Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹89.5 LAccepted-Finance | L1 | Accepted-Finance ok | |
| 2 | L2₹99.2 L+₹9.7 L (10.9%)Accepted-Finance | L2 | Accepted-Finance ok | |
| 3 | L3₹1.1 Cr+₹18.0 L (20.1%)Accepted-Finance | L3 | Accepted-Finance ok | |
| 4 | L4₹1.1 Cr+₹21.2 L (23.7%)Accepted-Finance | L4 | Accepted-Finance ok | |
| 5 | L5₹1.1 Cr+₹25.5 L (28.5%)Accepted-Finance 840 1B MADHUR VIHAR COLONY CIVIL LINES JHANSI UP 284 001 | JHANSI | JHANSI | UTTAR PRADESH | 284001 | L5 | Accepted-Finance ok |
Tender Value
₹1.3 Cr
EMD Value
₹2.6 L
Closing Date
18 Jan 2020, 6:00 pmClosed
CWE JHANSI
HQ CWE JHANSI
REPAIR / MAINT / REPLACEMENT OF EXTERNAL ELECTRIFICATOIN, LIGHTING ARRANGEMENT AND OTHER MISC WORKS AT ARMY AVN UNIT UNDER GE JHANSI
2019_MES_306809_1
CWE/JHA/J/56 OF 2019-20
Open Tender
Civil Works
Item Rate
180 days
JHANSI
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹1,000
GE JHANSI
₹2.6 L
Yes
28 Jan 2020
16 Dec 2019
23 Jan 2020
16 Dec 2019
18 Jan 2020
13 Jan 2020
Amount
M&L in replacement of Power Cables, Aluminum Stranded Conductor, XLPE Insulated, Cores Laid Up, PVC Inner sheathed, Armoured Galvanized Wire or Galvanized Steel Strip, PVC Sheathed, 1100V Grade As Per IS 7098(Part 1) 1988 complete laid in trenches / floors / fixed to poles/walls / drawn through pipes etc including provn of lugs, glands, nuts, bolts & washers etc for connecting as per site requirement and testing on completion for the following cable sizes. Note : (a) Excavation, earth work and provn of cable protection pipe shall be measured and paid separately under relevant items. (b) The contractor will produce Purchase Voucher & Test Certificate of UG Cable duly defaced by JE / Engr-in-Charge alongwith RAR/Bill payment. Make : Finolex / Havells / Polycab / RPG / KEI / Universal / Gloster.
185 sqmm, 3.5 core
95 sqmm, 3.5 core
50 sqmm, 3.5 core
25 sqmm, 4 core
16 sqmm, 2 core
Excavation in trenches not exc 1.5 m wide and not exc 1.5 m depth for laying of cable / pipe and getting out in any type of soil complete all as specified and directed by Engineer-in-Charge.
Returning, filling in, including leveling, watering and well ramming in layers not exc 25 cm complete all as specified and directed by Engineer-in-Charge.
Removing excavated material not exc 50m and depositing where directed at a level not exc 1.5m above the starting point complete all as specified and directed by Engineer-in-Charge.
M&L for cutting of existing road / hard standing up to 15 cm depth for laying of pipe lines and making good the disturbed surfaces by providing PCC 1:2:4 after laying of pipes lines and returning filling of soil, complete all as specified and directed. Note : Excavation and earth work below road / hard standing will be measured and paid under relevant items.
Supply and laying of factory made un-reinforced precast concrete cable protection cover, Class LV, Type-I with size 250mm x 150mm x 40mm, flat type, duly ISI marked with embossing of word 'Electrical', laid across the cable (i.e. width of cover along the lenght of cable) for LT cable protection complete all as specified and directed. Make : Mehtab Tiles or equivalent make approved by GE.
Supply and fix in replacement of 80mm dia bore tubes, 'light grade' galvanized, with all fitting and fixed complete to walls/ poles or laid in trenches/ floors for cable protection complete all as specified and directed by Engineer-in-Charge.
M&L for High density polyethylene pipes (HDPE) 50mm dia of pressure rating 6 kgf/cm2 laid in trenches/floors/duct or fixed on walls /pole for cable protection complete all as specified and directed. Make: Finolex / Kisan / Prince / Tirupati /Supreme / Jain Irrigation Sys.
Supply and fix in replacement of GI pipe light grade 40mm bore for cable protection complete all as specified and directed.
Supply and fix in replacement of MCCB 3 Pole, 415 V fixed thermal and fixed magnetic setting, 125 Amps with breaking capacity 25 KA complete all as specified and directed by Engineer-in-Charge. Make: L&T / Legrand / Schneider / ABB / Havells
Supply and fix in replacement of MCCB 4 Pole, 415 V, adjustable thermal and fixed magnetic setting, 250 Amps with breaking capacity 36 KA complete all as specified and directed by Engineer-in-Charge. Make : L&T / Legrand / Schneider / ABB / Havells.
Supply and fix in replacement of MCCB 4 Pole, 415 V, adjustable thermal and fixed magnetic setting, 400 Amps with breaking capacity 36 KA complete all as specified and directed by Engineer-in-Charge. Make : L&T / Legrand / Schneider / ABB / Havells.
Taking down existing LT panel of any description and Design, fabricate, supply, installation, testing and commissioning of new outdoor type cubicle panel board compartmentalized suitable for 3 phase 4 wire, 50 Hz supply system factory fabricated made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with locking arrangement complete with powder coat painting and suitable packing material for IP-54 degree of protection and including provision of 50mmx50mmx6mm angle iron base frame of suitable size for mounting the panel board at a height of 450mm above GL and grouted in PCC foundation. The size of panel board shall not be less than 1500mm x 1500mm x 500mm (outer dimensions) for accommodating and including provision of following switchgears including internal wiring complete. Note : The panel shall be got fabricated from reputed panel builder who have got their panels type tested from CPRI. The detailed drawing shall be got approved by GE before procurement.
Bus Bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeve insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCBs and outgoing MCCBs up to cable termination etc complete.
Outgoing (a) MCCB, 160 Amps, 36 KA breaking capacity, 3 Pole, 415 V, 50 Hz adjustable thermal and magnetic setting - 04 Nos (b) MCB, TPN 40 Amps, 10 KA breaking capacity, 415 V, 50 Hz - 03 Nos.
Taking down existing LT panel of any description and Design, fabricate, supply, installation, testing and commissioning of new outdoor type cubicle panel board compartmentalized suitable for 3 phase 4 wire, 50 Hz supply system factory fabricated made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with locking arrangement complete with powder coat painting and suitable packing material for IP-54 degree of protection and including provision of 50mmx50mmx6mm angle iron base frame of suitable size for mounting the panel board at a height of 450mm above GL and grouted in PCC foundation. The size of panel board shall not be less than 1200mm x 1200mm x 500mm (outer dimensions) for accommodating and including provision of following switchgears including internal wiring complete. Note : The panel shall be got fabricated from reputed panel builder who have got their panels type tested from CPRI. The detailed drawing shall be got approved by GE before procurement.
Bus Bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeve insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCBs and outgoing MCCBs up to cable termination etc complete.
Outgoing (a) MCCB, 160 Amps, 25 KA breaking capacity , 3 Pole, 415 V, 50 Hz, adjustable thermal and magnetic setting - 02 Nos (b) MCCB, 63 Amps, 16 KA breaking capacity , 3 Pole, 415 V, 50 Hz, fixed thermal and magnetic setting - 01 No (c) MCB, TPN 40 Amps, 10 KA breaking capacity , 415 V, 50 Hz - 03 Nos.
Taking down existing LT panel of any description and Design, fabricate, supply, installation, testing and commissioning of new outdoor type cubicle panel board compartmentalized suitable for 3 phase 4 wire, 50 Hz supply system factory fabricated made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with locking arrangement complete with powder coat painting and suitable packing material for IP-54 degree of protection and including provision of 50mmx50mmx6mm angle iron base frame of suitable size for mounting the panel board at a height of 450mm above GL and grouted in PCC foundation. The size of panel board shall not be less than 1000mm x 1000mm x 400mm (outer dimensions) for accommodating and including provision of following switchgears including internal wiring complete. Note: The panel shall be got fabricated from reputed panel builder who have got their panels type tested from CPRI. The detailed drawing shall be got approved by GE before procurement.
Bus Bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeve insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCBs and outgoing MCCBs up to cable termination etc complete.
Outgoing (a) MCCB, 100 Amps, 25 KA breaking capacity , 3 Pole, 415 V, 50 Hz, fixed thermal and magnetic setting - 01 No (b) MCCB, 63 Amps, 16 KA breaking capacity , 3 Pole, 415 V, 50 Hz, fixed thermal and magnetic setting - 01 No. (c) MCB, TPN 40 Amps, 10 KA breaking capacity , 415 V, 50 Hz - 03 Nos.
Supply and fix in replacement of Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of Pin type, porcelain, vitreous, white, brown or green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 150mm height, 150mm dia for 11000 volts grade complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of Disc type insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type, white, brown or green, single disc assembly for tension with tension clamps for conductors, working pressure 11000 volts complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of Switch Air Break, gang operated, Triple pole, mechanically operated, horizontal or vertical mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating up to 200 amps suitable for 11000 volts grade complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of 11000 volts grade, expulsion type fuse set mounted on insulators and steel frame of current rating up to 50 Amps complete all as specified and directed by Engineer-in-Charge
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95/120 sqmm complete all as specified and directed by Engineer-in-Charge. Make : Denson / Raychem /3M / M-Seal
Excavation in post holes (or similar holes) each not exceeding 0.5 Cum, getting out, returning filling in and ramming earth or broken rubble mixed with earth around, in layers not exc 25cm, watering, and removing surplus soil to a distance not exc 50m and making good surface complete in soft/loose soil.
Dismantling posts or struts (wood or RCC) any section including taking out embedded portion and making good disturbed ground complete all as directed
Dismantling of fencing wire mesh any type complete all as specified and directed
M&L for mild steel work as in replacement of posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire etc flat iron fillets(for securing wire mesh etc) including all necessary drilling, bolting or riveting etc and similar work confirming to Fe-290 Gde E-165 complete all as specified and directed.
M&L for preparation of new steel surfaces of any description not exc 10 cm in width or girth and painting with two coats of synthetic enamel paint of approved colour over a coat of red oxide primer complete all as specified and directed.
Supply and fix in replacement of coloured PVC covered galvanized chain link fencing of size 50mm x 50mm mesh, dia of wire 2.5mm with 1.5mm PVC cover (overall dia 4mm) fixed to any type of posts or struts (RCC or MS) complete all as specified and directed.
M&L for Framed work such as grills, gratings etc with ends of bars shouldered and/or riveted, or forged into spikes; framed and hung as gates, including lintel hinges, stops, hand-made sliding bolts, etc. conforming to Fe.290.Gde-E-165 including taking down existing framed work of any description complete all as specified and directed by Engineer-in-Charge.
M&L for MS screw bolts (machine made) with hexagonal or square heads at one end and screwed the other or screwed both ends each screwed end to be fitted with washers and one hexagonal or square nut exceeding 5.00 cm but not exceeding 10.00 cm long and dia of neck 10.00 mm - 15.00 mm complete all as specified and directed.
Surface excavation not exceeding 30 cm deep and averaging 15cm deep and getting out in hard/dense soil in the transformer yard complete all as specified and directed by Engineer-in-Charge.
Supply and spread graded coarse aggregate of 40 mm nominal size around outdoor transformer and HT 11 KV two/four pole structure complete all as specified and directed.
M&L for mild steel deformed TMT bars 6 mm To 8 mm dia, cut to length, bent to shape require for securing chain link fencing complete all as specified and directed.
Supply and spread M-sand in trenches for cushioning of cable / in the yard of outdoor substations complete all as specified and directed by Engineer-in-Charge. Note : Punned down thickness only shall be measured for the purpose of payment.
M&L for brick work with fly ash lime bricks (FALB) conforming to IS 12894, old size brick, straight or curved on plan exceeding 6m mean radius built in cm (1:6) complete all as specified and directed
M&L for rendering 10mm thick cement plaster 1:6 on fair faces of brick work or concrete surfaces finished even and smooth (with out using extra cement) complete all as directed.
M&L for preparation of new plastered surface and applying three coats of white wash on new plastered surface of wall complete all as specified and as directed.
Unbinding the existing HT/LT overhead lines of any configuration and size of conductor by opening the binding wire from insulators and Re-stringing to required tension and sag and binding with new aluminium binding wire of suitable gauge complete all as directed by Engineer-in-Charge.
Material and labour for Shackle Type, Porcelain, vitreous, white, brown or green insulator including galvanized mild steel straps, washers, insulator bolts, washers and nuts for working pressure 1100 volts of size 75mm height and 90mm dia complete all as specified and directed by Engineer-in-Charge.
Material and labour for Pin type, porcelain, vitreous, white, brown or green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 100mm height, 65mm dia for 1100 volts grade complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of ACSR conductor for HT/LT overhead line and proper stringing to required tension and sag including binding with new aluminium binding wire of suitable size complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of Stay assembly with 16mm dia stay rod and all accessories as shown in electrical plate No. 1 complete all as specified and directed by Engineer-in-Charge. Note: Loop type insulator, stay clamps, stay wire, excavation and concrete measured separately)
Supply and fix in replacement of Galvanized stay strand, 7/3.15mm including proper tightening to required tension complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of Loop type insulator, vitreous porcelain, white, brown or green Small size, with overall dimensions 65 x 90mm, clearance of hole 16mm complete all as specified and directed by Engineer-in-Charge.
Supply and erection of Hot dip galvanized tapered octagonal pole of height 7.0 mtr in single or double section having top dia 70mm and bottom dia 130mm made up of 3mm thick sheet and welded with a base plate of size 200mm x 200mm x 12mm thick and provided with 1000mm long single arm bracket with 15 degree of angle for mounting street light fitting complete with provision of 04 Nos of ‘J’ type foundation bolts of size not less than 20mm dia, 600mm long embedded in PCC foundation concrete as per manufacturer’s recommendation including necessary foundation work PCC/RCC, reinforcement bar etc (as per manufacturer design), with and including taking down of existing unserviceable pole of any description complete. A door should be provided at a height of 500mm from the base plate for accommodating and including provision of TPN aluminium bus bar system suitable for connecting upto 4 core, 25 sqmm aluminium cable and 01 No. of 6A SP MCB for street light protection inside the pole shaft. Radium reflector band / strips of 5cm wide in Green (02 Nos) & White (01 No.) colour shall be provided at a height of 1.25mtr from base plate. Numbering of pole shall be done in black colour on yellow background at suitable place on the pole complete as directed by Engr-in-Charge. Make : Bajaj / Philips / CG / Utkarsh. Note : 1. The cost of foundation bolts along with nuts, washers, anchor plate, template and complete foundation incl PCC/RCC, reinforcement bar etc (as per manufacturer design) is deemed to be included in the quoted rates and no extra payment will be made to contractor against it. 2. The earth work / excavation shall be measured and paid separately under respective items. 3. The drawing of pole and its foundation shall be approved by GE before placement of order. 4. The contractor will produce Purchase Voucher & Test Certificate of Pole duly defaced by JE/Engr-in-Charge alongwith RAR/Bill payment.
Supply, installation and testing, in replacement, of outdoor type, factory made cubicle panel board bus bar box with MCCB suitable for 3 phase 4 wire, 50 Hz supply system factory fabricated made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front openable door with locking arrangement complete with powder coat painting and suitable packing material for IP-54 degree of protection and including provision of 40mmx40mmx5mm angle iron base frame of suitable size for mounting the panel board at a height of 450mm above GL and grouted in PCC foundation. The size of panel board shall not be less than 500mm x 500mm x 300mm (outer dimensions) for accommodating and including provision of following switchgears complete:- (i) TPN Aluminium bus bar of 25 x 5 mm provided with heat shrinkable coloured PVC sleeve insulation mounted on insulators suitable for connecting 2 or 3 outgoing cables including provision suitable glands. (ii) MCCB, 160 Amps, 36 KA breaking capacity , 4 Pole, 415 V, 50 Hz, adjustable thermal and magnetic setting including spreader terminals - 01 No
M&L for earthing complete with galvanized iron earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level connecting to GI strip 25x4 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel and earth wire protected by 40mm dia GI pipe medium grade and connected to distribution board/earthing test point all as shown in electrical plate No. 3 of SSR Part-I(2009) and testing on completion complete all as specified and directed. Note : The unit rate quoted shall also include for excavation, earth work in any type of soil, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bras @ 150mm C/C both ways, GI funnel with watering pipe, wire mesh, protection pipe, earth strip up to 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II.
Supply, Installation, Testing & Commissioning, in replacement of, new Elevated Runway Edge Light, comprise of corrosion resistance die-cast aluminium alloy powder coated body with clear heat resistance hard glass cover and silicon rubber gasket complete with 200 Watt, 6.6 Amp Halogen Lamp, Secondary lead and Base Plate with 06 Nos M-10 stainless steel bolts and other fixing accessories, breakable coupling, suitable for 5-step constant current operation, Average light intensity > 10000 cd, conforming to FAA AC 150/5345-46E, full compliance with ICAO Annx 14 standards in Category I, II and III, full compliance with IS 7785 part – I to V, duly installation on CI Transformer Housing Box with and incl stainless steel hardware / fasteners / fixing arrangements including taking down existing unserviceable runway edge light, complete all as specified and directed. Make : AMA Airfield Lighting Systems / Vardhman Airport Solutions / Reliance Airfield lighting system (ADB Safegate). Note : 1. The contractor will produce Purchase Voucher & Test Certificate of Runway Edge Light, duly defaced by JE/Engineer-in-Charge, alongwith RAR/Bill payment. 2. The CI Transformer and housing box, as required will be measured and paid separately under respective items only. 3. The spare bulbs (halogen lamp) equal to 10% of total installed runway lights will be deposited to JE/Engineer-in-Charge. The cost of spare halogen lamps is deemed to be included in quoted rates only and no extra payment will be made to contractor against it. 4. The contractor has to replace the unserviceable lamps with these spare bulbs, as and when required, during Defect Liability Period. The cost of same is deemed to be included in quoted rates only and no extra payment will be made to contractor against it.
Supply, Installation, Testing and Commissioning in replacement of new LED Elevated Taxiway Edge Light comprise of corrosion resistance die-cast aluminium alloy powder coated body with heat resistance hard glass dome complete with 01 Watt LED, blue lens, breakable coupling, two pin secondary leads, Base Plate with 06 Nos M-10 stainless steel bolts and other fixing accessories suitable for 5-step constant current operation, Average light intensity > 2 cd (from 0o to 10o above the horizontal), conforming to FAA AC 150/5345-46 : L-861T, full compliance with ICAO Annex 14 Vol I, 5.3.17; 5.318 (for photometry) full compliance with IS 7785 part – I to V, duly installation on CI Transformer Housing Box with and incl stainless steel hardware / fasteners including taking down existing unserviceable taxiway edge light, complete all as specified and directed. Make : AMA Airfield Lighting Systems / Vardhman Airport Solutions / Reliance Airfield lighting system (ADB Safegate) Note : 1. The contractor will produce Purchase Voucher & Test Certificate of Taxiway Edge Light, duly defaced by JE/Engineer-in-Charge, alongwith RAR/Bill payment. 2. The CI Transformer and housing box as required will be measured and paid separately under respective items only.
Supply, Installation, Testing & Commissioning, in replacement of, new Elevated Approach / Threshold / End Light, comprise of corrosion resistance die-cast aluminium alloy powder coated body with clear heat resistance hard glass cover and silicon rubber gasket, complete with 200 Watt, 6.6 Amp Halogen Lamp, Secondary lead and Base Plate with 06 Nos M-10 stainless steel bolts and other fixing accessories, suitable for 5-step constant current operation, conforming to FAA AC 150/5345-46E, full compliance with ICAO standards in Category I, II and III, duly installation on CI Transformer Housing Box with and incl stainless steel hardware / fasteners and ground calibration with and including taking down existing unserviceable lights, complete all as specified and directed. Make : AMA Airfield Lighting Systems / Vardhman Airport Solutions / Reliance Airfield lighting system (ADB Safegate). Note : 1. The contractor will produce Purchase Voucher & Test Certificate of Approach / Threshold / End Light, duly defaced by JE/Engineer-in-Charge, alongwith RAR/Bill payment. 2. The CI Transformer and housing box, as required will be measured and paid separately under respective items only. 3. The spare bulbs (halogen lamp) equal to 10% of total installed lights will be deposited to JE/Engineer-in-Charge. The cost of spare halogen lamps is deemed to be included in quoted rates only and no extra payment will be made to contractor against it. 4. The contractor has to replace the unserviceable lamps with these spare bulbs, as and when required, during Defect Liability Period. The cost of same is deemed to be included in quoted rates only and no extra payment will be made to contractor against it.
Supply, Installation, Testing & Commissioning of new Landing 'T' indicator including taking down existing unserviceable landing 'T' indicator complete all as specified and directed. Make: AMA Airfield Lighting Systems / Vardhman Airport Solutions / Reliance Airfield lighting system (ADB Safegate)
Supply, Installation, Testing & Commissioning of Rotating Beacon including taking down existing unserviceable rotating beacon complete all as specified and directed. Make: AMA Airfield Lighting Systems / Vardhman Airport Solutions / Reliance Airfield lighting system (ADB Safegate)
Supply, Installation, Testing & Commissioning in replacement of new CI Transformer Housing Box, water tight round type, metal container of outside dia 330mm, height 450mm made of 10mm thick cast iron moulding all round, except the top surface which should be 15 mm thick suitable to receive a ground light fitting base plate on the top and underground housing suitable for keeping the isolating transformer along with connectors & leads, having two nos holes opposite as per site requirement on the periphery wall, 75 mm above bottom surface suitable to receive 50 mm (OD) DWC HDPE pipe as required; nominal min weight for CI box (without cover) with one hole shall be 41.7 Kg, with two holes 41.5 Kg and with three holes 41.3 Kg. The box should have two SS earth bolts of M10 x 40 mm tapped inside near the hole (approx 4" away from the hole centre); housing box should have a drain hole at the bottom suitably tapped to receive 15mm dia GI pipe 250mm long; the housing should have clear opening of 220 mm at the top surface and 6 Nos M-10 tapped hole; holes should be properly machined & tapped to avoid any burr/sharp edges; transformer Housing Box when installed with cover has to be water tight accordingly necessary rubber gasket & bolts has to be provided for each cover plate; complete Transformer Housing Box to be installed on 100 mm thick PCC base (of 1:3:6 type C2 using 40mm graded stone aggregate); over 100 mm thick PCC sub base (of 1:4:8 type D2 using 40mm graded stone aggregate); 150mm thick PCC cover all around Transformer Housing Box (of 1:2:4 type B1 using 20mm graded stone aggregate) with and including taking down existing unserviceable Transformer Housing Box, complete all as specified and directed. Make : AMA Airfield Lighting Systems / Vardhman Airport Solutions / Reliance Airfield lighting system (ADB Safegate) Note : 1. The drawing of the Transformer Housing Boxes alongwith foundation detail shall be got approved from the GE before procurement. 2. The housing box must be properly aligned with theodolite, before the concrete pedestal is casted. All the associated pipes for the series cable and the secondary leads shall also be provided and properly fixed with the housing box before fixing of housing box in PCC. 3. The cost of fixtures, SS bolts, rubber gaskets, GI drain pipe etc is deemed to be included in quoted rates. 4. The earth work as required, PCC will be measured and paid separately under respectively items only.
Supply and lay new Airfield Lighting Primary Cable 5KV Grade copper conductor 1C x 6 sqmm, PVC insulated, PVC sheathed primary cable along with new GI wire 8 SWG laid in existing / new pipe including taking down existing unserviceable airfield lighting cable complete all as specified and directed. Make : Polycab / Rallison / KEI / Gloster / Havells. Note: New pipe for cable protection, if required, shall be measured and paid separately under relevant items.
Supply and connect new Isolating Transformer 5KV Grade of rating 200 W, 6.6 / 6.6 Amps with primary and secondary lead including taking down existing unserviceable isolating transformer complete all as specified and directed. Make: AMA Airfield Lighting Systems / ATG Airports Ltd / Reliance Airfield lighting system (ADB Safegate) / Bildal / Electromach / Philips.
Supply and connect new Isolating Transformer 5KV Grade of rating 15 W, 6.6 / 6.6 Amps with primary and secondary lead including taking down existing unserviceable isolating transformer complete all as specified and directed. Make: AMA Airfield Lighting Systems / ATG Airports Ltd / Reliance Airfield lighting system (ADB Safegate) / Bildal / Electromach / Philips.
Taking down existing unserviceable cable connector kit of any description and Supply and connect new Primary Cable Connector Kit suitable for 5KV Grade copper conductor 1C x 6 sqmm cable including field connection with primary cable complete all as specified and directed. Make: AMA Airfield Lighting Systems / ATG Airports Ltd / Reliance Airfield lighting system (ADB Safegate) / Bildal / Vassanth.
Supply, Installation, Testing & Commissioning in replacement of new indoor type air cooled constant current regulator (CCR) 4 KW of micro processor controlled, thyristor type suitable for operation on 230/415 volts, 50Hz existing input AC supply with 6.6A output having 5 steps variation of current output and able to communicate with PC or PLC controlled system, with digital output ammeter (0-10A), over current, overvoltage, open circuit and earth fault protection and earth leakage meter, two stage earth leakage detector, positive back indication equipments and monitoring system module, hours run counter, Number/Percentage lamp failure indicator of the circuit load, LCD display, confirming to relevant FAA (Latest Edition) / ICAO specification, with and including taking down existing unserviceable CCR, complete all as specified and directed. Make : AMA Airfield Lighting Systems / ATG Airports Ltd / Reliance Airfield lighting system (ADB Safegate).
All as per srl item No 59 here-in-above, but 7.5 KW capacity
All as per srl item No 59 here-in-above, but 15.0 KW capacity
Supply, Installation, Testing and Commissioning of new Remote Control Desk suitable for airfield lighting system including taking down existing unserviceable Remote control desk complete all as specified and directed. Make: AMA Airfield Lighting Systems / Vardhman Airport Solutions / Reliance Airfield lighting system (ADB Safegate)
Supply, lay, connect and testing of 30C x 1.5 sqmm, 1.1 KV grade copper conductor control cable for AFLS laid in existing / new pipe including taking down existing unserviceable AFLS cable complete all as specified and directed. Note: New pipe for cable protection, if required, shall be measured and paid separately under relevant items. Make : Polycab / Rallison / KEI / Gloster / Havells or equivalent make approved by GE (as per recommendation of OEM).
Supply, lay, connect and testing of 3C x 4 sqmm, 1.1 KV grade copper conductor power cable for Helipad laid in existing / new pipe including takingdown existing unserviceable helipad cable complete all as specified and directed. Note: New pipe for cable protection, if required, shall be measured and paid separately under relevant items. Make : Polycab / Rallison / KEI / Gloster / Havells or equivalent make approved by GE (as per recommendation of OEM).
Supply, Installation, Testing and Commissioning of LED based traffic signal light 300mm dia, Red + Green (Two in One) suitable for working on 230V, 50 Hz AC supply with ultra bright LEDs, UV stabilized, Waterclear lens housed in polycarbonate body suitable for extreme weather conditions, front hood made of HDPE complete fixed on signal post with MS clamp including taking down existing unserviceable signal light complete all as specified and directed. Make: Trafitronics / Microtrans / Pyrotech
Earthing complete with galvanized steel pipe electrode, 40mm bore, medium grade, 2.5 meters length, buried directly and preferably vertically in ground with top edge not less than 1.25 meters below ground level connected with earthing lead of 4mm dia galvanized iron or steel wire all as shown in Plate No. 2 of SSR Part-I (2009) and connected to the earthing test point all as specified and indicated including testing on completion.
Supply and connect in replacement of PVC insulated and PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volts grade, conforming to IS 694, three core, 1.5 sqmm for connecting from junction box to street light fitting complete all as specified and directed by Engineer-in-Charge. Make: Finolex / Havells / Polycab / RPG / KEI.
Supply and fix SMC(Sheet Moulded Compound) outdoor type junction box of size 200mm x 140mm x 95mm (Outside Dimensions) with 63Amps rated four pole connector, one single pole MCB of 6 Amps rating mounted on DIN rail, stainless steel cable glands of suitable size for incoming and outgoing cables and PVC gland for street light control cable including fixing on steel tubular poles / PCC poles with 25mm x 3mm MS clamps (02 Nos), nuts & bolts etc including taking down existing u/s junction box of any type and size complete all as specified and as directed. Make: Sintex/ Hensel
Supply and fixing in replacement of 120 Watt LED street light fitting made up of Pressure die-cast aluminium alloy housing with toughened glass, IP66 protection and impact resistance of IK07 and individual high power LEDs with secondary optics having Lumen efficacy of LED ≥140 lm/W, Inbuilt potted electronic LED driver with APFC (SMPS based constant current supply), lower THD, Open Circuit protection, Over Voltage protection, Surge Voltage protection & other safety test as per IS 15885 Part-2/Sec 13 and BIS complying complete suitable for mounting on GI pipe bracket and all as specified and directed. Make : Bajaj / Philips / Wipro / Havells
Supply and fixing in replacement of 90 Watt LED street light fitting made up of Pressure die-cast aluminium alloy housing with toughened glass, IP66 protection and impact resistance of IK07 and individual high power LEDs with secondary optics having Lumen efficacy of LED ≥140 lm/W, Inbuilt potted electronic LED driver with APFC (SMPS based constant current supply), lower THD, Open Circuit protection, Over Voltage protection, Surge Voltage protection & other safety test as per IS 15885 Part-2/Sec 13 and BIS complying complete suitable for mounting on GI pipe bracket and all as specified and directed. Make : Bajaj / Philips / Wipro / Havells
M&L for PCC 1:4:8 type D2 using 40mm graded stone aggregate as in sub base, foundations fillings & mass concrete and similar works complete all as specified and directed.
M&L for PCC 1:3:6 type C2 using 40mm graded stone aggregate as in sub base, foundations fillings & mass concrete and similar works with and incl necessary form work as required complete all as specified and directed.
M&L for PCC 1:2:4 type B1 using 20mm graded stone aggregate as in coping & edge stop and similar works with and incl necessary form work as required complete all as specified and directed.
Supply and making cable route marker, made of plain cement concrete 1:2:4 type B1 (using 20mm graded stone aggregate) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm, with and including three coat of white wash on exposed surface and writing AFLS CABLE with black synthetic enameled paint complete all as specified and directed.
JAZZCON ENGINEERS PVT LTD
B R Engineers
PARAS BROTHERS
M/S Kumar Contractors
DURGAI ELECTRICALS
trading engineers
M/s Pragmatic Infrastructure Limited
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .