Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹17.8 LAccepted-AOC | L-1 | Accepted-AOC FOUND LOWEST AND REASONABLE | |
| 2 | L-2₹19.0 L+₹83,315 (4.59%)Rejected-Finance 38 49 D OLD IDGAH COLONY AGRA U P 282001 | AGRA | AGRA | UTTAR PRADESH | 282001 | L-2 | Rejected-Finance Being other than lowest |
Tender Value
₹23 L
EMD Value
₹46,000
Closing Date
1 Mar 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (AF) TECH AREA AGRA
GE (AF) TECH AREA AGRA
PROVN OF CERTAIN MINOR, CAPITAL AND SPECIAL REPAIR WORKS UNDER GE (AF) TECH AREA, AGRA.
2021_MES_420616_1
8200-1313/E8
Open Tender
Miscellaneous Works
Item Rate
120 days
GE (AF) TECH AREA AGRA
As per Tender Documents
8 documents required · 8 mandatory
₹500
GE (AF) TECH AREA AGRA
₹46,000
Yes
13 Mar 2021
9 Feb 2021
3 Mar 2021
9 Feb 2021
1 Mar 2021
15 Feb 2021
9 Feb 2021 - 13 Feb 2021
60 days
Amount
Taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fittings etc, including removal and making good disturbed surfaces of walls, ceilings etc complete all as specified & directed. Note:- Taking down of point wiring shall be carried out in such a way that serviceable fixtures and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fittings etc as obtained, to be re-used in this work under appropriate items here-in-after.
Taking down main switches/DB's (alongwith existing board, MCBs & isolators) including removing the same from site and making good disturbed surfaces complete all as specified & directed. Note:- Taking down of main switches (alongwith existing board, MCBs & isolators) shall be carried out in such a way that serviceable MCBs & isolators etc as obtained, to be re-used in this work under appropriate items here-in-after.
Taking down existing old/unserviceable XLPE cable of off sizes including removing the same from site complete all as specified & directed.
Taking down existing old/unserviceable sub main wiring of any type and description, removal of teak wood batten/ PVC pipe/ PVC casing & caping and making good disturbed surfaces of walls, ceilings etc. as per existing complete all as specified and directed.
M&L for point wiring concealed type with 1.50sqmm PVC insulated, unsheathed, single core, multistranded copper conductor cable 1100 volts grade including 1.5 sqmm PVC insulated unsheathed multistranded copper conductor cable as earth continuity conductor drawn through in and including rigid PVC conduit not less than 20mm dia with its accessories, pressed steel terminal box made of 1.2 mm thick MS sheet/anodised steel box, painted with one coat of red oxide primer including 3.0mm thick ISI marked laminated sheet cover for fixing switches/ socket/regulators etc. & making good the disturbed surface by applying putty & matching with colour to the adjoining wall for the one light/ fan/ exhaust fan point controlled by one no piano type switch 5 Amps single pole one way complete all as specified & directed.
M&L for point wiring concealed type with 1.50sqmm PVC insulated, unsheathed, single core, multistranded copper conductor cable 1100 volts grade including 1.5 sqmm PVC insulated unsheathed multistranded copper conductor cable as earth continuity conductor drawn through in and including rigid PVC conduit not less than 20mm dia with its accessories, pressed steel terminal box made of 1.2mm thick MS sheet/anodised steel box, painted with one coat of red oxide primer including 3.0mm thick ISI marked laminated sheet cover for fixing switches/ socket/regulators etc & making good the disturbed surface by applying putty & matching with colour to the adjoining wall for the one socket out let 3/5 pin 5 Amps controlled by one no piano type switch on the same board complete all as specified & directed.
M&L for point wiring concealed type with 1.50sqmm PVC insulated, unsheathed, single core, multistranded copper conductor cable 1100 volts grade including 1.5 sqmm PVC insulated unsheathed multistranded copper conductor cable as earth continuity conductor drawn through in and including rigid PVC conduit not less than 20 mm dia with its accessories, pressed steel terminal box made of 1.2 mm thick MS sheet/anodised steel box, painted with one coat of red oxide primer including 3.0 mm thick ISI marked laminated sheet cover for fixing switches/ socket/regulators etc. & making good the disturbed surface by applying putty & matching with colour to the adjoining wall for the one socket outlet 3/5 pins 5 Amps controlled by one no piano type switch on independent board complete all as specified & directed.
M&L for point wiring concealed type with 2.50sqmm PVC insulated, unsheathed, single core, multistranded copper conductor cable 1100 volts grade including 2.50 sqmm PVC insulated unsheathed multistranded copper conductor cable as earth continuity conductor drawn through in and including rigid PVC conduit not less than 20 mm dia with its accessories, pressed steel terminal box made of 1.2 mm thick MS sheet/ anodised steel box, painted with one coat of red oxide primer including 3.0 mm thick ISI marked laminated sheet cover for fixing switches/ socket/regulators etc. & making good the disturbed surfaces as per existing for one independent light/ socket outlet point controlled by one no switch, SP, one way, 15 amps complete all as specified & directed.
M&L for point wiring concealed type with 4.00sqmm PVC insulated, unsheathed, single core, multistranded copper conductor cable 1100 volts grade including 4.00 sqmm PVC insulated unsheathed multistranded copper conductor cable as earth continuity conductor drawn through in and including rigid PVC conduit not less than 20 mm dia with its accessories, pressed steel terminal box made of 1.2 mm thick MS sheet/ anodised steel box, painted with one coat of red oxide primer including 3.0 mm thick ISI marked laminated sheet cover for fixing switches/ socket/regulators etc. & making good the disturbed surfaces as per existing for one independent light/ socket outlet point controlled by one no switch, SP, one way, 15 amps complete all as specified & directed.
S&F switch piano, flush type single pole, one way 5/6 Amps, 240 volts complete all as specified & directed.
S&F socket outlet 2 in 1, 2 pin 5/6 Amps and 3 pin 5/6 Amps, flush universal type complete all as specified & directed.
S&F switch piano, flush type single pole, one way 15/ 16 Amps, 240 volts complete all as specified & directed.
S&F socket outlet 2 in 1, 3 pin 5 Amps and 3 pin 15 Amps, flush universal type complete all as specified & directed.
S&F ceiling rose, surface bakelite, 35x25mm surface type, two to three terminals, AC 240 volts complete all as specified & directed.
S&F lamp holder, PVC/ polycarbonate type with back plate suitable for batten/ pendant fittings complete all as specified & directed.
S&F rotory stepped type electronic fan regulator mini flush type 120/ 280 Volts complete all as specified & directed.
S&F in repair switch piano, flush type single pole, one way 15/ 16 Amps, 240 volts complete all as specified & directed.
S&F Surface and wall mounted Stout Plus 20 watt LED light fitting with one no. 20 Watt LED luminaires complete and fixed to wall/ ceiling with fixing accessories and connecting up with & including twin twisted copper flexible wire from ceiling rose to fittings complete all as specified & directed. Make:- Havells model No STOUT PLUS 600BS20WLED857SPCWH or equivalent of Bajaj/ Havells /Crompton
M&L for provision of sub main wiring with two runs of single core FRLS PVC insulated, unsheathed, multistranded copper conductor cable of size 4.0 sqmm drawn in and including PVC rigid conduit not less than 20mm dia with its accessories, surface type, including one run of single core FR PVC insulated, unsheathed, multistranded copper conductor cable of size 4.0sqmm as earth continuity and connected of common earth dolly complete all as specified & directed. Note :- Two runs of 4.0 sqmm cable & one run of 4.0 sqmm cable alongwith PVC conduit including its accessories shall be measured and paid one unit length.
M&L for provision of sub main wiring with two runs of single core FRLS PVC insulated, unsheathed, multistranded copper conductor cable of size 6.0 sqmm drawn in and including PVC rigid conduit not less than 25mm dia with its accessories, surface type, including one run of single core FR PVC insulated, unsheathed, multistranded copper conductor cable of size 6.0 sqmm as earth continuity and connected of common earth dolly complete all as specified & directed. Note:- Two runs of 6.0 sqmm cable & one run of 6.0 sqmm cable alongwith PVC conduit including its accessories shall be measured and paid one unit length.
M&L for provision of sub main wiring with two runs of single core FRLS PVC insulated, unsheathed, mutistranded copper conductor cable of size 10.0 sqmm drawn in and including PVC conduit pipe 32 mm dia ISI marked not less than 32mm width with its accessories or, surface type, including one run of single core FR PVC insulated, unsheathed, multistranded copper conductor cable of size 10.0 sqmm as earth continuity and connected of common earth dolly complete all as specified & directed. Note:- Two runs of 10.0 sqmm cable & one run of 10.0 sqmm cable alongwith PVC conduit including its accessories shall be measured and paid one unit length.
Supply, laying , fixing, testing of XLPE , armoured heavy duty under ground electric LT cable 1100 volts grade of size 16 Sqmm 4.0 core with aluminium conductor of IS 1554, laid in tranchies, fixing on wall, under road crossing, etc complete all as specified and directed.
M&L for 1.50 Mtr long house service bracket , made out of 32mm dia light grade GI pipe, bent to shape including MS hook & stay or guy and fixed to wall/ poles including all necessary nut/ bolts complete all as specified and directed.
M&L for factory made sheet metal enclosure 240 volts, 8 ways with 200A rated bus bar, SPN, double door type suitable for housing MCB/Isolators and fixed the same on & including mild steel hold fasts of suitable size & shape after grouting the hold fasts in the wall with and including PCC (1:2:4) type B1 using 20mm graded stone aggregate complete all as specified & directed.
M&L for factory made sheet metal enclosure 415 volts, 4 ways with 200A rated bus bar, TPN, double door type suitable for housing MCB/Isolators and fixed the same on & including mild steel hold fasts of suitable size & shape after grouting the hold fasts in the wall with and including PCC (1:2:4) type B1 using 20mm graded stone aggregate complete all as specified & directed.
S&F, MCB SP, 6 to 32 Amps, 240 volts, 'C' series 50Hz, 10 KA complete all as specified & directed. Make:- Make:- Legrand Cat Nos 4085 87 to 4085 95 or equivleant in ABB/ L&T
S&F , MCB SPN 40 to 63 Amp 240V, 'C' series 10 kA, complete all as specified and directed. Make:-Legrand cat No- 4086 18 to 4086 20 or equivleant in ABB/ L&T
S&F, in repair MCB TPN 63 Amps, 415 V, 50Hz,10 kA, 'C' series complete all as specified and directed. Make:- Legrand Cat Nos 4086 81 to 4086 83 or equivleant in ABB/ L&T
S&F , in repair MCCB four pole with enclosure, 415 volts, 250 Amps with breaking capacity 25kA complete all as specified & directed. Make:- Legrand / L&T/ ABB
S&F, in repair MCCB four pole with enclosure, 415 volts, 125 Amps with breaking capacity 16kA complete all as specified & directed. Make:- Legrand/ L&T/ ABB as approved by GE.
S&F in repair of LED Pluto panel (surface) aesthetrical designed 2x2 LED 42W flat panel for surface mounting to provides soft-light and glare free symmetrical illumination and fixutre size in mm (LxWxH) 600x600x70 (2x2) including neccessary fixing arrangement compelet all as specified and directed. Havells (Cat Part No PLUTOSURFACE2X2PLS42 LED857S ) and poduct description (42W 857 2x2). Make: Havells/Philips/Bajaj/equivalent.
M&L for earthing complete with galvansided steel earth plate electrode 600 x 600 x 6.0mm thick directly burried in the ground (Earth pit not less than 3.75 m deep below normal ground level) with top edge of earth plate not less than 3.0M below the normal ground level with and including provision of earth test point terminal block made out of gun metal or phosphorus bronze of size 75x75x25mm drilled and screwed with & including 3 Nos. 8mm dia 25mm long hexagonal head screw and necessary connections complete, connected to GI wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel, 15mm bore GI pipe medium grade including necessary fittings for protection of earthing wire, watering pipe 20mm bore GI light grade, concrete chamber in PCC (1:4:8) type D-2 using 40 mm grade aggregate, coping shall be in PCC (1:3:6) type C-1 using 20 mm grade aggregate and internal surfaces of concrete chamber shall be given 12 mm thick plaster in CM (1:4), funnel with wire gauge of 22 gauge (0.63 mm) 8 mesh per linear incl 50mm thick cover of RCC (1:2:4) type B-1 using 20mm grade stone aggregate reinforced with 8mm MS deformed bar @ 75 mm C/C both ways, char coal dust and common salt all as shown in electrical plate No. 3 of SSR Part-I (2009) including all necessary excavation & earth work and removal of surplus soil to a distance n. exc 50M and providing connection points with MS bolts & washers as required and connection from earth test point to earth electrode with same GI wire alongwith protection pipe (upto max distance of 7.5 mtr is included in unit rate) and testing on completion complete all as specified and directed.
Taking down and dismantling of AC Ceiling fan of any size and any make from bldg at different location and removing of all wornout parts washing thoroughly bearing/bush by kerosine, washing & cleaning of fan blade, body parts etc. and separating worn out / defective unserviceable parts (whenever necessary) reassembling the same including provision of twin core flexible wire up to 1.00 meter long and re-hanging the same at building and satisfactory test run. NOTE: Replacement of parts/rewinding shall be measured and paid separately under respective items of BOQ.
Supply only Capacitor 220 volts 2.5/3.0/4.0/6.0 MFD suitable for ceiling fan. MAKE : UNIVERSAL
Supply only Rubber reels, including nuts, bolts, washer and fixing complete all as specified and directed.
Supply only Split pin for holding down rod of ceiling fan / exhaust fan of approved make and fixing complete all as specified and directed.
Supply only down rod and clamps for hanging ceiling fan of any size/make and fixing complete all as specified and directed.
Taking down and dismantling of AC exhaust fan of any size and any make from bldg at different location and removing of all wornout parts washing thoroughly bearing/bush by kerosine, washing & cleaning of fan blade, body parts etc. and separating worn out / defective unserviceable parts (whenever necessary) reassembling the same including provision of twin core flexible wire up to 1.00 meter long and re-hanging the same at building and satisfactory test run all as specified and directed.. NOTE: Replacement of parts/rewinding shall be measured and paid separately under respective items of BOQ.
M & L for one coats of spray painting with DUCO spray paint, super glossy to fan body incl blades, down rod / frame canopy etc, after removing of loose paint rust, dust and all oily particle by washing and making surface suitable for enamel paint. Also includes writing of fan number etc in black paint all as directed for Ceiling fan of any size and make complete all as specified and directed.
M & L for one coats of spray painting with DUCO spray paint, super glossy to fan body incl blades, down rod / frame canopy etc, after removing of loose paint rust, dust and all oily particle by washing and making surface suitable for enamel paint. Also includes writing of fan number etc in black paint all as directed for exhaust fan of any size and make complete all as specified and directed.
Excavation in trenches not exceeding 1.5 Mtr wide and not exceeding 1.5 Mtr depth and getting out in soft / loose soil for laying UG cables etc. complete all as specified and directed.
Returning , filling in , including spreading , leveling, watering and well ramming in layers n.exc. 25cm thick in soft / loose soil complete all as specified and directed.
Removing surplus excavated materials n.exc.50mtr and depositing where directed at level n.exc 1.5 mtr above the starting point complete all as specified and directed
Material and labour for providing sand cushioning with dry fine sand including filling, spreading, levelling in layers in cable trench with approved quality of sand for protection of under ground cable complete all as specified and directed.
Supply & lay brick well burnt of sub-class 'B' locally available old size laid flat accross the length of trench for protection of cable complete all as specified and directed.
Supply, laying, fixing, testing of XLPE , armoured heavy duty under ground electric ,LT cable 1100 volts grade of size 70 Sqmm 3.5 core with aluminium conductor confirming to IS 1554, ISI laid in tranchies, fixing on wall, under road crossing, etc complete all as specified and directed.
S&F factory made epoxy powder coated Distribution Board VTPN 8 ways 250A, 415 volt with provison for DPX3 160 A MCCB with double door with acrylic top cover (IP-43 protection) fabricated from minimum 1.6mm thick CRCA sheet and fixed flush to wall and suitable for universal mounting and including 250 Amp copper bus bar, standard DIN rail, Earth bar and cable ties for cable management, top and bottom removeable glade plates with knock outs complete all as specified and directed. Make:- Legrand Cat no. 5077 47, 8 way DPX3 160+24 or equivalent model of make Siemens/ L&T/ Schneider as approved by GE.
S&F 1100 volts grade PVC insulated stranded aluminium conductor served with an inner sheathing of PVC tape and over all PVC sheathed one twin core cable flat or circular of 6.0sqmm (nominal dia) in service connections suspended by insulating hangers not more than 1.0 Mtr apart including 4mm dia suspension GI wire or alongwith wall (surface type) after bracket in and including PVC conduit not less than 25mm dia with its accessories including proper fixing of conduit with saddles complete all as specified and directed.
S&F in repair single pole and neutral sheet metal enclosure (AC box) with a two pin & earth plug and socket with one no. MCB SP of capacity 20 Amps 240 volts complete all as specified & directed.
S&F Isolator, SPN, AC, 240 volts of 6-40 Amps for inductive load connected through cable lugs of suitable size, complete all as specified & directed. Make-Legrand/ABB/Schneider
S&F LED light street/security light fitting of 30 Watt complete with new generation energy saving and environmental friendly long life versatile pressure die-cast aluminium IP66 roadway luminarie with high power LEDs of capacity 30 Watt and fixed on walls with the help of GI Pipe brackets made out by 32 mm GI pipe light grade 2.00 mtr long including flate iron clamp made out by 40x6 mm and necessary fittings all as specified and directed. (Make Havells ENDURACITYLITEPLATPLUSSL30WLED757 SASYBOPC /Bajaj /Phillips
Supply and installation hi wall 1.5 TR , AC split units indoor/ outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 5 star rating and EER 3.2 of capacity as under :-. (a) Fixing of cooling unit with grouting nuts, bolts , cutting groove to wall for gas pipe and water drainage pipe complete all as specified and directed at site. (b) Fixing cutting, bent to shape copper pipe of appropriate size from out door unit to indoor unit by cutting hole to wall including brazing the copper pipe of appropriate size all as required at site. (c) Insulation of both the copper pipe with insulating material and covering the complete pipes with PVC casing and capping of size 75x75 mm for mechanical protection of copper pipe complete. (d) S&F MS Bracket and fasterner of suitable for out door unit of split type AC.
Supply and installation of digital voltage stabilizer for automatic operation single phase neaturally air cooled in door type having time delay relay (TDR) of 2 to 3 minutes including over/under voltage cut off system & designed for input variation of voltage ,copper wind ,digital voltmeter with 160 to 280 output voltage stabilizer at 230V, 50 Hz with accuracy of ± 2.5 % any of capacity of single phase automatic control of 5 KVA capacity complete. Make-Volina Product ID5116877-33068800926 CodeVCDW05160/V gaurd or equivalent
S&F 40 mm bore GI tubing medium grade with and including required GI fitting and accessories at site laid in trenches complete all as specified and directed .
S&F 25 mm bore GI tubing medium grade with and including required GI fitting and accessories at site laid in trenches complete all as specified and directed .
S&F 20 mm bore GI tubing medium grade with and including required GI fitting and accessories at site fixed to wall, ceilng and floor complete all as specified and directed .
S&F 40 mm bore gun metal globe gate valve with iron wheel head, screwed both ends ISI mark complete all as specified & directed .
S&F 25 mm bore gun metal globe gate valve with iron wheel head, screwed both ends ISI mark complete all as specified & directed .
S&F 20 mm bore gun metal globe gate valve with iron wheel head, screwed both ends ISI mark complete all as specified & directed .
M&L, Cuting holes in brick walls superficial area exc 150 Sqcm but not exceeing 400 Sqcm and depth upto 20cm built in cement mortar or and stone walls built in cement mortar with and including filling holes with PCC 1:2:4, type B1 complete and finishing the surfaces with two coats of cement base paint or distemper to match with existing finishes complete all as specified and directed.
S&F, Framed work such as grills, gratings, etc.. with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work conforming to Fe.290.Gde-E-165 complete all as specified and as directed.
M&L, for preparation of new steel surfaces of any description over 10cm width or girth, not otherwise described and apply two coat of synthetic enamel paint over one coat of red oxide primer complete all as specified and as directed.
Supply only aluminium self supporting extendable ladder made of 4mm thick aluminium sections, extra heavy duty, Super Model No 2613 of M/s Super Industries or equivelant make Hindalco, Jindal as approved by GE with following specifications. All as specified and directed :- (a) Height of ladder 40 feet/12 mtr, open height 36 feet/11 mtr and collapsed height 20 feet/6mtr (b) Load bearing capacity of ladder shall be 250 Kg (c) Ladder shall be made of aluminium 'C' Sections of size 66.67 x 31.8mm as per ISI 733:1983 temper T-6 (d) Round corrugated rungus of size 25.4 mm provided at a distance of 300mm (e) Heavy duty locking system with pulley and rope for extending and collapsing the ladder shall be provided (f) All accessories to be provided (Tools tray, Platform, Safety belt, both side railings, 2 wheels with handle) (g) Contractor shall obtain 02 years warranty certificate from the manufacturer against manufacturing defects and submit to the Accepting Officer.
M&L for Brick work with sub-class `B' bricks, straight or curved on plan exceeding 6 M mean radius built in cement mortar 1:4 Complete all as specified and as directed.
M&L for rendering 15mm thick in cement mortar 1:4 on fair faces of brick work or concrete surfaces finished the surface enen and smooth without using extra cement complete all as specified and directed .
M&L for two coats of cement base paint over newely plastered surfaces of wall including preparation of surfaces complete all as specified and directed.
M&L PCC 1:4:8 type D2 using 40 mm graded stone aggregate as in foundation filling and mass concrete complete all as specified and as directed.
M&L 150 mm thick cement concrete type B- 2, 1:2:4 (using 40mm graded stone aggregate) as in floors and hardstanding etc. including side formworks complete all as specified and directed.
M&L for forming 20mm thick construction/expansion joints for 100 mm thick cement concrete paved path/hardstanding, filled with pre-formed bituminous filler and top 30mm primed and sealed with sealing compound, Grade 'A' complete all as specified and as directed.
S&F Aluminium Partition wall of section as in frame size 63.5 X 38.1 x 1.0mm thick including 5mm thick Glass at top portion and 12mm thick prelaminated particle board paneling (Size of panel n.exc 1.5 Sqm each) including all necessary snap beading , rubber packing , jointing cleats etc. complete all as specified and directed
S&F for aluminium door single leaf with anodized/powder coated aluminium frame of section 62.5x37x1.5mm thick, shutter with bottom & middle rail of section 112.50x 37x1.5mm thick and styles & top rail of section 83x37x1.5mm thick with centrally locking arrangement with lock make of ‘GODREJ’ or ‘LINK’ 7 lever with rebate including jointing cleats, and glazing with 5mm thick frosted/ plain glass / 12mm thick particle board and necessary fittings, fixtures such as stainless steel hinges 100mm -03 Nos, 150mm long aluminium anodised barrel tower bolt -02 Nos, oval shaped fancy aluminum door handles 125mm -02 Nos, aluminium door stopper 175mm long -01 No, floor spring 01 No in each shutter complete & aluminium snap beads, rubber packing etc. complete all as specified and directed.
GUPTA ENGINEERING WORKS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .