EEE-III/RZ/NZ
EEE-III/RZ/NZ
Provision of Semi High Mast Lights with Pole and provision of lighting arrangement at dark spots Sultanpuri, Ward No.45 under EEE/RZ. Sub-Head- P/o Semi High Mast Lights with Pole in Mpl Park near H.No. C-3/442-444 and lighting arrangement near H.
2021_NDMC_97007_1
EEE-III/RZ/NZ/TC/2021-22/14.7
Open Tender
Electrical Works
Item Rate
120 days
EEE-III/RZ/NZ
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
₹11,600
Yes
10 Dec 2021
3 Dec 2021
10 Dec 2021
3 Dec 2021
9 Dec 2021
3 Dec 2021
Amount
Earthing with GI earth pipe 4.5Mx40mm dia i/c accessories and providing masnary enclosure with cover plate having locking arrangement and watering pipe etc(but without charcoal or coke and salt complete) as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Upto 35 sq. mm
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal)
Supplying and erection of galvanized D-iron complete with shackle insulator (75 x 90 mm ) GI bolt and nut coach screws etc as required.
Wiring for sub-main with 2 x 25 Sq. mm single core two wires over head PVC insulated Al. conductor wire with 10 SWG dia G.I. bearer wire by providing cleats at a distance of one meter on existing pole etc. as reqd.
Supply of XLPE insulated PVC sheathed Al. Cond. Armoured cable of 1.1kV grade conforming to IS-7098 Part-I of following size. 2x16 sqmm
SITC of 150W LED Flood Light luminiare fitted with lense, made of pressure die cast aluminium housing & toughned glass cover complete with the following specification as reqd. (a) Total system wattage =150 watt +/- 5% b) Luminaire Efficacy>=100 Lm/w c) Power Factor>=0.95 d) Protection Class- IP-66
S/F 40mm dia GI pipe medium class along with the pole/wall for cable protection i/c painting etc as required.
Fabrication, Supplying, Installation, testing, Commissioning of 12 mts. high mast System with its accessories, Mast shaft shall be in one section, hot dip galvanized 4mm thick (single dip) inside & out sides & suitable for wind velocity as per IS 875 part3. There shall be in longitudinal seam weld per section and No circumferential weld. It should also included accessories For High Mast head frame, 2 point suspension system with steel wire rope 5mm dia (7/19construction) single drum winch, galvanized lantern carriage arrangement suitable for 4/6 Nos Flood Light luminaries symmetrically And its control gears boxes and lighting finial, the mast shall have integral type manual tool mounted at the base compartment of its raising and lowering operation with foundation bolts and Anchor plate and control panel housing suitable RCC (1:2:4) shallow foundation of size 1m(L) x 1m wide and 2m deep i/c excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 12 mm dia -2100mm long (approx.) - 16 nos.and reinforcement of cold twisted bar of 8 mm dia - 3700 mm (approx.) - 13 nos. (with 150 mm spacing) as required with positioning of foundation bolts and providing DWC HDPE pipe for cable entry & exit as required for the high mast considering The safe soil bearing capacity at site as 10T/sqm at 2mts. Depth with all material i/c 4 Nos SP MCB, 63Amp DP Isolator etc as reqd. Logo/Name of manufacturer shall be embossed on the pole. Galvanization as per relevant IS.
Supply and fabrication of pole protection system made up of 8SWG steel wire mesh of size25mmx75mm rectangular with 50mmx50mmx6mm MS angle iron for supporting the mesh and grounding the protection system in suitable quality of CC etc as reqd.
SITC of 60W LED Street Light luminiare fitted with lens, made of pressure die cast aluminium housing & toughened glass cover complete with the following specification as reqd. (a) Total system wattage =60 watt +/- 5% (b) Luminaire Efficacy>=100 Lm/w (c) Power Factor>=0.95 (d) Protection Class- IP-66
Fabrication, supplying and fixing class B galvanised double overhang arm bracket made out of 250mm long galvanised top tube with cap and 1000mm long 32 mm dia galvanised pipes with tightening bolts complete as required.
Fabrication, supplying and fixing class B galvanised single overhang arm bracket made out of 250mm long galvanised top tube with cap and 1000mm long 32 mm dia galvanised pipe with tightening bolts complete as required.
Fabrication, supply & erection of following size flange mounted hot dip galvanized octagonal pole made from HT steel plate, window with flash cover with full vertical window cover at appropriate height from the base plate on existing cement concrete pedestal as required. i/c supplying and fixing of 6 mm thick laminated mounted sheet inside the window mounted on and i/c providing and welding 3 nos. GI strips 4 mm thick of suitable length and having suitable size tapped holes as reqd, terminal block suitable for 25 sq mm conductor – 4 nos. & shorting links on DIN channel i/cpdg and fixing DIN channel of suitable length,, 6 Amp. SPMCB ‘C’ characteristics, earth stud, cable support clamp suitable for upto 4x25 sqmm cable. Logo/Name of manufacturer shall be embossed on the pole. Galvanization as per relevant IS. a) 5.0 mtr height, 3 mm thick, bottom dia of 130mm & top dia of 70mm base plate of size 225 x 225 x 12 mm thick
Providing and laying in position 1:2:4 grade reinforced cement concrete foundation of size 450 mm (L) ×450 mm wide and 1000 mm deep i/c excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 12 mm dia- 960 mm long(approx)-8 nos. and reinforcement of cold twisted bars of 8 mm dia- 1400 mm (approx) -6 nos.(with 150 mm spacing) as required with supplying and positioning of 4 nos. foundation bolts 16 mm dia,600 mm long, J type i/c 2 nos. template anchor plates of size 225mm×225mm×3mm and providing DCW HDPE for cable entry and exit as required for 3 m and 5 mtr pole.
stage.html
html • 0.02 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .