CE R N D Secunderabad
CE R N D Opp JBS Picket Secunderabad
PROVISION OF 132 KV POWER SUPPLY TO THERMO-STRUCTURAL TEST FACILITY AT THE TECHNICAL HANGER AF ASL AT RCI HYDER
2021_MES_478998_1
CERD/SEC/TOKEN/18 OF 2021-2022
Open Tender
Civil Works - Others
180 days
RCI Hyderabad
As per NIT
8 documents required · 8 mandatory
₹3,000
GE I R N D RCI Hyderabad
₹15 L
CE R N D Secunderabad
24 Jan 2022
1 Oct 2021
22 Nov 2021
1 Oct 2021
15 Nov 2021
26 Oct 2021
1 Oct 2021 - 15 Oct 2021
11 Oct 2021
Amount
Schedule 'A' Part - I (BUILDINGS AND STRUCTURES) This Schedule (contains under mentioned Sl. item No. 1.01 to 1.03) is not prepriced by MES and the prepriced rate indicated in Col - 5 as `0.00 indicates this fact only.The tenderer is required to quote their rates in Column 6.
Lumpsum price worked out by the contractor for Construction of Main Receiving Sub Station (MRS) building with RCC M25 framed structure etc, complete all as shown on drawings and as specified. etc complete all as shown on drawings and as specified.
Lumpsum price worked out by the contractor for Construction of Panel Room building with RCC M25 framed structure etc, complete all as shown on drawings and as specified. etc complete all as shown on drawings and as specified.
Lumpsum price worked out by the contractor Supply and laying on site LLDPE septic tank designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundaion, vent shaft, connection with upflow filter including media, complete all as shown on drawings and as specified.
Lumpsum price worked out by the contractor for Construction of Soak well of size 1.20m dia and 3.00 M effecive depth complete all as shown on drawings and as specified.
Lump sum price worked out by the Contractor for "SITE CLEARANCE / DEVELOPMENT AND EARTH WORK EXCAVATION” as listed in Schedule ‘A’ Part - II representing _______ % ________________ percent Above / Below the lumpsum price of `35,12,151.35 inserted by the MES in Schedule ‘A’ Part - II
Lump sum price worked out by the Contractor for “ ROADS, PATHS AND CULVERTS ” as listed in Schedule ‘A’ Part - III representing _______ % ______________ percent Above / Below the lump sum price of `39,93,020.00 inserted by the MES in Schedule ‘A’ Part - III
Lump sum price worked out by the Contractor for “ SEWAGE DISPOSAL ” as listed in Schedule ‘A’ Part - IV representing __________ % ____________ percent Above / Below the lump sum price of `1,69,186.02 inserted by the MES in Schedule ‘A’ Part - IV
Lump sum price worked out by the Contractor for " AREA DRAINAGE” as listed in Schedule ‘A’ Part - V representing _______ % __________________ percent Above / Below the lump sum price of `12,84,562.22 inserted by the MES in Schedule ‘A’ Part - V
Lump sum price worked out by the Contractor for " COMPOUND WALL / GATE / FENCING ” as listed in Schedule ‘A’ Part - VI representing _______ % __________________ percent Above / Below the lump sum price of `28,87,759.35 inserted by the MES in Schedule ‘A’ Part - VI
Lump sum price worked out by the Contractor for “ INTERNAL ELECTRIFICATIONS ” as listed in Schedule ‘A’ Part - VII representing _______ % _________________ percent Above / Below the lump sum price of `4,09,725.89 inserted by the MES in Schedule ‘A’ Part - VII
Lump sum price worked out by the Contractor for “ EXTERNAL ELECTRIC SUPPLY ” as listed in Schedule ‘A’ Part - VIII representing _______ % _________________ percent Above / Below the lump sum price of `55,24,878.57 inserted by the MES in Schedule ‘A’ Part - VIII
Lump sum price worked out by the Contractor for “EXTERNAL WATER SUPPLY ” as listed in Schedule ‘A’ Part - IX representing ______ % _________________ percent Above / Below the lump sum price of ` 1,23,989.14 inserted by the MES in Schedule ‘A’ Part - IX
Lump sum price worked out by the Contractor for “ INTERNAL WATER SUPPLY ” as listed in Schedule ‘A’ Part - X representing ______ % _________________ percent Above / Below the lump sum price of ` 7,694.34 inserted by the MES in Schedule ‘A’ Part - X
Lump sum price worked out by the Contractor for “ LIGHTENING PROTECTION ” as listed in Schedule ‘A’ Part - XI representing ______ % _________________ percent Above / Below the lump sum price of ` 1,43,498.80 inserted by the MES in Schedule ‘A’ Part - XI
Lump sum price worked out by the Contractor for “ CABLE TRENCH ” as listed in Schedule ‘A’ Part - XII representing ______ % _________________ percent Above / Below the lump sum price of ` 42,87,001.22 inserted by the MES in Schedule ‘A’ Part - XII
Lump sum price worked out by the Contractor for “ TRANSFORMER BASE AND FLOOR FILLING ” as listed in Schedule ‘A’ Part - XIII representing ______ % _________________ percent Above / Below the lump sum price of ` 48,80,758.60 inserted by the MES in Schedule ‘A’ Part - XIII
Lump sum price worked out by the Contractor for “ FIRE DAMPER WALL ” as listed in Schedule ‘A’ Part - XIV representing ______ % _________________ percent Above / Below the lump sum price of ` 21,73,674.21 inserted by the MES in Schedule ‘A’ Part - XIV
Schedule 'A' Part - XV This Schedule is not prepriced by MES and the prepriced rate indicated in Col - 5 as `0.00 indicates this fact only.The tenderer is required to quote their rates in Column 6. This Schedule constitutes Sl. Item No. 16.00 to 68.00
INTERNAL ELECTRIFICATION S & F light fitting 1 x 22 W, 230V with LED tube 1200mm complete with all accessories internally pre-wired and including connecting with twin core twisted flexible copper conductor cable of suitable size complete all as specified and directed. Make: Havells LUMILINEPLUSBS22WLED865SPCSS or equivalent of PHILIPS / WIPRO / CROMPTON GREAVES
S&F rugged LED midbay/highbay LED light fittings of capacity 60 watts, 13000 lm with black colour, powder coated aluminium heat sink for efficient heat dissipation and high purity anodized reflector with electro chemically anodized matt finish inside, the effective glass optics for maxmimum illumination radius of aluminium reflector not less than 240mm dia of outer peripherals. Driver and accessories prewired with luminaire lumen 13000lm colour temperature not less than 6600 K , Ingress Protection IP-65 the high lumen output minimum 130 lm/watts complete all as specified and directed. Make: Havell Cat Part No ILIOSBAYPLUSSHBP60WLED857SP90DTOPC or equivalent make of wipro/Philips
S&F LED Security light with aluminium pressure die cast housing, high purity diffuser with silicon gaskets for IP-65 protection, power consumption less than 20 W and luminaire lumen greater than 2500 lm and system efficiency greater than 100 lm/watt, in built electronic driver prewired upto terminal block with driver efficiency greater than 85% power factor as per IEC standard including GI Pipe medium grade ISI mark of size 32 mm dia length not less than 1.5 meters bent to shape for fixing light fitting and nuts, bolts, clamps as required to fix to wall complete all as specified and directed.
Supply and fix sheet metal enclosure distribution board (MCCB DB) TPN 4 Way, 200 Amps rated bus bar, neutral links and earth bar, double door vertical type, powder coated, suitable for use on 415 volts, 50 HZ supply, IP 43 IK 09 protection, MCCB used as incommer, complete all as specified and directed. Make: Legrand/L&T/Schneider/C&S
Earthing complete with GI earth plate electrode 600mm x 600mm x 6.0mm thick buried directly in ground vertically to a depth of not less than 2.25m deep below ground level with the top edge of earth plate at a depth of not less than 1.5m below ground level connected to GI earth wire 4mm, GI earth wire shall be protected by 15mm dia GI pipe 'light grade', watering pipe 20mm dia GI pipe 'medium grade', GI wire meshed funnel, alternate layer of charcoal and salt on all side to earth plate upto a thickness of 150mm, filling of black cotton soil in earth pit upto GL, and connected to earth plate including necessary excavation & earthwork, PCC (1:3:6) type C-1 earth chamber, 50mm thick RCC cover (1:2:4) type B1 mix with 8mm dia nominal reinforcement @ 75mm c/c both ways etc complete all as shown in electrical plate No.3 connected to earthing test point, including testing on completion, complete all as speciified and as directed. NOTE:-1 Rate quoted shall deemed to include cost of excavation in any type of strata, RFR and removal upto 50metre, PCC pit, funnel and RCC cover plate. 2. GI wire beyond 7.5m will be measured and paid seperately
Supply and Fix Energy saving Ceiling fan ISI marked with down rod of 240 volts, 1200mm sweep, BEE 5 star rated complete as specified and directed.
S&F Metalic exhaust fan suitable to operate on 230V, single phase AC supply of sweep 300 mm with louvre including necessary civil works complete all as specified an directed.
EXTERNAL ELECTRICAL SUPPLY 132 KV SYSTEM AND 132/11 KV SYSTEM AT MSDS Power Transformer step down, outdoor type of capacity 8.0 MVA (8000KVA) 132 KV/11 KV, 3 phase, 50cycles AC with On Load Tap Changing arrangements with remote control panel operation) on 132 KV sides to vary secondary voltage from +5% to (-) 15% in steps of 1.25% (16 steps/17 Position), impedance 8.35% at normal / common tap No 7 including suitable marshalling box and HV terminals 3 Nos outdoor bare bushings with sockets and LV terminals connectors to connect the transformer with HT XLPE Power cable of size 300 sqmm x 3 core with copper conductor and LV additional Neutral with one no solid porcelain type out door bushings with sockets on the transformer lid for earthing purpose complete in all respects with standard accessories and fittings conforming to IS-2026 primary side delta and secondary side star. The salient features of the transformer shall be as below: - (a) (i) Transformer shall be DYN 11 vector group oil immersed naturally cooled, doubled wound electrolytic copper winding core type, Radiator cooled MS tank complete with first fill of transformer oil as per IS-335 with ONAN cooling system. The temperature of oil shall not rise 55 degree centigrade of winding. Transformer shall be painted with two coats of synthetic enamel paint. (ii) Rating and diagram plate. (iii) Earthing terminals - 2 Nos. (iv) Lifting lugs.
(v) Thermometer pocket. (vi) Air release hole with plug. (vii) Oil filling hole with plug on & incl. conservator with drain valve and plug. (viii) Plain type oil indicator on one side of conservator with minimum and maximum oil level marking. (ix) Dehydrating breather - 01 No (x) Oil conservator with drawn valve and plug. (xi) Sampling valves, top and bottom. (xii) Under base with flat treaded bi-directional rollers. (xiii) Drain cum bottom filter valve with plug. (xiv) Top filter valve with plug. (xv) Explosion vent with diaphragm and equalizer pipe (pressure release device). (xvi) Jacking lugs and hauling holes. (xvii) Inspection cover. (xviii) Detachable radiators with shut off valves between radiators and tanks. (xix) Radiator with air release hole and plug. Oil drain hole with plug and lifting eye all as per manufacturer's standards. (xx) 150mm dia oil temperature indicator stem type with SCADA compatability. (xxi) Double float Bucholtz relay with two sets of contacts and isolating valves. (xxii) 150mm dia winding temperature indicator with maximum indicating pointer and resetting device with SCADA compatability. (xxiii) 100mm dia magnetic oil level gauge with low level alarm. (xxiv) Terminal arrangements. (xxv) Suitable wheels (width distance should be as per Broad Gauge rails). (xxvi) Marshalling box.
Supply, erection and testing and commissioning of Metering and Relay panel suitable for 145 KV SF-6 Breaker operation indoor type made out of CRCA sheet of 2mm thick confirming to IS 8623 totally enclosed dust and vermin proof with front and rear openings. The panel should be powder coated after 7 tank process all as specified with the following accessories :- (a) Digital ammeter (b) Digital Power factor meter (c) Indication lamp for circuit breaker ON, OFF, Gas pressures low, auto trip etc as per IE rules / norms / safety code. (d) The numerical relay operating on 110V DC should comprise of the following features:- (i) Three over current & one earth fault relay-one set (ii) High set, Low set. (iii) RS 485 communication (iv) Multiple time characteristics for both over current and earth fault. (v) Integrated breaker control/failure. (vi) Trip circuit supervision relay. (vii) Differential relay suitable for transformer protection type 3 x 4C 21, Make: Easun Reyrolls or equivalent in ABB POWER PRODUCT (viii) Restricted earth fault relay CAG-14/equivalent (ix) Hand reset type auxiliary relay for alarm and tripping, oil as well as winding temperature and bucholtz for transformer VAA-33:3 Nos / equivalent. (x) Lockout relay VAJH-13/Equivalent (xi) MCB protection for control circuit and space heater. Make: ABB POWER PRODUCT / SEIMENS / BHEL / EASUN REYROLLE.
Supply, erection and testing and commissioning of Current Transformer (oil impregnated) 132 KV class 100-50/1-1-1 CT Ratio, outdoor type oil immersed, dead tank as per IS 2705 (1992)IEC 61869 with insulator of 25mm/KV creepage distance with electrical connection as per manufacturers instruction complete, CT shall be with rated voltage 145 KV, accuracy class 1.0 for core1, 5P20 for core 2, PS for core 3 at 132 KV side, and class 1.0 for core 1, PS 10 for core 2, PS for core 3 (5PO/0.577A for difference) and VA burden should be 15VA for protection complete all as specified and directed. Make: ABB POWER PRODUCT / SIEMENS / CROMPTON GREAVES LTD.
Supply, erection and testing and commissioning of Air Break Switch Isolator (Horizontal type) triple pole with earth (two break per pole) mechnically operated mounted on insulators and steel frame with operating mechanism worked from ground level for current rating upto 1600Amps, with rated voltage 145 KV with discharge of regular voltage to earth all as per IS specifications and shall be as per manufacturere standards including locking arrangements (lock with double keys) complete all as directed and specified. Make: ABB POWER PRODUCT / SIEMENS / CROMPTON GREAVES LTD / ELPRO.
Supply, erection and testing and commissioning of Lightening Arrestor suitable for 132 KV (120KV rated voltaage) 65 KA imulse current, 10 KA discharge current station, class-III, heavy duty, gapless type, surge (lightning) arrestor (porcelain housed / Silicon Polymer housed) alongwith the insulating base and surge counter completed all as specified and directed. Make: ABB POWER PRODUCT / ELPRO / CROMPTON GREAVES LTD / LAMCO / OBLUM.
Supply, erection and testing and commissioning of Lattice structure, galvanised Iron, heavy duty for132 KV switch yard and 132 KV Tower-3 nos made of structural steel items like ISMB, MS channel, angle iron, MS flat etc of any size confirming to IS-2062 required length bend to shape as cross arms, bracings, supporting structures for GOD's, lightening arrestors, CTs PTs pin / disc insulators, bus bar support, cable support for all types of structures duly fabricated structural steel sections,Hot galvanised, drilling of holes of any size or shape as required for various equipments all as specified and directed. Note: i) Excavation, earth work and concreting shall be measured and paid separately Insulators, bus bar, LA, GOD, CTs, etc shall be measured and paid separately. ii) Design and Drawing for 132 KV Towers / Lattice structure, Foundation drawing etc shall be prepared and got approved by the Garrison Engineer. For reference existing towers and structures shall be inspected. (iii) GI nuts, bolts, fasteners, washers, stud plates etc. required shall be weighed and paid along with structure for payment against this item.
Supply and laying in trenches,Control cable 1100 volts with PVC insulated and steel armoured with multi stranded copper conductor of the following sizes: -
(a) 4 core 2.5 sqmm
(b) 7 core 2.5 sqmm
(c) 12 core 2.5 sqmm
(d) 16 core 2.5 sqmm
(e) 24 core 2.5 sqmm
(f) 2 core 2.5 sqmm Note: (for 31 to 31.06) (i) Control cabling shall be executed and certified through a licenced agency as per IE Rules. (ii) Submit the single line diagram of control wiring for transformers, SF6 circuit breaker and CRP panel. Make: TORRENT/ PRIME CABLE INDUSTRIES / UNIVERSAL / GLOSTER / DIAMOND / KEI.
Supply and fixing,Disc insulator (Polymer / Porcelain type), 15 KV 120 KN suitable for 132 KV line with Drake ACSR conductor complete with all accessories for tension tower all as per IS standards as specified and directed by E-in-Charge.
Supply and fixing,Post top insulators, solid core suitable for 132KV grade complete confirming to IS -731 and as per IS standard all as specified and directed by E-in-Charge. Make for item No. 32& 33: MODERN INSULATORS / BHEL / WS INDUSTRIES / BIRLA NGK INSULATORS / SARAVANA.
Supply and fixing,ACSR conductor ZEBRA with aluminium strands 54 Nos/3.18mm and GI strands 7 Nos/3.18mm, current carrying capacity 1621 Amps for 132 KV switch yard flexible connections all as specified and directed. Note: (i) Insulators shall be measured and paid separately under the relevant item. (ii) The cost is inclusive of any other hardware accessories which is required during execution of work all as IS standards. (iii) Metal part/clamps shall be measured and paid separately.
Supply and fixing,132 KV busbar of tubular aluminium pipe of size of 88.90mm outer diameter, 77.92 mm inner diameter, wall thickness 5.49mm, current carrying capacity 2350 Amps for outdoor application (Make-Indal /Jindal). Note: Metal part / clamps shall be measured and paid separately.
Supply and fixing,Clamps / connectors made out of aluminium alloy for jumpering and connection with necessary hardware including liberal application of conducting grease at 132 KV switchyard for ACSR tubular pipe, equipment etc.,
(a) Multi functional meter parameters: Accuracy class 0.5, as per IEC 62052-11 / IEC 62053-22 monitoring all electrical parameters like per phase, voltage, current, demand in KW, VA, VAR. Also monitoring all instantaneous integrated and demand parameters, neutral current, frequency, power factor, percentage of load, percentage of unbalance (V&I), phase angle on protocol mounting flush - 01 No. Make:ABB POWER PRODUCT/SIEMENS/SCHNEIDER (b) Flush mounting trivector meter with TOD, load survey data, 3 MDI and optical Port class I. Make L&T or equivalent. (c) Resin cast potential transformers with ratio 11KV/1.732, 110V/1.732, 200 VA class1 with HT fuses mounted on with drawable rack. (d) Resin cast current transformers with ratio 500-250/1-1-1 and following characteristics: Core 1-15VA, Class 1, Core 2-15 VA, class P5 10, core 3-class P5, burden depending upon knee voltage as per IS 2705-Part-IV-Set of three. (e) SCADA Compatible Feeder Protection Relay 50/51 (3 phase over current), 50/51N (earth over current), 67P (3-phase directional over current), 51V (voltage controlled over current), 37 (3-phase under current), 46 (negative phase sequence over current), 59N (residual over voltage), 32 (directional power protection (under active / over active / reactive)), 81 U/O (under / frequency), 49 breaker failure detection), cold pickup, inrush blocking relay will be as per IEC 61850 protocol - 01 No. Make: ABB POWER PRODUCT (REF 541 / SIEMENS (7SsJ62) / SCHNEIDER (Esergy P3U30). (f) Trip circuit supervision relay. Make: ABB POWER PRODUCT / SIEMENS / SCHNEIDER. (g) Master trip relay. Make: ABB POWER PRODUCT / SIEMENS / SCHNEIDER. (h) Power quality monitoring Meter Make: ABB POWER PRODUCT / SCHNEIDER / SIEMENS.
(III) Bus coupler Vacuum Circuit Breaker 1250A, HT, 11KV three phase, AC supply, 750MVA, 40 KA breaking capacity, short circuit ratings 3 second, complete:- with out any protection and metering-3 Nos. VCB PANEL SHOULD COMPRISE OF THE FOLLOWING FEATURES: - (a) Push buttons for accepting faults and reset. (b) LED indicating lamps for (duly control wired up) (i) Auto strip (ii) Spring charge (iii) Fault Alarm (iv) Trip Circuit Healthy (v) Trip circuit Unhealthy (vi) Breaker ON (vii) Breaker OFF (c) Motor operated spring stored energy trip for closing and opening of the breaker. (d) Manual charging / operating arrangement. (e) RS 485 communication. (f) Fuses for metering and protection system. (g) One No. internal bus earthing with flat GI strip of size 50x 6mm. (h) one No. of space heater with thermostat. (j) Inside moving spot LED light fitting and switch (11 W, 230V). (k) One No. of plug point with switch (5A, 230V). (l) Copper bus bar common for out going feeders with PVC sleeves.
Auxiliary Power Supply system for protection of panel complete with maintenance free lead acid batteries bank mounted on MS rack & connection complete in all respect with installed capacity 110 V of 2V/55 Nos, 200 AH including 110V-25 Amps booster & trickle charger as per specification & including DC DB for charger complete with DC ammeter, voltmeter switches for 11 KV system complete all as specified and directed. Make: AMARA RAJA / EXIDE.
Supply and laying of HT XLPE cable, XLPE insulated, insulation screened with extruded semi conducting compound in combination with copper tape (0.3 KA for one second), cores laid up, extruded PVC inner sheath with fillers, galvanised steel flat strip armoured and overall PVC sheathed cable, electric power cables (heavy duty) suitable for earthed system with COPPER conductor, 11000 V grade cross sectional area 300 Sqmm x 3 core confirming to IS: 7098 part-II/85 with latest amendments laid in trenches / ducts, fixed on walls/panels all as specified and directed. (From 8 MVA transformers to incomer VCB - 3 runs for each transformer). Make: UNIVERSAL / TORRENT / RPG ASIAN / GLOSTER. Note: (i) The High Voltage test and other relevant test shall be carried out at site after laying and before commissioning. (ii) Excavation, earthwork, sand cushioning, PCC cable cover protection pipe and jionts shall measured and paid separately.
Supply and fixing of Cable jointing kit for 11000V grade cable for indoor type for End termination cold shrinkable type complete with jointing material and accessories suiatble for 3 core XLPE armoured copper conductor cable of size 300 sqmm complete all as specified and directed.
Supply and fixing of Cable jointing kit for 11000V grade cable for outdoor type for End Termination cold shrinkable type complete with jointing material and accessories suiatble for 3 core XLPE armoured copper conductor cable of size 300 sqmm complete all as specified and directed.
Supply and fixing of Danger Notice Board plate of 1.6mm thick MS sheet vitreous enameled white with letter figures and conventional skull & bones in single red colour in front side fixed with MS clamps bolts, nuts, washers etc for 132 KV equipment as per IS-2551-82 of size 250 x 200mm complete all as specified and directed.
M & L Stringing of shield earthing by using 7/8 SWG GI wire and lightning masts / spikes along with necessary tightners and fasteners complete all as specified and directed.
M & L Earthing complete chemical type with copper earth plate electrode 600 mm x 600 mm x 3mm thick buried directly in ground (earth pit not less than 3mtr deep below ground level) with top edge of the plate not less than 2.25 mtr below normal ground level connected to and including copper strip earth lead 50 mm x 6 mm size by means of copper brazing strip and layers of salt, charcoal & magnesium sulphate including funnel with wire mesh including testing of earthing complete all as specified and directed by E-in-Charge. (Minimum three chemical pits are to be made and connected in a grid to meet the earth resistance specifications of <1.0 ohms). (a) Earthing to be done in presence of Eng-in-Charge. (b) Charcoal (small pieces)-250Kg, Salt (Crystal)-250 Kg, Magnesium suplhate (crystal) -100 Kg. (c) Copper strip shall be brazed with copper plate electrode. (d) Alternate layers of charcoal and salts should be laid in the earth pit on the top of copper plate at least 5 layers should be laid. (e) After laying the 5 alternate layers of charcoal and salt a two inch layer of magnesium sulphate to be laid. (f) The chemical salt and magnesium suplhate should not be mixed, but are to be laid in layers only. (g) Copper strip is to be extended inside the equipment and power room it should routed in the side wall of the underground ducts fixed with creamics / porcelain spacers. (h) Contractor shall pour sufficient water in earth pit before and after doing earthing. (j) 25mm dia GI pipe suitable length to reach just about copper plate fitted with funnel meshed along with cap and running water tap to be provided for keeping the soil wet.
Supply & Fix 50 mm x 6.0mm copper earth strip to be fixed by means of bolts, nuts, washers / spot welding all as specified including spreading up bentonite clay complete all as specified and directed.
Supply and lay of cable route indicator made out of PCC (1:2:4) type B1 using 20mm graded stone aggregate of size 300 x 300 x 400mm embedded in ground with 100mm projection above ground level and marked 11 KV HT complete all as specified and directed.
Supply and fixing, 60 Watts street light LED fitting, new generation energy saving, environmental friendly long life, versatile pressure die cast aluminium, IP66 with 10KV surge protection road way, luminaire with high power LED as light source with warranty option of 5 years and suitable driversetc connecting with 4.0 sqmm multi strandard aluminium conductor PVC insulated twin core weather proof cable from fitting to junction box and fixing to pole with and including bracket made out of GI pipe of 40mm dia light grade not less than 1.8 mtr long bent to shape, fixed to pole in any position with flat iron clamps of size 50x6 mm complete all as specified and directed. Model: Crompton Cat part LSTP-60-CDL or equivalent in Philps / Wipro / Crompton.
Supply and fixing of Out door type cable juction box IP 66 on mounted on pole for termination of pole connection incl. 01 Nos MCB 0 to 6 Amp capacity and incl. Busbar TP and feed of charge on street light cable termination for next pole complete all as specified and directed. Make: Hensel cat part No KF8350/SINTEX.
Supply and filing of Dry clean river sand free from clay laid in trenches for cable cushioning covering both top and bottom of cable all as specified and as directed. NOTE :- Punned thickness will be measured for the purpose of payment.
Supply, Install, Test and Commissioning Step down transformer copper wound, outdoor type, oil cooled complete with standard accessories 11KV on HT side, 3 phase, 433Volts on LT side, 3 phase, 50 Hz 4 wire for continuous operation with ON load tap changer on HT side to vary secondary voltage +5% to - 15% with tapings at every 1 ½ % intervals all as per IS-2026 (Level-II) impedance 6.25% as per IS 1180 of capacity 2000 KVA conventional/herimetical sealed with and including following accessories with SCADA compatability complete all as specified and directed. Make: PROLEC GE / KIRLOSKAR/ SCHNEIDER / SEIMENS / CG. (a) RTCC Panels as per required specification shall be designed by OEMs. (b) Necessary extension / adaptor boxes at LV side shall be suitable for bus duct and HV side shall be suitable for HT UG cable shall be designed as per specifications. (c) Oil conservator with filter type drain valve and oil level. (d) Dehydrating breather with first fill of dehydrating agent. (e) Pressure Release Valve. (f) Thermometer with pocket on tank cover (g) Rating plate and terminal marking plate. (h) Oil filling hole with cap / plug with connection plate complete. (j) Air release valve (k) Drain outlet pipe with brass gate valve and dummy plug. (l) Initial filling of transformer oil upto recommended level confirming to IS 335. (m) ONAN type cooling, vector group : DYN 11 (n) Double float Buchholtz relay with alarm and trip contacts including control cable of copper conductor as per OEM standard from Marshalling box to Relay of VCB / Hooter for relevant fault alarming. Buchholtz relay shall be provided with 2 shut off brass valves at ends.
(o) 150mm dia winding temperature indicator, dial type with alarm and trip contacts with SCADA compatability. (p) 150mm dia oil temperature indicator, dial type with alarm and trip contacts with SCADA compatability and 04 Nos lifting hook / lugs. (q) Test Report / on site inspection report shall be provided by OEM to EIC. (r) Marshalling box with double window, space heater element with switch, illumination CFL lamps, 16/6A socket completely prewired. (s) Neutral to be brought outside on the body of Transformer. (t) Neutral CT shall be provided.
S&F, following elements/components of Compact Low Tension Aluminium Sandwich type Busbar trunking system 4000A, 433V Sandwich type 3 Phase +100% Neutral and equipped with integral protective earth conductor of aluminium alloy with cross section not less than 50% of phase conductor in accordance with NEC(India) 2011, Busbar trunking system assembly conforming to IEC-614396-6 with KEMA-KEUR and ASTA Diamond certification, rated insulation voltage 1000 volts,rated impulse withsand voltage 8 KV, rated short circuit withstand capacity not less than 65 KA for 1 Sec, housing enclosure made of 1.5 mm thick GI sheet , epoxy polyster powder coated to atleast 60 microns, with high resistance to chemical agents, rigid and robust, compact and corrosion less; Busbar trunking system enclosure shall be designed for very high mechanical, electrical and heat loss efficiency; Enclosure shall be with IP-65 protection for outdoor suitable for power distribution and enclosure certified for a min of 1500 hr salt spray test as per IEC, horizontal or verticallly aqay direcction with span lengths jointed at regular intervals through removable block joints having all joint contact surfaces silver plated, together with all kinds of bends, tees etc with halogen free sandwitch insulation system of Class 130 with provison for termination inside power control centers of capacity for various types of loads, the busbar trunking system routed on rigid ladder type trays of appropriate span and adequate strength with support structures anchored to ground and also provided with GI canopy not less than 2mm thick complete all as per NEC : SP-30 : 2011, IS-8623, IEC-61439-6, IEC-60364-5-54, IEC-529 & latest relevant standards, all as specified and directed. Make: LEGRAND /GE /SCHNEIDER
S&F, following elements/components of Compact Low Tension Aluminium Sandwich type Bus bar trunking system 1600A, 433V Sandwich type 3 Phase +100% Neutral and equipped with integral protective earth conductor of aluminium alloy with cross section not less than 50% of phase conductor in accordance with NEC(India) 2011, Busbar trunking system assembly conforming to IEC-614396-6 with KEMA-KEUR and ASTA Diamond certification, rated insulation voltage 1000 volts,rated impulse withsand voltage 8 KV, rated short circuit withstand capacity not less than 65 KA for 1 Sec, housing enclosure made of 1.5 mm thick GI sheet , epoxy polyster powder coated to atleast 60 microns, with high resistance to chemical agents, rigid and robust, compact and corrosion less; Bus Duct enclosure shall be designed for very high mechanical, electrical and heat loss efficiency; Enclosure shall be with IP-65 protection for outdoor suitable for power distribution and enclosure certified for a min of 1500 hr salt spray test as per IEC, horizontal or verticallly aqay direcction with span lengths jointed at regular intervals through removable block joints having all joint contact surfaces silver plated, together with all kinds of bends, tees etc with halogen free sandwitch insulation system of Class 130 with provison for termination inside power control centers of capacity for various types of loads, the bustrunking system routed on rigid ladder type trays of appropriate span and adequate strength with support structures anchored to ground and also provided with GI canopy not less than 2mm thick complete all as per NEC : SP-30 : 2011, IS-8623, IEC-61439-6, IEC-60364-5-54, IEC-529 & latest relevant standards, all as specified and directed. Make: LEGRAND /GE /SCHNEIDER
Supply erect, test and commissioning of APFC panel of capacity 300 KVAR, 440 volt, 50 HZ, AC, detuned dynamic type the make of panel of capacitor bank as recommended by manufacture only with the following details:- Make : L&T / ABB POWER PRODUCT POWER PRODUCT / SEIMENS / SCHNIEDER (a) The 300 KVAR, at 440 volt, 3 phase, 50 Hz, AC grade AC automatic power factor Correction Panel shall be having a 14% detuning series Reactor, along with capacitors of 367 KVAR at 525 volt to give 300 KVAR at 440 volt, voltage rating in suitable KVAR rating to form a resonating circuit on 134 Hz. (b) Output resolution: Yhe dynamic detuned APFC panel should have output resolution of 10 KVAR at 440 volt, 50 Hz. Banking on the panel shall be such that the net compensation shall be 10 KVARx1+20 KVARx2+50 KVARx5. (c) Detuning reactors: Detuning reactors shall be tuned to a frequency of 134 Hz, enabling it to suppress Harmonics of the order of 3rd and 5th above. Ratings up to 15 KVAR shall be copper wound with lug termination whereas rating 20 KVAR and above shall be made of copper wound windings terminated on to a copper busbar of suitable ratings. These shall be incorporated to a temperature limiting device for thermal protection. Linearity of the series Reactor must be 0.95 XL for current upto 1.73 XII. (d) Capacitor: Internally Delta connected 3 phase capacitor units having rated voltage of 525 volt, 50 Hz AC should be used in series with the reactors to form a detuned bank to deliver required output and the tuning frequency. The capacitor should confirm the standards of IS: 13340/IEC 60831. These shall be triple concentric wound type with a wave cut film & vacuum impregnated with moisture free Nitrogen gas. The capacitor shall be UL approved.
(e) Thyristor switching modules: The solid state switching module complete with thyristor and other necessary components to have the capability of switching as fast as 20 ms and switching at “Zero crossing” of the current. The module should be made up to 2200 V PIV (Peak Inverse Voltage) devices to ensure reliable operation over time. (f) Suitable capacity of MCCB for incomer of capacitor panel – 01 No Make: Legrand/EPCOS/GE Energy/Visa Power/ABB Power Products.
Mobile trolley suitable for 2000KVA distribution transformer, chassis made up of suitable size MS channel and accessories with four wheel (tyre type tubeless) with grease nipple suitable size alongwith suitable load springs including towing hook with hydraulic breaks with 10mm thick MS sheet (Chequered type) platform with suitable fenced barricades around, and one gate all as specified and as directed by GE. Trolley should be suitable to accommodate the 2000 KVA outdoor type transformer including the working place suitable as per IE norms. (The contractor shall submit the drawings and obtain the approval of GE before process the same.)
M & L for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150mm dia suitable for 0.4mpa working pressure complete all as specified and directed.
M & L for interconnection adaptor box (IP-65) between LT panel and bus duct suitable for sandwich type bus trunking to house the copper flexible busbar and connected accessories of capacity 4000 Amps complete all as specified and directed. Make: LEGRAND / GE/ SCHNEIDER
M & L for interconnection adaptor box (IP-65) between LT panel and bus duct suitable for sandwich type bus trunking to house the copper flexible busbar and connected accessories of capacity 1600 Amps complete all as specified and directed. Make: LEGRAND / GE/ SCHNEIDER
Supply and fix bends suitable for LT sandwich type bus duct system of 4000 Amp capacity complete all as specified and directed.
Supply and fix bends suitable for LT sandwich type bus duct system of 1600 Amp capacity complete all as specified and directed.
Supply and fix flange end suitable for LT sandwich type bus duct system of 4000 Amp capacity complete all as specified and directed.
Supply and fix flange end suitable for LT sandwich type bus duct system of 1600 Amp capacity complete all as specified and directed.
M & L for Earthing complete with copper earth plate electrode 600x600x3mm buried directly in ground vertically to a depth of not less than 2.25mtr below ground level than 1.5mtr below ground level connected to and including copper strip 20x3mm by means of bolts washers etc made out of copper and alternate layers of charcoal and salt on all sides of earth plate upto 150mm earth strip will be protected by galvanized iron pipe medium grade 50mm bore up to main distribution board / main switch including necessary excavation and earth work PCC 1:3:6 type CI (using 20mm graded stone aggregate) RCC cover 1:2:4 type B1 including necessary reinforcement watering GI pipe 20mm dia medium grade complete all as show electric plate No. 3 of MES Such Part-I, directed by Engineer-in-Charge.
EXTERNAL WATER SUPPLY M & L for Masonry valve chamber 750 x 750 x 750 for 80 mm dia gate valve including excavation and earth work in any type of soil and 100 mm thick PCC 1:4:8 type D2 foundation, brick work in CM (1:6) plastring internal surface 15 mm thick in CM (1:4) PCC (1:3:6) type C1 coping 50 x50x6 mm angle iron 6 mm thick MS plate cover complete with locking arrangement painting steel and iron surface with two coat of synthetic enamel paint over a coat of zinc chrome primer all as specified and directed.
Supply and fixing Stop valves, cast copper alloy, fancy type, chromium plated, screwed down, high pressure, with capstan head handle, screwed both ends for iron pipe or for unions and fixed, 80mm bore of pipe, complete all as specified and directed.
LIGHTENING PROTECTION & EXTERNAL ELECTRIC SUPPLY M & L for Earthing complete with GI earth plate electrode 600mm x 600mm x 6.0mm thick buried directly in ground vertically to a depth of not less than 2.25m deep below ground level with the top edge of earth plate at a depth of not less than 1.5m below ground level connected to GI earth strip 32x6mm, GI earth strip shall be protected by 40mm dia GI pipe 'light grade', watering pipe 20mm dia GI pipe 'medium grade', GI wire meshed funnel, alternate layer of charcoal and salt on all side to earth plate upto a thickness of 150mm, filling of black cotton soil in earth pit upto GL, and connected to earth plate including necessary excavation & earthwork, PCC (1:3:6) type C-1 earth chamber, 50mm thick RCC cover (1:2:4) type B1 mix with 8mm dia nominal reinforcement @ 75mm c/c both ways etc complete all as shown in electrical plate No.3 connected to earthing test point, including testing on completion, complete all as speciified and as directed. NOTE:-1 Rate quoted shall deemed to include cost of excavation in any type of strata, RFR and removal upto 50metre, PCC pit, funnel and RCC cover plate. 2. GI earth strip above 7.5m will be measured and paid seperately
SAGGI ELECTRIC COMPANY
RSEE LAKSHMI ELECTRICAL SERVICES
SOOD ASSOCIATES PVT LTD
K KUMAR RAJA PROJECTS P LIMITED
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid