| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.2 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹18.4 L+₹1.2 L (6.96%)Rejected-AOC 3788 SHAH GANJ GB ROAD NEW DELHI 110006 | NORTH | DELHI | 110006 | L2 | Rejected-AOC Rejected | |
| 3 | L3₹18.8 L+₹1.6 L (9.25%)Rejected-AOC 1 OPP NAGAR NIGAM KATNI MAIN ROAD KATNI MADHYA PRADESH 483501 | KATNI | MADHYA PRADESH | 483501 | L3 | Rejected-AOC Rejected | |
| 4 | L4₹19.6 L+₹2.3 L (13.6%)Rejected-AOC | L4 | Rejected-AOC Rejected | |
| 5 | L5₹21.6 L+₹4.4 L (25.5%)Rejected-AOC | L5 | Rejected-AOC Rejected |
Tender Value
Refer Docs
EMD Value
₹42,340
Closing Date
12 May 2021, 6:00 pmClosed
CWE (AF) Tughlakabad
CWE (AF) Tughlakabad PIN 110080
SPECIAL REPAIR REPLACEMENT OF UG XLPE CABLE SUITABLE FOR STREET LIGHT AND WORK IN TECH AREA AT AFS TUGHLAKABAD
2021_MES_436328_1
CA No CWE/TKD/Token-02/2021-22
Open Tender
Electrical and Maintenance Works
Works
180 days
GE (AF) Tughlakabad
Please refer tender documents
8 documents required · 8 mandatory
₹500
GE (AF) Tughlakabad
₹42,340
Yes
2 Jun 2021
16 Apr 2021
14 May 2021
16 Apr 2021
12 May 2021
30 Apr 2021
Amount
Excavation in trenches in soft/loose soil , not.exc 1.5 mtr wide and not.exc 1.5 mtr deep and getting out in soft/loose soil for laying of cable/foundation of pole and stay etc. complete all as sepecified and directed.
M&L for sand cushioning in trenches for protection of LT under ground cable including watering and consolidation complete all as sepecified and directed.
Supply and laying well burnt sub class ‘B’ bricks, locally available in trenches for protection of underground cable complete all as sepecified and directed.
Removing excavated materials not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above ground level from starting point complete all as sepecified and directed.
Returning filling including spreading, levelling, watering and well ramming in layers n.exc 25 cm complete all as sepecified and directed.
M&L for cutting of Hardstanding/road by mannual method upto 1000mm deep and width for pipe line complete including filling with ready mix/ PCC and making good distrubed surface complete all as sepecified and directed.
Taking down old unsv UG cable of various size any type from trenches, pole, road , duct etc. including necessary unsv fittings and pipe etc complete all as specified and directed.
Supply and laying in replacement or fixing or passing through pipe cable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area of the following size. Note :-XLPE insulated PVC sheathing (heavy duty) armoured cable with aluminium conductor for working pressure up to and including 1100 volts to IS -7098 (Part-I)
25 Sqmm, 3½ Core .
35 Sqmm, 3½ Core .
50 Sqmm, 3½ Core .
16 Sqmm, 4 Core .
16 Sqmm, 2 Core .
10 Sqmm, 3 Core
120 Sqmm, 3.5 core
95 Sqmm, 3.5 Core
70 Sqmm, 3.5 Core
185 Sqmm, 3.5 Core
150 Sqmm, 3.5 Core
M&L for earthing complete with galvanized mild steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mtr below ground level) with top edge of earth plate not less than 1.5 Mtrs below ground level connected to GI strip 32x6mm as earth lead by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate, with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in cement mortar 1:4, funnel with wire gauge mesh, 80 mm thick RCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I (2009) and specified including provision of GI strip protected by 40 mm dia medium grade pipe and watering pipe shall be 20mm bore light grade, and including all excavation and earth work & connecting the earthing to an earthing test point complete all as specified & directed by Engr-in-Charge.
M&L for earthing complete with galvanized mild steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mtr below ground level) with top edge of earth plate not less than 1.5 Mtrs below ground level connected to galvanised earth lead wire 4.0mm dia by by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate, with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in cement mortar 1:4, funnel with wire gauge mesh, 80 mm thick RCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I (2009) and specified including provision of GI strip protected by 40 mm dia medium grade pipe and watering pipe shall be 20mm bore light grade, and including all excavation and earth work & connecting the earthing to an earthing test point complete all as specified & directed by Engr-in-Charge.
M & L for galvanised pipe of dia 100 mm, 'light grade' with all fitting,laid in trenches for passing of cable etc. complete all as specified and directed by Engr-in-charge.
M/S Anand Enterprises
Neeraj Enterprises
M/S Delhi Engineering Co.
M/S S.K.Electricals
M/S INDIA ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .