GE Utility Electric Supply
GE Utility Electric Supply Delhi Cantt-10
REPAIR AND MAINTENANCE LT PANEL ACBS MCCBS EARTHING AND CONNECTED ITEMS AT DHAULA KUAN PARTN II 5 RMC URI ENCLAVE RR COLONY 61 CAVALARY TODAPUR PERIRA ENCLAVE 1 WEC EETSU DASH AEC 48 MVH WESEE SIG CENTRE WEE WKSP BRAR SQUARE YELLOW DOUBLE STOREY
2026_MES_788425_1
GE ELECT/TOKEN-42/2026-2027
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE Utility Electric Supply
As Per Tender Documents
7 documents required · 7 mandatory
₹500
GE Utility Electric Supply
₹92,000
8 Sept 2026
8 Sept 2026
1 Oct 2026
8 Sept 2026
29 Sept 2026
22 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installing, testing and commissioning in replacement of factory made and tested (including CPRI type tested certified panel) LT Panel board, cubical compartmentalized, out door type double door, platform mounted, suitable for 415 volts, 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber with insulated aluminium bus bars four pole installed on porcelain/SMC insulator. The panel shall be dust and vermin proof. IP-65 class protection and shell be made of 3.15 mm CRCA MS sheet, and 50x50x6mm thick MS angle iron frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, front and rear opening type, with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid, copper conductor FRLS cable, IS-694 marked, 1100 volts grade of appropriate size ( but not less than 2.5 Sqmm) and comprising of the following Complete all as specified and directed by Engr-in -charge :-
(a) Incoming :-
(i) MCCB 4 pole, 315 Amps,50 Hz,415 Volts, 25 KA with microprocessor release - 01 No
(ii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No
(iii) Ammeter digital type with 4 way rotary selector switch - 01No
(iv) CTs ratio 250/5 A ,class 1, ISI marked -01 sets of three
(v) Indicating lamp- 01 set of three
(vi) Aluminium bus bar of rating 500 A- set of four
(b) Outgoing :-
(i) MCCB 4 pole, 100 Amps, 50 Hz, 415 Volts, 25 KA with thermal magnetic release - 02 Nos (ii) MCCB 4 pole, 63 Amps, 50 Hz, 415 Volts, 16 KA with thermal magnetic release - 04 Nos
(c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level.
Note :-
(i) All out going feeder shall be connected by cable through suitable size gland plate / glands.
(ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint.
(iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993 (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer | 3 | Each Job | - | - |
| - | All as in item No 1 here-in-before but comprising of the following :-
(a) Incoming :-
(i) MCCB 4 pole , 630 Amps,50 Hz,415 Volts, 36 KA, with microprocessor release - 01 Nos (ii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No
(iii) Ammeter digital type with 4 way rotary selector switch-01No
(iv) CTs ratio 315/5 A ,class 1, ISI marked -01 sets of three
(v) Indicating lamp- 01 set of three
(vi) Aluminium bus bar of rating 800A- set of four
(b) Outgoing
(i) MCCB 4 pole , 160 Amps,50 Hz,415 Volts, 25 KA with thermal magnetic release -01 Nos
(iii) MCCB 4 pole , 200 Amps,50 Hz,415 Volts, 16 KA with thermal magnetic release - 04 Nos | 1 | Each Job | - | - |
| - | All as in item No 1 here-in-before but comprising of the following :-
(a) Incoming :-
(i) MCCB 4 pole , 400 Amps,50 Hz,415 Volts, 35 KA, with microprocessor release - 01 Nos
(ii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No
(iii) Ammeter digital type with 4 way rotary selector switch-01No
(iv) CTs ratio 400/5 A ,class 1, ISI marked -01 sets of three
(v) Indicating lamp- 01 set of three
(vi) Aluminium bus bar of rating 800 Amps- set of four
(b) Outgoing
(i) MCCB 4 pole , 100 Amps,50 Hz,415 Volts, 25 KA with thermal magnetic release - 02 Nos
(ii) MCCB 4 pole , 200 Amps,50 Hz,415 Volts, 25 KA with thermal magnetic release - 01 Nos
(iii) MCCB 4 pole , 63 Amps,50 Hz,415 Volts, 25 KA with thermal magnetic release - 02 Nos | 1 | Each Job | - | - |
| - | All as in item No 1 here-in-before but comprising of the following :-
(a) Incoming :-
(i) MCCB 4 pole , 400 Amps,50 Hz,415 Volts, 36 KA, with microprocessor release - 01 Nos
(ii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No
(iii) Ammeter digital type with 4 way rotary selector switch-01No
(iv) CTs ratio 250/5 A ,class 1, ISI marked -01 sets of three
(v) Indicating lamp- 01 set of three
(vi) Aluminium bus bar of rating 500 Amps- set of four
(b) Outgoing
(i) MCCB 4 pole, 125 Amps,50 Hz,415 Volts, 25 KA with thermal magnetic release - 02 Nos
(ii) MCCB 4 pole, 63 Amps,50 Hz,415 Volts, 25 KA with thermal magnetic release - 04 Nos | 2 | Each Job | - | - |
| - | All as in item No 1 here-in-before but comprising of the following :-
(a) Incoming :-
(i) MCCB 4 pole , 630 Amps,50 Hz,415 Volts, 50 KA, with microprocessor release - 01 Nos
(ii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No
(iii) Ammeter digital type with 4 way rotary selector switch-01No
(iv) CTs ratio 600/5 A ,class 1, ISI marked -01 sets of three
(v) Indicating lamp- 01 set of three
(vi) Aluminium bus bar of rating 1200 Amps- set of four
(b) Outgoing
(i) MCCB 4 pole , 250 Amps, 50 Hz, 415 Volts, 36 KA with thermal magnetic release - 02 Nos (ii) MCCB 4 pole , 200 Amps,50 Hz,415 Volts, 36 KA with thermal magnetic release - 02 Nos | 1 | Each Job | - | - |
| - | All as in item No 1 here-in-before but comprising of the following :-
(a) Incoming :-
(i) MCCB 4 pole , 630 Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release - 01 Nos
(ii) Onload Changeover switch 400 Amp-01 Nos
(iii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No
(iv) Ammeter digital type with 4 way rotary selector switch-01No
(v) CTs ratio 400/5 A ,class 1, ISI marked -01 sets of three
(vi) Indicating lamp- 01 set of three
(vii) Aluminium bus bar of rating 800 Amps- set of four
(b) Outgoing
(i) MCCB 4 pole , 200 Amps, 50 Hz,415 Volts, 25 KA with thermal magnetic release - 02 Nos
(ii) MCCB 4 pole , 160 Amps , 50 Hz,415 Volts, 25 KA with thermal magnetic release - 01 Nos
(iii) MCCB 4 pole ,100 Amps , 50 Hz,415 Volts, 25 KA with thermal magnetic release - 02 Nos | 1 | Each Job | - | - |
| - | All as in item No 1 here-in-before but comprising of the following :-
(a) Incoming :-
(i) MCCB 4 pole , 630 Amps,50 Hz,415 Volts, 50 KA, with thermal magnetic release - 01 Nos
(ii) Onload Changeover switch 630 Amp-01 Nos
(iii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No
(iv) Ammeter digital type with 4 way rotary selector switch-01No
(v) CTs ratio 600/5 A ,class 1, ISI marked -01 sets of three
(vi) Indicating lamp- 01 set of three
(vii) Aluminium bus bar of rating 1200 Amps- set of four
(b) Outgoing
(i) MCCB 4 pole , 160 Amps, 50 Hz,415 Volts, 25 KA with thermal magnetic release - 05 Nos
(ii) MCCB 4 pole , 125 Amps , 50 Hz,415 Volts, 16 KA with thermal magnetic release - 01 Nos | 1 | Each Job | - | - |
| - | Supplying, fabrication, installation, testing and commissioning in replacement of LT panel not less than 3mm thick of modular polycarbonate thermoplastic enclosures Indoor type with copper bus bar of capacity 400A, factory made, CPRI approved,e floor mounting type, environment friendly, recyclable, UV resistant, halogen and silicon free, anti-acid and anti corrosive, enclosure should be IP-65 Protection in accordance with IEC 60529.The gasket material shall be polyurethane while the gasket shall be internally embedded including suitable working space in bus bar chamber suitable for 3 phase 4 wire system 415V,50HZ,AC supply and fixed on raised PCC 1:2:4,type B1 (20mm graded aggregate) raised base with cable glands, phase indicators, internal wiring, CT of suitable Ratio, digital voltmeter and ammeter, air passing holes with bproper spacing to accommodate to all control switches and other accessories, cable connections with suitable size of lugs/thimble etc including suitable size canopy to cover the panel with proper fixing arrangement including excavation and elarth work including dismantling the unserviceable panel and comprising the followings.
Incoming:-
(a) MCCB 250 Amps 3 Pole,36 KA- 01 No
(b) Rotary handle- 01 No
(C) spreader Link- 01 set( 08 Pcs)
(d) RYB Indicating lamp
(e) Digital laVoltmeter and ammeter of suitable rating
(f) set of ibtCT of ratio - 250/05 Amps
Outgoing.
(a) Suitable hole in bus bar for out going cable connection including suitable size nut bolt and fastener complete all as specified and directed. | 4 | Each Job | - | - |
| - | All as in item No 1 here-in-before but comprising of the following :-
(a) Incoming :-
(i) MCCB 4 pole , 630 Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release - 01 Nos
(ii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No
(iii) Ammeter digital type with 4 way rotary selector switch-01No
(iv) CTs ratio 400/5 A ,class 1, ISI marked -01 sets of three
(v) Indicating lamp- 01 set of three
(vi) Aluminium bus bar of rating 400 Amps- set of four
(b) Outgoing
(i) MCCB 4 pole , 100 Amps,50 Hz,415 Volts, 25 KA with thermal magnetic release - 02 Nos
(ii) MCCB 4 pole , 160 Amps,50 Hz,415 Volts, 10 KA with thermal magnetic release - 04 Nos | 2 | Each Job | - | - |
| - | All as in tem No 1 here-in-before but comprising of the following :-
(a) Incoming :-
(i) ACB 4 pole, 1000 Amp, 50 KA, 415 Volt AC with Microprocessor based LCD protection release for adjustable over current, short circuit and earth fault protection - 01 Nos
(ii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No
(iii) Ammeter digital type with 4 way rotary selector switch-01No
(iv) CTs ratio 1000/5 A ,class 1, ISI marked -01 sets of three
(v) Indicating lamp- 01 set of three
(vi) Aluminium bus bar of rating 2000A- set of four
(b) Outgoing
(i) MCCB 4 pole , 320 Amps,50 Hz,415 Volts, 36 KA with Thermal magnetic release - 02 Nos
(ii) MCCB 4 pole , 250 Amps,50 Hz,415 Volts, 25 KA with Thermal magnetic release - 02 Nos
(iii) MCCB 4 pole , 160 Amps,50 Hz,415 Volts, 25 KA with Thermal magnetic release - 01 Nos (iv) MCCB 4 pole , 100 Amps,50 Hz,415 Volts, 25 KA with Thermal magnetic release - 01 Nos (v) MCCB 4 pole , 63 Amps,50 Hz,415 Volts, 25 KA with Thermal magnetic release - 02 Nos | 2 | Each Job | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.28 MB
TD42.pdf
Tender Documents • 0.70 MB
BOQ_883737.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .