Tender Value
₹7.1 Cr
EMD Value
₹14.2 L
Closing Date
21 Sept 2026, 3:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Revenue
TENDER ELG
17 conditions · 3 needing a document upload
The tenderer must have minimum average annual contractual turnover ofV/N or 'V' whichever is less where V= Advertised value of the tender incrores of Rupees, N= Number of years prescribed for completion of workfor which bids have been invited. The average annual contractualturnover shall be calculated as an average of "total contractualpayments" in the previous three financial years, as per the auditedbalance sheet. However, in case balance sheet of the previous year isyet to be prepared/ audited, the audited balance sheet of the fourthprevious year shall be considered for calculating average annualcontractual turnover. The tenderers shall submit requisite information asper Annexure-VIB, along with copies of Audited Balance Sheets dulycertified by the Chartered Accountant/ Certificate from CharteredAccountant duly supported by Audited Balance Sheet.(In this connectionscanned copy of Annexure VIB duly filled up must be attached withoffer). In case of OEMs or sources approved by RDSO, the above criteriaare not essential as per Railway Board letter No.2019/Elect(G)/165/1 NewDelhi,dated :22.04.2020.)
As per Clause (ii) of 2019/Elect(G)/165/1 New Delhi, dated 22.04.2020"THE FINANCIAL ELIGIBILITY CRITERIA AS CONTAINED IN GCC 2018 orANY AMENDMENT THEREAFTER MAY BE DISPENSED WITH IN CASE OFBIDDERS, WHO ARE EITHER OEMS OR SOURCES APPROVED BY RDSO,THIS EXEMPTION SHALL BE EXTENDED TO PUs APPROVED SOURCESALSO FOR VARIOUS SAFETY/VITAL ITEMS WHICH WERE TRANSFERRED TOPUs VIDE BOARD'S LETTER NO. 2001/RS(G)779/7 dated 07.12.2016."(This Clause is applicable for this tender)
The tender has been invited for the bidders appearing in the approved list of RDSO for Roof Mounted Package Units (RMPU) as per Rly Board's Letter no. 2009/Elect(G)/138/1 dated: 07.02.2017. Offer from the bidders other than the RDSO approved list shall be summarily rejected.
13 conditions · 4 needing a document upload
The details of the uploaded documents should be produced whenever demanded for verification on written request at any point of time of the tender and contract within 7 days.
The following documents should be attached with the tender ( Annexure-V (A) certificate is to be given by attorney/authorized signatory/each member of Partnership firm/Joint Venture (JV) / Hindu Undivided Family (HUF) / Limited Liability Partnership (LLP) etc. & Scanned copy POA/Partnership deed is to be uploaded Duly filled up by the bidder
Scanned copy of valid GST (Goods & Service Tax)Registration Certificate.
Partnership deeds, power of Attorney etc. (if any) : The tender shall clearly specify whether the tender is submitted on his own or on behalf of a partnership concern. If the tender is submitted on behalf of partnership concern he should submit the certified copy of the partnership deed along with the tender authorisation to sign the documents on behalf of the partnership firm. If these documents are not enclosed along with the tender document, the tender will be treated as hearing lease submitted by the individual signing the tender documents. The Railway will not consider any power of Attorney granted by the tender or any changes in the composition of the firm made subsequent to the execution of the contract. It may however recognize such power of Attorney and change after obtaining proper legal advice, the cost of which will be chargeable to the contract.(Scanned copy POA/Partnership deed is to be uploaded Duly filled up by the bidder. As per clause no. 14(e) of GCC'22, the following documents to be uploaded in terms of Company registered under Companies Act2013: (i) The copies of MOA (Memorandum of Association) / AOA (Articles of Association) of the company (ii) A copy of Certificate of Incorporation (iii) A copy of Authorization/Power of Attorney issued by the Company (backed by the resolution of Board of Directors) in favour of the individual to sign the tender on behalf of the company and create liability against the company. (iv) All other documents in terms Para 10 of the Tender Form (Second Sheet) above.
Scanned copy of valid Trade license or Propitorship Certificate.
List of the Works completed in the last three financial years giving description of work. Organization for whom executed, approximate value of contract at the time of award, date of award and date of scheduled completion of work. Date of actual start, actual completion and date of payment and final value of contract should also be given. (Supportive documents/ certificates from the organization with whom worked/are working should be enclosed) (Please attach scanned copy of Annexure-I duly filled up).
List of works in hand indicating Supportive documents/certificates from the organization with whom worked/are working should be enclosed) description of work, contract value, approximate value of balance work yet to be done and date of award. (Supportive documents/certificates form the organization with whom worked/are working should be enclosed).(Please attach scanned copy of Annexure-IV duly filled up)
Option for receiving payment through Letter of Credit . (Please attach scannedcopy of ANNEXURE 1 LC & ANNEXURE 2 LC duly filled up by the firm if optedfor)
Railway Officers Associated with tenderer:RAILWAY OFFICERS ASSOCIATED WITH TENDERER 1. ExRailway Officer as tenderer: Should tenderer be a retired Gazetted Officer working before his retirement on any of the Railways owned and administered by the President of India, or should the tenderer being partnership firm have as one of its partners a retired Gazetted Officer as aforesaid, or should the tenderer being an incorporated company have any such retired Officer as one of its Directors, or should the tenderer have in his employment any retired Gazetted Officer as aforesaid, full information of such person shall be submitted along with his tender in the format given in annexure-VI to this chapter of this tender document. (Authority: ACS No.3 to GCC July,2014vide Boards letter No.2014/CEI/CT/O/9/RET dt.22.01.2015)(please attach scanned copy of Annexure-VI duly filled up by the firm).
The following documents should be attached with the tender: (i)Scanned copy of Pan Card. (ii)Scanned Copy of EFTMANDATE FORM Duly filled up by the bidder(iii)Tender Document (duly digitally signed by the bidder)
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
The Contractor/(firm) must go through the entire tender document along with all attachment for any kind of guidance regarding execution of the job & payment there after. In case any thing is left out or not clear then they should consult the General Condition of Contract & standard Specification as attached (uploaded ).The bidders are also advised to preserve a copy of entire tender document/ (Set) for their convenience.
Corrective Maintenance Contract of LHB and Non LHB type AC package units of different make for a period of 36 months
EL-HWH-25-21-3702~ER
EL-HWH-25-21-3702
Open
Works - General
36 Months
Howrah, West Bengal
₹0
₹14.2 L
21 Sept 2026
28 Aug 2026
7 Sept 2026
241 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 7,11,04,420 | ||
| — | — | — | Above/ 4126080.00 Below/P | ||
| Supply of new Scroll Compressor ZR-61KC-2TFD-523 or 522 as per RDSO specification including drier SR-075-1040 | — | 120.00 | — | — | |
| — | — | — | Above/ 812280.00 Below/P | ||
| Removal of defective Scroll Compressor ZR-61KC-2TFD-523 or 522as per RDSO specification including drier SR-075-1040 and Fitmentby new one including drier (all type of gas and vacuum pump requried will be supplied by Firm) (Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 120.00 | — | — | |
| — | — | — | Above/ 609210.00 Below/P | ||
| Removal of defective Scroll Compressor ZR-61KC-2TFD-523 or 522as per RDSO specification including drier SR-075-1040 and Fitmentby new one including drier (all type of gas and vacuum pump requried will be supplied by Firm) (Compressor will be supplied by Railway)(Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 90.00 | — | — | |
| — | — | — | Above/ 97200.00 Below/P | ||
| Removal of defective blower motor 1.5 HP 1400 RPM and fitment of new blower motor with TOP (Make- RDSO approved source) with released blower runner (A+B) Type SR-075- 1027 or compatible to LEEL, Amit, Daulatram, SSK, Sidwal, PRAG,Stasalit or any make as per site requirement)(Defective items to be returned to Sr.SEE/ACC/HWH or SYAE)(Blower motor will be supplied by Railway) | — | 60.00 | — | — | |
| — | — | — | Above/ 597540.00 Below/P | ||
| Supply of new condenser fan motor 1 HP / 1400 RPM (Make- RDSO approved source) | — | 60.00 | — | — | |
| — | — | — | Above/ 87780.00 Below/P | ||
| Removal of defective condenser fan motor 1 HP / 1400 RPM and fitment of new condenser fan motor 1400 RPM with TOP(Make- RDSO approved source) with released fan blade SR- 075-1028 (Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 60.00 | — | — | |
| — | — | — | Above/ 87780.00 Below/P | ||
| Removal of defective condenser fan motor 1 HP / 1400 RPM and fitment of new condenser fan motor 1400 RPM with TOP(Make- RDSO approved source) with released fan blade SR- 075-1028 (Defective items to be returned to Sr.SEE/ACC/HWH or SYAE)(Condenser motor will be supplied by Railway) | — | 60.00 | — | — | |
| — | — | — | Above/ 88164.00 Below/P | ||
| SS Spider for condenser Motor similar as fitted in LHB AC and Non-LHB RMPU as per site requirements | — | 36.00 | — | — | |
| — | — | — | Above/ 47808.00 Below/P | ||
| Removal/defective /broken SS Spider for condenser motor from AC coach and fit ment of new one (Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 36.00 | — | — | |
| — | — | — | Above/ 254220.00 Below/P | ||
| Supply of new plastic fan with Aluinium hub (SR-075-1036) or compatible to Sidwal,LEEL, Amit, Daulatram, SSK, PRAG or any other make RMPU as per site requirement | — | 60.00 | — | — | |
| — | — | — | Above/ 91620.00 Below/P | ||
| Removal of defective plastic fan with Aluminium hub and fitment with new one | — | 60.00 | — | — | |
| — | — | — | Above/ 61500.00 Below/P | ||
| Supply of drier (SR-075-1036) or compatible to Sidwal, LEEL, Amit, Daulatram, SSK, PRAG or any other make RMPU as per stire requirement | — | 30.00 | — | — | |
| — | — | — | Above/ 21770.00 Below/P | ||
| Supply of new SS welded round guard .(SR-075-1041) or equivalent as required | — | 10.00 | — | — | |
| — | — | — | Above/ 8200.00 Below/P | ||
| Removal of defective SS welded round guard and Fitment with new one (SR-075- 1041) or equivalent as required (Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 10.00 | — | — | |
| — | — | — | Above/ 1907070.00 Below/P | ||
| Leak test of the system, rectification , flushing the system with N2 Gas including charging of R-22/R-407 gas in LHB/SG coaches(all type of gas & vacuum pump required will be supplied by firm) | — | 330.00 | — | — | |
| — | — | — | Above/ 165810.00 Below/P | ||
| Removal and Fitment of Drier filter (1/2" Solder type) SR-075-1019 or equivalent as required (all associated jobs e.g. brazing, leak testing etc.alongwith all types of gas(R22/R407) & vacuum pump required will be supplied by firm)(Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 30.00 | — | — | |
| — | — | — | Above/ 440100.00 Below/P | ||
| Supply of new Hartige (Couplers) connector 24 pin SR-075-1001 or equivalent as required | — | 60.00 | — | — | |
| — | — | — | Above/ 133200.00 Below/P | ||
| Removal of defective / damage Hartige (Couplers) connector 24 pin and Fitment with new 24 pin Couplers SR-075-1001 or equivalent as required (Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 60.00 | — | — | |
| — | — | — | Above/ 23604.00 Below/P | ||
| Removal of new Hartige (Couplers) connector 16 pin and Fitment with new 16 pin Couplers SR-075-1002 or equivalent as required (Defective items to be returned to Sr.SEE/ACC/HWH or SYAE)(Material will be supplied by Firm) | — | 12.00 | — | — | |
| — | — | — | Above/ 18048.00 Below/P | ||
| Removal and Fitment of strainer capillary(all associated jobs e.g.brazing, leak testing etc.alongwith all types of gas (R22/R407) & vacuum pump required will be supplied by firm) (Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 3.00 | — | — | |
| — | — | — | Above/ 457440.00 Below/P | ||
| Supply of new Pressure Transmiter (0 - 10 bar) with new SR-075-1010 or equivalent as required (all associated jobs e.g. brazing, leak testing etc.alongwith all types of gas & vacuum pump required will be supplied by firm) | — | 60.00 | — | — | |
| — | — | — | Above/ 232440.00 Below/P | ||
| Removal of defective Pressure Transmiter (0-10 bar) and Fitment with new SR-075- 1010 or equivalent as required (all associated jobs e.g. brazing,leak testing etc.alongwith alongwith all types of gas and vacuum pump required will be supplied by firm)(Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 60.00 | — | — | |
| — | — | — | Above/ 458460.00 Below/P | ||
| Supply of new Pressure Transmiter (0 - 40 bar) with new SR-075-1011 or equivalent as required (all associated jobs e.g. brazing, leak testing etc.alongwith all types of gas & vacuum pump required will be supplied by firm) | — | 60.00 | — | — | |
| — | — | — | Above/ 232440.00 Below/P | ||
| Removal of defective Pressure Transmiter (0-40 bar) and fitment with new SR-075- 1011 or equivalent as required (all associated jobs e.g. brazing, leak testing etc.alongwith all types of gas & vacuum pump requried will be supplied by firm)(Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 60.00 | — | — | |
| — | — | — | Above/ 242460.00 Below/P | ||
| Supply of new Over heat protection for heater (OHP) Alert or any other make with prior (setting 65 Oeg.C.Max.) approval of RDSO for LHB/SG AC coaches or updated version by RDSO. | — | 180.00 | — | — | |
| — | — | — | Above/ 279000.00 Below/P | ||
| Removal of defective protection for heater (OHP) and Fitment by new one(Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 180.00 | — | — | |
| — | — | — | Above/ 38310.00 Below/P | ||
| Supply of new glass bulb Cartidge +130 ° . SR-075-1015 or equivalent as required | — | 30.00 | — | — | |
| — | — | — | Above/ 9900.00 Below/P | ||
| Removal of defective glass bulb Cartidge +130 ° and Fitment by new one(Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 30.00 | — | — | |
| — | — | — | Above/ 227826.00 Below/P | ||
| Supply of new ESTI switch assembly with cartridge SR-075-1014 or equivalent as required | — | 18.00 | — | — | |
| — | — | — | Above/ 30924.00 Below/P | ||
| Removal of defective ESTI switch assembly with cartridge SR-075-1014 or equivalent as required and fitment by new one.(Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 18.00 | — | — | |
| — | — | — | Above/ 6684.00 Below/P | ||
| Supply of new Air Heater coil consisting 400W with insulated backalite sheet | — | 12.00 | — | — | |
| — | — | — | Above/ 19104.00 Below/P | ||
| Removal of defective Air Heater coil consisting 400W with insulated backalite sheet and replacement by new one(Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 12.00 | — | — | |
| — | — | — | Above/ 28656.00 Below/P | ||
| Removal of defective Air Heater coil consisting 400W with insulated backalite sheet and replacement by new one(Defective items to be returned to Sr.SEE/ACC/HWH or SYAE)(Material will be supplied by Railway) | — | 18.00 | — | — | |
| — | — | — | Above/ 229320.00 Below/P | ||
| Supply of new Low pressure control switch (auto reset) SR-075-1037 orequivalent as required | — | 90.00 | — | — | |
| — | — | — | Above/ 380610.00 Below/P | ||
| Removal of defective Low pressure control switch (auto reset) & Fitment by new one SR-075-1037 or equivalent as required(all associated jobs e.g.brazing, leak testing etc.alongwith all types of gas & vacuum pump required will be supplied by firm)(Alco make to Alco make and Danfoss make to Alco make Danfoss make-KP-1/Alco make-PS3-AP3 HNK4/1,5b(Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 90.00 | — | — | |
| — | — | — | Above/ 159000.00 Below/P | ||
| Supply of new High pressure control switch (auto reset) SR-075-1038 or equivalent as required | — | 60.00 | — | — | |
| — | — | — | Above/ 253740.00 Below/P | ||
| Removal of defective High pressure Control switch (Auto reset) and fitment by new one (all associated jobs e.g.brazing, leak testing etc.alongwith all types of gas & vacuum pump required will be supplied by firm)(Alco make to Alco make and Danfoss make to Alco make Danfoss make-KP-5/Alco make-PS3-AP4 HNK23/20 '+/-0.3 bar(Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 60.00 | — | — | |
| — | — | — | Above/ 246870.00 Below/P | ||
| Supply of new Control pressure switch (Auto reset) | — | 90.00 | — | — | |
| — | — | — | Above/ 380610.00 Below/P | ||
| Removal of defective Control pressure switch (Auto reset) and fitment by new one (all associated jobs e.g.brazing, leak testing etc.alongwith alltypes of gas & vacuum pump required will be supplied by firm)(Alco make to Alco make and Danfoss make to Alco make Danfoss make-KP- 5/Alco make-PS3-AP4 HNK23/20 '+/-0.3 barKP-5/Alco make-PS3-AP4 HNK23/20 '+/-0.3 bar | — | 90.00 | — | — | |
| — | — | — | Above/ 434520.00 Below/P | ||
| Supply of new Expansion Valve SR-075-1039/TX3-H36 R22801772M ALCO or equivalent as required | — | 90.00 | — | — | |
| — | — | — | Above/ 552780.00 Below/P | ||
| Removal of defective Expansion Valve. SR-075-1039/TX3-H36 R22801772M ALCO or equivalent as required and fitment of new one (all associated jobs e.g. brazing, leak testing etc.alongwith all types of gas & vacuum pump required will be supplied by firm)(Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 90.00 | — | — | |
| — | — | — | Above/ 531588.00 Below/P | ||
| Supply of new Evaporator coil - Left hand SR-075-1042/ Right hand SR-075-1043, Evaporator Coil Left hand LEEL, Dwg No.: FRC3BWJ526/ Right hand LEEL, Dwg No.: FRC3BWJ527 or compatible for packages make SSK, Amit, Feeder Lloyds, Daulat Ram as required and also supply of drier | — | 12.00 | — | — | |
| — | — | — | Above/ 139104.00 Below/P | ||
| Removal of defective Evaporator coil - Left hand / Right hand and fitment with new o n e as required(all associated jobs e.g.brazing, leak testing etc.alongwith all types of gasand vacuum pump required will be supplied by firm) | — | 12.00 | — | — | |
| — | — | — | Above/ 164658.00 Below/P | ||
| Supply of condenser coil - Left hand / Right hand compatible for Sidwal (SR-075-1044 / SR-075-1045), LEEL (Dwg.No.FRC3BWJ526/FRC3BWJ525), SSK, Daulat Ram, Amit, Feeder Lloyds as required | — | 3.00 | — | — | |
| — | — | — | Above/ 34971.00 Below/P | ||
| Removal of defective condenser coil - Left hand / Right hand and fitment with new o n e as required (all associated jobs e.g.brazing, leak testing etc.alongwith all types of gas and vacuum pump required will be supplied by firm) | — | 3.00 | — | — | |
| — | — | — | Above/ 31050.00 Below/P | ||
| Supply of new 2 position Seclector Rotary switch with 2 auxiliary NO/NC 2 Pole of Power ON OFF as per RDSO specification | — | 30.00 | — | — | |
| — | — | — | Above/ 19530.00 Below/P | ||
| Removal and fitment of 2 position Seclector Rotary switch with 2 auxiliary NO/NC 2 Pole of Power on off SR-075-1048 or equivalent as required | — | 30.00 | — | — | |
| — | — | — | Above/ 14877840.00 Below/P | ||
| Supply and commissioning of LHB type 1 Microprocessor with matching sensor and digital display unit as per RDSO specification no. RDSO/PE/SPEC/AC/0139-2009 (Rev-II) or latest (For Passenger Car) | — | 120.00 | — | — | |
| — | — | — | Above/ 1859730.00 Below/P | ||
| Supply and commissioning of LHB type 2 Microprocessor with matching sensor and digital display unit as per RDSO specification no. RDSO/PE/SPEC/AC/0139-2009 (Rev-II) or latest (For Power Car) | — | 15.00 | — | — | |
| — | — | — | Above/ 995280.00 Below/P | ||
| Supply of new Display Panel with feather touch operation | — | 60.00 | — | — | |
| — | — | — | Above/ 80100.00 Below/P | ||
| Removal of defective / damaged Display Panel and fitment by new one(Defective / damaged items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 60.00 | — | — | |
| — | — | — | Above/ 168132.00 Below/P | ||
| Supply of new Hygrostat 35 - 100%. SR-075-1022 or equivalent as required | — | 12.00 | — | — | |
| — | — | — | Above/ 81612.00 Below/P | ||
| Removal of defective Hygrostat 35 - 100%. SR-075-1022 or equivalent as required and fitment of new one | — | 12.00 | — | — | |
| — | — | — | Above/ 254025.00 Below/P | ||
| Supply of new fresh air (5K ohm) temperature sensor for SRMC-22L controller or equivalent as required | — | 45.00 | — | — | |
| — | — | — | Above/ 58905.00 Below/P | ||
| Removal of defective fresh air (5K ohm) temperature sensor for SRMC-22L controller or equivalent as required and fitment of new one | — | 45.00 | — | — | |
| — | — | — | Above/ 289125.00 Below/P | ||
| Supply of new return / supply air (5K ohm) temperature sensor for SRMC-22L controller or equivalent as required | — | 45.00 | — | — | |
| — | — | — | Above/ 71235.00 Below/P | ||
| Removal of defective return/supply air (5K ohm) temperature sensor and fitment of new one for SRMC-22L controller or equivalent as required | — | 45.00 | — | — | |
| — | — | — | Above/ 221520.00 Below/P | ||
| Supply of new compressor contactor Type- LS18K 00 DC110V(With Diode 1HS 7K 10) 77-137 V DC AEG Make or TAL 40 -30 01+RT5/150 CA5 - 22 M ABB make or RDSO/RCF approved make | — | 60.00 | — | — | |
| — | — | — | Above/ 36720.00 Below/P | ||
| Removal of defective compressor contactor Type- LS18K 00 DC110V(With Diode 1HS 7K 10) 77-137 V DC AEG Make or TAL 40 -30 01+RT5/150 CA5 - 22 M ABB make or RDSO/RCF approved make and fitment of new one | — | 60.00 | — | — | |
| — | — | — | Above/ 173700.00 Below/P | ||
| Supply of new condensor motor contactor Type- LS4K 10E DC110V(With Diode ) 77- 137 V DC AEG Make or TAL 16 -30 01/110V DC+RT5/150+CA5-01ABB Make or RDSO/RCF approved make | — | 60.00 | — | — | |
| — | — | — | Above/ 36720.00 Below/P | ||
| Removal of defective condensor motor contactor Type- LS4K 10E DC110V (With Diode ) 77-137 V DC AEG Make or TAL 16 -30 01/110V DC+RT 5/150+CA5-01ABB Make or RDSO/RCF approved make and fitment of new one | — | 60.00 | — | — | |
| — | — | — | Above/ 130275.00 Below/P | ||
| Supply of new Blower motor contactor Type- LS4K 10B DC110V(With Diode 1HS 7K 01 )77-137 V DC AEG Make or TAL 16 -30 01/110VDC+RT5/150+CA5-01ABB Make or RDSO/RCF approved make | — | 45.00 | — | — | |
| — | — | — | Above/ 27540.00 Below/P | ||
| Removal of defective Blower motor contactor Type- LS4K 10B DC110V(With Diode 1HS 7K 01 )77-137 V DC AEG Make or TAL 16 -30 01/110VDC+RT5/150+CA5-01ABB Make or RDSO/RCF approved make and fitment of new one | — | 45.00 | — | — | |
| — | — | — | Above/ 74052.00 Below/P | ||
| Supply of new Heater contactor Type- LS4K 10B DC110V(With Diode 1HS 7K 01 )77- 137 V DC AEG Make or TAL 16 -30 01/110VDC+RT5/150+CA5-01ABB Make or RDSO/RCF approved make | — | 36.00 | — | — | |
| — | — | — | Above/ 22752.00 Below/P | ||
| Removal of defective Heater contactor Type- LS4K 10B DC110V(With Diode 1HS 7K 01 )77-137 V DC AEG Make or TAL 16 -30 01/110VDC+RT5/150+CA5-01ABB Make or RDSO/RCF approved make and fitment of new one | — | 36.00 | — | — | |
| — | — | — | Above/ 174360.00 Below/P | ||
| Supply of blower runner set (A+B) compatible for Sidwal, LEEL, Amit, SSK, Daulat Ram, Stesalit PRAG make RMPU as required for LHB AC Coaches. | — | 30.00 | — | — | |
| — | — | — | Above/ 58230.00 Below/P | ||
| Removal of defective blower runner set (A+B) compatible for Sidwal, LEEL, Amit, SSK, Daulat Ram, Stesalit or any other make RMPU and retrofitment with new one(Defective to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 30.00 | — | — | |
| — | — | — | Above/ 548808.00 Below/P | ||
| Supply of new blower housing complete with motor and runner other than VEM required for LHB AC coaches | — | 24.00 | — | — | |
| — | — | — | Above/ 58200.00 Below/P | ||
| Removal of defective blower housing complete with motor (other than VEM make) and runner and replacement by new assembly(Defective / damaged items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 24.00 | — | — | |
| — | — | — | Above/ 799740.00 Below/P | ||
| Supply of Double inlet centrifugal blower ,415V , 3 phase 50Hz 120W,450 cubic meter per hour discharge for exhausting air from lavotory /switch board cabinet (Make- RDSO approved source) | — | 60.00 | — | — | |
| — | — | — | Above/ 112200.00 Below/P | ||
| Removal of defective Double inlet centrifugal blower , 415V , 3 phase 50Hz 120W, 450 cubic meter perhour discharge for exhausting air from lavotory / switch board cabinet (Make- RDSO approved source) | — | 60.00 | — | — | |
| — | — | — | Above/ 434970.00 Below/P | ||
| Supply of Multifunctional monitoring relay for three phase main suitablefor 750 V system , monitoring phase parameters like Phase sequence,Phase failure Over and under voltage and phase unbalace GIC. Carlo Gavazzi, or ABB as latest version (Make- ABB , Type no - CM-MPN.72) | — | 45.00 | — | — | |
| — | — | — | Above/ 151110.00 Below/P | ||
| Removal of defective Multifunctional monitoring relay for three phase main suitable for 750 V system , monitoring phase parameters like Phase sequence, Phase failure Over and under voltage and phase unbalance (Make- ABB , Type no - CM-MPN.72)and fitment with new one | — | 45.00 | — | — | |
| — | — | — | Above/ 11772000.00 Below/P | ||
| Cleaning of Cooling coil, Condenser coil by high pressure jet water with cleaning agent and tightness checking, greasing of all motors during schedule attention of AC coaches, cleaning of return air filters, fresh air filters after removing from RMPU to be replaced with new one if found unserviceable and refitment with new one inside duct diffuser and return grill cleaning with brush and air blower by duly opeing ceiling, return grill and refixiing the same and testing with proper instrument reading of Amp of various motors and refrigerant pressure, Air flow measurement to be recorded Microprocessor data to be downloaded and to be submitted to SSE/concerned.Sealing Compound, Cleaning Agent -Orion 510 D, High Pressure water Jet, Air blower and other equipmentmust be supplied by the firm | — | 2700.00 | — | — | |
| — | — | — | Above/ 770130.00 Below/P | ||
| Supply new Feeder Contact 415 V (IS-13703) Contactor for Net -1& 2, rated voltage 1000 V AC rated kva 100 at rated voltage and 70 degree C and utilisation categary 6A, Main pole 4, Auxoliarycontact 2No+2 NC control voltage415V AC with surge arrestor | — | 45.00 | — | — | |
| — | — | — | Above/ 121545.00 Below/P | ||
| Installation and re-fitment of new one Feeder Contact 415 V (IS-13703) Contactor for Net -1& 2, rated voltage 1000 V AC rated kva 100 at rated voltage and 70 degree C and utilisation categary 6A, Main pole 4, Auxoliary contact 2No+2 NC control voltage415V AC with surge arrestor | — | 45.00 | — | — | |
| — | — | — | Above/ 1965600.00 Below/P | ||
| Cleaning of Perforated sheet inside the coach over celling in Air flow pocket and Cleaning ofReturn Air duct/Supply Air Duct in Ac coaches during D-3 Schedule by digital air sucking procedure | — | 1200.00 | — | — | |
| — | — | — | Above/ 128400.00 Below/P | ||
| Supply of Indication lamp of LHB Coaches. Different colour & variety as per requirement | — | 1200.00 | — | — | |
| — | — | — | Above/ 3133100.00 Below/P | ||
| Supply of new water proof fire retardent meta amide supply air duct with metalic frame on both end as per RDSO (Set) | — | 100.00 | — | — | |
| — | — | — | Above/ 1059600.00 Below/P | ||
| Removal of defective supply air duct & fitment of new meta amide duct with metalic frame on both side (Defective to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 100.00 | — | — | |
| — | — | — | Above/ 1308500.00 Below/P | ||
| Supply of new water proof fire retardent meta amide return air duct with metalic frame on both end as per RDSO | — | 100.00 | — | — | |
| — | — | — | Above/ 420000.00 Below/P | ||
| Removal of def. return air duct & fitment of new meta amide duct with metalic frame on both end (Defective to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 100.00 | — | — | |
| — | — | — | Above/ 792000.00 Below/P | ||
| Supply of return air filter complete with felt compatible for Sidwal, LEEL, Amit, SSK, Daulat Ram,Stesalit PRAG or any make as per site requirement make RMPU as per RDSO as required | — | 600.00 | — | — | |
| — | — | — | Above/ 61950.00 Below/P | ||
| Supply of new condenser fan motor 1 HP / 910 RPM (Make- RDSO approved source)as per requirement for SG coach | — | 6.00 | — | — | |
| — | — | — | Above/ 10896.00 Below/P | ||
| Removal of defective condenser fan motor 1 HP / 910/1400 RPM and fitment of new condenser fan motor 910/1400 RPM (Make- RDSO approved source) with released FRP fan blade for SG coach (Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 6.00 | — | — | |
| — | — | — | Above/ 18333.00 Below/P | ||
| Removal of defective blower runner set (A+B) compatible for Sidwal, LEEL,FL Amit, SSK,Daulat Ram, Stesalit make RMPU and retrofitment with new one for SG coach (Defective to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 9.00 | — | — | |
| — | — | — | Above/ 6723.00 Below/P | ||
| SS Spider for Condenser Motor similar as fitted in SG AC Coachs as per site requirements | — | 3.00 | — | — | |
| — | — | — | Above/ 2832.00 Below/P | ||
| Removal /Defective /Broken SS Spider for Condenser Motor from AC Coach and fitment with new one for SG coach (Defective items to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 3.00 | — | — | |
| — | — | — | Above/ 21792.00 Below/P | ||
| Removal of defective plastic fan with Aluminium hub and fitment with new one ,Material supplied by Railway ( Fan blade to be supply by railway) for SG coach | — | 12.00 | — | — | |
| — | — | — | Above/ 16614.00 Below/P | ||
| Removal of defectlve HP/LP cut out and fitment with new HP/LP Cut-Out & Charging refrigerant gas. Material supplied by Railway (gas to be supplied by railway) for SG coach. | — | 9.00 | — | — | |
| — | — | — | Above/ 12675.00 Below/P | ||
| Supply &fittment of new 415/110v 400va Isolation Transformer(make- Guru or equivalent) as per site requirement for SG coach (Defective material to be returne to the Sr.SEE/ACC/HWH, SYAE) | — | 3.00 | — | — | |
| — | — | — | Above/ 19032.00 Below/P | ||
| Supply & fitment of new electronic time dealy relay material should be from RDSO approved source, as per site requirement for SG coach (Defective material to be returne to the Sr.SEE/ACC/HWH, SYAE) | — | 3.00 | — | — | |
| — | — | — | Above/ 387510.00 Below/P | ||
| Supply & fitment of new 3P 32 Amps MPCB of any RDSO approved make as per site Defective requirement (Defective material to be returne to the Sr.SEE/ACC/HWH, SYAE) | — | 30.00 | — | — | |
| — | — | — | Above/ 28230.00 Below/P | ||
| Supply & fitment of new 3P 16 Amps MCB of any RDSO approved make as per site requirement (Defective material to be returne to the Sr.SEE/ACC/HWH, SYAE) | — | 30.00 | — | — | |
| — | — | — | Above/ 5040.00 Below/P | ||
| Supply & fitment of 2P 4 Amps MCB of any RDSO approved make as per site requirement(Defective material to be returne to the Sr.SEE/ACC/HWH, SYAE) | — | 6.00 | — | — | |
| — | — | — | Above/ 36456.00 Below/P | ||
| Removal of defective accumulator with new one with necessary leak test by N2 gas and re charging of R-22/R-407 gas after leack test. Accumulator to be supplied by railway (Defective material to be returne to Sr.SE/ACC/HWH or SYAE | — | 6.00 | — | — | |
| — | — | — | Above/ 40158.00 Below/P | ||
| Supply of new heater bank stainless steel with fins and fitment of new OHP with proper insulated sleeve as per site requirement for SG coach. | — | 6.00 | — | — | |
| — | — | — | Above/ 9924.00 Below/P | ||
| Removal of defective heater bank stainless steel with fins and OHP with insulated sleeve (Defective items to be returned to Sr.SE/ACC/HWH or SYAE for SG coach. | — | 6.00 | — | — | |
| — | — | — | Above/ 35322.00 Below/P | ||
| Supply of new complete control harness set from electrical contral panel to Upper socket near power JB as per latest RDSO spec. as per site requirement for SG coach. | — | 6.00 | — | — | |
| — | — | — | Above/ 11604.00 Below/P | ||
| Removal of defective control harness from electrical contral panel to Upper socket near & fitment the new one. (Defective item to be returned to Sr.SE/ACC/HWH or SYAE | — | 6.00 | — | — | |
| — | — | — | Above/ 24042.00 Below/P | ||
| Supply of new control herness upper plug portion near power junction box socket to other control safety switch with all wire as per site requirement. Material should be RDSO approved make for SG coach. | — | 6.00 | — | — | |
| — | — | — | Above/ 4902.00 Below/P | ||
| Removal of defective control harness uper plug portion near power junction box shocket to other control shefty switch with all wire & fitment the new one. (Defective item to be returned to Sr.SE/ACC/HWH or SYAE) For SG coach. | — | 6.00 | — | — | |
| — | — | — | Above/ 33756.00 Below/P | ||
| Supply of new control harness socket portion including all wires in inside panels as per site requirement. Material should be RDSO approved make. For SG coach. | — | 6.00 | — | — | |
| — | — | — | Above/ 6714.00 Below/P | ||
| Removal of defective control harness socket portion including all wires from electrical control panel & fitment the new one for SG coach(Defective item to be returned to Sr.SE/ACC/HWH or SYAE | — | 6.00 | — | — | |
| — | — | — | Above/ 52180.00 Below/P | ||
| Supply of new 3P (BFM-2.4 to 3.6 & CDFM-1.7-2.4) MPCB with auxilary contact for blower & condenser motor. (make as per RDSO approved make as per site requirement for SG coach. | — | 20.00 | — | — | |
| — | — | — | Above/ 6760.00 Below/P | ||
| Removal of defective 3P (BFM-2.4 to 3.6 & CDFM-1.7-2.4) MPCB with auxilary contact for blower condenser motor and replace with new one.(Defective item to be returned to Sr.SE/ACC/HWH or SYAE) | — | 20.00 | — | — | |
| — | — | — | Above/ 97460.00 Below/P | ||
| Supply of new 3P, 12-16 A MPCB with auxilary contact for compressor motor. (make as per RDSO approved make as per site requirement for SG coach. | — | 20.00 | — | — | |
| — | — | — | Above/ 8720.00 Below/P | ||
| Removal of defective 3P 12-16 A MPCB for Compressor motor and replace with new one. (Defective item to be returned to Sr.SE/ACC/HWH or SYAE) | — | 20.00 | — | — | |
| — | — | — | Above/ 100203.00 Below/P | ||
| Supply of new blower housing complete with motor,runner and all other accessories as per site requirement for SG coach as suitable in SGAC Coaches. | — | 3.00 | — | — | |
| — | — | — | Above/ 10086.00 Below/P | ||
| Removal & replacement of defective blower housing with new assemblyas suitable in SGAC coaches (Defective item to be returned to Sr.SE/ACC/HWH or SYAE) | — | 3.00 | — | — | |
| — | — | — | Above/ 32682.00 Below/P | ||
| Supply of new water proof fire retardent return air canvas ducting set with metalic frame at both ends as per RDSO guideline as per site requirement for SG AC coach | — | 6.00 | — | — | |
| — | — | — | Above/ 11838.00 Below/P | ||
| Removal of defective return air canvas ducting set and fitment the new canvas duct. (Defective item to be returned to Sr.SE/ACC/HWH or SYAE) | — | 6.00 | — | — | |
| — | — | — | Above/ 28218.00 Below/P | ||
| Supply of new water proof fire retardent supply air canvas ducting set with metalic frame at both ends as per RDSO guideline as per site requirement | — | 6.00 | — | — | |
| — | — | — | Above/ 5898.00 Below/P | ||
| Removal of defective supply air canvas ducting set and fitment the new canvas duct. (Defective item to be returned to Sr.SE/ACC/HWH or SYAE) | — | 6.00 | — | — | |
| — | — | — | Above/ 37068.00 Below/P | ||
| Removal of defective capillary and replacement with new one with necessary leak test by N2 and recharging of R-22/R-407 refrigerant after leak test.(N2,R-22/R-407 gas required will be supplied by firm) (Defective item to be returned to Sr.SE/ACC/HWH or SYAE | — | 6.00 | — | — | |
| — | — | — | Above/ 11820.00 Below/P | ||
| Supply of the Fedder selection rotary switch ( with auxilary) with marking "I-0-II" net 1 - local main supply - net 2 (chaqnge over switch with 0- position 3-pole ) rated voltage 690 V AC, rated current 16A | — | 30.00 | — | — | |
| — | — | — | Above/ 5070.00 Below/P | ||
| Removal of def. Fedder selection rotary switch & fitment the new rotary switch. (Defective item to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 30.00 | — | — | |
| — | — | — | Above/ 130920.00 Below/P | ||
| Supply of the Auto-Manual by-pass rotary switch for air- condition, as per RDSO spec RDSO/PE/SPEC/AC/0184 (Rev.2) or latest | — | 60.00 | — | — | |
| — | — | — | Above/ 155820.00 Below/P | ||
| Removal of def. Auto-Manual by-pass rotary switch & fitment the new rotary switch. (Defective item to be returned to Sr.SEE/ACC/HWH or SYAE) | — | 60.00 | — | — | |
| — | — | — | Above/ 10846437.00 Below/P | ||
| GST as applicable (at present @ 18%) | — | 1.00 | Lumpsum | — |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TenderClause3702.pdf
ATTACHMENT
Advancecorrectionslipsupto11.pdf
ATTACHMENT
GCC_April-2022.pdf
ATTACHMENT
Annexure-VA.pdf
ATTACHMENT
TenderBooklet.pdf
ATTACHMENT
TenderFormandAnnexuresnew_1.pdf
ATTACHMENT
EligibilityCriteriaTejPratapNarayan22.04.20.pdf
ATTACHMENT
OEMorRDSOApprovedSourceMahendraKumar07.02.17.pdf RDSO Approved Source
ATTACHMENT
PolicyletterforVendor_Appr_Safety07.12.16.pdf
ATTACHMENT
AnnexureVIB.pdf
ATTACHMENT
OEMorRDSOApprovedSourceMahendraKumar07.02.17.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .