Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.7 LAccepted-AOC | L1 | Accepted-AOC BEING LOWEST | |
| 2 | L2₹21.9 L+₹22,543 (1.04%)Rejected-Finance | L2 | Rejected-Finance NOT LOWEST | |
| 3 | L3₹23.2 L+₹1.5 L (6.74%)Rejected-Finance 340 11 M S NATIONAL ENGINEERING CORP 340 11 SATTI STREET ROORKEE ROORKEE HARIDWAR UTTARAKHAND 247667 | HARIDWAR | UTTARAKHAND | 247667 | L3 | Rejected-Finance NOT LOWEST | |
| 4 | L4₹23.3 L+₹1.7 L (7.61%)Rejected-Finance 154 HANUMAN MANDIR DIKSHI TAL NIPHAD DIST NASHIK 422 302 | NASHIK | MAHARASHTRA | 422302 | L4 | Rejected-Finance NOT LOWEST | |
| 5 | L5₹24.0 L+₹2.3 L (10.6%)Rejected-Finance | L5 | Rejected-Finance NOT LOWEST |
Tender Value
₹21.8 L
EMD Value
₹44,000
Closing Date
25 Mar 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE DEOLALI
HQ CWE DEOLALI, ONSLOW ROAD, DEOLALI (MH)
AS PER TENDER DOCUMENTS
2023_MES_583137_1
86908/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
DEOLALI
AS PER NIT
7 documents required · 7 mandatory
₹500
Yes
GE DEOLALI
₹44,000
Yes
30 Mar 2023
27 Feb 2023
27 Mar 2023
27 Feb 2023
25 Mar 2023
13 Mar 2023
28 Feb 2023 - 6 Mar 2023
Amount
Supply, erecting, testing and commissioning complete of manufacturer or OEM manufactured static, silent (Sound Proof enclosure) Diesel Engine Driven Generating Set capable of delivering 250 KVA at power factor 0.8. water coolled, 415 Volts (AC three phase, 4 wire system of supply) 50 Hz. The DG Set shall consists of diesel engine coupled to a matching alternator, through flexible coupling and mounted on common base frame and complete with control panel standardized by manufacturer, fuel tank with mounting arrangements and inlet, outlet, return inlet oil arrangement exhaust pipe complete and suitable for conditions prevalent at devlali (Capacity of Engine, alternators shall be worked out taking all derating factors into consideration) including PCC foundation (of suitable size leaving at least 0.5 M all around for ease up movment and 0.5M height above NGL) anti-vibration pads, including all features to comply with latest CPCB guidelines .and comprising of followings:-
(i) Engine (Prime Mover):- Diesel Engine 1500 RPM, Direct injection multi Cylinders, four stroke, confirming to ISO 3046/BS 5514, water cooled, naturally turbo charged, capable of giving adequate BHP to drive Alternator capable of delivering 250 KVA at outdoor atmospheric conditions at Devlali, (Taking all derating factor into consideration), 12/24 Volt (as per manufacturer recommendations) electrical battery start, complete with fly wheel with all standerd fittings/fixtures as per manufacturer and including suitable panel for tachometer, lub oil temperature, pressure gauge and frequency meters and also including self starter system, dynamo, fuel electric control panel with electronic governor (ECPG) and Engine protection system (Shut down, indication for High water temperature, low lub oil, oil pressure, over speed etc.), multi functional meter for RPM, PF,hrs runs,frequency, oil pressure,temp,amps and voltage indications, fuel tank and first fill of lub oil, coolant and other consumables etc. (ii) Alternator:- Brushless AC alternator, 3 Phase, 415 Volt, 4 wire, rated for output of 250 KVA, at power factor 0.8, 1500 RPM, IP 23 class enclosure, insulation Class "H", salient pole, revolving field, single bearing automatic voltage regulator coupled through flexible coupling with and to match the above engine. (iii) BASE PLATE :- made out of structural steel as per manufacturers recommended design/specifications. .
(iv) ACOUSTIC ENCLOSURE: Sheet metal fabricated cope type silent enclosure manufactured on CNC machines as per CPCB norms and powder coated after seven tank process, the enclosure shall be designed for reducing the sound level to 75 DB (A) at a distance of 1 M at 75 % load under field condition and & 70DB at 3 M from Gen set when DG set is working at full load along with testing conformance, labeling certification etc as laid down in GSR No.371(E) dt 17 May 2002. (v) Foundation/Plinth/Base : shall be provided as per manufacturers recommendation, however minimum 0.5 m space should be available all around the set and height of plinth shall not be less than 0.5 M (vi) Diesel storage tank of capacity adequate for storage of diesel for 12 hours operation of Gen set. (vii) MISC : Tool kit, Operation and maintenance catalogue, spare part list overhauling manuals guarantee card etc shall be provided as per manufacturer standard pratices.NOTES:-(i) The capacity of Generator set shall be net after all due derating factors as per relevant ISI design. (ii) Rate quoted shall be deemed to be inclusive of cable and terminations form Generator all as specified and directed. (iii) The quoted rate shall be deemed to be inclusive of first fill of oil, coolant and final successful acceptance test. (iv) The quoted rate shall be deemed to be inclusive of 12 hours test run at site including of half an hour on 10% overhead in presence of representative detailed by accepting Officer, all arrangements including consumables like diesel, oil, coolant, load for testing etc are to be made by the contractor for the tests.
.Notes (Contd/..) : Engine shaft suitable for generating application and capable of giving output of 250 KVA for coupled alternator under NTP conditions, complete with following : (i) Suitable fuel pump and fuel piping of size as recommended by manufacturer (ii) Fuel filter with water separator and filter element. (iii) Lub - Oil filter with filter element. (iv) D.C. starter 12 Volts. (v) Maint free storeage type Battery of suitable Voltage and Ampere hours as recommanded by the manufactures. (vi) Industrial type silencer including MS exhaust pipe lagged with asbestos rope of 5 mm dia all around and over this 50 mm thick flat mineral wool insulated sheet cover and then, 24 SWG Aluminium sheet cladding with rivets all over the length. (vii) Support/ fixing arrangement for muffler with cilling through anti vibration pads. (viii) Engine overspeed stop/ trip switch. (ix) Radiator with fan. (x) Dynamo for battrey charging. (xi) Correosion inhibitor coolant. (xii) Engine control panel electronic, digital display type consisting of bty Voltage indicator, lub oil temp and pressure guages, coolant water temp guage, RPM indicator-cum-hour meter etc. (xiii) Safety controls for alarm due to high water temp (HWT) and low lub oil pressure (LLOP) (xiv) Any other devices/ accessories recommended/ supplied by the manufactures as standard eqpt.
(xv) Skid : The engine and alternator shall be coupled, aligend and mounted on a specially designed common base frame fabricated from MS channels of suitable corss sectional area and length with bottom drilled holes suitable for and including supplying and fixing anti vibration pads. Make : Anti vibration pads :- Dunlop/ Polybond of required size and numbers as recommended by the manufactures for mounting of 200 KVA DG set.(xvi) Diesel tank of adequate capacity for 12 hrs continous run on full load with calibrated scale f(fuel level indicatorf) dip stick, fuel inlet/ outlet, Air vent, drain plug and inlet arrangement for direct filling, including suitable size gun metal gate valve in outlet, tank shall be fitted all as per manufacture's requirements/ specification. (xvii) Acoustic enclosure with canopy cover shall be provided as per latest CPCB norms. (xviii) Industrial type silencer including MS exhaust pipe lagged with asbestos rope of 5 mm dia all around and over this 50 mm thick flat mineral wool insulator sheet cover and then, 24 SWG Aluminimum sheet cladding with revets. all over the length. (xix) Support/ fixing arrangement for muffler with ceillign through antt vibration (xx) Documents : Three sets of fwg docus :- Maint and Ops manuals for enigne and alternator, spare parts catalogue, warranty/ test certificates, schematic diagrams of control panels. (xxi) Connecting cable in new panel with required accessories etc complete. (xxii) Optional items : list of tools and as per manufactures recommended lists, duly proced, item wise. (xxiii) Contractors shall satisfactorily conduct load test of each DG set for 12 hrs including run on 10% overload for 1 hrs. (xxiv) Testing eqpt will be arranged by the Contractor under his own arrangement and cost.
NOTE :(A) DG set shall comply with emission parameters as per CPCB-II. Minium specified Particulate Matter (PM)capturing efficiency of 70%, type approved by bone of the five Central Pollution Control Board (CPCB) recognzed labs. (B) The emission limits for DG set as per CPCB-II norms for DG set of Power Category more than 75 kW upto 800 kW shall be as under:- (i) Emission Limits (g/kW-hr) NOx+ HC (Oxides of Nitrogen and Hydrocarbon) : < 4.0 CO (Carbon Monoxide) : < 3.5 PM 2.5 (Particulate Matter) : < 0.2 (ii) Smoke Limit (Light Absorption Coefficient, m1 : < 0.7 (c) Smoke shall not exceed above value throught the operating load points of the test cycle.
M&L for earthing complete with galvanized steel earth plate electrode size 600 x 600 x 6.0mm thick buried directly in ground vertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and including galvanized iron strip 32 X 6 mm earth lead by means of bolts, nuts, check nuts and washers of galvanized steel including GI pipe light grade of size of 40 mm dia for protection and GI pipe light grade 20mm dia bore for watering funnel with wire mesh. CI cover with frame, PCC chamber pit with PCC 1:3:6 type C-2 excavation and earth work of any type strata all as shown in electrical plate No 5 connected to earthing test point all as specified or indicated including testing on completion. Note : The unit rate includes for protection pipe and GI earth strip of size 32 6 mm from top of earth plate up to 7.5 meter above ground level.
Supply, Laying , jointing and testing of LT underground cable, heavy duty, 1100 Volts, XLPE insulated and sheathed, armoured with multi-stranded aluminium conductor cable , laid in trenches/ducts or fixed to poles/walls or laid under roads/paths/drains/culverts duly encased in galvanised steel pipe of suitable sizes including cable gland of suitable sizes and aluminium lugs for connection complete all as specified and directed of size 150 Sqmm 3.5 core.
Excavation in trenches n. exc. 1.5 mtr in wide and n. exc. 1.5 mtr in depth for laying of underground cable and getting out in soft/loose soil complete all as specified and directed.
Supply & lay in trenches double walled corugated HDPE pipe 75 mm dia high density for protection of under ground cables( Note: pipe couplers with seal, bends, end covers etc are deemed to be included in rate quoted)
Returning, filling in excavated soil in trenches including spreading, leveling, watering and well ramming in layers n. exc. 25 cm thick complete all as specified and directed
Removing of excavted soil to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed.
Supply & fix On load chenge over swith 400 Amps rating in sheet metal enclosure out door type double door enclosure mounted on angle iron stand of size 50x50x5m.The enclosure manufactured fromm 3.15 CRCA sheet duly poweder coated and factory made with arrangement for two incoming and one out going cable & 600 Amps bus-bar 03 Nos for R-Y-B (PHASE) and 400 Amps one No for Neutral with locking arrangement.
DHARMESH ENTERPRISES
NATIONAL ENGINEERING CORPORATION
MAHIMA CONSTRUCTION
vedant engineering enterprises
Rama Electricals
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .