Design, manufacture, assembly, supply, installation, testing, delivery and commissioning of 10 kVA UPS of Continuous rating, inbuilt SNMP for online monitoring, double conversion mode 3 ph input and 1 ph output UPS system with IGBT rectifier. The UPS Cabinet shall consist of a Breaker and breaker cabinet, rectifier / charger, a three-phase inverter, static transfer switch, logic, synchronizing equipment, protective devices, display module shall show clear graphical / text based overview of alarms, status data and instructional help, Front/ Back cable entry provision, Parallel kit with necessary BMS compatibility (Hardware & software items for third party integration) with MODBUS protocol-RS 485 and accessories as required for proper operation. The model shall be suitable for parallel redundant & including one year standard warranty & 02 years CAMC post-expiry of DLP (Including Buy back of old UPS and battery bank)
1
pieces
Mayuri Rabha Roy
781022,ESIC Model Hospital Beltola Jayanagar
60
2
Battery
Supply, installation, testing and commissioning of Battery banks of requisite quantity and 12V, 42 AH rating suitable for 10kVA (Continuous rating) online UPS system with one suitably rated DC circuit breaker with all necessary interconnecting links/wiring for each of above UPS units with autonomy to 30 minutes at the end of Battery life span at rated load. Battery shall be of the sealed maintenance free Valve Regulated Lead Acid (VRLA) stationary type 12V blocks, Battery Rack and base frame shall be designed to cater a point load to be conformed by vendor. Minimum VAH required - 10080
20
pieces
Mayuri Rabha Roy
781022,ESIC Model Hospital Beltola Jayanagar
60
3
Battery rack
Supply and installation of Open Battery Rack suitable for the Battery bank for 10kVA UPS system as per point 2 item including UPS mounting)
1
set
Mayuri Rabha Roy
781022,ESIC Model Hospital Beltola Jayanagar
60
4
ITC
Charges for Installation & Commissioning of the whole system including the charges for providing proper training to the Electrician of the Site/Hospital
1
lot
Mayuri Rabha Roy
781022,ESIC Model Hospital Beltola Jayanagar
60
5
MCB DB 1
Supplying and fixing TP sheet steel enclosure on surface/ recess with 40/ 63 A FP MCB complete with connections, testing and commissioning etc. as required.
1
each
Mayuri Rabha Roy
781022,ESIC Model Hospital Beltola Jayanagar
60
6
MCB DB 2
Supplying and fixing DP sheet steel enclosure on surface/ recess with 25/32 A, C -curve DP MCB complete with connections, testing and commissioning etc. as required.
1
each
Mayuri Rabha Roy
781022,ESIC Model Hospital Beltola Jayanagar
60
-
7
Wiring 1
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required -2 X 10 sq. mm + 1 X 6 sq. mm earth wire
20
meter
Mayuri Rabha Roy
781022,ESIC Model Hospital Beltola Jayanagar
60
8
Wiring 2
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required -2 X 6 sq. mm + 1 X 6 sq. mm earth wire
25
meter
Mayuri Rabha Roy
781022,ESIC Model Hospital Beltola Jayanagar
60
Stage Documents
Award of Contract
contract_GEMC-511687716132141.pdf
GEM_CONTRACT • 0.13 MB
Documents
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .