| Sl No | Description | Qty | Unit | Sumit Enterprises L1 | SKYLIGHT INNOVATIONS L2 |
|---|---|---|---|---|---|
| 1.00Supply, Installation, Testing & Commissioning of motorised combined fire damper complete with control panel, inter connecting wiring including taking down manual fire damper complete all as specified and directed. | |||||
| 1.01 | (a) Fire dampers 18 SWG with local smoke and temperature sensor | 85 | Sqm | 15,250 ₹12,96,250 | 9,800 ₹8,33,000 Lowest |
| 1.02 | (b) Actuators of Belimo make, model No. NFA-S2, or approved equivalent from Siemens/Honeywell, spring-return, fail-safe, having nominal supply voltage of 24–240 V AC/24–125 V DC, minimum rated torque of 10 N·m, provided with a minimum of two (2) SPDT auxiliary switches, and a maximum angle of rotation not exceeding 95 degrees, complete in all respects and installed as per specifications and directions of the Engineer-in-Charge. | 85 | Each | 11,300 ₹9,60,500 Lowest | 14,500 ₹12,32,500 |
| 1.03 | (c) Control panel suitable for fire damper actuators, with outgoing connections for damper actuator control and AHU interlocking. The panel shall accept input signals from the Fire Alarm Control Panel (FACP), local temperature sensor, and smoke detector. On receipt of any fire signal, the panel shall command the fire dampers to close. The AHU shall be interlocked to shut down when the dampers are closed and shall be permitted to operate only when the dampers are in the open position | 85 | Each | 9,800 ₹8,33,000 Lowest | 18,000 ₹15,30,000 |
| 2.00Supply, installing, balancing, testing and commissioning of Galvanized steel sheet, including taking down of old ducting, rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter damper vanes, hangars, supports as per SMACNA specifications of following sheet thickness, complete all specified and directed as under:- | |||||
| 2.01 | (a) 22 gauge galvanised steel sheet | 90 | Sqm | 790 ₹71,100 Lowest | 1,350 ₹1,21,500 |
| 2.02 | (b) 20 gauge galvanised steel sheet | 130 | Sqm | 850 ₹1,10,500 Lowest | 1,480 ₹1,92,400 |
| 3.00 | M&L for modification/alteration of existing AHU panel wiring to provide power supply and control to fire damper control panel, including provision of step-down transformer (240V/24V) of suitable capacity (if required), relays, timers, contactors, and necessary interlocking of AHU motor with fire damper operation, complete in all respects as specified and as directed. | 85 | Each Job | 1,800 ₹1,53,000 Lowest | 28,500 ₹24,22,500 |
| 4.00 | S&F PVC insulated cable 1.5 sqmm 2 core copper cable fixed on wall with cable clip complete all as specified and as directed. | 695 | RM | 70 ₹48,650 Lowest | 200 ₹1,39,000 |
| 5.00 | Supply and fixing of addressable control module compatible with the existing fire alarm system, of approved make such as Apollo / Edwards (EST) / Siemens / Honeywell / Notifier/Agni or equivalent, complete with monitored control output for interfacing with external devices. The module shall be loop-powered, programmable from the Fire Alarm Control Panel, and provided with LED status indication. The module shall comply with EN 54-18 (or UL/FM equivalent). Complete with mounting accessories, wiring, addressing, testing, commissioning, and integration with the fire alarm system, complete in all respects as specified and as directed
Note:
1. The control module will be fitted in existing fire alarm loop and fire panel, contractor should visit the site before quoting rates.
2. The specification given above are minimum and any higher specification required for existing loop/panel the same shall be provided by contractor and rates are deemed to be included in quoted rates. | 85 | Each | 2,390 ₹2,03,150 Lowest | 3,500 ₹2,97,500 |
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
18 Apr 2026, 6:00 pmClosed
CWE NEW DELHI
HQ CWE NEW DELHI RAO TULA RAM MARG DELHI CANTT-10
SPL REPAIR REPLACEMENT OF MECHANICAL FIRE DAMPER OF MAIN HOSPITAL BLDG P-100 AND ADC P-105 AT AHRR UNDER GE EM RR HOSP DELHI CANTT-10
2026_MES_757322_1
CWE-ND/70/2025-26
Open Tender
Civil Works - Others
Item Rate
120 days
DELHI CANTT
Please refer Tender documents.
10 documents required · 10 mandatory
₹500
GE E/M RR HOSP DELHI CANTT-10
₹98,000
5 Jun 2026
23 Mar 2026
20 Apr 2026
23 Mar 2026
18 Apr 2026
6 Apr 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| - | Supply, Installation, Testing & Commissioning of motorised combined fire damper complete with control panel, inter connecting wiring including taking down manual fire damper complete all as specified and directed. | - | - | - | - |
| - | (a) Fire dampers 18 SWG with local smoke and temperature sensor | - | Sqm | - | - |
| - | (b) Actuators of Belimo make, model No. NFA-S2, or approved equivalent from Siemens/Honeywell, spring-return, fail-safe, having nominal supply voltage of 24–240 V AC/24–125 V DC, minimum rated torque of 10 N·m, provided with a minimum of two (2) SPDT auxiliary switches, and a maximum angle of rotation not exceeding 95 degrees, complete in all respects and installed as per specifications and directions of the Engineer-in-Charge. | - | Each | - | - |
| - | (c) Control panel suitable for fire damper actuators, with outgoing connections for damper actuator control and AHU interlocking. The panel shall accept input signals from the Fire Alarm Control Panel (FACP), local temperature sensor, and smoke detector. On receipt of any fire signal, the panel shall command the fire dampers to close. The AHU shall be interlocked to shut down when the dampers are closed and shall be permitted to operate only when the dampers are in the open position | - | Each | - | - |
| - | Supply, installing, balancing, testing and commissioning of Galvanized steel sheet, including taking down of old ducting, rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter damper vanes, hangars, supports as per SMACNA specifications of following sheet thickness, complete all specified and directed as under:- | - | - | - | - |
| - | (a) 22 gauge galvanised steel sheet | - | Sqm | - | - |
| - | (b) 20 gauge galvanised steel sheet | - | Sqm | - | - |
| - | M&L for modification/alteration of existing AHU panel wiring to provide power supply and control to fire damper control panel, including provision of step-down transformer (240V/24V) of suitable capacity (if required), relays, timers, contactors, and necessary interlocking of AHU motor with fire damper operation, complete in all respects as specified and as directed. | - | Each Job | - | - |
| - | S&F PVC insulated cable 1.5 sqmm 2 core copper cable fixed on wall with cable clip complete all as specified and as directed. | - | RM | - | - |
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.61 MB
BOQ_848305.xls
BOQ • 0.30 MB
tender70.pdf
Tender Documents • 1.60 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .