Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.4 LAccepted-Finance | ₹18.4 L | L1 | Accepted-Finance 1st Lowest |
| 2 | L1₹18.4 LAccepted-Finance PLOT NO 53 GAYATRI NAGAR DHENKANAL 759001 | DHENKANAL | ODISHA | 759001 | ₹18.4 L | L1 | Accepted-Finance 1st Lowest |
| 3 | L1₹18.4 LAccepted-Finance | ₹18.4 L | L1 | Accepted-Finance 1st Lowest |
Tender Value
₹18.4 L
EMD Value
₹19,000
Closing Date
5 Mar 2026, 5:00 pmClosed
SE Dhenkanal R and B Division
SE Dhenkanal R and B Division
Construction of 11KV line and installation of 250 KVA Substation for power supply to Newly constructed Collectorate Building in the District of Dhenkanal
2026_EICCL_126387_1
SE DKL (R and B) 39/ 2025-26
Open Tender
Electrical Works
60 days
Dhenkanal
Please refer tender document
2 documents required · 2 mandatory
₹6,000
₹19,000
Yes
27 Mar 2026
21 Feb 2026
6 Mar 2026
21 Feb 2026
5 Mar 2026
21 Feb 2026
Scope of Work: PART- A 11 KV Cut Point with 90 Degree Angle
WPB (GI) Pole 160x152 (13Mtr. Long, 30.44KG/Mtr.) (Total Pole Weight with Base Plate & Stiffner=395.72 KG+10.74 KG= 406.46 KG)
Straight Cross Arm 100X50X6mm, 9.56 KG/Mtr., each Channel(GI) length 1.2 mtr., 4 no's Channel(GI) required =( 4x9.56x1.2)
Fish Plate(GI) 50x6 mm., 2.36 kg/Mtr., each 0.280 mtr. length, 16 no's required = (16x2.36x0.280)
Straight Cross Arm 100X50X6mm, 9.56 KG/Mtr., each Channel(GI) length 0.306 mtr., 4 no's Channel(GI) required =( 4x9.56x0.306)
Danger Plate, 1 no's.
Back Clamp for danger Plate 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 1 no's = (1x0.59x0.510)
GI barbed wire anticlimbing device 3 Kg. Per support
Back Clamp for anticlimbing device 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 4 no's = (4x0.59x0.510)
11 KV pin insulator polymer
H W fitting(B&S) 70KN, 3Bolt
Disc insulator (B&S) 70 KN polymer
Earthing of Support ( Coil Type )
No-8 GI wire (Dia 4.6mm) 0.131 KG/ Mtr.- 2 Mtr. For connecting pole with Coil earthing
NON METALLIC TIES -11KV 55SQMM CVRD AAAC
IPC for 55 sq.mm AAA conductor (For covered conductor)-11kV
WEDGE CONNECTOR FOR 55 sqmm CVRD AAAC
H.T. Stay clamp, 50x8 mm. Flat(GI), 3.14Kg/Mtr., 0.551 Mtr. Length, 2 no's qty. required ( 1 Pair)
H.T. Stay set (Complete )
H.T. Stay Insulator Type-C
7/10 SWG Stay Wire 15kg /stay
GI Nut , Bolt & Washer of different sizes (7.433 Kg each Cut Pole)
Black Paint(GIS Numbering & Zebra Stripping)
Yellow Colour Paint(GIS Numbering & Zebra Stripping) for Background
Civil & Services
Fixing of complete 11KV line Complete stay set includes 1) Turn Buckle Assembly 2) Stay Rod & Stay plate 3) Stay Insulator 4) Stay Wire. 5)Stay clamps with Nuts & bolts BA will do the excvation including excvation, supply of 0.5Cum cement concrete foundation 1:2:4 size ( 500mmx500mmx800mm) using 20mm BHG metal with all labour and material as per TPCODL Drawing & Standard.
Concreting ratio 1:1.5:3(M-20 Grade) (500mmX500mmX1800mm) = 0.45Cu.mtr(Per Pole)
Couping ratio 1:1.5:3(M-20 Grade) with dimension ( 500X500X450)= 0.1125 Cu mtr(Per Pole)
Scope of Work: PART- B 11 KV Pin Points With WPB
55 SQ.MM. AAAC XLPE Covered Conductor
Scope of Work: PART- C DP Metering UNIT
WPB (GI) Pole 160x152 (13Mtr. Long, 30.44KG/Mtr.) (Total Pole Weight with Base Plate & Stiffner=395.72 KG+10.74 KG= 406.46 KG)
Top Channel 100X50X6mm, 9.56 KG/Mtr., each channel length 3 mtr., 2 no's channel required =( 2x9.56x3)
Fish Plate 50x6 mm., 2.36 kg/Mtr., each 0.280 mtr. length, 16 no's required = (16x2.36x0.280)
AB switch Mounting Channel 75X40X4.8mm, 7.14KG/Mtr, each channel length 3 Mtr., 2 no's channel required =( 7.14x3x2)
HT MU Mounting channel 100x50x6mm /9.56kg/mtr each channel lenghth 3 mtr
HG/DO Fuse mounting channel (GI)75x40x4.8 mm GI Channel (7.14Kg/mtr 2 nos )
cantilever support channel 75x40x4.8 mm GI Channel (7.14Kg/mtr 2 nos )
Angle for cantilever arrangement for HT MU 50x50x6-1282mm each 2 nos(4.5kg per mtr)
MU and AB Switch Side Support Channel 100X50X6mm,9.56 KG/Mtr., each channel length 0.35 mtr., 4 no's channel required =( 9.56x4x0.35)
Channel Support for down Pipe 75X40X 4.8mm., 7.14KG/Mtr . each channel length 0.8 Mtr .. 1 no's channel required=( 7.14x0.8x1)
Double pole bracing channel 75X40X 4.8mm., 7.14KG/Mtr . each channel length 3 Mtr .. 2 no's channel required=( 7.14x3x2)
50X50X6 MM GI Bracing angle ,4.5 kg /mtr ,each channel length 3.512 mtr ,2 nos angle required =(4.5x3.5x2)
Danger plate 2 nos.
Back Clamp for danger Plate 25X3 mm. flat, 0.59Kg/Mtr. Flat of 0.510 mtr length 2 no's = ( 2 x0.59x0.510)
55mm2 all alloy alluminium conductor (AAAC)- for jumpering
HT Stay Clamp 50x8mm, flat 3.14kg/mtr, 0.551 mtr length 2nos. Qty required (1 pair)
HT Stay Set (complete)
Supply & installation of HT Stay insulator Type-C
Supply & installation of 7/10 SWG GI Stay wire (15 Kg/set)
GI Pipe earthing 40mm, 3 meters long
50x6mm GI Flat for earthing, 2.36kg/mtr . (12.5 mtr for L.A, 3mtr for AB switch body, 2.5 mtr. For mesh formation and 2.5 mtr For raising) 20.5x2.36
GI barbed wire anticlimbina device 3 Kg Per support 2 no's qty. required =(2x3kg)
Back Clamp for anticlimbing device 25X3 mm. flat, 0.59Kg/Mtr. Flat of 0.510mtr length 8 no's =(8x0.59x0.510)
Lightning Arrestor (11KV-10KA) Station class-2
AB Switch (11KV,200A,3pole,50 HZ)
11KV Pin insulator Polymer
HW fittng ( B & S) 70KN, 3bolt
Disc Insulator (B & S) 70KN polymer
WEDGE CONNECTOR FOR 55 sqmm CVRD AAAC
S/F of GI Nut, Bolt & washer of different sizes (13.718 kg each DP with AB switch)
..Polycarbonate bird guard
Supply & painting with black Paint.
Supply& painting with yellow colour paint for background
DO FUSE(11KV,200A ,3 POLE)
10Amp fuse link
Civil & Services
Fixing of complete 11KV line Complete stay set includes 1) Turn Buckle Assembly 2) Stay Rod & Stay plate 3) Stay Insulator 4) Stay Wire. 5)Stay clamps with Nuts & bolts BA will do the excvation including excvation, supply of 0.5Cum cement concrete foundation 1:2:4 size ( 500mmx500mmx800mm) using 20mm BHG metal with all labour and material as per TPCODL Drawing & Standard.
Concreting ratio 1:1.5:3 (500mmX500mmX1800mm) = 0.45Cu.mtr
Couping ratio 1:1.5:3 with dimension ( 500X500X450)= 0.1125 Cu mtr
Construction earthing chamber including installation of earthing pipe. Making earthing chamber including excavation, soil treatment with bentonide powder, calculation of earth resistance including installation pf 3mtr GI pipe 40mm/50mm including welding of GI flat around pipe.
Supply and erection of GI Fencing with gate
Material for Line Protecting Guarding for Road crossing
Guarding Channel(GI) 75x40x4.8 mm, 7.14 KG/Mtr., each Channel(GI) length 3.5 mtr., 4 no's Channel(GI) required =( 4x7.14x3.5) ( For Double Pole)
No-6 GI wire (0.192 kg/mtr.) for Main String
No-8 GI wire (0.131 kg/mtr.) for lacing
Eye Bolt (236mm, 16mm dia, 1.577kg/mtr.)
Gi Pipe Earthing 40mm. 3 Mtr. Long
50x6mm Flat(GI) for earthing, 2.36kg/mtr., (10.7 mtr For raising)= 10.7x2.36
Construction Earthing chamber including installation of earthing pipe.Making earthing chamber including excavation , soil treatment with bentonide powder , calculation of earth resistance, including Installation of 3Mtr GI Pipe 40mm/50mm including welding of Flat(GI) around pipe .
Scope of Work: PART-D :- Installation of 11/0.4 KV, 250 KVA DSS-1 No
WPB (GI) Pole 160x152 (11Mtr. Long, 30.44KG/Mtr.)
Top Channel(GI) GI 100 X 50 X 6 MM (3000 mm long) (9.56Kg./Mtr, 2 No's.) (Each 2x3.000x9.56= 57.36 Kg)
Fish Plate(GI) 50x6 mm., 2.36 kg/Mtr., each 0.280 mtr. length, 6 no's required = (6x2.36x0.280)
M.U Channel(GI) GI 75x40x4.8 mm (3000 mm long)(7.14Kg./Mtr., 2 No's.) (Each 2x3.000x7.14= 42.84 Kg)
AB Switch Mounting Channel(GI) 75x40x4.8 mm GI Channel(GI) (3000 mm long)(7.14Kg./Mtr., 2 No's.) (Each 2x3.000x7.14= 42.84 Kg)
AB Switch Side Support Channel(GI) 100X50X6mm,9.56 KG/Mtr., each Channel(GI) length 0.35 mtr., 2 no's Channel(GI) required =( 9.56x2x0.35)
Channel(GI) Support for down Pipe 75X40X 4.8mm., 7.14KG/Mtr., each Channel(GI) length 0.8 Mtr., 1 no's Channel(GI) required =( 7.14x0.8x1)
HG/ DO Fuse Mounting Channel(GI) 75x40x4.8 mm GI Channel(GI) (3000 mm long)(7.14Kg./Mtr., 2 No's.) (Each 2x3.000x7.14= 42.84 Kg)
Cantilever Support Channel(GI) 75x40x4.8 mm GI Channel(GI) (810 mm long,2 No's.) (7.14Kg./Mtr., 2 No's.) (Each 2x0.810x7.14= 11.57 Kg)
Cantilever Support Angle(GI) 50 X 50 X 6MM GI (1282 mm long) (4.5Kg./Mtr, 2 No's.) (Each 2x1.282x4.5= 11.54Kg)
Double Pole Belting Channel(GI) 75X40X 4.8mm., 7.14KG/Mtr., each Channel(GI) length 3.0 Mtr., 2 no's Channel(GI) required =( 7.14x3x2)
50x50x6mm.GI Bracing Angle(GI), 4.5Kg./mtr., each Angle(GI) length 3.512 mtr., 2 nos Angle(GI) required = (4.5x3.512x2)
50x6mm Flat(GI) for earthing, 2.36kg/mtr., (2.5x7 mtr. For mesh formation, 12 Mtr. For LA and 2.5 mtr. For raising, 11 mtr for AB switch, 2.8 mtr for HG Fuse, 5x2 mtr. for DTR Nutral, (1.3+4.5) mtr. For DTR Body, 0.500 mtr for LTDB & AB Switch operating handle, 3 mtr. for Fencing) ( Each 65.6x 2.36= 154.81 Kg)
250 KVA , 11/ 0.4 KV (Cu) Transformer with Tap Changer BIS Energy Loss level II, Ammendment-4
LT Distribution Box with MCCB, Aluminium Busbar for 3 Bay with kit kat fuse for 250 KVA S/S
55 SQ.MM. AAAC XLPE Covered Conductor
1 Cx 400 mm2 LT XLPE Cable(Un-Armoured)
LT Cable Supporting Channel(GI) 100 X 50 X 6 MM GI Channel(GI) (2000 mm long)(9.56 Kg./Mtr., 2 No's.) (Each 2x2x9.56= 28.56 Kg)
LT Cable Supproting Angle(GI), 50x50x6mm.GI 4.5Kg./mtr., each Angle(GI) length 2 mtr., 4 nos Angle(GI) required = (4.5x4x2)
Supply of 1.1kV, 4Core, 150 sqmm, XLPE insulation armoured -Aluminium UG cable from LTDB to Pole
AB Switch(11KV,200A.3pole,50Hz)
H.G.Fuse( 11KV.200A.3Pole)
WEDGE CONNECTOR FOR 55 SQMM.CONDUCTOR
POLYCARBONATE BIRD GUARD
Disc insulator (B&S)70 KN polymer
H W fitting (B&S)70KN(3bolted)
Lightning Arrester(12KV,10KA) Station Class 2
11KV pin insulator polymer
HT stay set complete
HT stay Clamp (1.9Kg/pair)
HT stay insulator TYPE-C
7/10 SWG GI stay wire, Grade -2 (15Kg./ Set)
40 mm Nominal bore GI pipe (medium gauge) earthing device with 3 mtr .Long
GI Nuts & Bolts of Assorted size (25 Kg/ DSS DP)
GI Barbed wire/Anticlimbing device (3Kg /Pole)
Back Clamp for anticlimbing device 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 8 no's = (8x0.59x0.510)
Danger plate 11kv
Back Clamp for danger Plate 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 2 no's = (2x0.59x0.510)
Name plate
Structure Numbering and Marking
Yellow Colour Paint(GIS Numbering & Zebra Stripping) for Background
Black Colour Paint(GIS Numbering & Zebra Stripping) for numbering
Concreting ratio 1:1.5:3(M-20 Grade) (500mmX500mmX1800mm) = 0.450Cu.mtr(Per Pole) (For WPB Pole)
Couping ratio 1:1.5:3(M-20 Grade) (500mmX500mmX450mm) = 0.113Cu.mtr(Per Pole)
PCC ratio 1:3:6(M-10 Grade) For DSS Area (3.5X2.5X0.1)= 0.875 Cu. mtr.
Fixing of stay set with 0.5Cum cement concrete foundation 1:3:6(M-10 Grade) size ( 900mmx600mmx900mm) using 40mm BHG metal with all labor and material except stay set , stay wire , stay insulator .
Construction Earthing chamber including installation of earthing pipe.Making earthing chamber including excavation , soil treatment with bentonide powder , calculation of earth resistance, including Installation of 3Mtr GI Pipe 40mm/50mm including welding of Flat(GI) around pipe .
LTDB Plinth
DTR Plinth
Laying of 4 Cx 150 mm2 LT XLPE Cable
Laying of 1.1kV cable from 400 to 1000sqmm
SITC and Erection of GI Fencing with Gate
Concreting ratio 1:1.5:3(M-20 Grade) (500mmX500mmX1500mm) = 0.375Cu.mtr(Per Pole) (For PSC Pole)
GST@18%(mailto:GST@18%25塹ᴻ䡿ⲯ嶂藄挧ꮥ)
Supply of AL Lugs suitable for 150 sq mm cable/conductor, Crimping with cable and Fixing/connecting include supply and erection of PVC Tape as per voltage requirement.
Supply and erection of double Compression Flameproof Type Glanding for armored Cable 1C 300-1000 sqmm including making hole in Base plate and dressing of cable along with vermin proofing properly .Supply to be done as per TPCODL Spec and approved make dowells.
Supply and erection of double Compression Flameproof Type Glanding for armored Cable 3.5/4C 120-185sqmm including making hole in Base plate and dressing of cable along with vermin proofing properly .Supply to be done as per TPCODL Spec and approved make dowells.
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
fin_eval.pdf
finance_582236.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.33 MB
DTCN_Collectorate.pdf
Tender Documents • 0.81 MB
BOQ_582236.xls
BOQ • 0.90 MB
Download all tender documents and submit your bid