Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.7 LAccepted-AOC RAJKOT ROAD AIR FORCE STATION HALWARA 141106 PUNJAB | HALWARA | LUDHIANA | PUNJAB | 141106 | L1 | Accepted-AOC Being lowest and reasonable | |
| 2 | L2₹14.5 L+₹3.8 L (35.0%)Rejected-Finance | L2 | Rejected-Finance Being not lowest | |
| 3 | L3₹15.1 L+₹4.4 L (41.1%)Rejected-Finance | L3 | Rejected-Finance Being not lowest | |
| 4 | L4₹15.4 L+₹4.7 L (43.8%)Rejected-Finance | L4 | Rejected-Finance Being not lowest | |
| 5 | L5₹18.4 L+₹7.7 L (71.6%)Rejected-Finance 2549 NATHA SINGH STREET MEHNA MOHALLA BATHINDA PB 151001 | BATHINDA | BATHINDA | PUNJAB | 151001 | L5 | Rejected-Finance Being not lowest |
Tender Value
Refer Docs
EMD Value
₹40,000
Closing Date
5 Oct 2020, 6:00 pmClosed
GE (AF) Halwara
GE (AF) Halwara
INTERNAL WIRING INCLUDING REPLACEMENT OF CFL WITH LED FITTINGS AND MISC EM WORKS AT AF STATION BARNALA UNDER GE AF HALWARA
2020_MES_374939_1
GE/HAL-33/2020-21
Open Tender
Civil Works
Item Rate
183 days
GE (AF) Halwara
MES ENLIESTED CONTRACTORS CLASS E CATEGORY b i
8 documents required · 8 mandatory
₹500
Yes
GE (AF) Halwara
₹40,000
Yes
8 Oct 2020
5 Sept 2020
7 Oct 2020
5 Sept 2020
5 Oct 2020
21 Sept 2020
Amount
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc
Point wiring concealed type complete with 1.5 sqmm PVC insulated unsheathed and multi stranded copper conductor, PVC conduit 20 mm bore having 2 mm wall thickness with all conduit accessories for one light point controlled by one 6 Amps one way switch including continuous 1.00 sqmm copper conductor, stranded (green colour, earth), PVC insulated unsheathed earth wire to common earth and connected to earth dolly to be terminated in and including suitable size module boxes for housing of module switches/sockets etc complete all as specified and directed Note : Unit rates quoted by contractor shall be deemed to included for cutting chases in walls and making good in cement morter (1:3) and finishing the surface to match with exisiting surface.
All as per Si item No.2 above but one bell/ buzzer point controlled by one push button on the independent with cables 1.5 sq.mm size.
All as per Si item No.2 above but one celing/Exhaust fan point controlled by one 5 Amps one-way switch.
All as per Si item No.2 above but one 5 pin 5 Amps switch socket outlet point on independent board
All as per Si item No.2 above but one 5 pin 5Amps switch socket outlet point on same board .
All as per item No. 2 here in before but 4 Sqmm copper conductor wiring with 2.5 Sqmm copper conductor as earth continuity for 15 Amps socket out let on independent board.
Material labour for point wiring complete with 1.5 Sqmm PVC insulated unsheathed single core multi multistranded copper conductor FRLSH cable (Phase and neutral) 1100 V grade drawn through casing caping for one switch 6 Amps one way on wall/ceiling and terminated to MS box of 1.6 mm thick and 3 mm thick laminated sheet top cover including machine screws and washer etc for fixing modular switches sockets etc including 1.5 Sqmm copper conductor , stranded (green colour earth), PVC insulated unsheathed earth wire to common earth and connected to earth dolly as specified and directed by Engr-in- charge. Note : Unit rates quoted by contractor shall be deemed to included for cutting chases in walls and making good in cement morter (1:3) and finishing the surface to match with exisiting surface.
All as per Si item No.8 above but one bell/ buzzer point controlled by one push button on the independent board
All as per Si item No.8 above but one celing/Exhaust fan point controlled by one 5 Amps one-way switch.
All as per Si item No.8 above but one 5 pin 5Amps switch socket outlet point on independent board
All as per Si item No.8 above but one 5 pin 5Amps switch socket outlet point on same board .
All as per item No. 8 here in before but 4 Sqmm copper conductor wiring with 2.5 Sqmm copper conductor as earth continuity conductor for 15 Amps socket out let on independent board.
Material labour for point wiring complete with 1.5 Sqmm PVC insulated unsheathed single core multi multistranded copper conductor FR cable (Phase and neutral) 1100 V grade drawn through surface Conduit for one light point controlled by one 6 Amps one way switch on wall/ceiling and terminated to MS box of 1.6 mm thick and 3 mm thick laminated sheet top cover including machine screws and washer etc for fixing switches sockets etc including 1.5 Sqmm copper conductor , stranded (green colour earth), PVC insulated unsheathed earth wire to common earth and connected to earth dolly as specified and directed by Engr-in- charge.
All as per Si item No.14 above but one bell/ buzzer point controlled by one push button on the s independent board
All as per Si item No.14 above but one celing/Exhaust fan point controlled by one 5 Amps one-way switch .
All as per Si item No.14 above but one 5 pin 5Amps switch socket outlet point on independent board
All as per Si item No.14 above but one 5 pin 5Amps switch socket outlet point on same board .
All as per item No. 14 here in before but 4 Sqmm copper conductor wiring with 2.5 Sqmm copper conductor as earth continuity for 15 Amps socket out let on independent board.
Supply and fix switch modular type single pole one way 6 Amps including suitable size of module cover with frame.
Supply and fix switch modular type single pole one way 16 Amps including suitable size of module cover with frame etc.
Supply and fix socket outlet 5 pin 6 Amp modular type including suitable size of cover with frame.
Supply and fix socket outlet 6A /16Amp 6 pin suirable size of cover with frame.
Supply and fixing Modular Bell push 6A 1 module
Supply & Fixing Bell Multi Music type
Supply and fixing of Ceiling rose, 3 phase/PVC/ polycarbonate, isolated body
S &F Switch piano, flush type single pole, one way 5 Amp
S & F socket 2 in 1, 5 pin, 5 A flush type universal
S & F Switch socket combination 2 in 1, 6 pin, 15A Amp flush type universal
S & F Lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings
S & F 9 watt LED bulb all as specified and directed.
S & F as in repairs IP-20 linear retro LED T-8 tubular lamp with extruded Aluminium/PC body and PC diffuser complete with in built driver 1X20 watt including new decorative box type fitting prewired LED tube with blue colored end caps.
S & F in repairs recessed LED ceiling panel provided with best in class aesthetics premium white powder coated frame blends assembly with ceiling layout suitable for 600 X600 mm modular ceiling grid and also can be suspended with provided kit.
S&F in repairs sheet metal enclosures factory made, (Single door) for DBs, single pole and neutral, 240 volts, 4 ways with 200Amp rated busbar fixed on walls, including connecting both incoming and outgoing cable termination with proper taping, lagging, testing and commissioning, complete all as specified.
S&F in repairs sheet metal enclosures factory made, (Single door) for DBs, single pole and neutral, 240 volts, 8 ways with 200Amp rated busbar fixed on walls, including connecting both incoming and outgoing cable termination with proper taping, lagging, testing and commissioning, complete all as specified and directed.
S&F in repairs sheet metal enclosures factory made, (Single door) for DBs, single pole and neutral, 240 volts, 6 ways with 200Amp rated busbar fixed on walls, including connecting both incoming and outgoing cable termination with proper taping, lagging, testing and commissioning, complete all as specified and directed.
MCB single pole & Netural 32 Amps 230 Volts'C' series, 10 KA complete all as specified and directed.
MCB single pole & Netural 40 Amps 230 Volts'C' series, 25KA complete all as specified and directed.
MCB's single pole 240 volts 6 to 32Amps 10 KA 'C' series, all as specified and as directed by Engr -in-Charge.
Earthing in replacement complete with galvanized steel earth plate electrode 60cmx 60cmx6mm thick buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to galvanized iron wire 4.0mm dia by means of bolts, nuts and washers of galvanized iron or steel, protected by GI light grade pipe 15mm bore including GI light grade water pipe 20mm dia with funnel all as shown in electric plate No. 03 of 2009 SSR Pt-I and testing on complete including earth work in any type of soil, PCC 1:2:4 type B-0 as in earth pit and cover 40mm thick reinforced with XPM (weight not less than 4.0Kg/Sqm) and frame of angle iron 25x25x3mm with lugs 2 Nos and with 6mm dia MS bar handle made to shape, common salt, charcoal and testing on completion, all as specified and directed.
S&F in replacement of 1100 volts grade heavy duty cable PVC insulated multi stranded aluminium conductor served with PVC tape and over all PVC sheathed in service connections suspended by insulating hangers not more than 1 m apart including 4mm dia GI suspension wire, one twin core Cable flat of circular of size 6 Sqmm 2 Core including taking down existing old service connection, complete all as specified and directed.
S&F in replacement of 1100 volts grade heavy duty cable PVC insulated multi stranded aluminium conductor served with PVC tape and over all PVC sheathed in service connections suspended by insulating hangers not more than 1 m apart including 4mm dia GI suspension wire, one twin core cable flat of circular of size 10 Sqmm 3 core including taking down existing old service connection, complete all as specified and directed.
Wiring for circuit/submain wiring concealed in PVC Conduit 20 mm dia along with earth wire with 2x2.5Sqmm+1x1.5Sqmm as earth wire of FR PVC insulated copper conductor single core cable (ISI marked) including taking down old wiring, complete all as specified and directed.
Wiring for circuit/submain wiring concealed in PVC Conduit 20 mm dia along with earth wire with 2x4Sqmm+1x2.5Sqmm as earth wire of FR PVC insulated copper conductor single core cable (ISI marked) including taking down old wiring, complete all as specified and directed.
Supply and fixing or energy saving eco-friendly IP 65 protection 25 watt LED Bldg light fixed in replacement complete all are specified and directed by Engr-in-Charge.
Supply /cutting and fixing of hylam sheet brown /white colour , heat resistance ,weather resistance, wear resistance , smooth surface grade P-1 ,density 2.2 Kg/Sq Cm, rectangular shape 3 mm thickness with screw , suitable for fixing of switch /sockets /Bell push/fan regulator, all as specified and directed by EIC.
M & L for 10 Watt LED mirror light length 2 ft, Voltage range 100 - 300 v ac , Total light output 900 - 1200 lumens, Color temperature pure white: 5500k – 7000k general specifications1. Operating temperature 0 – 50 deg cDimensions 600 mm x 25 mm fixed in replacement complete all as specified and directed.
S K BANSAL AND CO.
m/s k.k. construction co.
SANGAM ENGINEERS
VISHAV CONSTRUCTIONS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .