29 NON DSR-9 Providing and fixing heavy duty copper armored cables 1.1 KVA grade
including necessary support clamps at ceiling level and connection legs
complete in all respects.
29.01 Power cable 3 core 16 Sq.mm Metre 30 846.91 0.00 25407.17
29.02 Power cable 3 core 95 Sq.mm Metre 45 3499.91 0.00 157496.14
30 DSR-2018 E&M- Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop Metre 150 57.00 8550.00 0.00
5.16 earthing as requried.
31 DSR-2018 E&M- Supplying and installing following size of perforated painted with
4.1 powder coating M.S. cable trays with perforation not more than
17.5%, in convenient sections, joined with connectors, suspended
from the ceiling with M.S. suspenders including bolts & nuts, painting
suspenders etc as required.
31.01 4.1.2 150mm width x 50mm depth x 1.6 mm thickness. Metre 40 531.00 21240.00 0.00
31.02 4.1.4 300mm width x 50mm depth x 1.6 mm thickness. Metre 30 621.00 18630.00 0.00
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No DSR 2019/NON Description Unit Qty Rate DSR-2019 Rate NON Amount DSR Amount NON
32 DSR-2018 E&M- Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below Metre 60 131.00 7860.00 0.00
5.9 ground as strip earth electrode, including connection/ terminating
with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be
done by overlapping and with 2 sets of G.I. nut bolt & spring washer
spaced at 50mm)
33 DSR-2019 ITEM Providing, fixing, testing & commissioning of installation
NO-24 control valve of cast iron body, brass/bronze working parts
comprising of water motor alarm, bronze seat clapper, clapper
arm and hydraulically driven mechanical gong bell to sound
continuous alarm when the wet riser/sprinkler system activates,
pressure gauges, emergency releases, strainer, pressure switch,
cock valve complete with drain valve and bypass, test control box,
ball valves, MS pipe of required size, flanges, orifice plate, gasket etc
of follwing sizes as required :
34 DSR-2019 ITEM Providing & fixing flow switch in following sizes M.S. pipe including
NO-23 connection etc as required.
35 NON DSR-10 Providing, fixing, inspecting, testing of built in drain assembly with
sight glass for installation on Sprinkler System, in brass body consisting
of steel single lever ball valve for multiple test and drain functions,
including inlet connection of specified size, sight glass, connections to
the main header and line drain complete as per requirements. Product
shall suitable for min. 10 kg/cm2 working pressure and shall be UL
Listed / FM Approved.
50mm Drain size and 15mm (5.6K) Testing Orifice Set 4 10283.73 0.00 41134.92
AUTOMATIC SPRINKLER SYSTEM
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No DSR 2019/NON Description Unit Qty Rate DSR-2019 Rate NON Amount DSR Amount NON
36 DSR-2019 ITEM Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb
NO-21 type sprinklers of rating 68 degree centigrade with required
36.01 21.1 Pendent Sprinkler Each 262 484.00 126808.00 0.00
36.02 21.2 Upright Sprinkler Each 362 484.00 175208.00 0.00
37 DSR-2019 ITEM Supplying, installation, testing & commissioning of sprinkler
NO-25 flexible pipe (UL Listed) of stainless steel complete with 15 NPT
on reducer thread with maximum working pressure of 175 PSI test
pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT
male thread to sprinkler head (Outlet) 15mm NPT female thread
with reducer, nipple, 2 side brackets, center bracket, stockbar of
following sizes complete as required.
38 DSR-2019 ITEM Providing, installation, testing & commissioning of adjustable rosette Each 10 207.00 2070.00 0.00
NO-29 plate for 15mm dia in white finish UL Listed or FM approved complete
39.00 DSR-2019 ITEM Supplying, installation, testing & commissioning of deluge valve (to be
NO-26 used for water curtains) UL listed with wet pilot basic trim assembly
for DVA with test and alarm, drip and drain valve with water motor
gong complete as required.
40.00 DSR-2019 ITEM Providing, installation, testing & commissioning of water curtain Each 42 663.00 27846.00 0.00
NO-27 nozzle 15mm dia nickel chrome plated brass, BSPT, K-factor as per
design consideration complete as required.
FIRE EXTINGUISHER
41 NON DSR-11 Supply, installation, testing and commissioning ISI marked (IS:15683) Each 28 7163.55 0.00 200579.46
Fire Extinguisher, Carbon-di-oxide type capacity 4.5 Kg. Flat base
including valve, discharge hose of not less than 10 mm dia, 1M long
and complete in all respects including initial fill with CO2 gas
conforming to IS:307-1966 and wall suspension braket as required as
per specifications.
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
S.No DSR 2019/NON Description Unit Qty Rate DSR-2019 Rate NON Amount DSR Amount NON
42 NON DSR-12 Supply, installation, testing and commissioning of 6kg ABC (Powder Each 28 2980.46 0.00 83452.77
Type) Fire Extinguisher. Mild Steel Cylinders ISI marked fitted with
pressure indicating gauge, internal tube, squeeze lever type valve fully
charged with ABC 90 powder (Mono Ammonium Phosphate)
pressured by Nitrogen complete in all respects including wall
suspension bracket and conforming to IS:15683 as required as per
specifications.
43 NON DSR-13 Supply, installation, testing and commissioning ISI marked (IS:15683) Each 4 4121.38 0.00 16485.51
portable fire extinguisher, water (gas pressure) type capacity 9 ltr. with
gun metal cap and nozzle and complete in all respects including initial
fill and wall suspension brackets as required as per specifications. FOR
PUMP ROOM,GUARD ROOM & UTILITY BUILDING
44 NON DSR-14 Providing and fixing CO2 type fire extinguishers consisting of welded Each 2 20517.74 0.00 41035.49
M.S. cylindrical body automatic modular CO2 type extinguisher
actuated through a sprinkler head mounted on The extinguisher body
finished externally with red enamel with trolly mounted complete with
internal charge.(Capacity 22.5 Kg.) FOR PUMP ROOM & UTILITY
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
Name of Work- Construction and development of Pre Engineered Manufacturing Unit at Industrial Plot No. B-208, at sector Phase-II, Noida
Internal Plumbing work
SI.No. DSR-2021/ NON Description of Item UNIT TOTAL QUANTITY DSR RATE NON DSR RATE DSR AMOUNT NON DSR AMOUNT
SUB HEAD - INTERNAL PLUMBING WORKS
A) SANITARY INSTALLATION
1.01 17.2 Providing and fixing white vitreous china pedestal type
water closet (European type W.C. pan) with seat and
lid, 10 litre low level white P.V.C. flushing cistern,
including flush pipe, with manually controlled device
(handle lever), conforming to IS : 7231, with all fittings
and fixtures complete, including cutting and making
good the walls and floors wherever required.
17.2.1 W.C. pan with ISI marked white solid plastic seat and Each 2 5540.55 11081.10 0.00
1.02 17.1 Providing and fixing water closet squatting pan (Indian
type W.C. pan ) with 100 mm sand cast Iron P or S
trap, 10 litre low level white P.V.C. flushing cistern,
including flush pipe, with manually controlled device
(handle lever) conforming to IS : 7231, with all fittings
and fixtures complete, including cutting and making
good the walls and floors wherever required:
17.1.1 White Vitreous china Orissa pattern W.C. pan of size Each 8 5781.35 46250.80 0.00
580x440 mm with integral type foot rests
1.03 17.80 Providing and fixing white vitreous china battery Each 8 7004.45 56035.60 0.00
based infrared sensor operated urinal of approx. size
610 x 390 x 370 mm having pre & post flushing with
water (250 ml & 500 ml consumption), having water
inlet from back side, including fixing to wall with
suitable brackets all as per manufacturers
specification and direction of Engineer-in-charge.
1.04 8.10 Providing and fixing stone slab with table rubbed,
edges rounded and polished, of size 75x50 cm deep
and 1.8 cm thick, fixed in urinal partitions by cutting a
chase of appropriate width with chase cutter and
embedding the stone in the chase with epoxy grout or
with cement concrete 1:2:4 (1 cement : 2 coarse sand
: 4 graded stone aggregate 6 mm nominal size) as per
direction of Engineer-in-charge and finished smooth.
8.10.2 Granite Stone of approved shade Sqm 3 3542.85 10628.55 0.00
1.05 18.21.2.1 Providing and fixing uplasticised PVC connection pipe Each 24 85.20 2044.80 0.00
with brass unions : 45 cm length , 15 mm nominal bore
1.06 17.7 Providing and fixing wash basin with C.I. brackets, 15
mm C.P. brass pillar taps, 32 mm C.P. brass waste of
standard pattern, including painting of fittings and
brackets, cutting and making good the walls wherever
17.7.4 White Vitreous China Flat back wash basin size Each 8 1679.60 13436.80 0.00
550x400 mm with single 15 mm C.P. brass pillar tap
1.07 17.31 Providing and fixing 600x450 mm beveled edge mirror Each 8 1411.15 11289.20 0.00
of superior glass (of approved quality) complete with 6
mm thick hard board ground fixed to wooden cleats
with C.P. brass screws and washers complete.
1.08 17.34 Providing and fixing toilet paper holder :
1.09 17.71 Providing and fixing PTMT liquid soap container 109 Each 6 146.30 877.80 0.00
mm wide, 125 mm high and 112 mm distance from
wall of standard shape with bracket of the same
materials with snap fittings of approved quality and
colour, weighing not less than 105 gms.
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
SI.No. DSR-2021/ NON Description of Item UNIT TOTAL QUANTITY DSR RATE NON DSR RATE DSR AMOUNT NON DSR AMOUNT
1.10 17.22A Providing and fixing CP Brass 32mm size bottle trap of Each 8 886.25 7090.00 0.00
approved quality & make and as per the direction of
engineer in charge.
1.11 17.72 Providing and fixing PTMT towel ring trapezoidal Each 6 204.70 1228.20 0.00
shape 215 mm long, 200 mm wide with minimum
distances of 37 mm from wall face with concealed
fittings arrangement of approved quality and colour,
weighing not less than 88 gms.
1.12 NON DSR Providing and fixing Coat Hook. Each 10 766.45 0.00 7664.55
1.13 NON DSR Providing ,Fixing of straight / offset type flexible single Each 10 560.91 0.00 5609.09
body push fit type WC pan connector of with integral
single mould sealing fins made of flexible EVA body to
be fixed with manufacture supplied grease, including
rubber bush / adaptor for use with uPVC pipe as
supplied with the pan connector.
1.14 18.49 Providing and fixing C.P. brass bib cock of approved Each 2 434.20 868.40 0.00
quality conforming to IS:8931 :
1.15 17.16a Providing and fixing 8mm dia C.P./S.S. Jet with flexible Each 2 299.35 598.70 0.00
tube upto 1meter long with S.S. Triangular plate to
european type W.C. Of approved quality and make as
approved by engineer in charge.
1.16 18.51 Providing and fixing C.P. brass long body bib cock of
approved quality conforming to IS standards and
weighing not less than 690 gms.
1.17 18.53.1 Providing and fixing C.P. brass angle valve for basin Each 24 500.35 12008.40 0.00
mixer and geyser points of approved quality
conforming to IS:8931 15mm nominal bore
1.18 18.65 Providing and fixing PTMT soap Dish Holder having Each 2 96.75 193.50 0.00
length of 138mm, breadth 102mm, height of 75mm
with concealed fitting arrangements, weighing not less
1.19 17.73 Providing and fixing PTMT towel rail complete with
brackets fixed to wooden cleats with CP brass screws
with concealed fittings arrangement of approved
quality and colour.
17.73.1 450 mm long towel rail with total length of 495 mm, Each 2 573.60 1147.20 0.00
78 mm wide and effective height of 88 mm, weighing
not less than 170 gms
1.20 NON DSR Providing & Fixing of Grab bar 600 mm of non slipping Each 4 4753.64 0.00 19014.55
grip as per standard specification of use in disabled
toilet complete with brackets suitable for wall
installation as per approved sample complete in all
TOTAL FOR SANITARY INSTALLATION 184641.00 32288.00
B) WATER SUPPLY
2.01 18.8 Providing and fixing Chlorinated Polyvinyl Chloride
(CPVC) pipes, having thermal stability for hot & cold
water supply, including all CPVC plain & brass
threaded fittings, i/c fixing the pipe with clamps at
1.00 m spacing. This includes jointing of pipes &
fittings with one step CPVC solvent cement and the
cost of cutting chases and making good the same
including testing of joints complete as per direction of
Engineer in Charge.
Concealed work, including cutting chases and making
good the walls etc.
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
SI.No. DSR-2021/ NON Description of Item UNIT TOTAL QUANTITY DSR RATE NON DSR RATE DSR AMOUNT NON DSR AMOUNT
e) Based on DSR-2021 40 mm nominal bore Mtr. 18 497.00 8747.20 0.00
2.02 18.7 Providing and fixing Chlorinated Polyvinyl Chloride
(CPVC) pipes, having thermal stability for hot & cold
water supply, including all CPVC plain & brass
threaded fittings, including fixing the pipe with clamps
at 1.00 m spacing. This includes jointing of pipes &
fittings with one step CPVC solvent cement and testing
of joints complete as per direction of Engineer in
Internal work - Exposed on wall
2.03 NON DSR Providing and fixing Forged Brass Ball Valve (Screwed).
with setting and gland of superior quality having
minimum working pressure of 16 kg/cm2.
a) 15 mm nominal bore Each 2 579.09 0.00 1158.18
b) 20 mm nominal bore Each 2 763.64 0.00 1527.27
c) 25 mm nominal bore Each 1 1125.45 0.00 1125.45
d) 32 mm nominal bore Each 2 1844.55 0.00 3689.09
e) 40 mm nominal bore Each 4 2635.45 0.00 10541.82
2.04 18.62 Providing and fixing PTMT Ball cock of approved
quality, colour and make complete with Epoxy coated
aluminium rod with L.P./ H.P.H.D. plastic ball.
a) 18.62.4 40 mm nominal bore, 206mm long, weighing not less Each 1 653.40 653.40 0.00
2.05 18.48 Providing and placing on terrace (at all floor levels) per litre 30000 9.70 291000.00 0.00
polyethylene water storage tank, ISI : 12701 marked,
with cover and suitable locking arrangement and
making necessary holes for inlet, outlet and overflow
pipes but without fittings and the base support for
2.06 NON DSR Providing & fixing Auto Air vent for cold water supply
risers, suitable for pressure not less than 15 Kg/Sq.cm.
TOTAL FOR WATER SUPPLY 418054.00 18944.00
C) INTERNAL DRAINAGE
Providing and fixing soil, waste and vent pipes
3.01 NON DSR Providing, fixing & testing uPVC SWR pipes confirming
to IS 13592 (Type B) alongwith all required fittings like
tees, bends, crosses with or without access doors
jointed with approved solvent cement as per
manufacturer's recommendations, fixed to walls and
ceilings with clamps complete including cutting and
making good the floors and walls where required
complete of outer diameter.
3.02 NON DSR Providing, fixing, jointing and testing in position the
following uPVC pipes conforming to IS 4985 of 6
kg/sqcm pressure rating including all fittings, solvent
weld joints, testing complete for drainage system cut
to required length to be laid under floor including
covering all around with cement concrete and making
good the same complete as required.
For waste pipes
(a) 40mm OD (6 kg pressure) Metre 11 371.82 0.00 4090.00
(b) 50mm OD (6 kg pressure) Metre 7 491.82 0.00 3246.00
(c) 63mm OD (6 kg pressure) Metre 13 727.27 0.00 9600.00
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
SI.No. DSR-2021/ NON Description of Item UNIT TOTAL QUANTITY DSR RATE NON DSR RATE DSR AMOUNT NON DSR AMOUNT
3.03 NON DSR Providing and Fixing 110x110 mm uPVC 'P' trap with
Height riser/Saddle as required size ftting with seal 50
mm of self cleansing design floor/urinal trap without
vent suspended with supporting clamp or in sunken
portion including cutting and making good the walls
and floors wherever required complete in all respects.
3.04 NON DSR Providing and Fixing uPVC floor drain of following
size inlet and outlet including cutting and making good
the walls and floors wherever required complete in all
3.05 NON DSR Providing and fixing 125 mm dia, 3 mm thick Stainless
steel grating with frame for floor traps or drains of
required pattern including cutting and making good
the floors complete.
3.06 NON DSR Providing & fixing PVC clean out plug with suitable
insert keys for opening in: brass cap, male threaded
joint with threaded uPVC socket fixed to uPVC pipe
joints as required complete in all respects.
TOTAL FOR DRAINAGE 0.00 209534.00
D) RAIN WATER WORK
4.01 12.41 Providing and fixing on wall face unplasticised Rigid
PVC rain water pipes conforming to IS : 13592 Type A,
including jointing with seal ring conforming to IS :
5382, leaving 10 mm gap for thermal expansion, (i)
Single socketed pipes.
4.02 12.42 Providing and fixing on wall face unplasticised - PVC
moulded fittings/ accessories for unplasticised Rigid
PVC rain water pipes conforming to IS : 13592 Type A
including jointing with seal ring conforming to IS :
5382 leaving 10 mm gap for thermal expansion.
a) 12.42.2 Single Push fit coupler
b) 12.42.3 Single Tee with door
c) 12.42.5 Bend 87.5 Deg
d) 12.42.6 Shoe (Plain)
4.03 12.44 Providing and fixing to the inlet mouth of rain water Each 35 47.90 1676.50 0.00
pipe cast iron grating 15 cm diameter and weighing
not less than 440 grams.
4.04 12.43 Providing and fixing unplasticised -PVC pipe clips of
approved design to unplasticised - PVC rain water
pipes by means of 50x50x50 mm hard wood plugs,
screwed with M.S. screws of required length, including
cutting brick work and fixing in cement mortar 1:4 (1
cement : 4 coarse sand) and making good the wall etc.
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
SI.No. DSR-2021/ NON Description of Item UNIT TOTAL QUANTITY DSR RATE NON DSR RATE DSR AMOUNT NON DSR AMOUNT
4.05 12.22 Making khurras 45x45 cm with average minimum Each 5 266.60 1333.00 0.00
thickness of 5 cm cement concrete 1:2:4 (1 cement : 2
coarse sand : 4 graded stone aggregate of 20 mm
nominal size) over P.V.C. sheet 1 m x1 m x 400 micron,
finished with 12 mm cement plaster 1:3 (1 cement : 3
coarse sand) and a coat of neat cement, rounding the
edges and making and finishing the outlet complete.
TOTAL FOR RAIN WATER WORK 186418.00 0.00
TOTAL INTERNAL PLUMBING 789113.00 260766.00
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
Name of Work- Construction and development of Pre Engineered Manufacturing Unit at Industrial Plot No. B-208, at sector Phase-II, Noida
External Plumbing Work
SI.No. DSR-2021/ NON DSR Description of Item UNIT TOTAL DSR RATE NON DSR DSR AMOUNT NON DSR
QUANTITY RATE AMOUNT
SUB HEAD - EXTERNAL PLUMBING WORKS
A) EXTERNAL WATER SUPPLY
1.01 18.12 Providing and fixing G.I. pipes complete with G.I.
fittings including trenching and refilling etc.
a) 18.12.6 50 mm nominal dia Pipes Metre 230 654.20 150466.00 0.00
b) 18.12.5 40 mm nominal dia Pipes Metre 40 558.35 22334.00 0.00
1.02 18.40 Painting G.I. pipes and fittings with two coats of anti-
corrosive bitumastic paint of approved quality :
a) 18.40.6 50 mm dia nominal bore Metre 230 25.25 5807.50 0.00
b) 18.40.5 40 mm dia nominal bore Metre 40 20.95 838.00 0.00
1.03 18.41 Providing and filling sand of grading zone V or coarser
grade alround the GI pipes in external work.
a) 18.41.6 50mm dia nominal bore Metre 230 176.90 40687.00 0.00
b) 18.41.5 40mm dia nominal bore Metre 40 170.50 6820.00 0.00
1.04 18.13 Making connection of G.I. distribution branch with
G.I. main of following sizes by providing and fixing
tee, including cutting and threading the pipe etc.
1.05 19.6 Providing and laying non-pressure NP2 class (light
duty) R.C.C. pipes with collars jointed with stiff
mixture of cement mortar in the proportion of 1:2 (1
cement : 2 fine sand) including testing of joints etc.
a) 19.6.1 100 mm dia. R.C.C. pipe (hume pipe) Metre 10 447.25 4472.50 0.00
1.06 18.60 Providing and fixing enclosed type water meter (bulk
type) conforming to IS : 2373 and tested by Municipal
Board complete with bolts, nuts, rubber insertions
etc. (The tail pieces if required will be paid
1.07 Based on DSR-E&M- Providing & fixing of following sizes of butterfly valve
2018,16.11.1 of rating PN 16, wafer type, in cast iron body with
Ductile Iron disc, EPDM seal, SS single piece shaft,
conforming to IS-13095 of the following sizes
complete with cast iron hand lever companion
flanges, bolts, nuts, washers & inserted rubber
gaskets, as required and as per enclosed
1.08 18.34 Constructing masonry Chamber 90x90x100 cm inside,
in brick work in cement mortar 1:4 (1 cement : 4
coarse sand) for sluice valve, with C.I. surface box 100
mm top diameter, 160 mm bottom diameter and 180
mm deep (inside) with chained lid and RCC top slab
1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size ), i/c necessary
excavation, foundation concrete 1:5:10 (1 cement : 5
fine sand : 10 graded stone aggregate 40 mm nominal
size ) and inside plastering with cement mortar 1:3 (1
cement : 3 coarse sand) 12 mm thick, finished with a
floating coat of neat cement complete as per
standard design :
a) 18.34.1 With common burnt clay F.P.S.(non modular) bricks Each 1 17577.90 17577.90 0.00
of class designation 7.5
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
SI.No. DSR-2021/ NON DSR Description of Item UNIT TOTAL DSR RATE NON DSR DSR AMOUNT NON DSR
QUANTITY RATE AMOUNT
TOTAL FOR EXTERNAL SUPPLY 266344.00 0.00
B) GARDEN IRIGATION SUPPLY
2.01 18.12 Providing and fixing G.I. pipes complete with G.I.
fittings including trenching and refilling etc.
a) 18.12.6 50 mm nominal dia Pipes Metre 372 654.20 243362.40 0.00
b) 18.12.3 25 mm nominal dia Pipes Metre 11 417.95 4597.45 0.00
2.02 18.40 Painting G.I. pipes and fittings with two coats of anti-
corrosive bitumastic paint of approved quality :
a) 18.40.6 50mm dia nominal bore Metre 372 25.25 9393.00 0.00
a) 18.40.3 25mm dia nominal bore Metre 11 15.25 167.75 0.00
2.03 18.41 Providing and filling sand of grading zone V or coarser
grade alround the GI pipes in external work.
a) 18.41.6 50 mm dia nominal bore Metre 65 176.90 11498.50 0.00
2.04 19.6 Providing and laying non-pressure NP2 class (light
duty) R.C.C. pipes with collars jointed with stiff
mixture of cement mortar in the proportion of 1:2 (1
cement : 2 fine sand) including testing of joints etc.
a) 19.6.1 100 mm dia. R.C.C. pipe (hume pipe) Metre 32 447.25 14312.00 0.00
2.05 Based on DSR-E&M- Providing & fixing of following sizes of butterfly valve
2018,16.11.1 of rating PN 16, wafer type, in cast iron body with
Ductile Iron disc, EPDM seal, SS single piece shaft,
conforming to IS-13095 of the following sizes
complete with cast iron hand lever companion
flanges, bolts, nuts, washers & inserted rubber
gaskets, as required and as per enclosed
2.06 NON DSR Providing & fixing in position 25 mm dia lawn Each 11 2748.18 0.00 30230.00
hydrants consisting of 25 mm dia Ball valve, GI nipple
and threaded hose receiver complete as required.
TOTAL FOR GARDEN IRIGATION SUPPLY 285875.00 30230.00
C) EXTERNAL SEWAGE WORK
3.01 2.10 Excavating trenches of required width for pipes,
cables, etc including excavation for sockets,
anddressing of sides, ramming of bottoms, depth up
to 1.5 m, including getting out the excavated soil, and
then returning the soil as required, in layers not
exceeding 20 cm in depth, including
consolidatingeach deposited layer by ramming,
watering, etc. and disposing of surplus excavated soil
as directed,within a lead of 50 m :
2.10.1 All kinds of soil
2.10.1.2 Pipes, cables etc. exceeding 80 mm dia but not metre 77 417.35 32135.95 0.00
exceeding 300 mm dia
3.02 2.8 Earth work in excavation by mechanical means
(Hydraulic excavator) /manual means in foundation
trenches or drains (not exceeding 1.5 m in width or
10 Sqm on plan), including dressing of sides and
ramming of bottoms, lift upto 1.5 m, including getting
out the excavated soil and disposal of surplus
excavated soil as directed, within a lead of 50 m.
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
SI.No. DSR-2021/ NON DSR Description of Item UNIT TOTAL DSR RATE NON DSR DSR AMOUNT NON DSR
QUANTITY RATE AMOUNT
3.03 NON DSR Supplying and laying of following size DWC SN8 pipe
ISI marked along with all accessories like socket,
bend, couplers etc. conforming to IS 16098, Part II
complete with fitting and cutting,jointing etc.direct in
ground (75 cm below ground level) including
excavation and refilling the trench but excluding sand
cushioning and protective covering etc., complete as
3.04 19.2 Providing and laying cement concrete 1:5:10 (1
cement : 5 coarse sand : 10 graded stone aggregate
40 mm nominal size) all-round S.W. pipes including
bed concrete as per standard design :
a) 19.2.3 200 mm diameter S.W. pipe metre 77 1276.70 98305.90 0.00
3.05 19.4.1.1 Providing and fixing square-mouth S.W. gully trap Each 3 2453.55 7360.65 0.00
class SP-1 complete with C.I. grating brick masonry
chamber with water tight C.I. cover with frame of
300x300 mm size (inside) the weight of cover to be
not less than 4.50 kg and frame to be not less than
2.70 kg as per standard design: 100x100 mm size P
type. With common burnt clay F.P.S. (non modular)
bricks of class designation 7.5
3.06 19.7 Constructing brick masonry manhole in cement
mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top
slab with 1:2:4 mix (1 cement : 2 coarse sand : 4
graded stone aggregate 20 mm nominal size),
foundation concrete 1:4:8 mix (1 cement : 4 coarse
sand : 8 graded stone aggregate 40 mm nominal size),
inside plastering 12 mm thick with cement mortar 1:3
(1 cement : 3 coarse sand) finished with floating coat
of neat cement and making channels in cement
concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded
stone aggregate 20 mm nominal size) finished with a
floating coat of neat cement complete as per
standard design :
Inside size 90x80 cm and 45 cm deep including C.I.
cover with frame (light duty) 455x610 mm internal
dimensions,total weight of cover and frame to be not
less than 38 kg (weight of cover 23 kg and weight of
19.7.1.1 With common burnt clay F.P.S.(non modular) bricks Each 2 11687.10 23374.20 0.00
of class designation 7.5
3.07 19.8 Extra for depth for manholes:
Size 90x80x90 cm
19.8.1.1 With common burnt clay F.P.S.(non modular) bricks Mtr 0.30 8127.45 2438.24 0.00
of class designation 7.5
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
SI.No. DSR-2021/ NON DSR Description of Item UNIT TOTAL DSR RATE NON DSR DSR AMOUNT NON DSR
QUANTITY RATE AMOUNT
3.08 19.9 Constructing Brick Masonry circular type manhole
0.91 m internal dia at bottom and 0.56m dia at top
with FPS bricks class designation 75 in cement
mortar 1:4 (1 cement : 4 Coarse sand), inside cement
plaster 12mm thick with cement mortar 1:3 ( 1
cement : 3 coarse sand) finished with a floating coat
of of neat cement, foundation concrete 1:3:6 mix ( 1
cement : 3 coarse sand : 6 graded stone aggregate
40mm nominal size) and making necessary channel in
Cement Concrete 1:2:4 ( 1 Cement : 2 Coarse Sand : 4
Graded Stone Aggregate 20mm nominal size) finished
with a floating coat of neat cement complete as per
standard design.
19.9.1 0.91m deep with SFRC cover and frame (heavy duty
HD-20 grade designation) 560mm internal diameter
conforming to I.S:12592, total weight of cover and
frame to be not less than 182Kg. fixed in cement
concrete 1:2:4 mix (1cement: 2 coarse sand: 4 graded
stone aggregate 20mm nominal size) including
centering, shuttering all complete.(Excavation foot
rests and 12mm thick cement plaster at the external
surface shall be paid for separately)
19.9.1.1 with common burnt clay F.P.S.(non module) brick of Each 4 11886.45 47545.80 0.00
class designation 7.5
3.09 19.10 Extra depth for circuler type manholes 0.91 m
internal dia ( at bottom ) beyond 0.91m to 1.67 m .
19.10.1 with common burnt clay F.P.S.(non module) brick of Meter 0.4 6986.80 2794.72 0.00
class designation 7.5
3.08 19.16 Providing orange colour safety foot rest of minimum Each 16 487.10 7793.60 0.00
6 mm thick plastic encapsulated as per IS : 10910, on
12 mm dia steel bar conforming to IS: 1786, having
minimum cross section as 23 mmx25 mm and over all
minimum length 263 mm and width as 165 mm with
minimum 112 mm space between protruded legs
having 2 mm tread on top surface by ribbing or
chequering besides necessary and adequate
anchoring projections on tail length on 138 mm as
per standard drawing and suitable to with stand the
bend test and chemical resistance test as per
specifications and having manufacture's permanent
identification mark to be visible even after fixing,
including fixing in manholes with 30x20x15 cm
cement concrete block 1:3:6 (1 cement : 3 coarse
sand : 6 graded stone aggregate 20 mm nominal size)
complete as per design.
3.09 13.7 12 mm cement plaster finished with a floating coat of
neat cement of mix :
TOTAL FOR EXTERNAL SEWAGE WORK 232617.00 58450.00
D) EXTERNAL STORM WATER WORK
4.01 2.10 Excavating trenches of required width for pipes,
cables, etc including excavation for sockets,
anddressing of sides, ramming of bottoms, depth up
to 1.5 m, including getting out the excavated soil, and
then returning the soil as required, in layers not
exceeding 20 cm in depth, including
consolidatingeach deposited layer by ramming,
watering, etc. and disposing of surplus excavated soil
as directed,within a lead of 50 m :
2.10.1 All kinds of soil
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
SI.No. DSR-2021/ NON DSR Description of Item UNIT TOTAL DSR RATE NON DSR DSR AMOUNT NON DSR
QUANTITY RATE AMOUNT
2.10.1.2 Pipes, cables etc. exceeding 80 mm dia but not metre 510 417.35 212848.50 0.00
exceeding 300 mm dia
2.10.1.3 Pipes, cables etc. exceeding 30 mm dia but not metre 102 651.55 66458.10 0.00
exceeding 600 mm dia
4.02 2.8 Earth work in excavation by mechanical means
(Hydraulic excavator) /manual means in foundation
trenches or drains (not exceeding 1.5 m in width or
10 Sqm on plan), including dressing of sides and
ramming of bottoms, lift upto 1.5 m, including getting
out the excavated soil and disposal of surplus
excavated soil as directed, within a lead of 50 m.
4.03 19.6 Providing and laying non-pressure NP2 class (light
duty) R.C.C. pipes with collars jointed with stiff
mixture of cement mortar in the proportion of 1:2 (1
cement : 2 fine sand) including testing of joints etc.
For storm water pipe
19.6.3 250 mm dia. R.C.C. pipe For Electrical Road Crossing metre 50 811.15 40557.50 0.00
19.6.4 300 mm dia. R.C.C. pipe For Electrical Road Crossing metre 200 902.05 180410.00 0.00
4.04 19.35 Providing and laying Non Pressure NP-3 class
(Medium duty) R.C.C. pipes including collars/spigot
jointed with stiff mixture of cement mortar in the
proportion of 1:2 (1 cement : 2 fine sand) including
testing of joints etc. complete
For storm water pipe road crossing
4.05 19.3 Providing and laying cement concrete 1:5:10 (1
cement : 5 coarse sand : 10 graded stone aggregate
40 mm nominal size) up to haunches of RCC. pipes
including bed concrete as per standard design :
d) Analysed dsr 19.3.5 450 mm dia. R.C.C. pipe metre 70 1430.18 0.00 100112.73
19.3.4 250 mm dia. R.C.C. pipe For Electrical Road Crossing metre 50 943.90 47195.00 0.00
19.3.5 300 mm dia. R.C.C. pipe For Electrical Road Crossing metre 200 1089.10 217820.00 0.00
4.06 19.2 Providing and laying cement concrete 1:5:10 (1
cement : 5 coarse sand : 10 graded stone aggregate
40 mm nominal size) all-round RCC pipes including
bed concrete as per standard design :
For Storm Water road crossing
a) Analysed dsr 19.2.4 450 mm dia. R.C.C. pipe metre 32 1947.18 0.00 62309.82
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
SI.No. DSR-2021/ NON DSR Description of Item UNIT TOTAL DSR RATE NON DSR DSR AMOUNT NON DSR
QUANTITY RATE AMOUNT
4.07 19.9 Constructing Brick Masonry circular type manhole
0.91 m internal dia at bottom and 0.56m dia at top
with FPS bricks class designation 75 in cement
mortar 1:4 (1 cement : 4 Coarse sand), inside cement
plaster 12mm thick with cement mortar 1:3 ( 1
cement : 3 coarse sand) finished with a floating coat
of of neat cement, foundation concrete 1:3:6 mix ( 1
cement : 3 coarse sand : 6 graded stone aggregate
40mm nominal size) and making necessary channel in
Cement Concrete 1:2:4 ( 1 Cement : 2 Coarse Sand : 4
Graded Stone Aggregate 20mm nominal size) finished
with a floating coat of neat cement complete as per
standard design.
19.9.1 0.91m deep with SFRC cover and frame (heavy duty
HD-20 grade designation) 560mm internal diameter
conforming to I.S:12592, total weight of cover and
frame to be not less than 182Kg. fixed in cement
concrete 1:2:4 mix (1cement: 2 coarse sand: 4 graded
stone aggregate 20mm nominal size) including
centering, shuttering all complete.(Excavation foot
rests and 12mm thick cement plaster at the external
surface shall be paid for separately)
19.9.1.1 with common burnt clay F.P.S.(non module) brick of Each 21 11886.45 249615.45 0.00
class designation 7.5
4.08 19.10 Extra depth for circuler type manholes 0.91 m
internal dia ( at bottom ) beyond 0.91m to 1.67 m .
19.10.1 with common burnt clay F.P.S.(non module) brick of Meter 2.1 6986.80 14672.28 0.00
class designation 7.5
4.09 19.16 Providing orange colour safety foot rest of minimum Each 63 487.10 30687.30 0.00
6 mm thick plastic encapsulated as per IS : 10910, on
12 mm dia steel bar conforming to IS: 1786, having
minimum cross section as 23 mmx25 mm and over all
minimum length 263 mm and width as 165 mm with
minimum 112 mm space between protruded legs
having 2 mm tread on top surface by ribbing or
chequering besides necessary and adequate
anchoring projections on tail length on 138 mm as
per standard drawing and suitable to with stand the
bend test and chemical resistance test as per
specifications and having manufacture's permanent
identification mark to be visible even after fixing,
including fixing in manholes with 30x20x15 cm
cement concrete block 1:3:6 (1 cement : 3 coarse
sand : 6 graded stone aggregate 20 mm nominal size)
complete as per design.
4.10 13.7 12 mm cement plaster finished with a floating coat of
neat cement of mix :
4.11 19.28 Constructing brick masonry road gully chamber
45x45x77.5 cm with bricks in cement mortar 1:4 (1
cement : 4 coarse sand ) with precast R.C.C. vertical
grating complete as per standard design :
19.28.1 with common burnt clay F.P.S.(non module) brick of Each 32 6258.20 200262.40 0.00
class designation 7.5
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
SI.No. DSR-2021/ NON DSR Description of Item UNIT TOTAL DSR RATE NON DSR DSR AMOUNT NON DSR
QUANTITY RATE AMOUNT
4.12 19.29 Constructing brick masonry road gully chamber
110x50x77.5 cm with bricks in cement mortar 1:4 (1
cement : 4 coarse sand) including 500x450 mm
precast R.C.C. horizontal grating with frame and
vertical grating complete as per standard design :
19.29.1 with common burnt clay F.P.S.(non module) brick of Each 11 10596.95 116566.45 0.00
class designation 7.5
4.13 19.21 Making connection of drain or sewer line with
existing manhole including breaking into and making
good the walls, floors with cement concrete 1:2:4 mix
(1 cement : 2 coarse sand : 4 graded stone aggregate
20 mm nominal size) cement plastered on both sides
with cement mortar 1:3 (1 cement : 3 coarse sand),
finished with a floating coat of neat cement and
making necessary channels for the drain etc.
19.21.3 For pipes 350 to 450 mm diameter Each 1 1134.65 1134.65 0.00
TOTAL FOR EXTERNAL STORM WATER WORK 2542513.00 162423.00
E) RAIN WATER HARESTING PIT BOREWELL
5.01 23.1 Boring/drilling bore well of required dia for casing/
strainer pipe, by suitable method prescribed in IS:
2800 (part I), including collecting samples from
different strata, preparing and submitting strata
chart/ bore log, including hire & running charges of
all equipments, tools, plants & machineries required
for the job, all complete as per direction of Engineer-
in-charge, upto 90 metre depth below ground level.
Depth of Boring as per site condition
23.1.1 All types of soil
5.02 23.3 Supplying, assembling, lowering and fixing in vertical
position in bore well, unplasticized PVC medium well
casing (CM) pipe of required dia, conforming to IS:
12818, including required hire and labour charges,
fittings & accessories etc. all complete, for all depths,
as per direction of Engineer -in-charge.
23.3.3 200 mm nominal size dia Metre 60.00 951.95 57117.00 0.00
5.03 23.4 Supplying, assembling, lowering and fixing in vertical
position in bore well unplasticized PVC medium well
screen (RMS) pipes with ribs, conforming to IS:
12818, including hire & labour charges, fittings &
accessories etc. all complete, for all depths, as per
direction of Engineer-in-charge.
23.4.3 200 mm nominal size dia Metre 90.00 1099.25 98932.50 0.00
TOTAL HARVESTING PIT BOREWELL 244857.00 0.00
TOTAL EXTERNAL PLUMBING 35,72,206.00 2,51,103.00
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
Name of Work- Construction and development of Pre Engineered Manufacturing Unit at Industrial Plot No. B-208, at sector Phase-II, Noida
STP & WTP works
SI.No. DSR-2021/ NON Description of Item UNIT TOTAL DSR RATE NON DSR DSR AMOUNT NON DSR
DSR QUANTITY RATE AMOUNT
SUB HEAD- STP & WTP WORKS
A) WATER SUPPLY PUMPS & EQUIPMENTS
1.01 NON DSR Pumps
Supply Installation testing and commissioning of Vertical/horizontal
monoblock centrifugal transfer pumping set with SS-316 body and SS-316
impeller, SS-316 shaft mechanical seal, connected to a TEFC induction
motor suitable for 415 volts ± 3% phase 50 cycles AC supply with a common
suction header with valves on main connecting & pumps inlet and a
common delivery header with valves, includingt water shock absorber, non
return valves with MS galvanized supports and painting with one coat of
primer and two coats of synthetic enamel paint including a 100mm dia
pressure gauge, Vibration eliminating pads under foundation, all mounted
on a common base plate of MS 80x40mm I section bolted to RCC
foundation, including control panel complete in all respects.
(i) NON DSR FOR FILTER FEED PUMP
No. of Pumps: 2 (1 Working + 1 Stand by )
Capacity : 90 LPM
(ii) NON DSR FOR GARDEN IRRIGATION PUMP
No. of Pumps: 2 (1 Working + 1 Stand by )
Capacity : 70 LPM
(iii) NON DSR FOR DOMESTIC WATER SUPPLY PUMP
No. of Pumps: 2 (1 Working + 1 Stand by )
Capacity : 90 LPM
1.02 NON DSR Submersible single stage single entry pumps with C.I.body and C.I. two vane
enclosed type impeller connected to TEFC submersible motor for 415 volts,
3 phase, 50 cycles including MCC panel with level controllers, auto control,
sequential change over facility with one proper working at low level & two
proper working at high level with an audible alarm including all
interconnectivity cables, with both pumps connected to common outlet
header including valves, non return valves, lifting chains etc. complete in all
(one working + one standby/both working in high flow conditions)
PUMP ROOM SUMP PUMP
(Solid handiling capacity 10-12mm)
Capacity- 200 lpm (Each)
1.03 Providing and fixing vertical type skid mounted of required diameter. The
shell shall be fabricated from M.S. plates conforming to IS: 2041 suitable to
withstand design pressure. The minimum thickness of shell shall be 6 mm &
dished shall be 8 mm thick which shall include corrosion allowance and mill
allowance respectively. The scaling allowance on dished ends to be
considered by the bidder as per requirement of IS:2825.
a) One no. pressure tight manholes and at least one no. pressure tight side
hole for maintenance purposes.
b) Initial charge of Filter Media.
c) Complete underdrain system and raw water distributor as per
manufacturer's design.
Complete MS C Class frontal face piping conforming to IS:1239) and valves
battery with CI Butterfly valves, pressure gauges and sampling points at
inlet and outlet. etc. covering all functions of service, backwash, rinse, air
e) Pressure gauges (100 mm dia bourdon type pressure gauge)/ sampling
points as per manufacturer design.
f) All internal parts of the filtration plant shall be coated with two coats of
epoxy paint after thorough sand blasting. All external surfaces of the plant
including piping shall be coated with two coats of red iron oxide/zinc
chromate primer followed by two coats of high gloss enamel paint .
g) The filter shall be complete with all gaskets/fasteners of standard quality
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
SI.No. DSR-2021/ NON Description of Item UNIT TOTAL DSR RATE NON DSR DSR AMOUNT NON DSR
DSR QUANTITY RATE AMOUNT
h) The filter shall be designed to give rated output at given raw water
quality and flow rate without any operational problem and should not get
any loss of performance as long as the operating pressure remains within
the given range. Any additional provision is required to make the item
complete, the same should be included herein.
i) Filter shall be painted inside with minimum two coats of non-toxic
corrosion resistant paint and one coat of red oxide primer outside.
a) Dual Media filter
Capacity : 5400 lph
Filtration rate : 11500 lph/m2
Filter dia approx. : 800 mm
Working pressure : 3.0 kg/cm2
Test pressure : 4.5 kg/cm2 Set 1 246685.00 0.00 246685.00
1.04 POST CHLORINATION OF WATER
Supply Installation testing and commissioning of On line electronic chemical
solution dosing system comprising of electronic metering pump (with both
frequency and stroke length controls to control the dosage rate between
10-100 % of rated maximum capacity), virgin HDPE chemical grade solution
tank of rquired capacity, necessary injection fitting assembly, foot valve
cum strainer and suction and delivery tubing etc. upto the point of injection
complete in all respects as required.
For Cholorination of filtered water
NON DSR Dosing capacity : 0-6 ltrs. per hour, Dosing Head : 3.5 kg/cm2 Each 1 79810.00 0.00 79810.00
1.05 NON DSR To switch on the pumps (including Raw Water Pump, Domestic water
supply pump etc.) when the level of water in the supply water tank is low
and to cut off the pump when the level in the receiving water tank is high
and switch off the pumps when the level of water in the supply water tank
To indicate 5 levels of water in all tanks through a control panel with LEDs
To start the pumps in a cyclic order.
The system shall be complete to ensure automatic quotation of pump in
accordance to water level in respective tanks.
The Contractor will include all the under ground and over head tanks and Set 2 14511.00 0.00 29022.00
all the pumps as required for level control in this item
1.06 Based on DSR-E&M- Providing & fixing of following sizes of butterfly valve of rating PN 16, wafer
2022,16.11.1 type, in cast iron body with Ductile Iron disc, EPDM seal, SS single piece
shaft, conforming to IS-13095 of the following sizes complete with cast iron
hand lever companion flanges, bolts, nuts, washers & inserted rubber
gaskets, as required and as per enclosed specification.
1.07 DSR-2022 E&M-1.17 Supplying and drawing following sizes of FRLS PVC insulated copper
conductor, single core cable in the existing surface/ recessed steel/ PVC
conduit as required.
1.08 DSR-2022 E&M-5.16 Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop Metre 120 70.00 8400.00 0.00
earthing as requried.
1.09 DSR-2022 E&M-4.1 Supplying and installing following size of perforated painted with powder
coating M.S. cable trays with perforation not more than 17.5%, in
convenient sections, joined with connectors, suspended from the ceiling
with M.S. suspenders including bolts & nuts, painting suspenders etc as
a) 4.1.2 150mm width x 50mm depth x 1.6 mm thickness. Metre 30 604.00 18120.00 0.00
b) 4.1.3 200mm width x 50mm depth x 1.6 mm thickness. Metre 30 689.00 20670.00 0.00
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
SI.No. DSR-2021/ NON Description of Item UNIT TOTAL DSR RATE NON DSR DSR AMOUNT NON DSR
DSR QUANTITY RATE AMOUNT
1.10 NON DSR Design, fabrication, assembling, wiring, supply, installation, testing and
commissioning of motor control centre shall be fabricated out of 14 gauge
CRCA sheet steel in form in 3b formation with reinforcement of suitable
size angle iron, channel ‘T’ sections irons and /or flats wherever necessary.
Cable gland plates shall be provided on top as well as at the bottom of the
panels. Panels shall be treated with all anticorrosive process before
painting as per specifications with 2 coats of red oxide primer and final
approved shade of powder coated paint. 2 Nos. earthing terminals shall be
provided for 3 phase, 4 wire, 50 Hz supply system. Lifting hooks shall also
be provided in case of large panels. Approval shall be taken for each panel
before fabrication. Cadmium Plated hardware shall be used in fabrication of
panels. Quoted rates shall inclusive of cables, cable trays, earthing (in
accordance to specification) with earthing from panel to each motor /
MCC for Plumbing system
2 Nos. 150A, 4P MCCB, 35KA, thermal magnetic based release (Ics = Icu =
100%) with with O/L , S/C & E/F protection as per specification and with
following accessories
1 No. Digital MFM meter and 3 nos. CTs of ratio 100/5A , Class I accuracy
and 10 VA burden. digital multifunction meter suitable to measure voltage,
Ampere, Frequency, Power Factor with RS-485 Port
1 Set of ON/ OFF/TRIP Indicating LED Lamps with 2 Amp MCB.
1 Set of phase indicating LED lamps with 2 amp back up MCB.
1 No. 200A, 4P MCCB, 35KA, thermal magnetic based release (Ics = Icu =
100%) with with O/L , S/C & E/F protection with 1 Set of ON/ OFF
Indicating LED Lamps with 2 Amp MCB.
4P copper bus bars of 163A capacity with heat shrinkable coloured sleeves
and i/c, SMC bus bars supports at required intervals complete for cross
section, size supports & their spacing etc. for withstanding fault level of 35
2 No. MPCB of 32 Amp. i/c 1.1 KW DOL starter and providing outgoing
feeder of 3 core, armoured coper cable of size of 6 Sq. mm to Filter feed
pump (including 1 No. as standby). Each compartment shall contain auto /
manual selector swtich and indicating and pushbutton lamps etc. as
2 No. MPCB of 32 Amp. i/c 1.1 KW DOL starter and providing outgoing
feeder of 3 core, armoured coper cable of size of 6 Sq. mm to Domestic
Water Transfer pump (including 1 No. as standby). Each compartment
shall contain auto / manual selector swtich and indicating and pushbutton
lamps etc. as required.
2 No. MPCB of 25 Amp. i/c 1.1 KW DOL starter and providing outgoing
feeder of 3 core, armoured coper cable of size of 6 Sq. mm to Sump pump
(including 1 No. as standby). Each compartment shall contain auto /
manual selector swtich and indicating and pushbutton lamps etc. as
Spare MCCBof following capacities:
25 amps 4P MCCB 2 Nos.
Necessary cable alleys, internal wiring, and interlocking, earthing for all
equipment shall also be included.
a. All MPCBs shall be of 35 KA breaking capacity and suitable for motor duty
b. Provision shall be made to ensure system protection from dry running of
c. All incomers and Buscoupler breakers shall be electrical and mechanical
interlocked with suitable accessories.
d. 2 Nos. Type-2 SPD 65kA 4P with 1No. Red Indicator Light for SPD with
1Set. SPD Back up fuse 1P 50A 20kA including all necessary accessories.
For Plumbing System as described above. Set 1 348261.00 0.00 348261.00
TOTAL FOR WATER SUPPLY PUMPS 155150.00 1339615.00
B) STP PACKAGED TYPE 20 KLD
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
SI.No. DSR-2021/ NON Description of Item UNIT TOTAL DSR RATE NON DSR DSR AMOUNT NON DSR
DSR QUANTITY RATE AMOUNT
2.01 Design, Supply, Installation testing & commisioning of Sewerage treatment
plant in MBBR (MOOVING BED BIO REACTOR TECHNOLOGY) process with
all the required item completely for Domestic Sewege capciaty 20
cum/day. Outlet Parameter should be match for using the water for
Gardening purpose. Bidder should include following items as specified
below suitable for 20 cum/day STP. (Bidder Must visit the site before quote)
Depth of Incomming sewer 1.3m to be consider.
A The stp shall be designed based on the following parameters:
Daily average flow - 20 Cum / Day
S. Solids - 150 Mg/L
COD - 300 – 500 Mg/L
Oil & Grease -20 Mg / L
B Effluent discharge standard after treatment
BOD5 - Less than 30 Mg/L
S. Solids - 10 Mg/L
Oil & Grease - 10 Mg / L
c Sewerage treatment plant contaning following Tank and Electro Mech.
1.01 All the tanks are MSEP tanks except Equalization Tank Set
1.02 1 Nos. Stainless Steel-316 Perforated Corrugated Screen of fabricated
through 5mm thick plate having holes of 8 mm at a distance of 10 mm with Set
suitable lifting arrangement
1.03 mechanical punched hole fine screen for 2-3 mm size complete as required
1.04 Level and Measurmement Control.
1.05 sight tube (of 3.5 to 4.5 m length) with isolation valve at top/bottom
1.06 Equalization Transfer pump (1 Working +1 standby) Set
1.07 2 No. twin type rotary air blowers (1W + 1S) for Aeration Tank and
Equlisation tank
1.08 Disc type, EPDM membrane based, non clog type air dispersion system for
Imported fine bubble membrane diffusers for equalisation tank, aeration
tank & sludge holding tank, MBBR tank,MS pipe (C Class),SS Piping (
Schedule 10),Butterfly Valve,Non-Return Valve,Ball Valve,MS Class 'B'with
hot dip galvanized puddle flange,instrument for the auto operation of
System and saftey,
1.09 MBBR module immersed type with permeate Set
1.10 Automation of complete plant from raw effluent pump to permeate pump
out put with proper flow control
1.11 Tertiary treatment with multimedia filter Set
1.12 MBBR Permeate pump (1 Working +1 standby) Each
1.13 Sludge Recycling Pump (1 Working +1 standby) (Solid handling size for this
pump shall be 7-10 mm)
1.14 Hypo solution dosing pump comprising of FRP tank with inlet / outlet
1.15 Ultravoilet dis-infection unit
1.16 Basket type Centrifuge Machine 48'' with Perforated Plate-4mm thick, SS
304 Main Shaft-En 8, Base Frame-MS Channel.Basket Size: 1500 (Dia) Set
1.17 Self priming sludge Feed pump (1 Working +1 standby) Set
1.18 Electrical Panel with Cable, Earthing Set
1.19 It also include the transportation charges to the site Set
Sewerage treatment plant 20 cum/day complete following above items. Each 1 1668753.00 0.00 1668753.00
TOTAL FOR STP 0.00 1668753.00
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
Name of Work- Construction and development of Pre Engineered Manufacturing Unit at Industrial Plot No. B-208, at sector Phase-II, Noida
External & Internal Electrical works
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
A SUPPLY, LAYING AND TERMINATION OF 11KV HT CABLES
1.0 11KV HT CABLE SUPPLY
1.1 NON DSR Supply of 11kV 3Cx 240 sqmm (E) XLPE cable conforming to IS 7098 II. Mtrs 300 2,442 7,32,488
2.0 11KV HT CABLE LAYING
2.1 DSR-2022 (8.1) Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 kV
Page No. 28 grade of following size direct in ground including excavation, sand cushioning,
protective covering and refilling the trench etc. as required.
2.2 DSR-2022 (8.1.2) Above 120 sq. mm and upto 400 sq. mm
3.0 TERMINATION OF H.T. CABLES
3.1 DSR-2022 (10.4) Supplying and making indoor cable end termination with heat shrinkable jointing kit
Page No. 32 complete with all accessories including lugs suitable for following size of 3 core, XLPE
aluminium conductor cable of 11 kV grade as required.
3.3 DSR-2022 (10.5) Supplying and making outdoor cable end termination with heat shrinkable jointing
Page No. 32 kit complete with all accessories including lugs suitable for following size of 3 core,
XLPE aluminium conductor cable of 11 kV grade as required.
4.0 NON DSR Supply, Erection, Testing & Commissioning of 11kV LA/GO/DO Switch complete with
all hardware fittings & accessories. Each 1 - 49,581 49,581
5.0 NON DSR Supply and Erection of 11 Meter long HT PCC Pole as per UPPCL / SEB specifications.
6.0 DSR-2022 (11.1) Erection of RCC/ PCC pole of following length in brick ballast and ramming the
Page No. 34 foundation, finishing with 150 mm thick cement concrete (1:3:6) layer on top with
including excavation and refilling etc. as required.
6.1 DSR-2022 (11.1.3) Above 8.0 meter and upto 11.0 meter
7.0 NON DSR Supply, fabrication and fixing of mild steel material like channel, angles, flats, across
ametres, clamps, hardware, nut-bolts etc. as required. Kg 500 - 161 80,287
8.0 NON DSR Supply & providing stay set in H.T./L.T. line as per requirement. Set 1 - 4,028 4,028
TOTAL of SH (A) HT CABLE 3,24,466 9,04,979
B SUPPLY, LAYING AND TERMINATION OF LT CABLES
1.0 SUPPLY OF MV CABLING
The Cable and Cable Containment System specified herein, must confimetre to
technical Specifications, in addtion to the description given in respective items of
BOQ, whether explicitly specified or not. In case of contradiction between
specifications and description in BOQ, the most stringent of the condition will apply.
All the items / parts mentioned in relevant clauses of the technical specifications and
not specifically mentioned in BOQ shall be deemed to be included in the quoted
rates, unless specifically excluded.
It may be noted that Contractor will be required to carry out cable sizing based on
actual cable lengths, as per Working Drawings developed by him and after
incorporating any changes in load requirements from the tendering stage.
Optimisation must be carried out during cable sizing to reduce the cable requirement
and size. Further, Contractor must obtain Engineer's approval on the Cable SIzing
1.1 1.1 Supply of LT Cable
Supply of multi core / single core, stranded / solid aluminum / copper conductor,
XLPE / FRLS PVC insulated armoured, PVC outer extruded sheathed 1100V grade
cables of the following sizes confirming to IS 1554 & IS 7098 part I.
1.1.1 NON DSR 3.5 Core, 300 Sqmm stranded Al, XLPE, Armd Cable. Mtrs 26 - 1,737 45,159
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
1.1.2 NON DSR 3.5 Core, 150 Sqmm stranded Al, XLPE, Armd Cable. Mtrs 126 - 886 1,11,616
1.1.3 NON DSR 3.5 Core, 120 Sqmm stranded Al, XLPE, Armd Cable. Mtrs 142 - 761 1,08,080
1.1.4 NON DSR 3.5 Core, 50 Sqmm stranded Al, XLPE, Armd Cable. Mtrs 105 - 365 38,273
1.1.5 NON DSR 4 Core, 25 Sqmm stranded Al, XLPE, Armd Cable. Mtr 290 - 238 68,919
1.1.6 NON DSR 4 Core, 16 Sqmm stranded Al, XLPE, Armd Cable. Mtr 368 - 182 66,970
1.1.7 NON DSR 4 Core, 10 Sqmm stranded Al, XLPE, Armd Cable. Mtr 675 - 154 1,04,052
1.1.8 NON DSR 4 Core, 6 Sqmm stranded Al, XLPE, Armd Cable. Mtr 75 - 131 9,835
1.1.9 NON DSR 4 Core, 6 Sqmm stranded Cu, PVC, Armd Cable. Mtr 285 - 366 1,04,189
1.1.10 NON DSR 3 Core, 6 Sqmm stranded Cu, PVC, Armd Cable. Mtr 90 - 271 24,375
1.1.11 NON DSR 4 Core, 4 Sqmm stranded Cu, PVC, Armd Cable. Mtr 152 - 251 38,157
1.1.12 NON DSR 3 Core, 4 Sqmm stranded Cu, PVC, Armd Cable. Mtr 105 - 194 20,345
1.1.13 NON DSR 3 Core, 2.5 Sqmm stranded Cu, PVC, Armd Cable. Mtr 2800 - 117 3,28,215
1.1.14 NON DSR 1 Core, 16 Sqmm stranded Cu, Flexible Cable. Mtr 85 - 225 19,108
1.2 Laying of LT Cable
1.2.1 DSR-2022 (7.1) Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV
Page No. 26 grade of following size direct in ground including excavation, sand cushioning,
protective covering and refilling the trench etc. as required.
a) DSR-2022 (7.1.1) Upto 35 sq. mm
b) DSR-2022 (7.1.2) Above 35 sq. mm and upto 95 sq. mm
1.2.2 DSR-2022 (7.5) Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV
Page No. 26 grade of following size in the existing RCC/ HUME/ METAL pipe as required.
a) DSR-2022 (7.5.1) Upto 35 sq. mm
b) DSR-2022 (7.5.3) Above 95 sq. mm and upto 185 sq. mm
c) DSR-2022 (7.5.4) Above 185 sq. mm and upto 400 sq. mm
1.2.3 DSR-2022 (7.8) Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable
Page No. 27 of 1.1 kV grade of following size on cable tray as required.
a) DSR-2022 (7.8.1) Upto 35 sq. mm (clamped with 1mm thick saddle)
1.2.4 DSR-2022 (7.9) Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2
Page No. 27 coarse sand : 4 graded stone aggregate 20 mm nominal size) of size 60 cm X 60 cm at
the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including
inscription duly engraved as required. Each 42 585 24,570 -
1.2.5 DSR-2022 (7.10) Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate
Page No. 27 with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60
cm long and fixing the same in ground as required. Each 42 508 21,336 -
1.3 Terminations of LT Cable
DSR-2022 (9.1) Supplying and making end termination with brass compression gland and aluminium
Page No. 29 lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium
conductor cable of 1.1 kV grade as required.
1.3.1 DSR-2022 (9.1.22) 3.5 Core, 50 Sqmm stranded Al, XLPE, Armd Cable. Sets 2 413 826 -
1.3.2 DSR-2022 (9.1.25) 3.5 Core, 120 Sqmm stranded Al, XLPE, Armd Cable. Sets 10 613 6,130 -
1.3.3 DSR-2022 (9.1.26) 3.5 Core, 150 Sqmm stranded Al, XLPE, Armd Cable. Sets 12 697 8,364 -
1.3.4 DSR-2022 (9.1.30) 3.5 Core, 300 Sqmm stranded Al, XLPE, Armd Cable. Sets 2 1,195 2,390 -
1.3.5 DSR-2022 (9.1.33) 4 Core, 16 Sqmm stranded Al, XLPE, Armd Cable. Sets 10 309 3,090 -
1.3.6 DSR-2022 (9.1.34) 4 Core, 25 Sqmm stranded Al, XLPE, Armd Cable. Sets 6 315 1,890 -
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
1.3.7 DSR-2022 (9.1.32) 4 Core, 10 Sqmm stranded Al, XLPE, Armd Cable. Sets 38 269 10,222 -
1.3.8 NON DSR 4 Core, 6 Sqmm stranded Al, XLPE, Armd Cable. Sets 4 - 549 2,197
1.3.9 NON DSR 4 Core, 6 Sqmm stranded Cu, PVC, Armd Cable. Sets 4 - 597 2,389
1.3.10 NON DSR 3 Core, 6 Sqmm stranded Cu, PVC, Armd Cable. Sets 2 - 597 1,194
1.3.11 NON DSR 4 Core, 4 Sqmm stranded Cu, PVC, Armd Cable. Sets 6 - 545 3,271
1.3.12 NON DSR 3 Core, 4 Sqmm stranded Cu, PVC, Armd Cable. Sets 6 - 489 2,933
1.3.13 NON DSR 3 Core, 2.5 Sqmm stranded Cu, PVC, Armd Cable. Sets 290 - 459 1,33,164
1.3.14 NON DSR 1 Core, 16 Sqmm stranded Cu, Flexible Cable. Sets 16 - 104 1,668
1.4 DSR-2021 (19.7) Constructing brick masonry manhole in cemtn mortar 1:4 (1 cement : 4 coarse sand)
Page No. 439 with R.C.C. top slab with 1:1 5:3 mix (1 cement : 1.5 coarse sand (zone-III) : 3 graded
stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4
coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size), inside
plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished
with floating coat of neat cement and making channels in cement concrete 1:2:4 (1
cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with
a floating coat of neat cement complete as per standard design:
1.4.1 DSR-2021 (19.7.1) Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty)
Page No. 439 455x610 mm internal dimeter, total weight of cover and frame to be not less than 38
kg (weight of cover 23 kg and weight of frame 15 kg):
1.4.1.1 DSR-2021 (19.7.1.1) With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
1.4.2 DSR-2021 (19.7.2) Inside size 120x90 cm and 90 cm deep including C.I. cover with frame (medium duty)
Page No. 439 500 mm internal diameter, total weight of cover and frame to be not less than 116 kg
(weight of cover 58 kg and weight of frame 58 kg):
1.4.2.1 DSR-2021 (19.7.2.1) With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
1.4.3 DSR-2021 (19.8) Extra for depth for manholes:
1.4.3.1a DSR-2021 (19.8.1.1) With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
1.4.4.1 DSR-2021 (19.8.2.1) With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
TOTAL of SH (B) LT CABLES 10,96,296 12,34,109
C CABLE TRAY, BENDS AND TEES
1.0 CABLE TRAY
Supplying and installing following size of perforated painted with powder coating
M.S. cable trays with perforation not more than 17.5%, in convenient sections,
joined with connectors, suspended from the ceiling with M.S. suspenders including
bolts & nuts, painting suspenders etc. as required.
1.1 NON DSR 50 mm width X 25 mm depth X 1.6 mm thickness Mtrs 31 - 386 11,965
1.2 DSR-2022 (4.1.2) 150 mm width X 50 mm depth X 1.6 mm thickness
1.3 DSR-2022 (4.1.4) 300 mm width X 50 mm depth X 1.6 mm thickness
1.4 DSR-2022 (4.1.6) 450 mm width X 50 mm depth X 2.0 mm thickness
1.5 DSR-2022 (4.1.7) 600 mm width X 50 mm depth X 2.0 mm thickness
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
2.0 CABLE TRAY BENDS
Supplying and installing following size of perforated painted with powder coating
M.S. cable trays bends with perforation not more than 17.5%,, joined with
connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts,
painting suspenders etc as required.
2.1 NON DSR 50 mm width X 50 mm depth X 1.6 mm thickness Each 2 - 714 1,428
2.3 DSR-2022 (4.2.2) 150 mm width X 50 mm depth X 1.6 mm thickness
2.4 DSR-2022 (4.2.4) 300 mm width X 50 mm depth X 1.6 mm thickness
2.5 DSR-2022 (4.2.6) 450 mm width X 50 mm depth X 2.0 mm thickness
3.0 CABLE TRAY TEE
Supplying and installing following size of perforated painted with powder coating
M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors,
suspended from the ceiling with M.S. suspenders including bolts & nuts, painting
suspenders etc as required.
3.1 NON DSR 50 mm width X 50 mm depth X 1.6 mm thickness Each 1 - 862 862
3.3 DSR-2022 (4.3.2) 150 mm width X 50 mm depth X 1.6 mm thickness
3.4 DSR-2022 (4.3.4) 300 mm width X 50 mm depth X 1.6 mm thickness
3.5 DSR-2022 (4.3.6) 450 mm width X 50 mm depth X 2.0 mm thickness
4.0 CABLE TRAY REDUCER
Supplying and installing following size of perforated painted with powder coating
M.S. cable trays Reducer with perforation not more than 17.5%, joined with
connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts,
painting suspenders etc. as required.
4.1 NON DSR 50 mm width X 50 mm depth X 1.6 mm thickness Each 2 - 665 1,330
4.3 DSR-2022 (4.5.2) 150 mm width X 50 mm depth X 1.6 mm thickness
4.4 DSR-2022 (4.5.4) 300 mm width X 50 mm depth X 1.6 mm thickness
4.5 DSR-2022 (4.5.6) 450 mm width X 50 mm depth X 2.0 mm thickness
4.6 DSR-2022 (4.5.7) 600 mm width X 50 mm depth X 2.0 mm thickness
5.0 CABLE TRAY SUPPORTS
NON DSR Supply, installation of hangers and supports for cable tray, cable tray of various width
in one/two/three or five tier fashion either on one side of the wall or on two sides of
the wall/column/truss or at other places as required as per drawing. The work
involve fabrication of clamps, hooks, suspension rod or strip painted with two coats
of red oxide and one coat afterward with paint as per the approved colour. Before
fabricating, the contractor has to get the design approved. In this, item shall be
inclusive of square section, channel, angle etc. Kgs 3500 - 183 6,40,891
TOTAL of SH (C) CABLE TRAY, BENDS AND TEES 3,62,032 6,56,475
D MAIN LT PANEL & SUB DISTRIBUTION PANELS
1.0 NON DSR LT ISOLATOR PANEL (OUTDOOR TYPE) (IP-55) (Ics = 25kA)
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
Supply, installation, testing & commissioning of LT Isolator panels (Outdoor type).
These will be floor mounted, free standing, outdoor duty in IP-55 enclosure, dust
proof, vermin proof, front operated, electrical panel fabricated as per specifications
laid in this document and will be complete with the main and auxiliary bus bars,
interconnection, earth bus and will be powder coated finish with 70 micron
thickness. The Panel will be made as per detailed specifications & drawings forming
part of this document. There should be double door throughout for all chambers
with canopy of not less than 1.2mm thickness.
1 No. 400A TPN incomer feeder comprising 1 no. 400A FP MCCB with microprocessor
based O/C, S/C & E/F release and ON/OFF indications. Suitable links shall be
provided for min 2Rx3.5cx240 Sq.mm AL XLPE Armoured power cables for both
incoming & outgoing. Incomer shall have following.
1 No. digital multifunction meter (Elite-444 or equivalent) with harmonics
communicating on modbus & RS 485 port with matching cast resin CT's of class 0.5.
3 nos. indicating lights for ON/ OFF/ TRIP position.
1 No. 0-500V 96 sqmm digital voltmeter with selector switch, 3 Nos. phase indicating
lamps to show the incoming power with control MCB.
Other items such as
1 Lot of control wiring.
1 Set of designation plates. No 1 - 1,05,726 1,05,726
2.0 NON DSR MAIN LT PANEL
Supply, installation, testing & commissioning of Main LT Panel. This will be floor
mounted, free standing, indoor duty, dust proof, vermin proof, front operated,
electrical panel fabricated as per specifications laid in this document and will be
complete with the main and auxiliary bus bars, interconnection, earth bus and will be
powder coated finish with 70 micron thickness. The Main LT Panel shall use all draw
out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply
system. Each incoming & outgoing breaker will have microprocessor based releases.
The Panel will be made as per detailed specifications & drawings forming part of this
(Each MCCB will have variable current setting for over current and short circuit, front
extended lockable handle, pad lockable in off position, indication light for ON,
shrouding on incomer side, termination shall be suitable for aluminium bus bars.)
2.1 Main LT Panel Expandable Type (Ics = 25kA)
Incomers:- Three numbers (1x800A FP EDO ACB uP based from Trafo + 1x200A FP
MCCB µP based from 100kVA DG).
2.1a Incomer :- One number (1x800A, 4P EDO ACB from transformer)
One no. (1X800A 4P EDO ACB) with microprocessor based over current, short circuit
& earth fault release. ACB releases shall have over current different time settings,
short ckt. release with variable setting, short time delay, instantaneous current
setting, earth fault release, earth fault time delay. Suitable links shall be provided for
min. 3Rx3.5x300 Sq.mm AL XLPE Arm cables. Incomer shall have following.
1No. digital multifunction meter (showing harmonics along with all other electrical
parameters such as voltage current, KW, KWHr, PF.) with RS 485 port with matching
cast resin CT's.
1No. 0-500V 96 sqmm digital voltmeter with selector switch.
3Nos. Phase indicating lamps to show the incoming power with control MCB.
1No. ON/OFF indication.
1No. 3 phase voltage monitoring relay cum phase sequence meter
1No. 800/400/5A CT of Class.05.
2.1b Incomer:- One number (1x200A, 4P MCCB from DG)
1No. 200A TPN incomer feeder comprising 1no. 200A FP MCCB with µP based O/C,
S/C & E/F release and ON/OFF indications.
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
1No. digital multifunction meter (showing harmonics along with all other electrical
parameters such as voltage current, KW, KWHr, PF.) with RS 485 port with matching
cast resin CT's.
1No. 0-500V 96 sqmm digital voltmeter with selector switch.
3Nos. Phase indicating lamps to show the incoming power with control MCB.
1No. 3 phase voltage monitoring relay cum phase sequence meter.
1No. ON/OFF indication.
1No. RPR relay with 1no. 120/5A cast resin CT of class 0.5
2.1c Bus Coupler
1 No. number 400A 4 Pole MCCB with thermal magnetic based over current and
short circuit release as bus coupler. Necessary interlocking both electrical &
mechanical shall be done between all incomer feeders and buscoupler.
A Set of TPN Aluminium bus bar rated for 500A (after considering all necessary
deratings) 3 phase 4wire, 50Hz. A minimum derating factor of 0.75 must be taken for
calculation of bus bar sizes. The bus bar size after derating shall be equal to the
ampere given in the BOQ The conductivity of bus bar shall not be less than 57% and
earth bus size shall be be as per bus fault level of panel.
A Set of TPN Aluminium bus bar rated for 800A (after considering all necessary
deratings) 3 phase 4wire, 50Hz. A minimum derating factor of 0.75 must be taken for
calculation of bus bar sizes. The bus bar size after derating shall be equal to the
ampere given in the BOQ The conductivity of bus bar shall not be less than 57% and
earth bus size shall be as per bus fault level of panel.
(Under no case temperature of main LT panel shall be more at any point of the
panel. To avoid heating necessary exhaust fans shall have to be provided along with
2.3 Outgoings:-
Outgoing on First Bus Bar
2Nos. 100A TPN feeders. Each having 1no. 100A TP MCCB with isolable neutral &
ON/OFF indication with thermal magnetic based release, 1no. digital multifunction
meter with RS 485 port and matching cast resin CT's.
1No. 100A TPN feeder having 1no. 100A TP MCCB with isolable neutral & ON/OFF
indication with thermal magnetic based release.
3Nos. 63A TPN feeders. Each having 1no. 63A TP MCCB with isolable neutral &
ON/OFF indication with thermal magnetic based release.
1No. 40A TPN feeder having 1no. 40A TP MCCB with isolable neutral & ON/OFF
indication with thermal magnetic based release, 1no. digital kWHr meter with RS 485
port and matching cast resin CT's.
2Nos. 40A TPN feeders. Each having 1no. 40A TP MCCB with isolable neutral &
ON/OFF indication with thermal magnetic based release.
1 No. fabrication compartment space for 100A MCCB.
Outgoing on Second Bus Bar
2Nos. 400A TPN feeders. Each having 1no. 400A TP MCCB with isolable neutral &
ON/OFF indication with thermal magnetic based release, 1no. digital multifunction
meter with RS 485 port and matching cast resin CT's.
1No. 400A TPN feeder having 1no. 400A TP MCCB with isolable neutral & ON/OFF
indication with thermal magnetic based release, 1no. digital multifunction meter
with RS 485 port and matching cast resin CT's. Feeder shall be tapped from trafo
- 1No. 160A TPN feeder having 1no. 160A TP MCCB with isolable neutral & ON/OFF
indication with thermal magnetic based release, 1no. digital multifunction meter
with RS 485 port and matching cast resin CT's.
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
- 1No. 160A TPN feeder having 1no. 160A TP MCCB with isolable neutral & ON/OFF
indication with thermal magnetic based release.
- 1No. 125A TPN feeder having 1no. 125A TP MCCB with isolable neutral & ON/OFF
indication with thermal magnetic based release, 1no. digital multifunction meter
with RS 485 port and matching cast resin CT's.
- 1No. 63A TPN feeder having 1no. 63A TP MCCB with isolable neutral & ON/OFF
indication with thermal magnetic based release.
2 Nos. fabrication compartment space for 100A MCCB.
- 1No. 4 mode MOV type phase to neutral & neutral to earth type 1+2 surge suppresor
(25kA) with HRC fuses (HRC fuses as per manufacturer recommendation). SPD shall
withstand 440V for 2 hrs.
- Other items such as
- Interlocking logic between two incomers and 1no. bus coupler through PLC.
- 1 Lot of control wiring
- 1 Set of designation plates No 1 - 6,69,091 6,69,091
3.0 MDB / PDB / PANEL
Supply, installation, testing commissioning of PDB’s / MDB's. These will be floor
mounted, free standing, indoor duty, dust & vermin proof, front operated, having
front hinged lockable doors, electrical panel fabricated as per specifications laid in
this document and will be complete with the main and auxiliaries bus bars,
interconnection, earth terminals, earth bus and will be powder coated finished with
70 micron. The PDB & MDB panel shall use all for 415 V AC, 3 phase, 50 Hz, 3 phase 4
wire supply system. The panels will be made as per detailed specifications and
drawings forming part of this document. The incoming and outgoing for different
PDBs shall be as follows:
- (Each MCCB will be variable current setting for over current and short circuit, front
extended lockable handle, pad lockable in off position, indication light for ON,
shrouding on incomer side, termination shall be suitable for aluminium bus bars.)
- Bus bar shall be of Aluminium and continuous throughout the width of the panel and
vertical cross section of bus bar shall be equal to the total ratings of feeders fed by
the vertical bus bars subjected to minimum size being used as per fault level. Bus bar
shall have minimum conductivity of 58%.
3.1 NON DSR PANEL (L+P)-1 (WAREHOUSE) (Ics = 10kA)
- 1No. Incomer 125A FP MCCB with microprocessor based releases for O/C, S/C, 3
Nos. phase indicating lamps to show the incoming power with control MCB, 1no.
ON/OFF indication, 1no. voltmeter, voltage selector switch, 1no. KWHr Meter and
matching cast resin CT's.
- A Set of TPN Aluminium bus bar rated for 150A (after considering all necessary
deratings) 3 phase 4wire, 50Hz. A minimum derating factor of 0.75 must be taken for
calculation of bus bar sizes. The bus bar size after derating shall be equal to the
ampere given in the BOQ The conductivity of bus bar shall not be less than 58% and
earth bus size shall be as per bus fault level of panel.
- The outgoing feeders are as follows :
- 2Nos. 63A TPN feeders. Each having 1no. 63A TP MCCB with isolable neutral.
- 2Nos. 63A 4P feeders. Each having 1no. 63A 4P MCB (Curve `C').
- 5Nos. 40A 4P feeders. Each having 1no. 40A 4P MCB (Curve `C').
- 2Nos. 40A DP feeders. Each having 1no. 40A DP MCB (Curve `C').
- 1 set of complete wiring No 1 - 1,07,135 1,07,135
4.0 NON DSR FEEDER PILLAR (OUTDOOR TYPE) IP 65
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
Supply, Installation, testing & commissioning of Outdoor type feeder pillar with
epoxy paint and locking arrangement. This panel shall be mounting on concrete
/mesonary pedestal upto 400mm high from finished floor level, compartmentalized,
cubical, dust, vermin proof and outdoor type (IP65) fabricated as per specification
laid in document with following incoming and outgoing feeders including making
connections / inter-connections with lugs / glands crimping tools testing and earthing
4.1 Feeder Pillar - 1 (Ics = 10kA)
- 1No. Incomer 100A FP MCCB with microprocessor based releases for O/C, S/C, 3Nos.
phase indicating lamps to show the incoming power with control MCB, 1no. ON/OFF
indication, 1 no. voltmeter, voltage selector switch, 1no. ammeter, ammeter with
selector switch and matching cast resin CT's.
- A Set of TPN Aluminium bus bar rated for 150A (after considering all necessary
deratings) 3 phase 4wire, 50Hz. A minimum derating factor of 0.75 must be taken for
calculation of bus bar sizes. The bus bar size after derating shall be equal to the
ampere given in the BOQ The conductivity of bus bar shall not be less than 58% and
earth bus size shall be as per bus fault level of panel.
- The outgoing feeders as follow:
- 1No. 40A TPN feeder having 1no. 40A TP MCCB's with isolable neutral.
3Nos. 40A FP MCB (Curve 'C')
1No. 63A 4P feeder followed by: (Please refer SLD also)
1No. Incomer 63A 4P RCBO followed by 70A FP Contactor with Digital Synchronising
timer with all accessories complete in everyway & outgoing shall be followed.
A Set of TPN Alm. bus bar rated for 100A (after considering all necessary deratings) 3
phase 4wire, 50Hz. A minimum derating factor of 0.75 must be taken for calculation
of bus bar sizes. The conductivity of bus bar shall not be less than 58% and earth bus
size shall be as per fault level.
- 7Nos. 10A FP MCB (Curve 'C')
- 1 Set of complete wiring No 1 - 1,48,124 1,48,124
5.0 NON DSR CHANGEOVER PANEL (FIRE FIGHTING)
Supply, unloading, installation, testing & commissioning of ON load change over
switch panel. This will be indoor duty, dust proof, vermin proof, front operated,
electrical panel fabricated as per specifications laid in this document and will be
complete with incoming & outgoning terminals suitable for XLPE arm cables. cable
and will be powder coated finish with 70 micron thickness. The Panel shall use on
400A 4P On Load Change Over Switch suitable for 415 V AC, 3 phase, 50 Hz, 3 phase
4 wire supply system. Each incomer shall have three sets of 3 indicating lights for
incoming power, 1 Voltmeter 0-500 V with voltmeter selector switch & outgoing
shall have ammeter with selector switch along with suitable links on input and
output side. All cable entry and exit shall be from top.
- 1 set of complete wiring No 1 - 78,675 78,675
6.0 NON DSR 80kVAr Capacitor Panel (Ics = 25kA) (Expandable Type)
80 kVAr CAPACITOR PANEL SHALL HAVE (2x5kVAr+4x10kVAr+2x15kVAr). THESE
CAPACITOR VALUES SHALL BE DERATED FROM 440V TO 415V.
Supply, testing & commissioning of 80kVAr at 415V capacitor panel having 1 no.
incomer 400 Amps TPN isolator as incomer. Incomer to have 3 control fuses,
3indicating lights for incoming power, 1no. Volt meter 0-500 V, 96 sqmm with volt
meter selector switch, 1no. auto manual selector switch, 3 Nos. of CT's, PF meter and
1no. APFCR (14 steps) with display of all parametrs and suitable 15 VA CT’s. Each
vertical feeder will have minimum 800 cfm fan for forced cooling and necessary
louvers will be provided only at bottom.
A Set of TPN Aluminium bus bar rated for 500A (after considering all necessary
deratings) 3 phase 4wire, 50Hz. A minimum derating factor of 0.75 must be taken for
calculation of bus bar sizes. The bus bar size after derating shall be equal to the
ampere given in the BOQ. The conductivity of bus bar shall not be less than 58% and
earth bus size shall be as per bus fault level of panel.
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
- 2nos. x 5kVAr capacitor banks. Each 5kVAr section will have 32A magnetic type TP
MCCB with 1no of 32A TP contactor, 1no. heavy duty 5.6kVAr (at 440V) capacitor
with hot spot temperature. of 80 degree C, 1 set lights ON/OFF, 1 set of ON/OFF
push buttons, 1no. CT operated ammeter 0-50A.
- 4nos. x 10kVAr capacitor banks. Each 10kVAr section will have 63A magnetic type TP
MCCB with 1no of 70A TP contactor, 1no. heavy duty 11.2kVAr (at 440V) capacitor
with hot spot temperature. of 80 degree C, 1 set lights ON/OFF, 1 set of ON/OFF
push buttons, 1no. CT operated ammeter 0-50 amps.
- 2nos. x 15kVAr capacitor banks. Each 15kVAr section will have 63A magnetic type TP
MCCB with 1no of 70A TP contactor, 1no. heavy duty 16.8kVAr (at 440V) capacitor
with hot spot temperature. of 80 degree C, 1 set lights ON/OFF, 1 set of ON/OFF
push buttons, 1no. CT operated ammeter 0-50 amps.
Each capacitor bank shall be able to operate in either manual or auto mode
individually through APCR relay and separately in auto mode.
- 1 set of complete wiring No 1 - 2,30,947 2,30,947
TOTAL of SH (D) MAIN LT PANEL & SUB DISTRIBUTION PANELS - 13,39,698
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
1.1 DSR-2022 (5.2) Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and
Page No. 23 providing masonry enclosure with cover plate having locking arrangement and
watering pipe etc. with charcoal / coke and salt as required. Each 11 6,855 75,405 -
1.2 DSR-2022 (5.4) Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories,
Page No. 23 and providing masonry enclosure with cover plate having locking arrangement and
watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
1.3 DSR-2022 (5.6) Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including
Page No. 23 accessories, and providing masonry enclosure with cover plate having locking
arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as
required. Set 4 13,838 55,352 -
1.4 NON DSR Supply and laying, testing and commissioning of copper / GI Strips / wire for
interconnecting the earthing stations to panels, DB's etc. of the following sizes in
built up trenches / surface / wall / ground complete with holes and fixing jointing /
temetreinating accessories as per specifications and drawing as required (Quality
shall be paid as per the approved drawings as executed).
a 50 x 6 mm thick GI strip Each 224 - 430 96,232
b 40 x 5 mm thick GI strip Each 20 - 362 7,240
c 25 x 6 mm thick GI strip Each 450 - 239 1,07,754
d 25 x 6 mm thick Cu strip Each 30 - 2,000 60,004
1.5 DSR-2022 (5.7) Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor
Page No. 23 earth electrode, including connection/ termination with GI thimble etc. as required.
1.5.1 DSR-2022 (5.16) Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as
Page No. 24 required. Metre 30 70 2,100 -
1.5.2 NON DSR Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for
connections etc. as required. Metre 30 - 3,361 1,00,824
TOTAL of SH (F) Earthing 2,78,265 3,72,055
F LIGHTNING PROTECTION SYSTEM AS PER IEC62305
1.1 NON DSR Supply, instalation, testing & commissioning of 8mm dia aluminium solid round
conductor for height of building. Supply of 8mm Aluminum solid round conductor to
meet the requirements of IS / IEC 62305 and IEC 62561-2. Mtrs 578 - 189 1,08,960
1.2 NON DSR Supply, instalation, testing & commissioning of stainless steel or polyamide with steel
base parapet conductor holder at every one metre at every one metre for for 8-
10mm aluminium solid round conductor above concrete parapet with fixing screws
meet the requirements of IS / IEC 62305. Tested for electrical, mechanical and
chemical as per as per IEC 62561-2. Nos 18 - 74 1,295
1.3 NON DSR Supply, instalation, testing & commissioning of stainless steel or polyamide with steel
base metal roof conductor holder at every one metre for 8-10mm aluminium solid
round conductor for horizontal air terminal above metal sheet with fixing screws
meet the requirements of IS / IEC 62305. Tested for electrical, mechanical and
chemical as per as per IEC 62561-2. Nos 506 - 248 1,25,262
1.4 NON DSR Supply, instalation, testing & commissioning of stainless steel cross connector for
8mm solid round aluminium conductor to meet the requirements of IS/IEC 62305.
Tested for electrical, mechanical and chemical as per IEC 62561. Nos 23 - 356 8,222
1.5 NON DSR Supply, installation, testing & commissioning of vertical air terminal 1mtr with rigid
mounting accessories on metal sheet to meet the requirment for IS/IEC62305.
1.6 NON DSR Supply, instalation, testing & commissioning of expansion piece to compensate the
expansion and contraction of solid round aluminium conductor during temperature
variations to be provided on conductor length over 20 meters with expansion piece
connector to connect solid round aluminium conductor at both ends to meet the
requirements of IS/IEC 62305. Nos 31 - 327 10,056
1.7 NON DSR Supply, instalation, testing & commissioning of aluminium ferrule for connecting
expansion piece at both ends to meets the requirement of IS / IEC 62305. Tested for
electrical, mechanical and chemical as per IEC 62561. Nos 62 - 74 4,534
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
1.8 NON DSR Supply, instalation, testing & commissioning of 8mm dia aluminium solid round
conductor for height of building. Supply of 8mm aluminum solid round conductor to
meet the requirements of IS/IEC 62305 and IEC 62561-2 Tested for electrical,
mechanical and chemical as per IEC 62561. (Only for LCD). Mtrs 158 - 189 29,886
1.9 NON DSR Supply, instalation, testing & commissioning of stainless steel metal roof conductor
holder for 8-10mm aluminium solid round conductor for horizontal air terminal
above metal sheet with fixing screws meet the requirements of IS/ IEC 62305. Tested
for electrical, mechanical and chemical as per as per IEC 62561-2.
1.10 NON DSR Supply, instalation, testing & commissioning of stainless steel conductor holder or
polyamide with steel base for fixing the (wall) down conductor after test joint for
holding 8-10mm solid conductor to meet the requirement of IS/IEC - 62305. Nos 53 - 211 11,163
1.11 NON DSR Supply, instalation, testing & commissioning of bridging 16 sqmm Cu cable insulated
with heat shrink sleeve (1.0Mtrs length) with connecting accessories for connecting
8mm dia aluminium conductor in a metal building to meet the requirement of IS/IEC
1.12 NON DSR Supply, instalation, testing & commissioning of bridging 16 sqmm Cu cable insulated
with heat shrink sleeve (1.5Mtrs length) with connecting accessories for connecting
8mm dia aluminium conductor in a metal building to meet the requirement of IS/IEC
1.13 NON DSR Supply, instalation, testing & commissioning of test joint round to round suitable
connector for 8 mm round aluminium conductor & 10 mm round copper coated
conductor with polycarbonate enclosure to meet the requirement of IS/IEC - 62305.
Tested for electrical, mechanical and chemical as per IEC 62561. Nos 13 - 669 8,832
1.14 NON DSR Supply, instalation, testing & commissioning of lightnig counter-LCD screen shows
the number of lightning strikes, hour and date of lightning events. Buttons enable
TIME/DATE setting and log viewing. Replaceable battery, working life minimum five
years, complies with IEC/EN 62561-6. No 1 - 45,630 50,193
EARTHING SYSTEM IN SOIL
1.15 NON DSR Supply, instalation, testing & commissioning of 10mm minimum 250 micron copper
bonded round steel solid conductor for ring earthing meet the requirements of IS /
1.16 NON DSR Supply, installation, testing & commissioning of 10 feet. UL listed MS rod of 14mm
dia copper bonded with 250 micron steel. The earthing rod shall be interconnected
to grid mesh with in soil exothermic welding. The work involves digging pit in the
soil, connecting earthing rod to stud / clamp, interconnecting further from clamp to
earthing mesh (appx distance 1.5 mtr) with appropriate exothermic welding.
Earthing grid on periphery is laid by copper bonded conductor & exothermic welding
from earthing rod to earth grid / mesh shall have similar material.
1.17 NON DSR Supply,Installation,testing & commissioning of UL listed exothermic welding Joint: T-
Joint, L-Joint / Straight Joint / X-Joint. Nos 44 - 669 29,439
TOTAL of SH (F) Lighting Protection as per IEC62305 - 6,86,065
G SUB STATION SAFETY EQUIPMENTS
1.0 Supply and erection of the following equipment at suitable place in the sub-station
building as required and as per detailed specifications.
1.1 NON DSR Carbon dioxide (CO2) type fire extinguisher with suitable base pipe & horn
(conforming to IS 2876 with cylinders fully charged of capacity 9.0 Kgm). Nos 1 - 8,647 8,647
1.2 NON DSR G.I buckets of followings capacity paint and written with white paint Fire and
mounted on M.S. angle iron bracket of sizes 50 mm x 50 mm x 6 mm thick and 500
mm long including grouting in wall etc. as required including filling with dry sand 9 ltr
capacity. Nos 3 - 1,819 5,457
1.3 NON DSR First aid box as approved by St. John Ambulance Brigade/Indian Red Cross
Conforming to IS:2217 - 1963. Nos 1 - 2,425 2,425
1.4 NON DSR Shock treatment chart at least in three languages duly mounted ona wooden frame
with glass as required. Nos 1 - 1,819 1,819
1.5 NON DSR Rubber mat 1000 mm wide and 2.5mm thick to withstand 1.1 KV dielectric strength
as per IS 15652-2006. ammended IS. Mtrs 16 - 1,243 19,888
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
1.6 NON DSR Rubber mat 1000 mm wide and conforming to IS15652-2006 withstand 11 KV
dielectric strength. Mtrs 2 - 1,007 2,013
1.7 NON DSR Providing Single Line Diagram on 5mm thick Aluminium sheet in A0 Size duly
laminated. Each 1 - 3,032 3,032
1.8 NON DSR Providing Single Line Diagram on 5mm thick Aluminium sheet in A1 Size duly
laminated. Each 1 - 3,032 3,032
1.9 NON DSR Supplying of Rubber hand gloves suitable for 11 kV. Pair 1 - 1,334 1,334
1.10 DSR-2022 (2.21) Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild
Page No. 12 steel, at least 2 mm thick, and vitreous enameled white on both sides, and with
inscription in single red colour on front side as required. Nos 2 269 538 -
1.11 DSR-2022 (2.22) Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild
Page No. 12 steel, at least 2 mm thick, and vitreous enameled white on both sides, and with
inscription in single red colour on front side as required. Nos 2 292 584 -
Total of SH (G) Substation equipments 1,122 47,647
H EXTERNAL LIGHTING
1 NON DSR SINGLE ARM STREET LIGHTING POLE (9.5 Mtr.)
Supply, installation, wiring, connection, testing and commissioning of external
boundary lighting system conforming to the technical specifications & drawings
forming part of this document. The work for each light point comprises of: - of 9.5
meter long MS tubular pole. Weighing 129Kgs (as per IS 2713 1980 of pole code 410
SP 35) + end bracket wt.5Kg. / mtr. + base plate 300x300x10mm plate Wt 4.3Kg. +
Nipple Wt. 800gm. Fixture will come at top of the pole along with reducer.
- Providing weather proof electrical junction box on surface.
- Digging for making foundation of the pole.
- Erecting the pole by grouting in concrete foundation (The civil construction materials
are the part of the supply against this assignment) made out of 1:3:6: mixture of
cement concrete.
- Supply of weather proof MS junction box of 250mm x 200mm with 1A DP MCB and
arrangement for terminating incoming and outgoing three phase cable.
- Mounting the street light fixture or approved equal on the pole top.
- Connecting the fixture by using 3Cx 2.5mm PVC flexible copper wires of colour green,
red and black to the junction box.
- Testing the connections and completing the installation.
- Providing two numbers 38 mm GI Pipe for incoming and outgoing cables from cable
laying depth to outside foundation.
- Painting the pole with 2 coats of red oxide and 2 coats of aluminium paint.
- The incoming cable work, out going cable work and the earthing of poles are covered
under the cabling and earthing. Nos 14 - 31,692 4,43,694
2 NON DSR POLE FOR SOLAR LIGHT (7.5 Mtr.)
- Supply, installation, testing and commissioning of 7.5mtrs MS tubular pole
conforming to the technical specifications & drawings forming part of this document.
Each 7.5 meter long 60mm dia 3.65mm thick MS tubular pole shall have barcket for
mounting Solar Light at top, 300x300x6mm base plate. Solar Panel will come at top
of the pole. This scope cover Digging for making foundation of the pole. Erecting the
pole by grouting in concrete foundation (The civil construction materials are the part
of the supply against this assignment) made out of 1:3:6: mixture of cement
concrete. Nos 2 16,542 33,084
3 NON DSR BRACKET LIGHT AT BUILIDING / COLUMN
- Supply, Installation, wiring, connection, testing and commissioning of bracket
- Supply of GI tubular 38mm dia 2 Mtrs bracket with tubular support.
- Mounting the junction box on the wall / cable tray.
- Welding / fixing the bracket on the wall /column .
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
- Mounting the street light fixture on the bracket top.
- Connecting the fixture by using 3C x 2.5sq. mm PVC flexible copper wires of color
green, red and black to the junction box.
- Testing the connection and completing the installation.
- Painting the bracket with two coats of red oxide and three coats of ALuminium paint.
- The incoming cable work, out going cable work and the earthing of poles are covered
under the cabling and earthing. Nos 11 - 2,183 24,016
4 NON DSR Supply, Installation, wiring, connection, testing and commissioning of an outdoor
street lighting fixtures of 45W LED luminare with Epoxy Powder Coated Pressure die
casted aluminium housing; IP 66 UV Stabilised, IK 08 Front Glass cover; Power factor
>0.95; Total current Harmonics <10%; The LED source used shall be medium/high
power complying with LM80 standards & system efficacy of 100 lms/w.The system
lumen output of the luminaire of a minimum of 4500 lumens with color temprature
of 5700 deg K (ANSI Bin) and CRI>80. Integral Driver with constant current constant
voltage (CVCC), P.F>0.95 and Surge Protection of atleast 5KV. INDIABULLS CAT NO.
Spectra LED IORL02-45WH HSP or equivalent with att required accessories and
hardware. Nos 25 - 2,254 56,342
5 NON DSR Supply, Installation, wiring, connection, testing and commissioning of LED Mirror
Light fixture with Maximum 9 Watt with minimum 850 lumen, CCT of 5700K with
IP20 Protection. INDIABULLS CAT NO. IIBN02-09 XX or equivalent with all required
harware and accessories complete in everyway line junction box, connectors, loop in
loop out strip, flexible cable etc. Nos 6 - 246 1,479
6 NON DSR Supply, Installation, wiring, connection, testing and commissioning of LED SURFACE
MOUNTED Light fixture with Maximum 24 Watt with minimum 1800 lumen, CCT of
5700K with IP20 Protection. INDIABULLS CAT NO. IRLDS21SQ or equivalent with all
required harware and accessories complete in everyway line junction box,
connectors, loop in loop out strip, flexible cable etc. Each 8 - 1,431 11,449
7 NON DSR Supply, Installation, wiring, connection, testing and commissioning of LED SURFACE
MOUNTED Light fixture with Maximum 40 Watt with minimum 4800 lumen, CCT of
5700K with IP65 Protection. INDIABULLS CAT NO. IIEL03-04 WH120 or equivalent
with all required harware and accessories complete in everyway line junction box,
connectors, loop in loop out strip, flexible cable etc. Each 55 - 2,324 1,27,826
8 NON DSR Supply, Installation, wiring, connection, testing and commissioning of LED RECESSED
MOUNTED Light fixture with Maximum 18 Watt with minimum 1650 lumen, CCT of
6500K with IP20 Protection. INDIABULLS CAT NO. IRLDR01RD or equivalent with all
required harware and accessories complete in everyway line junction box,
connectors, loop in loop out strip, flexible cable etc. Each 28 - 669 18,734
9 NON DSR Supply, Installation, wiring, connection, testing and commissioning of LED HIGHBAY
Light fixture with Maximum 80 Watt with minimum 8000 lumen, CCT of 5700K with
IP65 Protection. INDIABULLS CAT NO. IIBL12RD-80 WH (90 DEG) or equivalent with
all required harware and accessories complete in everyway line junction box,
connectors, loop in loop out strip, flexible cable etc. Each 142 - 3,944 5,60,040
10 NON DSR Supply, Installation, wiring, connection, testing and commissioning of LED HIGHBAY
Light fixture with Maximum 120 Watt with minimum 12000 lumen, CCT of 5700K
with IP65 Protection. INDIABULLS CAT NO. IIBL19RD-120 WH (60 DEG) or equivalent
with all required harware and accessories complete in everyway line junction box,
connectors, loop in loop out strip, flexible cable etc. Each 30 - 4,860 1,45,785
11 Supply, installation, testing and commissionin of following polycarbonate weather
proof (IP-65) junction boxes including terminal / connector block complete as
11.1 NON DSR One way Nos 2 - 470 941
11.2 NON DSR Two way Nos 2 - 470 941
11.3 NON DSR Three way Nos 2 - 470 941
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
12 NON DSR Supply, Installation, wiring, connection, testing and commissioning of an outdoor
35W LED Stree Lighting fixtures with 6000 with lumens with Aluminium Pressure die
casted anti-corresive coating and poly carbonate cover; IP 65, CRI>70, CCT-5700k.
Solar Street light fixture shall have 60watt solar panel module, 12V DC, 384AH inbuilt
battery bank (LiFePo4), PIR sensor. The fixture shall have integrated MPPT charger
with driver. This fixture shall be pole mounted and shall have adjustable angle upto 0-
15 degre. The fixture shall have driver with efficienncy 90%. Philips Cat No. LED
BRP710LED60 CW MR HY FDIN20 SOLAR IN or equivalent with att required
accessories and hardware. Nos 2 69,019 1,38,038
Total of SH (H) External Lighting - 15,63,309
I SUBSTATION WIRING & ACCESSORIES
1.1 DSR-2022 (1.3) Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm
Page No. 1 FRLS PVC insulated copper conductor single core cable in surface / recessed steel
conduit, with modular switch, modular plate, suitable GI box and earthing the point
with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as
a DSR-2022 (1.3.3) Group C
1.2 DSR-2022 (1.54) Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell
Page No. 9 point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper
conductor single core cable in surface/ recessed steel conduit, and earthing the point
with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as
a DSR-2022 (1.54.3) Group C
1.4 DSR-2022 (1.5) Wiring for light / power plug with 2X4 sq. mm FRLS PVC insulated copper conductor
Page No. 1 single core cable in surface / recessed steel conduit alongwith 1 No. 4 sq. mm FRLS
PVC insulated copper conductor single core cable for loop earthing as required.
1.5 DSR-2022 (1.7) Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FR
Page No. 2 / FRLS PVC insulated copper conductor in the surface / recessed ISI marked 20 mm
dia MS conduit alongwith MS inspection / bends, MS sockets, iron staples / saddles /
screws, fasteners and terminating pipe at both ends using suitable MS adaptor as
required. Rates shall be all inclusive of wiring, MS conduits, suspenders and all other
related accesories as required in complete.
a DSR-2022 (1.7.2) 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
Page No. 4 Meter 17 137 2,261
Page No. 4 Meter 109 206 22,433
1.7 DSR-2022 (1.18) Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed
Page No. 4 copper conductor, unarmored telephone cable in the existing surface/ recessed
steel/ PVC conduit as required.
Page No. 4 Meter 40 38 1,520
1.8 DSR-2022 (1.20) Supplying and fixing of following sizes of steel conduit along with accessories in
Page No. 5 surface/recess including painting in case of surface conduit, or cutting the wall and
making good the same in case of recessed conduit as required.
a DSR-2022 (1.20.1) 20 mm dia ISI mark Steel conduit
b DSR-2022 (1.20.2) 25 mm dia ISI mark steel Conduit
c DSR-2022 (1.20.3) 32 mm dia ISI mark steel Conduit
d DSR-2022 (1.20.4) 40 mm dia ISI mark steel Conduit
1.9 DSR-2022 (1.24) Supplying and fixing following modular switch / socket on the existing modular plate
Page No. 6 & switch box including connections but excluding modular plate etc. as required.
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
a DSR-2022 (1.24.1) 5/6 amps switch
Page No. 6 Each 8 103 824 -
c DSR-2022 (1.24.3) 15/16 A switch
d DSR-2022 (1.24.4) 3 pin 5/6 amp socket outlet
Page No. 6 Each 8 122 976 -
e DSR-2022 (1.24.5) 6 pin 15/16 A socket outlet
f DSR-2022 (1.24.6) Telephone socket outlet
Page No. 6 Each 4 148 592 -
1.10 NON DSR 2 module RJ-45 socket outlet in existing outlet complete in every way as required.
1.11 NON DSR Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/
recessed Steel / PVC conduit as required. Metre 40 - 52 2,085
1.12 NON DSR Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed
copper conductor, unarmored telephone cable in the existing surface/ recessed
steel/ PVC conduit as required. (For Telephone) Metre 40 - 30 1,200
1.13 DSR-2022 (1.25) Supplying and fixing two module stepped type electronic fan regulator on the
Page No. 6 existing modular plate switch box including connections but excluding modular plate
etc. as required. Each 2 369 738 -
1.14 DSR-2022 (1.26) Supplying and fixing modular blanking plate on the existing modular plate & switch
Page No. 6 box excluding modular plate as required. Each 4 40 160 -
1.15 DSR-2022 (1.27) Supplying and fixing following size / modules, GI box alongwith modular base & cover
Page No. 6 plate for modular switches in recess etc as required.
a DSR-2022 (1.27.1) 1 or 2 Module (75mmX75mm)
b DSR-2022 (1.27.2) 3 Module (100mmX75mm)
c DSR-2022 (1.27.3) 4 Module (125mmX75mm)
1.16 DSR-2022 (1.28) Supplying and fixing following Modular base & cover plate on existing modular metal
Page No. 6 boxes etc. as required.
a DSR-2022 (1.28.1) 1 or 2 Module
Page No. 6 Each 4 133 532 -
b DSR-2022 (1.28.2) 3 Module
c DSR-2022 (1.28.3) 4 Module
1.16 DSR-2022 (1.33) Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box / wooden
Page No. 7 block including connection etc as required. Each 116 87 10,092 -
1.17 DSR-2022 (1.38) Supplying and fixing call bell / buzzer suitable for single phase, 230 V, complete as
Page No. 7 required. Each 1 99 99 -
1.18 DSR-2022 (1.45) Installation, testing and commissioning of ceiling fan, including wiring the down rods
Page No. 8 of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper
conductor, single core cable, including providing and fixing phenolic laminated sheet
cover on the fan box etc. as required. Each 2 339 678 -
1.19 DSR-2022 (1.49) Numbering of ceiling fan/ exhaust fan/ fluorescent fittings as required.
1.20 DSR-2022 (1.50) Installation of exhaust fan in the existing opening, including making good the
Page No. 8 damage, connection, testing, commissioning etc. as required.
a DSR-2022 (1.50.1) Upto 450 mm sweep
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
b DSR-2022 (1.51) Extra for fixing the louvers / shutters complete with frame for a exhaust fan of all
Page No. 8 sizes. Each 17 207 3,519 -
1.21 NON DSR Supply of 300mm diameter single phase, 230 V AC, 50 Hz Industrial exhaust fan for
toilets complete with motor, capacitor, fan assembly mounting frame & louvers with
3 core flexible wire.. Each 11 - 4,860 53,455
1.22 NON DSR Supply of 450mm diameter single phase, 230 V AC, 50 Hz Industrial exhaust fan for
toilets complete with motor, capacitor, fan assembly mounting frame & louvers with
3 core flexible wire.. Each 6 - 5,733 34,397
1.23 NON DSR Supply of 48/56 inch diameter, three blade, single phase, 230 volt AC, 50 Hz, ceiling
fan complete with the motor, starting capacitor, fan assembly, hang pipe, top bottom
domes, required hardwares etc. Each 2 - 2,733 5,465
TOTAL of SH (I) Supply & Fixing of Fans 8,63,969 1,01,249
J. MCCB, MCB & DBs
1.1 DSR-2022 (2.3) Supplying and fixing following way, single pole and neutral, sheet steel, MCB
Page No. 10 distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar,
neutral bus bar, earth bar, din bar, interconnections, powder painted including
earthing etc. as required. (But without MCB/RCCB/Isolator)
a DSR-2022 (2.3.1) 6 way , Double door
b DSR-2022 (2.3.2) 8 way , Double door
c DSR-2022 (2.3.3) 12 way , Double door
1.2 DSR-2022 (2.4) Supplying and fixing following way, horizontal type three pole and neutral, sheet
Page No. 12 steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned
copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted
including earthing etc. as required. (But without MCB / RCCB / Isolator)
a DSR-2022 (2.4.1) 4 way (4 + 12), Double door
b DSR-2022 (2.4.2) 6 way (4 + 18), Double door
c DSR-2022 (2.4.3) 8 way (4 + 24), Double door
1.3 NON DSR Supply, installation, testing and commissioning of wall mounted, vermin proof, dust
proof, indoor duty, front door for access SDB's will have FOUR TIER PPI type 12 Ways
TPN DB metal casing with double door and shall be of fabricated with minimum 1.4
mm thick CRCA sheet and powder coated, as mentioned in this document and shall
have lockable front door and this lock shall be flushed with main door with common
key for all SDB. (This item excludes MCBs and incomer).
1.4 DSR-2022 (2.5) Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V,
Page No. 11 TPN MCB distribution board of sheet steel, dust protected, duly powder painted,
inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for
mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type
MCB TPDB is normally used where 3 phase outlets are required.)
a DSR-2022 (2.5.1) 4 way (4 + 12), Double door
b DSR-2022 (2.5.2) 8 way (4 + 24), Double door
1.5 DSR-2022 (2.10) Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit
Page No. 11 breaker suitable for inductive load of following poles in the existing MCB DB
complete with connections, testing and commissioning etc. as required.
a DSR-2022 (2.10.1) Single pole
b DSR-2022 (2.10.4) Triple pole
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
c DSR-2022 (2.10.5) Triple pole and neutra
1.6 DSR-2022 (2.11) Supplying and fixing single pole blanking plate in the existing MCB DB complete etc.
Page No. 11 as required. Each 5 13 65 -
1.7 DSR-2022 (2.12) Supplying and fixing following rating, double pole, 240 volts, isolator in the existing
Page No. 11 MCB DB complete with connections, testing and commissioning etc. as required.
1.8 DSR-2022 (2.13) Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB
Page No. 11 DB complete with connections, testing and commissioning etc. as required.
1.9 DSR-2022 (2.14) Supplying and fixing following rating, double pole, (single phase and neutral), 240 V,
Page No. 12 residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the
existing MCB DB complete with connections, testing and commissioning etc. as
8.10 DSR-2022 (2.16) Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A,
Page No. 12 240 V “C” curve DP MCB complete with connections, testing and commissioning etc.
as required. Each 1 1,169 1,169 -
8.11 DSR-2022 (2.18) Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and
Page No. 12 earth, metal enclosed plug top alongwith 20 A, “C” curve, SP, MCB, in sheet steel
enclosure, on surface or in recess, with chained metal cover for the socket out let
and complete with connections, testing and commissioning etc. as required.
8.12 DSR-2022 (2.19) Supplying and fixing 20 A, 415 V, TPN Industrial type socket outlet, with 4 pole and
Page No. 12 earth, metal enclosed plug top alongwith 20 A, “C” curve, TP MCB, in sheet steel
enclosure, on surface or in recess, with chained metal cover for the socket out let
and complete with connections, testing and commissioning etc. as required.
TOTAL of SH (J) MCCB, MCB & DBs 2,87,158 18,050
K 11KV HT METERING
1 NON DSR Supplying fixing connecting testing and commissioning of 11 KV metering cubicicle
panel complete with CT's and PT's and Trivector Meter with MDI complete with
necessary accessories and connections etc as required
3 Each 11kV/110V Single phase cast resin PT's (50 VA) burden, Accuracy Class 0.5)
3 Each 15/5A, 11kV cast resin CT's (15 VA) burden, Accuracy Class - 0.5)
1 No. electrtic digital Trivector Meter with MDI (Accuracy Class 0.5)
HT Cable Box suitable for 2 Each 3 Core x 185 sqmm HT AL cable (incoming and
Thje contractor shall get tested and arrange approval of metering panel as well as
equipment including their sealing etc. from UPPCL as required.
The erection rate shall include meter testing charges etc.
In case State Electricity Board provides above panel then this item will not be
executed. Contractor has to get approval from State Electrical Board before
procuring this panel. Set 1 - 1,33,743 1,33,743
Total of SH (K) HT METERING - 1,33,743
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
L 11 KV HT VCB PANEL
1.0 NON DSR Supply, unloading, placing to foundation, erection, testing and commissioning of
OUTDOOR TYPE (IP55) ICOG Panel Board / HT Panel - 11 KV, 630A, 3 Phase, 50 Hz,
metal clad, dead front, 350MVA repturing capacity VCB incoming & outgoing as per
specification and and schematic drawing including connections etc. complete with
following incomer and outgoings including door interlocking and expendable as
1No 630A, 18.3kA for 3sec motorised type drawout VCB circuit breaker horizontally
insulated horizontal drawout, electrical motor operated, spring charged with facility
of manual closing.
1No. Three phase 11kV/√3/110V/√3/110V/√3 Fixed PT star/star/satar rated 50 VA
for 1st secondary, class 0.5 for metering & 50 VA for second secondary, class 3P for
protection connected to incoming side of the breaker through fuse on H.T side &
through MCB on LT side along with auxiliary contacts. PT shall be manufactured and
tested as per IEC standard.
1 Set of Phase indicating lamps with suitable MCB
1 No 0-15 kV Digital Voltmeter with selector switch
1 set of indicating lamps to indicate OPEN, CLOSE, TRIP, SPRING CHARGED, TRIP
CIRCUIT HEALTHY.
Push botton for ON, OFF, TRIP & TRIP circuit healthy.
3 Nos combined 11kV cast resin 30/15/5+5A current transformer 1st winding of
5P20,10VA class for protection, 2nd winding of 0.5 class for metering. CT burden
shall be minimum 10 VA for metering and protection. The CT shall have short links.
The CT shall be manufactured and tested as per IEC standard for partial discharge.
The CT shall with stand fault level of 18kA for 1 sec.
One no. numerical combined based three phase over current with earth fault relay
having IDMT and instantaneous with high set element, 1 no. trip circuit supervision
relay, 1 no. master trip relay, 1 no. anti-pumping relay. Only master trip relay and
trip supervision relay will be electro mechanical. The main numerical relay shall be
micro-processor based.
1 No 0-630 Digital Amps ammeter with slector switch
1 Set of undervoltage relay and Overvoltage relay
1 No. power pack with 24V DC, 17AH (minimum) battery bank capacity.
1 Set of MCB, control wiring, protection wiring, and other item required for the
desired operation of the unit selector switch to indicate the currents.
1 Set indicating light for Spring Charge / Discharge. The spring shall immediately
charge itself for next operation.
Annunciator window (minimum 6 window) for all electrical fault.
Cable entry to the breaker can be from bottom as per site conditions.
All interconnected control wiring. Set 1 - 5,96,807 5,96,807
1.1 NON DSR Supply, unloading, placing to foundation, erection, testing and commissioning of
OUTDOOR TYPE (IP55) ICOG Panel Board / HT Panel - 11 KV, 630A, 3 Phase, 50 Hz,
metal clad, dead front, 350MVA repturing capacity VCB incoming & outgoing as per
specification and and schematic drawing including connections etc. complete with
following incomer and outgoings including door interlocking and expendable as
1No 630A, 18.3kA for 3sec motorised type drawout VCB circuit breaker horizontally
insulated horizontal drawout, electrical motor operated, spring charged with facility
of manual closing.
1No. Three phase 11kV/√3/110V/√3/110V/√3 Fixed PT star/star/satar rated 50 VA
for 1st secondary, class 0.5 for metering & 50 VA for second secondary, class 3P for
protection connected to incoming side of the breaker through fuse on H.T side &
through MCB on LT side along with auxiliary contacts. PT shall be manufactured and
tested as per IEC standard.
1 Set of Phase indicating lamps with suitable MCB
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
1No 0-15 kV Digital Voltmeter with selector switch
1 Set of indicating lamps to indicate OPEN, CLOSE, TRIP, SPRING CHARGED, TRIP
CIRCUIT HEALTHY.
Push botton for ON, OFF, TRIP & TRIP circuit healthy.
3 Nos combined 11kV cast resin 30/15/5+5A current transformer 1st winding of
5P20,10VA class for protection, 2nd winding of 0.5 class for metering. CT burden
shall be minimum 10 VA for metering and protection. The CT shall have short links.
The CT shall be manufactured and tested as per IEC standard for partial discharge.
The CT shall with stand fault level of 18kA for 1 sec.
One no. numerical combined based three phase over current with earth fault relay
having IDMT and instantaneous with high set element with 1 no. seperate static
standby earth fault relay, 1 no. trip circuit supervision relay, 1 no. master trip relay, 1
no. anti-pumping relay, 5 nos. two element transformer auxiliary relay for oil &
winding temperature, Buck holz , Oil surge and PRV. Only master trip relay and trip
supervision relay will be electro mechanical. The main numerical relay shall be
micro-processor based.
1 no. gap less surge suppressor at 10 kV with minimum 5kA discharge current for
8/20 microsecond heavy duty type meeting IEEE std.
1No 0-630 Digital Amps ammeter with slector switch
1No. Multifunction meter of class 0.5
1 Set of undervoltage relay and Overvoltage relay
1No. Digital Power factor meter.
1 No. power pack with 24V DC, 17AH (minimum) battery bank capacity.
Breaker shall have 24V DC cloosing and tripping.
- 1 Set of MCB, control wiring, protection wiring, and other item required for the
desired operation of the unit selector switch to indicate the currents.
- 1 set indicating light for Spring Charge / Discharge. The spring shall immediately
charge itself for next operation.
Annunciator window (minimum 12 window) for all electrical fault.
1.1a Cable entry to the breaker can be from bottom as per site conditions.
1.1b Any extra item which is required to execute the above work satisfactorily as per
specs & drawings. Set 1 - 6,54,135 6,54,135
Total of SH (L) 11 KV HT VCB PANEL Rs. - 12,50,943
M TRANSFORMER (200 KVA)
1 NON DSR Supply, installation, testing and comissioning of 200 kVA oil filled, 11kV/433V, ONAN
type copper wound out door type with OCTC, weather proof type transformer with
Impedence 4.5% and transformer losess shall be as per efficiency level 2 (50% load
losess -0.78kW and 100% load losess -2.3kW). Transformer shall have cable box for
both HT & LT side and with 9 steps from +10% to -10% tap in step of 2.5%.
Transformer shall be designed with ambient temperature at 50 degree. Permissible
temperature rise above ambient shall be 40 degree in oil and 45 degree in winding.
The transformer shall have oil temperature gauge and transformer shall be complete
with all accessories making all connection and carrying out all routine test before
commissioning. No. 1 - 6,82,938 6,82,938
Total of SH (M) TRANSFORMER - 6,82,938
N INVERTER SYSTEM
1.1 5KVA INVERTER
NON DSR Supply, installation, testing, rectification and commissioning of 5kVA 1ph inverter
with maintenance free batteries (Tubular), upto 90 minutes back-up complete with
M.S. batteries rack / trolley & with connecting wires. Nos. 1 - 1,45,582 1,45,582
1.2 0.5KVA INVERTER
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 / DSR-2022 NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY
NON DSR RATE AMOUNT RATE AMOUNT
NON DSR Supply, installation, testing, rectification and commissioning of 0.5kVA 1ph inverter
with maintenance free batteries (Tubular), upto 90 minutes back-up complete with
M.S. batteries rack / trolley & with connecting wires. Nos. 3 - 21,604 64,813
Total of SH (N) INVERTER - 2,10,395
TOTAL AMOUNT 32,13,308 92,01,655
TOTAL AMOUNT 32,13,308 92,01,655
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
Name of Work- Construction and development of Pre Engineered Manufacturing Unit at Industrial Plot No. B-208, at sector Phase-II, Noida
Fire alarm & PA works
DSR-2022 RATE NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY REMARKS
NON DSR RATE AMOUNT RATE AMOUNT
A FIRE ALARM AND PUBLIC ADDRESS SYSTEM
1.0 AUTOMATIC ADDRESSABLE FIRE DETECTION & ALARM SYSTEM
1.1 DSR-2022 Supplying, installation, testing and commissioning of micro processor based
(17.2.1) intelligent addressable main fire alarm panel, central processing unit with
Page No. 57 the following loop modules and capable of supporting not less than 240
devices (including detectors) and minimum 120 detectors per loop and loop
length up to 2 km, network communication card, minimum 320 character
graphics/ LCD display with touch screen or other keypad and minimum 4000
events history log in the non volatile memory (EPROM), power supply unit
(230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free
batteries with automatic charger. The panel shall have facility to connect
printer to printout log and facility to have seamless integration with
analog/digital voice evacuation system (which is part of the schedule of
work under SH: PA System) and shall be complete with all accessories. The
panel shall be compatible for IBMS system with open protocol BACnet/
Modbus over IP complete as per specifications.
1.1.1 DSR-2022 Two Loop Panel.
1.2 DSR-2022 Supplying, installation, testing & commissioning of repeater panel wih 320
(17.2.3) character/ Touch screen LCD display with inbuilt reset, acknowledge and
Page No. 57 silence switches complete as required. No 1 108,688 108,688 -
1.3 DSR-2022 Supplying, installation, testing & commissioning of intelligent analog
(17.2.4) addressable photothermal detector complete with mounting base complete
Page No. 57 as required. Nos 164 2,858 468,712 -
1.4 DSR-2022 Supplying, installation, testing & commissioning of response indicator on
(17.2.5) surface/recessed MS Box having two LED, metallic cover complete with all
Page No. 57 connections etc as required. Nos 10 276 2,760 -
1.5 DSR-2022 Supplying, installation, testing & commissioning of addressable beam
(17.2.12) detector with short circuit isolator (inbuilt or seperate) complete with
Page No. 58 emitter and receiver including connections with remote test features etc
complete as required. No 1 74,937 74,937 -
1.6 DSR-2022 Supplying, installation, testing & commissioning of addressable manual call
(17.2.14) point complete as required.
1.7 DSR-2022 Supplying, installation, testing & commissioning of addressable horn cum
(17.2.15) strobe complete as required.
1.8 NON DSR Supplying & laying of 2C x 2.5 sqmm Copper armoured FRLS cable complete
in everyway. Mtrs. 1500 - 88 131,671
2.0 PAVA SYSTEM
2.1 DSR-2022 Supplying, installation, testing & commissioning of 6 zone, voice alarm
(17.3.1) controller with USB, MP3 player (including 6 zone button paging station)
Page No. 58 with seamless integration facility with main fire alarm panel for voice
evacuation complete as required. No. 1 126,411 126,411 -
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
DSR-2022 RATE NON DSR
Sr. No. DESCRIPTION OF ITEM UNIT QTY REMARKS
NON DSR RATE AMOUNT RATE AMOUNT
2.2 NON DSR Supply, Installation,Testing & Commissioning of Duel channel 250W Power
Amplifier with high efficiency, low power consumption with self indicator
testing function, self-protection from overheat, overcurrent,
overvoltage,under voltage, overload and short circuit, balanced and
unbalanced audio inputs. Make: Henrich/Bosch/Ateis
2.3 NON DSR Supply, Installation, Testing & Commissioning of wall Mounted Voice
Evacuation horn type Speaker having power taps upto 30W and cable tags
and Ferruling etc. complete as required.Complete Aluminum grille and
Metal baffle, line matching transformer 100/70V line. Make:
Henrich/Bosch/Ateis No. 9 - 4,930 44,369
2.4 NON DSR Supply, Installation, Testing & Commissioning of 20W Bidirectional
projection loudspeakers with following features:-component 2*6",
Complete metal grille and line matching transformer 100/70V line. Variable
wattage tapings of 5/10/20W, Effective frequency range 100-15kHz
(BS6840), SPL@1m/1W=91dB, Peak SPL 110dB complete with necessary
mounting hardware & accessories. Make: Henrich/Bosch/Ateis/Ahuja
2.5 DSR-2022 Supplying, installation, testing & commissioning of 1.5/3/6W metal box
(17.3.2) ceiling/wall speakers complete as required.
2.6 DSR-2022 Supplying, installation, testing & commissioning of 1.5/3/6W metal box
(17.3.3) ceiling/wall speakers complete as required.
2.7 NON DSR Supplying & laying of 2C x 2.5 sqmm Copper armoured FRLS cable complete
in everyway. Mtrs. 600 - 88 52,669
Total of SH (O) FIRE ALARM AND PUBLIC ADDRESS SYSTEM 1,180,681 365,339
Digitally signed by
MOHD MOHD TAFSEER
TAFSEER 13:16:35 IST
aoc.pdf
Download all tender documents and submit your bid